0% found this document useful (0 votes)
234 views32 pages

KSB RioRioZ

This document provides specifications for Rio and Rio Z circulator pumps with manual speed selection, including: 1) The pumps are designed for hot water heating, heat recovery, and cooling systems and can handle clean water or water with additives like glycol or antifreeze. 2) The Rio pump has a maintenance-free wet rotor and the Rio Z is a twin pump for standby or peak load operation. 3) Materials include cast iron casing, chrome steel shaft, and glass-fiber reinforced polypropylene impeller. Carbon bearings are lubricated by the pumped fluid. 4) Charts and curves show flow rates, heads, and efficiency for single and twin pump configurations

Uploaded by

Srdjan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
234 views32 pages

KSB RioRioZ

This document provides specifications for Rio and Rio Z circulator pumps with manual speed selection, including: 1) The pumps are designed for hot water heating, heat recovery, and cooling systems and can handle clean water or water with additives like glycol or antifreeze. 2) The Rio pump has a maintenance-free wet rotor and the Rio Z is a twin pump for standby or peak load operation. 3) Materials include cast iron casing, chrome steel shaft, and glass-fiber reinforced polypropylene impeller. Carbon bearings are lubricated by the pumped fluid. 4) Charts and curves show flow rates, heads, and efficiency for single and twin pump configurations

Uploaded by

Srdjan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Type Series Booklet

1115.51/6-10 Rio/Rio Z
Circulator Pumps
with Manual Speed Selection

Energy efficiency
Rio Rio Z class
see technical data

Applications Design
F Hot-water heating systems Rio: Maintenance-free wet rotor pump (glandless), flanged or
F Heat recovery systems screw-ended, with three speed levels.
F Cooling circuits in air-conditioning systems Rio Z: Rio twin pump for standby operation (integrated swing
check valve) or on option peak-load operation (parallel opera-
Fluid Pumped tion).
Clean water and/or water treated in accordance with the rele-
vant regulations, not containing aggressive, abrasive or solid
substances.
Bearings
Water with commercial antifreeze agents based on glycols Special plain bearings lubricated by the fluid handled.
(mixture ratio max. 1:1) with inhibitors (antirust). If the glycol
content exceeds 20 %, the operating data must be checked and Materials
verified. Volute casing cast iron EN-GJL-250 5)
Heating water in accordance with VDI 2035. with cataphoretic dip coating
Shaft chrome steel X 46 Cr 13
Operating Data Impeller glass-fibre reinforced polypropylene
Screw-ended pumps Flanged pumps 1) Bearings special carbon, metal-impregnated
Rp 1 and 1 1/4 DN 32 to 100
5) To EN 1561 (previously GG-25)
Q up to 8.6 m3/h, 2.4 l/s up to 120 m3/h, 33.3 l/s 2)
H up to 11 m up to 18 m
P1 up to 390 W up to 3100 W Drive
p 10 bar 6 bar, 10 bar on option Canned motor, IP 44, thermal class H
t --20 ˚C to +130 ˚C 3) --20 ˚C to +130 ˚C 3)
(for short periods (for short periods Connection to power supply
up to +140 ˚C) 4) up to +140 ˚C) 4) 1~230--240 V, 50 Hz
Ambient temperature max. +40 °C. 3~400--415 V, 50 Hz
1) RFI emission to EN 61000-6-3
DN 32 -- DN 65: adapter flanges PN 6/PN 10
2) Interference immunity to EN 61000-6-2
If operated in parallel.
3) Rio/Rio Z 80-150 and 80-200 +110 ˚C
4) Rio/Rio Z 80-150 and 80-200 +130 ˚C

Designation
Rio Z 50 - 100
Type series
Twin pump
Nominal diameter in mm
Discharge head in m x 10 (example 100 =10 m)
Rio/Rio Z

Selection Chart, Single Pumps 2800 rpm

Rio

Selection Chart, Twin Pumps 2800 rpm


The characteristic curves refer to parallel operation of both pumps.

Rio Z

2
Rio/Rio Z

Modular Design Principle

Heat insulation Pump casing

Terminal box

Impeller Cartridge Motor

Sectional Drawing
Energy-saving
-- Highly efficient impeller
-- Heat insulation as standard

Reduction in logistics and


storage costs
-- Flexible installation options thanks
to PN 6 / PN 10 adapter
(oval bolt hole) flange (up to DN 65)

Reliable operation
-- Shaft made of corrosion-resistant
chrome nickel steel
-- Rotor with corrosion-proof
protective sleeve Low operating costs
-- Canned motor with -- Carbon bearings wear-resistant and
condensation-proof winding safe to run dry for short intervals

