Machine Lab Combine
Machine Lab Combine
Machine Lab Combine
APPARATUS REQUIRED: -
CIRCUIT DIAGRAM: -
But, Eb = =K
Hence, V =K + IaRa
N= Kᶦ
i. An increase in the IaRa drop will decrease the value of speed if V remains
constant.
ii. Speed varies inversely as the field flux and hence varies inversely as the
exciting current, if below saturation.
(a) Field Diverter- The series winding are shunted by a variable resistance
known as field diverter. Any desired amount of current can be passed
through the divertor by adjusting its resistance. Hence the flux can be
decreased and consequently, the speed of the motor increased.
(b) Armature Divertor- A divertor across the armature can be used for giving
speeds lower than the normal speed. For a given constant load torque.
(c) Variable resistance in series with Motor- By increasing the resistance in
series with the armature the voltage applied across the armature terminals
can be decreased. With reduced voltage across the armature, the speed is
reduced.
Procedure: -
Observations:-
Total
S.NO Speed Id If
current(I)
Total
S.NO Speed Id Ia
current(I)
S.NO Speed I Va
Graphs:
Case a: - plot a graph between speed along y-axis and total current (I) along x-
axis.
Case b: - plot a graph between speed along y-axis and total current (I) along x-
axis.
Case c: - plot a graph between speed along y-axis and voltage across armature
(Va) along x-axis
Discussion:-
1. Compare the three methods and discuss the advantages and disadvantages
of each method.
2. Discuss the graph you obtained.
Retardation Test on DC Shunt Motor
Aim of the experiment: - To separate the mechanical and iron losses of the
given dc shunt machine.
Apparatus Required: -
Let the rated speed of the machine is N rpm. Let the machine be brought up to a
speed of (N+ ) rpm as a motor where N is conveniently chosen small value.
If the armature supply is now suddenly removed, the speed of the motor will
fall. Let the time taken for the speed to reach (N- ) rpm is ΔT Sec.
Average rate of fall of speed = rad/sec2. This is assumed as the rate of fall
of speed when speed is N rpm. The retarding torque at N rpm is J
joules/radians, where, J is the moment of inertia of the rotor in kg – m2. The
corresponding retarding power is NJ watts. This obviously equals
the losses in the machine at the rated speed.
In the experiment, the rate of fall of speed is observed under three different
conditions. In every case, the armature is run upto the speed (N+ ) rpm as a
motor on no load.
I condition: Supplies to both armature and field are simultaneously removed
such that the armature and field current are zero. The only losses which retard
the motor are mechanical losses.
II condition: Supply to the armature is removed while the field supply is
retained. Here in addition to the mechanical losses, iron losses are also present
and retard the motor.
III condition: Field supply is retained, armature supply is removed and the
armature is connected to a load resistance. In this case the machine functions as
a generator. Mechanical losses, Iron losses and the power converted to heat in
circulating current through the armature and load resistances, all contribute in
retarding the motor, and speed falls down most rapidly.
The power converted to heat in the armature and the load resistance in the III
condition is calculated. Hence, the iron losses, mechanical losses and moment
of inertia of the rotor can be calculated from the above conditions.
When the motor is running at the rated speed with normal excitation, let the
mechanical and iron losses be Wm and Wi watts respectively and moment of
inertia of the rotor is J kg – m2.
Let , and be the rates of fall of speed in rpm/sec under the I, II
and III conditions respectively. Let the average copper losses due to generator
action in the third condition of the test be WCu.
(3) – (1) gives us an expression for WCu, in which all the terms (including WCu)
except J are known. So, J can be calculated. We can get Wm and Wi from (1)
and (2).
At the instant, the armature is disconnected from the supply and thrown to the
load,
When the speed reaches (N - ) rpm, let these values be VL2 and IL2
respectively. Average load voltage and load current during the period of
retardation are
Where, Ra is the armature resistance, which has to be separately measured.
Procedure: -
Current(I) Voltage(V) R=
Sl.No RAvg(Ω)
(in Amp) (in volts) (in ohm)
N =
T1=
T2=
T3=
In case III, at the instant the armature is disconnected from the supply,
Load voltage =
Load current =
At the instant when speed reaches 2900 rpm,
Load voltage =
Load current =
Armature resistance Ra =
Swinburne’s Test
Aim of the experiment: To pre-determine the efficiency of a D.C shunt
machine considering it as a motor by performing Swinburne’s test on it.
Apparatus Required:
Theory:
Testing of D.C. machines can be divided into three methods: (a) direct, (b)
regenerative, and (c) indirect. Swinburne’s Test is an indirect method of testing
a D.C. machine. In this method, the constant losses of the D.C. machine are
calculated at no-load. Hence, its efficiency either as a motor or as a generator
can be pre-determined. In this method, the power requirement is very small.
Hence, this method can be used to pre-determine the efficiency of higher
capacity D.C. machines as a motor and as a generator.
