The document provides details on installing a fire detection alarm system for a proposed 5-story college building. It includes details on mounting heights for smoke detectors, a riser diagram showing the layout of detectors on each floor and their connections back to the main control panel, and a schedule listing the devices on each floor including 14-15 smoke detectors and 2 heat detectors per floor. Manual pull stations are also shown on the diagrams.

Uploaded by

Mark Jerez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
348 views8 pages

FDAS

The document provides details on installing a fire detection alarm system for a proposed 5-story college building. It includes details on mounting heights for smoke detectors, a riser diagram showing the layout of detectors on each floor and their connections back to the main control panel, and a schedule listing the devices on each floor including 14-15 smoke detectors and 2 heat detectors per floor. Manual pull stations are also shown on the diagrams.

Uploaded by

Mark Jerez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

SMOKE DETECTOR INSTALLATION DETAIL

SUPPORT DETAIL

MOUNTING HEIGHTS:

MANUAL PULL ALARM STATION


MOUNTING

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 4 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-01
SMOKE DETECTOR INSTALLATION DETAIL

SUPPORT DETAIL

FACP zone 1 S S S S S S S S S S S S S S S EOL

zone 2
S S S S S S S S S S S EOL

zone 3
S S S S S S S S S S S S S EOL

zone 4
S S S S S S S S S S S S S EOL

zone 5
S S S S S S S S S S S S S EOL

MANUAL PULL ALARM STATION


MOUNTING RISER DIAGRAM
SCALE NTS

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 2 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-01
A B C D A B C D

6 6

S
HD HD S
S

5 5

S S
S

4 4
S

S
S S S

3 3

TO FACP
15 SMOKE DETECTOR
2 MANUAL PULL STATION
W/ SOUNDER
2 HEAT DETECTOR
S S S S

FACP
2 2
TO FACP
14 SMOKE DETECTOR
2 MANUAL PULL STATION
W/ SOUNDER

ELEVATOR
1 1

GROUND FLOOR 2ND FLOOR


SCALE 1:100mts SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 4 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-02
A B C D A B C D

6 6
B2 23 MIS B2 26
S S S
S

S S

LIBRARY
5 5

S S S

B2 22 B2 25
S

4 4 S S

S
SUPPLY ROOMS CRIMINOLOGY

3 3
TO FACP
B2 2111 SMOKE DETECTOR
S B2 24
2 MANUAL PULL STATION
W/ SOUNDER

S S

ACADEMIC ROOM S CHS S

FACP
TO FACP
0
5
1

15 SMOKE DETECTOR
2 3 MANUAL PULL STATION 2
W/ SOUNDER

S S S S

1 1

GROUND LEVEL 2ND FLOOR


SCALE 1:100mts SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 2 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-02
A B C D A B C D

6 6

B4 34 B4 38 B4 44 B4 48
S S S

S S

5 5

B4 33 B4 37 B4 43 B4 47
S S S S

4 4
S S
B4 32 B4 36 B4 42 B4 46
S S S S

3 3

B4 31 B4 35 B4 41 B4 45
TO FACP
TO FACP
13 SMOKE DETECTOR
13 SMOKE DETECTOR 2 MANUAL PULL STATION
2 MANUAL PULL STATION S S S
S S S W/ SOUNDER
W/ SOUNDER

2 2

S S S S
ELEVATOR

ELEVATOR
1 1

3RD FLOOR 4TH FLOOR


SCALE 1:100mts
SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 4 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS -03
A B C D A B C D

6 6

5 5

4 4

3 3
TO FACP
TO FACP
13 SMOKE DETECTOR
2 MANUAL PULL STATION 13 SMOKE DETECTOR
2 MANUAL PULL STATION
W/ SOUNDER
W/ SOUNDER

2 2

S S S S

1 1

AS-BUILT

3RD FLOOR 4TH FLOOR


SCALE 1:100mts
SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 2 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-03
A B C D

6
B4 54 B4 58
S S

5
FACP zone 1 S S S S S S S S S S S HD HD S S
B4 53 B4 57
S S
EOL S S

4
S
B4 52 B4 56
zone 2
S S S S S S S S S S S S S S S S EOL

3
zone 3
S S S S S S S S S S S S S EOL
B4 51 B4 55
TO FACP
13 SMOKE DETECTOR
S S S 2 MANUAL PULL STATION
W/ SOUNDER

zone 4
S S S S S S S S S S S S S EOL
2

S S

zone 5
EOL

ELEVATOR
1
S S S S S S S S S S S S

RISER DIAGRAM
5TH FLOOR SCALE NTS
SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 4 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-04
A B C D A B C D

6 6

S S S

5 5

4 4
S S S

ROOF TOP GYM

3 3

TO FACP
13 SMOKE DETECTOR
2 MANUAL PULL STATION
W/ SOUNDER

S S S

S S

2 2
TO FACP
14 SMOKE DETECTOR
S S S 3 MANUAL PULL STATION
S S W/ SOUNDER

1 1

AS-BUILT AS-BUILT

5TH FLOOR ROOF TOP GYM


SCALE 1:100mts SCALE 1:100mts

DATE : This drawing are documents of


Sub-CONTRACTOR : ENGINEER : OWNER : PROJECT TITLE : MAR 2023 information to be used only by SHEET CONTENTS : DRWG NO.:
the
VIVIEN CO PROPOSED 5STY ICCT COLLEGE BLDG. 2 DESIGNED ARCHITECT and General
: MJAE Contractor
FIRE DETECTION ALARM SYSTEM They are the sole property of
MBPA Engineering Services DRAWN
PTR NO.: REG NO.: LOCATION : MJAE _______________________________ AS SHOWN SHEET
ISSUED ON: TIN : and cannot be copied nor NO. :
Cainta, Rizal CHECKED reproducedREP. ACT 545
ISSUED AT: NO.: : without their written ermission
FDAS-04