3
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 25-50 Rio 25-50


Rio 30-50 Rio 30-50
1~230 V -- Rp1/Rp11/4 3~400 V -- Rp1/Rp11/4

Rio 25-70 Rio 25-70


Rio 30-70 Rio 30-70
1~230 V -- Rp1/Rp11/4 3~400 V -- Rp1/Rp11/4

4
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 25-100 Rio 25-100


Rio 30-100 Rio 30-100
1~230 V -- 3~400 V --
Rp1/Rp11/4 Rp1/Rp11/4

Rio 30-40 Rio 30-40


1~230 V -- Rp11/4 3~400 V -- Rp11/4

5
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 40-40 Rio 40-40


1~230 V -- DN 40 3~400 V -- DN 40

Rio 40-70 Rio 40-70


1~230 V -- DN 40 3~400 V -- DN 40

6
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 40-100 Rio 40-150


3~400 V -- DN 40 3~400 V -- DN 40

Rio 50-40 Rio 50-40


1~230 V -- DN 50 3~400 V -- DN 50

7
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 50-70 Rio 50-100


3~400 V -- DN 50 3~400 V -- DN 50

Rio 50-150 Rio 65-70


3~400 V -- DN 50 3~400 V -- DN 65

8
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 65-100 Rio 65-130


3~400 V -- DN 65 3~400 V -- DN 65

Rio 80-70
Rio 65-150
3~400 V -- DN 80
3~400 V -- DN 65

9
Rio/Rio Z

Single Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio 80-100 Rio 80-150


3~400 V -- DN 80 3~400 V -- DN 80

Rio 80-200 Rio 100-100


3~400 V -- DN 80 3~400 V -- DN 100

10
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 30-50 Rio Z 30-50


1~230 V -- Rp 1 1/4 1~230 V -- Rp 1 1/4

Rio Z 30-50 Rio Z 30-50


3~400 V -- Rp 1 1/4 3~400 V -- Rp 1 1/4

Single pump Parallel


operation operation

11
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 32-70 Rio Z 32-70


1~230 V -- DN 32 1~230 V -- DN 32

Rio Z 32-70 Rio Z 32-70


3~400 V -- DN 32 3~400 V -- DN 32

Single pump Parallel


operation operation

12
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 32-100 Rio Z 32-100


1~230 V -- DN 32 1~230 V -- DN 32

Rio Z 32-100 Rio Z 32-100


3~400 V -- DN 32 3~400 V -- DN 32

Single pump Parallel


operation operation

13
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 40-30 Rio Z 40-30


1~230 V -- DN 40 1~230 V -- DN 40

Rio Z 40-30 Rio Z 40-30


3~400 V -- DN 40 3~400 V -- DN 40

Single pump Parallel


operation operation

14
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 40-70 Rio Z 40-70


1~230 V -- DN 40 1~230 V -- DN 40

Rio Z 40-70 Rio Z 40-70


3~400 V -- DN 40 3~400 V -- DN 40

Single pump Parallel


operation operation

15
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 40-100 Rio Z 40-100


3~400 V -- DN 40 3~400 V -- DN 40

Rio Z 40-150 Rio Z 40-150


3~400 V -- DN 40 3~400 V -- DN 40

Single pump Parallel


operation operation

16
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 50-70 Rio Z 50-70


3~400 V -- DN 50 3~400 V -- DN 50

Rio Z 50-100 Rio Z 50-100


3~400 V -- DN 50 3~400 V -- DN 50

Single pump Parallel


operation operation

17
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 50-150 Rio Z 50-150


3~400 V -- DN 50 3~400 V -- DN 50

Rio Z 65-100 Rio Z 65-100


3~400 V -- DN 65 3~400 V -- DN 65

Single pump Parallel


operation operation

18
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 65-130 Rio Z 65-130


3~400 V -- DN 65 3~400 V -- DN 65

Rio Z 65-150
Rio Z 65-150
3~400 V -- DN 65
3~400 V -- DN 65

Single pump Parallel


operation operation

19
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 80-100 Rio Z 80-100


3~400 V -- DN 80 3~400 V -- DN 80

Rio Z 80-150 Rio Z 80-150


3~400 V -- DN 80
3~400 V -- DN 80

Single pump Parallel


operation operation

20
Rio/Rio Z

Twin Pump Characteristic Curves ≈2800 rpm


= Speed level and ηopt.

Rio Z 80-200 Rio Z 80-200


3~400 V -- DN 80 3~400 V -- DN 80

Single pump Parallel


operation operation

Min. Pressure Pipe Connection


Min. pressure p min at the pump suction nozzle to avoid cavita- Flanged pumps fitted with an adapter flange (oval bolt hole pat-
tion noise at an ambient temperature of +40 ˚C and a pumped tern) can be connected to PN 6 and PN 16 mating flanges to
water temperature t: DIN or DIN EN up to nominal diameters of DN 65. Adapter
flanges of this type cannot be connected with other adapter
The values are applicable up to 300 m above sea level. flanges. Use bolts of property class 4.6 or higher for the flange
connections. The washers included in the scope of supply must
For installation altitudes >300 m, +0.01 bar/100 m must be add- be fitted between the bolt / nut head and the adapter (oval bolt
ed. hole) flange.