Disadvantages:
(1) Efficiency at actual load is not accurately known.
(2) Temperature rise on load is not known.
(3) Sparking at commutator on load is not known.
Power input at No-load = Constant losses + Armature copper losses
Power input at No-load = Constant losses
Power input = Va Ia + Vf If
Losses in a D.C. Machine:
The losses in a D.C. machine can be divided as 1) Constant losses, 2) Variable
losses, which changes with the load.
Constant losses:
Mechanical Losses: Friction and Windage losses are called mechanical losses.
They depend upon the speed. A D.C. shunt machine is basically a constant
speed machine both as a generator and as a motor. Thus, the mechanical losses
are constant.
Iron Losses: For a D.C. shunt machine, the field current hence the flux. Hence,
hysteresis and eddy current losses (which are also called as iron losses) remain
constant.
Field Copper Losses: Under normal operating conditions of a D.C. shunt
machine, the field current remains constant. Thus, power received by the field
circuit (which is consumed as field copper losses) is constant.
Constant losses in a D.C. shunt machine = Mechanical losses + Iron Losses + Field
copper losses
Variable Losses:
The power lost in the armature circuit of s D.C. machine increases with the
increase in load.
Thus, the armature copper losses are called as variable losses.
Efficiency of a D.C. machine:
% Efficiency = (Output Power/ Input Power) x100
As a generator Input power, Pin = (Pout) + (constant losses) + (armature copper
losses at a given load Ia2Ra
Pout = VLIL
where, Ia = IL + If self-excited generator (Vf.If is not encountered for Pin)
Ia = IL separately excited generator
Note: While calculating the armature copper losses on load condition, the hot
resistance of the armature = 1.2Ra (normal temperature) is considered.
Procedure:
Current(I) Voltage(V) R=
Sl.No RAvg(Ω)
(in Amp) (in volts) (in ohm)
Observations for Swinburne’s test:
At no-load (separately excited D.C. motor):
Speed =
Armature voltage =
Field voltage =
Armature current =
Field current =
Armature resistance =
Field resistance =
As a Motor:
As a Generator:
Formula:
Armature copper loss = Ia2Ra
Field copper loss = If2Rf
Armature input = VaIa
Mechanical loss + iron loss = armature input – armature copper loss
Total constant loss = Mechanical loss + iron loss + field copper loss
Efficiency as a motor:
Input to the motor = input to the armature (VaIa) + input to the field (VfIf)
Total loss = constant loss + armature copper loss
Output = input – total losses
Efficiency, m=output/input
Efficiency as a generator:
Output= VaIa
Total loss= constant losses + armature copper losses
Input = output + total losses
Efficiency, g = output/input
Graph:
Draw the graph between Efficiency and IL of the machine as a motor and as a
generator on the same graph sheet.
Model Graph:
Measurement of Armature and Field Winding Resistances
Aim of the Experiment - To measure the field and armature resistance of a DC
machine by ammeter and voltmeter method and to study the variations of these
resistances.
APPARATUS REQUIRED-
Field Winding-The field winding is connected in shunt with the armature winding.
It has larger number of turns with small cross-section and they are usually used to
excite the field poles, hence are also called as exciting winding. As the field circuit
resistance is increased, the excitation increases to a point, after this the dc machine
fails to exite which is called as the critical resistance for that machine. Generally
this winding is made up of copper.
Armature winding- It consists of large no. of insulated coils each having one or
more turns. These are made up of copper and usually form wound. These placed in
slots and approximately connected in series and parallel depending upon the type
of winding required i.e lap winding or wave winding. The resistance of both the
winding can be calculated with the use of ohm’s law i.e, R= . As the resistance of
winding are responsible for the speed control of the dc shunt motor i.e, increase in
armature resistance increase the speed and increase in field resistance is also
responsible to operate. The shunt motor above/below the rated speed.
PROCEDURE-
(1) Make connections as given in (1) of circuit diagram. Keep the rheostat in the
maximum resistance position and switch the supply. Adjust rheostat so that a
certain current flows. Take the readings of ammeter and voltmeter at one
minute interval. Continue for 15 mins.
(2) Change the current of the circuit by adjusting the rheostat. Take the readings
of ammeter and voltmeter after allowing current to flow for sufficient value.
Repeat for several value of currents till maximum current consistent with
rheostat reading flows.
(3) Repeat step 1 and 2 for armature circuit.
OBSERVATION
Current(I) Voltage(V) R=
Sl.No RAvg(Ω)
(in Amp) (in volts) (in ohm)
DISCUSSION-
Q1) What is the difference between armature winding and field winding ʔ
Q3) Why the field winding resistance is high as compared to the armature winding
resistance ʔ
DETERMINATION OF EFFICIENCY AND PERCENTAGE
REGULATION OF TWO IDENTICAL TRANSFORMERS BY BACK TO
BACK TEST AT DIFFERENT LOAD AND POWER FACTOR
Apparatus: -
Circuit Diagram: -
W1
2.5A
2A
M L
P A1 P
C 300V
230V V1 250V
N N
C 230V C 230V
Pri
Sec
C 230V C 230V
V3
1 Variac W2 600V
10A
M V2
L A2 30/60V
150V
C 10/20A
Input
Theory:
ATN: Two identical transformers are operated with back to back connection in
order to determine their efficiency and regulation at different load and power
factor.
