0% found this document useful (0 votes)
120 views3 pages

403-0006 Sita Manual Call Point: Installation and Maintenance Instructions

This document provides installation and maintenance instructions for the Sita Manual Call Point. It is an addressable fire alarm device that attaches to the loop of compatible control panels. It allows for user activation of the fire alarm system and latches into the alarm position until manually reset. The instructions cover device spacing, installation including wiring specifications, resetting and testing procedures, and technical specifications.

Uploaded by

amartins1974
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
120 views3 pages

403-0006 Sita Manual Call Point: Installation and Maintenance Instructions

This document provides installation and maintenance instructions for the Sita Manual Call Point. It is an addressable fire alarm device that attaches to the loop of compatible control panels. It allows for user activation of the fire alarm system and latches into the alarm position until manually reset. The instructions cover device spacing, installation including wiring specifications, resetting and testing procedures, and technical specifications.

Uploaded by

amartins1974
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

INSTALLATION AND MAINTENANCE INSTRUCTIONS

403-0006 Sita Manual Call Point

General Description
The Sita Manual Call Point allows for user activation of the fire alarm system. An
optional clear front cover is available if required (Part No. 25-0083-303). Once
operated the device latches into the alarm position and requires manually resetting
via a special key. The MCP is an addressable unit that attaches to the loop. Digital
communication technology to the control panel is implemented allowing for accurate
data transfer at high transmission speeds. This device is only compatible with the
Sita200plus, Duonet and Quadnet ranges of control panel.

Before Installation
The MCP must be installed in compliance with the control panel installation manual.
The installation must also meet the requirements of any local authority. For maximum
performance the call point should be installed in compliance with
BS5839 Pt1 : 2002 + A2 : 2008.

Spacing

Fike recommends spacing of call points in accordance with BS5839 Pt1 2002. For more specific information
regarding MCP spacing, placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008.

Device Installation

All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any
special recommendations documented in the control panel installation manual. All wiring must be installed in
compliance with the recommendations laid out by BS 5839 as well as any special recommendations documented in
2
the control panel installation manual. The cabling used should be of a 2-core 1.5mm screened, fire resistant
type, with the following characteristics:

Max Capacitance Core to Screen ................................................... 180pF / m


Max Capacitance Core to Core....................................................... 100pF / m
Max Inductance............................................................................... 1.0mH / km
Max Resistance Two Core Screened 1.5mm² ................................ 12.1Ω / km

It is to be wired in the form of a screened 2-core loop returning to the control panel. The use of spurs on
this system is not permitted. Cables may be terminated into the connectors, as shown overleaf. If the device is
flush mounted then the loop cabling must be attached to the device via a suitable connection block (not supplied).
Cut off crimp fork terminals, strip ends for desired length and twist conductor strands together neatly as shown
below. Terminate your cables directly into a flying terminal block. If using a metal back box, do not connect the
screen to the back box earth terminal or allow it to come into contact with the metal box

26-1075 Issue 4
Care should be taken when terminating devices to ensure all cables are correctly sleeved and connections are
secure. Improper connections will prevent a system from responding properly in the event of a fire.

Terminal Description Y

RED Loop +ve IN E YELLOW


YELLOW Loop +ve OUT
BLUE Loop -ve IN and OUT BLUE RED

E Screen IN and OUT B R

The Loop +ve (positive) IN and the Loop +ve (positive) OUT connections are split within the module. For cable
continuity readings at the commissioning stage they must be temporarily removed and connected through. Please
remember that all high voltage testing must be carried out before the installation of the electronics, otherwise the
electronics will be damaged. Please also note that the E terminal should only be connected to the loop screen and
NOT to the building earth.

Once all testing has been carried out on the cabling and continuity & insulation has been proven,
the MCP can be connected, with each of the three wires from the MCP front being connected to the
corresponding terminal in the backbox according to the wire colour. The MCP front may then be
installed by locating the upper mounting hook into the receiver in the back box and then pushing the
unit gently home. The single fixing screw may then be tightened as required.

NOTE: Before installing the MCP remember to note the serial number of the device (located on the rear of the unit)
on to your drawings or configuration sheets to enable you to prove its location later. The address allocation for the
device is carried out automatically by the control panel whilst in initialisation mode, so addresses do not need to be
set manually. See the system Installation and Operating Instructions for further details.

Reset and Test


The Manual Call Point contains a re-settable element, which latches in position when
operated and does not need to be replaced. Inserting the key as shown and turning it
clockwise until the element clicks back into place will reset the unit. Testing the Call Point
may be carried out either by pressing the element or by using the key in the same
manner as for resetting but without having pressed the element

Technical Data
Dimensions: Width x Height 87mm x 87mm
Depth: Standard inc base 53mm
Depth: Flush mounted 25mm
Flush Back Box Dimensions: Required Minimum Depth 47mm
o o
Operating Temperature: -10 C to +50 C.
Voltage Range (Loop): 24 to 42V DC
LED Indication: Activated 0.3s interval
Flammability UL94-V2
IP Rating IP 21C
System Compatibility: Sita200plus V2.00 onwards.
Duonet and Quadnet V1 onwards.

26-1075 Issue 4
PRODUCT DESCRIPTION LOOP CURRENT (mA)

Product
Type Name Quiescent Alarm Low Medium High
Code

MCP 403 0006 Sita Manual Call Point Mk3 0.18 2.89 - - -

BATTERY CURRENT (mA)

Product
Type Name Quiescent Alarm Low Medium High
Code

MCP 403 0006 Sita Manual Call Point Mk3 0.18 6.00 - - -

DLU RATING

Product
Type Name Alarm Low Medium High
Code

MCP 403 0006 Sita Manual Call Point Mk3 3 - - -

0832
Technical Support
Fike Safety Technology Ltd
Contact your supplier for technical support on this Unit 31, Springvale Ind. Est.
product. Torfaen, NP44 5BD
Due to the complexity and inherent importance of a life risk 11
type system, training on this equipment is essential, and DoP-403-0006
commissioning should only be carried out by competent EN54-11: 2001 +A1: 2005, EN54-17: 2005
persons. Fike cannot guarantee the operation of any Isolator Technical Data: See 26-1112
equipment unless all documented instructions are complied
with, without variation. This unit complies with the EMC 403-0006
directive.
Intended for use in the fire detection and fire
Fike’s policy is one of continual improvement and the right to alarm
change a specification at any time without notice is reserved. Systems in and around buildings
Whilst every care has been taken to ensure that the contents Essential characteristics Performance
of this document are correct at time of publication, Fike shall Nominal activation
be under no liability whatsoever in respect of such contents. conditions/Sensitivity,
E&OE. Response delay (response time) and Pass
performance
under fire conditions
Operational reliability Pass
Tolerance to supply voltage Pass
Durability of operational reliability and
Pass
response delay, Temperature resistance
Durability of operational reliability,
Pass
Vibration resistance
Durability of operational reliability,
Pass
Humidity resistance
Durability of operational reliability,
Pass
Corrosion resistance
Durability of operational reliability,
Pass
Electrical stability
Performance under fire conditions Pass

26-1075 Issue 4

You might also like