t 50 ˚C 95 ˚C 110 ˚C 130 ˚C
pmin Recommended bolt lengths:
Rio/Rio Z bar bar bar bar
Rp 1, Rp 1 1/4 0.05 0.5 1.1 2.4 Thread Tightening
g g Min. bolt length
DN 32 0.05 0.5 1.1 2.4 torque DN 32/DN 40 DN 50/DN 65
DN 40 0.05 0.5 1.1 2.4
DN 50 0.3 1.0 1.6 2.9 PN 6 flanged connection
DN 65 0.3 1.0 1.6 2.9
DN 80 0.3 1.0 1.6 2.9 M 12 40 Nm 55 mm 60 mm
DN 100 0.3 1.0 1.6 2.9 PN 10 flanged connection
M 16 95 Nm 60 mm 65 mm
21
Rio/Rio Z

Technical Data

Rio 1) ISO 7/1 Speed Speed P1 P2 Motor Cable Rated current EEC Max. permissible operating pressure
level max p gland 2)
protection to g 3)
terminal 230 V 400 V 230 V PN 6 PN 10
wiring 1~ 3~ 3~
diagram
Rp/DN rpm W W A A A kg kg
max. 2320 100 -- 140 0.65 -- --
25-50 E 1 1640 75 -- 110 50 A 1 0.55 -- -- D -- -- 29 132 121 4.5
min. 1200 55 -- 75 0.35 -- --
max. 2650 85 -- 150 -- 0.40 0.65
25-50 D 1 2190 55 -- 100 50 B 1 -- 0.20 0.35 D -- -- 29 132 122 4.5
min. 1890 40 -- 75 -- 0.15 0.25
max. 2600 140 -- 195 0.95 -- --
25-70 E 1 2300 110 -- 175 90 A 1 0.87 -- -- D -- -- 29 130 550 5.0
min. 1800 85 -- 120 0.62 -- --
max. 2600 120 -- 200 -- 0.45 0.78
25-70 D 1 2100 85 -- 130 90 B 1 -- 0.25 0.43 D -- -- 29 130 551 5.0
min. 1750 65 -- 90 -- 0.17 0.30
max. 2700 225 -- 390 1.90 -- --
25-100 E 1 2550 190 -- 385 180 C 2 1.87 -- -- D -- -- 29 132 123 6.3
min. 2400 165 -- 335 1.72 -- --
max. 2650 190 -- 380 -- 0.78 1.35
25-100 D 1 2250 140 -- 270 180 D 2 -- 0.48 0.84 D -- -- 29 132 124 6.3
min. 1950 115 -- 195 -- 0.35 0.61
max. 2660 145 -- 180 0.85 -- --
30-40 E 1 1/ 4 2340 95 -- 150 70 A 1 0.75 -- -- D -- -- 29 132 125 5.0
min. 1710 70 -- 110 0.55 -- --
max. 2610 95 -- 160 -- 0.40 0.65
30-40 D 1 1/ 4 2120 60 -- 105 70 B 1 -- 0.20 0.35 D -- -- 29 132 126 5.0
min. 1810 40 -- 75 -- 0.15 0.25
max. 2320 100 -- 140 0.65 -- --
30-50 E 1 1/ 4 1640 75 -- 110 50 A 1 0.55 -- -- D -- -- 29 132 127 4.5
min. 1200 55 -- 75 0.35 -- --
max. 2650 85 -- 150 -- 0.40 0.65
30-50 D 1 1/ 4 2190 55 -- 100 50 B 1 -- 0.20 0.35 D -- -- 29 132 128 4.5
min. 1890 40 -- 75 -- 0.15 0.25
max. 2600 140 -- 195 0.95 -- --
30-70 E 1 1/ 4 2300 110 -- 175 90 A 1 0.87 -- -- D -- -- 29 130 552 5.0
min. 1800 85 -- 120 0.62 -- --
max. 2600 120 -- 200 -- 0.45 0.78
30-70 D 1 1/ 4 2100 85 -- 130 90 B 1 -- 0.25 0.43 D -- -- 29 130 553 5.0
min. 1750 65 -- 90 -- 0.17 0.30
max. 2700 225 -- 390 1.90 -- --
30-100 E 1 1/ 4 2550 190 -- 385 180 C 2 1.87 -- -- D -- -- 29 130 554 6.3
min. 2400 165 -- 335 1.72 -- --
max. 2650 190 -- 380 -- 0.78 1.35
30-100 D 1 1/ 4 2250 140 -- 270 180 D 2 -- 0.48 0.84 D -- -- 29 130 555 6.3
min. 1950 115 -- 195 -- 0.35 0.61
max. 2550 155 -- 195 0.95 -- --
40-40 E 40 2100 130 -- 175 90 A 1 0.87 -- -- D -- -- 29 132 129 9.5
min. 1600 100 -- 120 0.62 -- --
max. 2550 145 -- 195 -- 0.45 0.78
40-40 D 40 2050 100 -- 130 90 B 1 -- 0.25 0.43 D -- -- 29 132 130 9.5
min. 1700 70 -- 90 -- 0.17 0.30
max. 2650 250 -- 390 1.93 -- --
40-70 E 40 2450 220 -- 380 180 C 2 1.88 -- -- D -- -- 29 132 131 11.0
min. 2200 200 -- 330 1.70 -- --
max. 2600 220 -- 370 -- 0.76 1.31
40-70 D 40 2100 165 -- 260 180 D 2 -- 0.47 0.81 C -- -- 29 132 132 11.0
min. 1800 130 -- 185 -- 0.33 0.57
max. 2800 300 -- 585 -- 1.17 2.02
40-100 D 40 2500 230 -- 465 350 D 2 -- 0.82 1.43 C -- -- 29 132 133 14.0
min. 2200 200 -- 365 -- 0.65 1.12
max. 2800 500 -- 905 -- 1.84 3.19
40-150 D 40 2500 380 -- 720 570 D 2 -- 1.30 2.25 D -- -- 29 132 134 20.6
min. 2200 330 -- 585 -- 1.05 1.82
max. 2650 280 -- 330 1.62 -- --
50-40 E 50 2450 255 -- 320 180 C 2 1.61 -- -- D -- -- 29 132 135 13.0
min. 1950 235 -- 290 1.51 -- --
max. 2600 245 -- 330 -- 0.71 1.25
50-40 D 50 2100 190 -- 240 180 D 2 -- 0.44 0.78 D -- -- 29 132 136 13.0
min. 1700 145 -- 180 -- 0.32 0.56
max. 2800 360 -- 610 -- 1.19 2.06
50-70 D 50 2450 285 -- 470 350 D 2 -- 0.83 1.43 C -- -- 29 132 137 16.0
min. 2150 245 -- 375 -- 0.66 1.14
max. 2700 450 -- 880 -- 1.73 3.00
50-100 D 50 2300 330 -- 680 450 D 2 -- 1.20 2.09 C -- -- 29 132 138 17.0
min. 2000 280 -- 500 -- 0.89 1.54
max. 2800 1060 --1570 -- 3.13 5.43
50-150 D 50 2500 830 --1260 1100 D 2 -- 2.25 3.90 C -- -- 29 132 139 25.0
min. 2200 720 --1005 -- 1.81 3.14

22
Rio/Rio Z

Technical Data
Rio 1) ISO 7/1 Speed Speed P1 P2 Motor Cable Rated current EEC Max. permissible operating pressure
level max gland 2)
protection to g
p 3)
terminal 230 V 400 V 230 V PN 6 PN 10
wiring 1~ 3~ 3~
diagram
Rp/DN rpm W W A A A kg kg
max. 2800 340 -- 590 -- 1.16 2.01
65-70 D 65 2450 270 -- 470 350 D 2 -- 0.82 1.42 C -- -- 29 132 140 18.5
min. 2150 235 -- 375 -- 0.66 1.14
max. 2650 525 -- 845 -- 1.67 2.89
65-100 D 65 2250 410 -- 630 450 D 2 -- 1.10 1.91 C -- -- 29 132 141 21.1
min. 1950 340 -- 470 -- 0.83 1.44
max. 2800 1000 --1450 -- 2.93 5.07
65-130 D 65 2550 810 -- 1180 1100 D 2 -- 2.10 3.64 C -- -- 29 132 142 25.5
min. 2250 700 -- 960 -- 1.74 3.00
max. 2850 1170 --1685 -- 3.41 5.91
65-150 D 65 2650 925 --1425 1300 D 2 -- 2.53 4.38 C -- -- 29 132 143 29.0
min. 2400 815 --1210 -- 2.18 3.78
max. 2700 560 -- 730 -- 1.53 2.65
80-70 D 80 2400 430 -- 560 450 D 2 -- 1.00 1.74 C 29 132 144 26.0 29 132 145 24.3
min. 2100 350 -- 470 -- 0.79 1.36
max. 2800 1100 --1590 -- 3.13 5.43
80-100 D 80 2500 880 --1290 1100 D 2 -- 2.29 3.96 C 29 132 146 28.0 29 132 147 30.0
min. 2150 745 --1015 -- 1.84 3.19
max. 2900 1610-- 2350 -- 4.81 --
80-150 D 80 2700 1320-- 1995 1800 D 2 -- 3.63 -- C 29 132 148 42.0 29 132 149 42.0
min. 2400 1190-- 1670 -- 3.19 --
max. 2900 2060-- 3100 -- 6.05 --
80-200 D 80 2700 1670-- 2635 2200 D 2 -- 4.73 -- C 29 132 150 44.8 29 132 151 44.8
min. 2450 1490-- 2230 -- 4.24 --
max. 2800 1100 --1590 -- 3.13 5.43
100-100 D 100 2500 880 --1290 1100 D 2 -- 2.29 3.96 C 29 132 152 28.5 29 132 153 30.5
min. 2150 745 --1015 -- 1.84 3.19

1) E = 1~230 V, D = 3~400 V
2) Type of PG cable gland (for each motor) -- 1 = 1 x PG 13.5. 2 = 2 x PG 13.5
3) Energy efficiency class

Wiring Diagrams for Rio / Rio Z


Wiring Diagram A Wiring Diagram B

Power supply 3~400 V, 50 Hz


3~230 V, 50 Hz (with optional switch plug 3~230 V)
Power supply 1~230 V, 50 Hz
Internal protection against excessive winding temperatures
Internal protection against excessive winding temperatures Trip: Internal interruption of motor phase
Trip: Internal interruption of motor voltage Reset: Interrupt mains voltage, let motor cool down, turn mains
Reset: Automatic after motor has cooled down voltage back on

Wiring Diagram C Wiring Diagram D

GFI
TCB

GFI
TCB
Power supply 3~400 V, 50 Hz
Power supply 1~230 V, 50 Hz 3~230 V, 50 Hz (with optional switch plug 3~230 V)

TCB = Thermal circuit breaker Full motor protection with integrated trip electronics in the terminal box
Full motor protection at all speed levels with switchgear DV/DVP for all speed levels
Trip: Internal trip at the switchgear/control device Trip: All poles of motor switched off by integrated trip electronics
Reset: Manual reset at the switchgear/control device required Reset: Manual reset at the terminal box required

Current-carrying capacity of volt-free NC contact to VDI 3814 for gen-


eral fault indication (GFI) 1 A, 250 V~
23
Rio/Rio Z

Technical Data
Rio 1) Speed Speed P1 P2 max Motor
oo Cab e
Cable Rated current EECC Max. permissible operating pressure
level protection to gland 2) 230 V 400 V 230 V
3)
PN 6 PN 10
terminal 1~ 3~ 3~
wiring
DN rpm W W diagram A A A kg kg
max. 2320 100 -- 140 0.65 -- --
Z 30-50 E 1 1/ 4 1640 75 -- 110 50 A 1 0.55 -- -- D -- -- 29 132 154 8.0
min. 1200 55 -- 75 0.35 -- --
max. 2650 85 -- 150 -- 0.40 0.65
Z 30-50 D 1 1/ 4 2190 55 -- 100 50 B 1 -- 0.20 0.35 D -- -- 29 132 155 8.0
min. 1890 40 -- 75 -- 0.15 0.25
max. 2600 140 -- 195 0.95 -- --
Z 32-70 E 32 2300 110 -- 175 90 A 1 0.87 -- -- E -- -- 29 130 574 14.0
min. 1800 85 -- 120 0.62 -- --
max. 2600 120 -- 200 -- 0.45 0.78
Z 32-70 D 32 2100 85 -- 130 90 B 1 -- 0.25 0.43 D -- -- 29 130 575 14.0
min. 1750 65 -- 90 -- 0.17 0.30
max. 2600 260 -- 410 2.05 -- --
Z 32-100 E 32 2500 210 -- 395 180 C 2 1.95 -- -- D -- -- 29 132 156 18.0
min. 2300 185 -- 340 1.75 -- --
max. 2600 210 -- 400 -- 0.79 1.37
Z 32-100 D 32 2200 160 -- 280 180 D 2 -- 0.49 0.84 D -- -- 29 132 157 18.0
min. 1800 130 -- 200 -- 0.35 0.61
max. 2660 145 -- 180 0.85 -- --
Z 40-30 E 40 2340 95 -- 150 70 A 1 0.75 -- -- E -- -- 29 132 158 15.0
min. 1710 70 -- 110 0.55 -- --
max. 2610 95 -- 160 -- 0.40 0.65
Z 40-30 D 40 2120 60 -- 105 70 B 1 -- 0.20 0.35 D -- -- 29 132 159 15.0
min. 1810 40 -- 75 -- 0.15 0.25
max. 2650 250 -- 390 1.93 -- --
Z 40-70 E 40 2450 220 -- 380 180 C 2 1.88 -- -- D -- -- 29 132 160 20.5
min. 2200 200 -- 330 1.70 -- --
max. 2600 220 -- 370 -- 0.76 1.31
Z 40-70 D 40 2100 165 -- 260 180 D 2 -- 0.47 0.81 D -- -- 29 132 161 20.5
min. 1800 130 -- 185 -- 0.33 0.57
max. 2800 300 -- 585 -- 1.17 2.02
Z 40-100 D 40 2500 230 -- 465 350 D 2 -- 0.82 1.43 C -- -- 29 132 162 29.5
min. 2200 200 -- 365 -- 0.65 1.12
max. 2800 500 -- 905 -- 1.84 3.19
Z 40-150 D 40 2500 380 -- 720 570 D 2 -- 1.30 2.25 D -- -- 29 132 163 40.0
min. 2200 330 -- 585 -- 1.05 1.85
max. 2800 360 -- 610 -- 1.19 2.06
Z 50-70 D 50 2450 285 -- 470 350 D 2 -- 0.83 1.43 C -- -- 29 132 164 30.5
min. 2150 245 -- 375 -- 0.66 1.14
max. 2700 450 -- 880 -- 1.73 3.00
Z 50-100 D 50 2300 330 -- 680 450 D 2 -- 1.20 2.09 D -- -- 29 132 165 33.5
min. 2000 280 -- 500 -- 0.89 1.54
max. 2800 1060 -- 1570 -- 3.13 5.43
Z 50-150 D 50 2500 830 -- 1260 1100 D 2 -- 2.25 3.90 D -- -- 29 132 166 50.0
min. 2200 720 -- 1005 -- 1.81 3.14
max. 2650 525 -- 845 -- 1.67 2.89
Z 65-100 D 65 2250 410 -- 630 450 D 2 -- 1.10 1.91 D -- -- 29 132 167 38.2
min. 1950 340 -- 470 -- 0.83 1.44
max. 2800 1000 -- 1450 -- 2.93 5.07
Z 65-130 D 65 2550 810 -- 1180 1100 D 2 -- 2.10 3.64 D -- -- 29 132 168 50.0
min. 2250 700 -- 960 -- 1.74 3.00
max. 2850 1170 -- 1685 -- 3.41 5.91
Z 65-150 D 65 2650 925 -- 1425 1300 D 2 -- 2.53 4.38 D -- -- 29 132 169 55.5
min. 2400 815 -- 1210 -- 2.18 3.78
max. 2800 1100 -- 1590 -- 3.13 5.43
Z 80-100 D 80 2500 880 -- 1290 1100 D 2 -- 2.29 3.96 D 29 132 170 54.5 29 132 171 56.0
min. 2150 745 -- 1015 -- 1.84 3.19
max. 2900 1610 -- 2350 -- 4.81 --
Z 80-150 D 80 2700 1320 -- 1995 1800 D 2 -- 3.63 -- D 29 132 172 78.6 29 132 173 78.6
min. 2400 1190 -- 1670 -- 3.19 --
max. 2900 2060 -- 3100 -- 6.05 --
Z 80-200 D 80 2700 1670 -- 2635 2200 D 2 -- 4.73 -- D 29 132 174 85.1 29 132 175 85.1
min. 2450 1490 -- 2230 -- 4.24 --
1) E = 1~230 V, D = 3~400 V
2) Type of PG cable gland (for each motor) -- 1 = 1 x PG 13.5. 2 = 2 x PG 13.5
3) Energy efficiency class

24
Rio/Rio Z

Rio Outline Drawings


A B

C D

Rio Pipe connection/ Thread Pump dimensions Weight Outline


Nom. diameter approx. drawing
kg
Rp/DN G I0 I2 a1 a2 a3 l1 b1 b2 b3 b4 b5 PN 6/10
25-50 Rp 1 G 1 1/2 180 92 150 40 65 90 50 52 88 60 44 4.5 A
25-70 Rp 1 G 1 1/2 180 92 165 34 56 90 66 56 80 60 44 5.0 A
25-100 Rp 1 G 1 1/2 180 102 172 45 68 90 69 68 92 66 66 6.3 B
30-40 Rp 1 1/4 G2 180 92 156 50 65 90 53 65 88 60 44 5.0 A
30-50 Rp 1 1/4 G2 180 92 150 40 65 90 50 52 88 60 44 4.5 A
30-70 Rp 1 1/4 G2 180 92 172 34 64 90 66 57 88 60 44 5.0 A
30-100 Rp 1 1/4 G2 180 102 172 45 68 90 69 68 92 66 66 6.3 B
40-40 40 -- 220 102 178 54 76 110 83 60 103 60 44 9.5 C
40-70 40 -- 250 102 193 46 72 125 78 62 97 66 66 11.0 D
40-100 40 -- 250 109 216 58 88 125 90 79 121 66 66 14.0 D
40-150 40 -- 250 119 258 55 83 125 99 86 135 66 66 20.6 D
50-40 50 -- 240 102 199 52 80 120 93 64 112 66 66 13.0 D
50-70 50 -- 280 109 224 65 82 140 91 77 119 66 66 16.0 D
50-100 50 -- 280 109 222 70 91 140 101 86 123 66 66 17.0 D
50-150 50 -- 340 119 242 81 113 170 105 90 137 66 66 25.0 D
65-70 65 -- 280 109 234 74 97 140 111 86 124 66 66 18.5 D
65-100 65 -- 340 109 241 67 97 170 110 89 132 66 66 21.1 D
65-130 65 -- 340 119 253 80 100 170 118 98 136 66 66 25.5 D
65-150 65 -- 340 119 283 80 100 170 118 98 136 66 66 29.0 D
80-70 80 -- 360 119 227 96 130 180 111 87 135 66 66 26.0 D
80-100 80 -- 360 119 258 95 130 180 135 108 159 66 66 28 / 30 D
80-150 80 -- 360 143 316 89 119 180 129 108 150 66 66 42.0 D
80-200 80 -- 360 143 316 89 119 180 129 108 150 66 66 44.8 D
100-100 100 -- 360 119 258 95 130 180 135 108 159 66 66 28.5/30.5 D
25
Rio/Rio Z

Flange Dimensions
Rio Flange Nom. Pump flange dimensions
diameter
DN ∅D f1 f2 ∅d ∅k/ n x dL /
∅ kL1/kL2 n x dL1/dL2
40-40 Adapter flange PN 6/10 40 150 65 65 84 100 / 110 4 x ∅ 14/19
40-70 (selected as for PN 16, to EN 1092-2)
40-100
40-150
50-40 Adapter flange PN 6/10 50 165 70 70 99 110 / 125 4 x ∅ 14/19
50-70 ((selected as for PN 16,, to EN 1092-2))
50-100 75
50-150 75 83
65-70 Adapter flange PN 6/10 65 185 80 80 118 130 / 145 4 x ∅ 14/19
65-100 (selected as for PN 16, to EN 1092-2)
65-130
65-150
80-70 Flange PN 6 80 200 90 90 132 150 4 x ∅ 19
(selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2) 160 8 x ∅ 19
80-100 Flange PN 6 80 200 90 98 150 4 x ∅ 19
(selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2) 138 160 8 x ∅ 19
80-150 Flange PN 6 80 200 90 90 132 150 4 x ∅ 19
80-200 (selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2) 80 200 90 90 132 160 8 x ∅ 19
100-100 Flange PN 6 100 220 100 100 156 170 4 x ∅ 19
(selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2)
1092 2) 180 8 x ∅ 19
26
Rio/Rio Z

Outline Drawings Rio Z


A B

C F

Rio Z Pipe connection/ Thread Pump dimensions Weight Out-


Nom. diameter line
approx. kg d
dra-
Rp/DN G I0 I1 I2 a1 a2 b1 b2 b4 b5 y1 y2 z1 PN 6/10 wing

30-50 Rp 1 1/4 G2 180 105 92 150 40 112 112 120 102.5 -- -- -- 8.0 A
32-70 32 -- 220 115 99 172 38 126 119 123 107 -- -- -- 14.0 B
32-100 32 -- 220 110 102 173 60 144 143 141 141 107 11 172 18.0 C/F
40-30 40 -- 250 135 92 156 75 126 133 123 107 108 14 154 15.0 B
40-70 40 -- 250 135 104 193 75 150 140 153 153 108 11 172 20.5 C/F
40-100 40 -- 250 135 111 216 75 178 172 167 167 132 35 225 29.5 C/F
40-150 40 -- 250 125 119 258 65 200 195 172 172 132 25 225 40.0 C/F
50-70 50 -- 280 160 111 224 82.5 179 169 167 167 132 30 225 30.5 C/F
50-100 50 -- 280 155 111 222 82.5 198 192 176 176 157 50 228 33.5 C/F
50-150 50 -- 340 170 119 243 86 214 201 173 173 184 30 252 50.0 C/F
65-100 65 -- 340 170 109 241 81 214 201 172 172 180 25 225 38.2 C/F
65-130 65 -- 340 185 120 253 92.5 223 209 187 187 162 25 225 50.0 C/F
65-150 65 -- 340 185 120 283 92.5 223 209 187 187 162 25 225 55.5 C/F
80-100 80 -- 360 205 120 253 100 249 231 183.5 206 180 43 240 54.5/56.0 C/F
80-150 80 -- 360 180 143 316 90 259 248 201 201 185 20 270 78.6 C/F
80-200 80 -- 360 180 143 316 90 259 248 201 201 185 20 270 85.1 C/F
27
Rio/Rio Z

Flange Dimensions
Rio Z Flange Nom. Pump flange dimensions
diameter
DN ∅D f1 f2 ∅d ∅k n x dL
∅ kL1/kL2 n x dL1/dL2
32-70 Adapter flange PN 6/10 32 140 -- -- 78 90 / 100 4 x ∅ 14/19
(flange PN 16 to DIN 2533)
32-100 Adapter flange PN 6/10 60 60
(flange PN 16 to EN 1092-2)
40-30 Adapter flange PN 6/10 40 150 -- -- 88 100 / 110 4 x ∅ 14/19
(selected as for PN 16, to DIN 2533)
40-70 Adapter flange PN 6/10
40-100 (selected as for PN 16, to EN 1092-2)
40-150 Adapter flange PN 6/10 65 65 84
(selected as for PN 16, to EN 1092-2)
50-70 Adapter flange PN 6/10 50 165 -- -- 102 110 / 125 4 x ∅ 14/19
50-100 (selected as for PN 16, to EN 1092-2)
50-150 Adapter flange PN 6/10 65 82,5 99
(to DIN 2533, to EN 1092-2)
65-100 Adapter flange PN 6/10 65 185 80 80 118 130 / 145 4 x ∅ 14/19
(selected as for PN 16, to EN 1092-2)
65-130 Adapter flange PN 6/10 -- -- 122
65-150 (selected as for PN 16, to EN 1092-2)
80-100 Flange PN 6 80 200 -- -- 132 150 4 x ∅ 19
(selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2) -- -- 160 8 x ∅ 19
80-150 Flange PN 6 90 90 150 4 x ∅ 19
80-200 (selected as for PN 16, to EN 1092-2)
Flange PN 16 (to EN 1092-2) 160 8 x ∅ 19
28
Rio/Rio Z

Pump Accessories
Rio/Rio Z

Rp 1 1/4

DN 100
DN 40
DN 50
DN 65
DN 80
Rp 1
Ident. No. ~kg
Y-pipes for twin pumps suction side X 40 000 688 12.0
PN 10 / 16 discharge side X 40 000 679 13.0
Scope of supply: bolts, nuts, suction side X 40 000 689 15.0
gaskets and integrated changeover discharge side X 40 000 680 17.0
flap (on discharge side only) suction side X 40 000 690 19.0
discharge side X 40 000 681 20.0
suction side X 48 936 065 25.0
discharge side X 48 936 202 28.0
suction side X 40 000 692 33.0
discharge side X 40 000 440 35.0
Screw union set with internal thread
of malleable cast iron X 40 980 836 0.2
X 40 980 837 0.2

Extension Modules and Electrical Accessories


Rio
25-50 E 25-50 D 25-100 E 25-100 D
25-70 E 25-70 D 30-100 E 30-100 D
30-40 E 30-40 D 40-70 E to
30-50 E 30-50 D 50-40 E 100-100 D
30-70 E 30-70 D Z 32-100 E Z 32-100 D
40-40 E 40-40 D Z 40-70 E to
Z 30-50 E Z 30-50 D Z 80-200 D
Z 32-70 E Z 32-70 D
Z 40-30 E Z 40-30 D Ident. No. kg
Function modules
Plug-in modules for type series Rio and Rio Z
(2 modules required) with mains connection
1~230 V, 50 Hz, (E) or 3~400 V, 50 Hz (D)

Additional functions:
-- Fault message (SSM)
-- ”In operation” message (SBM)
-- Control input ”Priority off”
-- Blocking detector with trip
-- Full motor protection with trip
-- Twin pump management (Rio Z)
Type 22 E X 01 100 533 0.6
Type 22 D X 01 100 534 0.6
Type 32 E X 01 100 535 0.6
Type 32-52 D X 01 100 536 0.6
Switch plug X X 01 084 050 0.1
for connecting Rio and Rio Z
with three-phase current motor
to 3~230 V 50 Hz

Switchgear DVP 84x130x66 X 01 018 335 0.35


Switchgear as above, but with volt-free
contacts for operation and fault reporting.

29
Rio/Rio Z

Additional functions of function modules Wiring diagram for single pumps Rio

KSB function module


Type 22 E -- 1~230 V
Mains terminals

F Fault message SSM as volt-free NC contact, can be set


as individual or general fault message Control terminals
F ”In operation” message SBM as volt-free NO contact, can
be set as individual or general fault message
F Control input ”Priority off” by external volt-free (NC) con-
tact
F Blocking message of the pump is recognized and reported
as fault
F Full motor protection with integrated trip
Type 32 E -- 1~230 V
F Fault acknowledgement
F Integrated twin pump management with the following
functions (Rio Z only) Mains terminals
-- Duty/stand-by operation with switchover from duty to
stand-by pump after 24 operating hours
-- Fault-based switchover to stand-by pump ready for
operation

Technical data of function modules


Ambient temperature: max. +40 ˚C Control terminals
Fluid temperature: --20 °C to +110 ˚C
Weight: approx. 0.6 kg
Enclosure: IP 44
Interference suppression class: N
Thermal class: F
4 cable entries Pg 9 (control cable max. 6-core)
No separate mains supply required. Type 22 D -- 3~400 V
Mains terminals
Terminal diameter: max. 2.5 mm2 Mains terminals
Message terminals
Max. switching capacity 250 V/1 A
Terminal diameter: max. 2.5 mm2

Control terminals Ext.Off Control terminals


Min. contact rating: 24 VDC, 10 mA
Terminal diameter: min. 0.75 mm2, max. 2.5 mm2

Dimensional drawing of function modules

Type 32-52 D -- 3~400 V

Mains terminals

Module as ls Control terminals


Type 22 E 27 61
Type 22 D 27 61
Type 32 E 28 63
Type 32-52 28 63
30
Rio/Rio Z

Wiring diagram for twin pumps Rio Z


KSB function module
Type 22 E -- 1~230 V

Mains terminals Mains terminals

Control terminals Control terminals

To be supplied by the owner/


operator: 2-core connection
cable, min. 2 x 0.75 mm2
Connection protected
against polarity reversal.
Type 32 E -- 1~230 V

Mains terminals Mains terminals

Control terminals Control terminals


To be supplied by the owner/
operator: 2-core connection
cable, min. 2 x 0.75 mm2
Connection protected
against polarity reversal.
Type 22 D -- 3~400 V

Mains terminals Mains terminals

Control terminals Control terminals


To be supplied by the owner/
operator: 2-core connection
cable, min. 2 x 0.75 mm2
Connection protected
against polarity reversal.
Type 32-52 D -- 3~400 V

Mains terminals Mains terminals

Control terminals Control terminals


To be supplied by the owner/
operator: 2-core connection
cable, min. 2 x 0.75 mm2
Connection protected
against polarity reversal.

31
Rio/Rio Z

1115.51/6-10 / 1.10.2008 Subject to technical modification without prior notice.

You might also like