1. Keeping auto transformer output voltage as zero, full supply voltage is given
to primary windings, W1,V1 and A1 will read no load power loss, voltage and
current regularly.
2. Now a very small voltage is injected to secondary side by auto transformer,
the auto transformer output voltage is so adjusted that desired current (full
load, % load or over load) circulates in secondary ckt. This adjusted current
will be reflected on primary side also, but as secondary’s are in opposition,
reflected current in primary side will circulate in both the windings only
without affecting reading of ammeter A1 & wattmeter W1. Thus wattmeter
W1 will always read no load loss. Copper loss which takes place due to
circulating full load or over load or % load currents in both the transformers
will be supplied by auto transformer and W2 will record it.
3. Take reading of all instruments, adjusting auto transformer output from zero
to a value which does not cause more than 125% of rated current.
4. Tabulate the results as follows :
Computed result
Sl.No. V1 I1 W1 V2 I2 W2
Efficiency Regulation
5. From the above reading find out R0, X0, R, X of transformer & calculate
efficiency and regulation at different load at 0.8 and power factors. Draw
equivalent circuit and vector diagrams at full load and 0.8 p.f.
6. Draw load current vs. efficiency, Regulation, copper loss and iron loss on
same graph paper. Observe that maximum efficiency point to point of
intersection of copper loss and iron loss curves, are at the same load current.
Aim of the Experiment: - To perform load test on DC shunt motor & plot the
performance characteristics curve.
Apparatus Required: -
CIRCUIT DIAGRAM: -
THEORY: -
The shunt motor is the one in which field windings are in parallel with armature.
The current Ia is opposite to back emf E,
Therefore,
V = E + IaRa
Where,
V = Applied voltage
T = KɸIa
This Expression reveals that if the flux ɸ is constant as in a shunt motor, the torque
would increase linearly with armature current Ia, however larger be the Ia the net
flux decreases due to the demagnetizing effect of armature reaction.
Wm =
T = G.b
b= Arm length
PROCEDURE: -
B.H.P =
ɳele =
ɳ mech =
OBSERVATION: -
Sl. Voltag IL (A) Speed b VIL H.P Torque B.H. ɳele ɳmec
No. e (N) (arm (N-M) P h
(V) Ia If (rpm) length) G.b
FORMULA USED: -
1. O/P Power =
Where IL = Ia + If
5. Efficiency(ɳ) = =
DISCUSSION: -
Apparatus: -
Quantity (in
SL.No. Name of item Specification
nos.)
1 Voltmeter 0-300/600V,MI 1
Theory: -
When all the three 1 phase transformer are put in one unit, central limb becomes
useless, as it carries sum of three fluxes which are equal in magnitude but 120˚
apart to each other. As such the sum is zero and central limb is removed. Finally
we have the shape of a 3 phase transformer as shown above, having 3 limbs,
each having a primary and secondary. All the three primary and or secondary
can be so connected that they may form a (a) star-delta or (b) star-star or (c)
delta-star or (d) delta-delta system.
In the experiment 3 single phase transformer are taken and their primaries and
secondary’s are connected in star-star and star-delta ways.
Note: - In the laboratory connect all primaries in star, as supply voltage is 400
V line to line and each transformer winding is rated for 230 volts. Thus with
primaries connected in star, voltage across each phase (primary) will be 400/√
=230 volts (which is the rating of transformer and transformer will be safe).
1. Connect primaries in star. On the secondary side connect the phases in star.
Measure voltage between two line terminals. If it is √ times phase voltage then
connection for those two phases is correct (if not reverse connection of one
phase). After this measure the voltage across third terminals and line terminal of
any previous phase. If it reads √ times phase voltage then connection for third
phase is correct.
If not reverse the connections for third phase. The above measurements are
drawn to ensure that all neutrals of 3 winding are connected only, to form star
neutral point.
1. After completing run (b) open the star point. Mark terminals according to
scheme given in connection diagram. Connect the 50% tapping points so as to
get a double star connection. Measure voltage between line to neutral, between
adjacent points and between diameterical opposite points.
Observations:-
a. Star-delta connection
SL.N Vn Vn Vn Vn Vn Vn V1. V2. V3. V4. V5. V6. V1. V2. V3.
o -1 -2 -3 -4 -5 -6 2 3 4 5 6 1 4 5 6
Report: In the case of six phase connections what is the relation between
voltage between adjacent points and voltage between diametrically opposite
points.
Questions:
1. While making delta connections, why do you close the delta only when
voltage across open delta points is zero.
2. How do you get 6 phase from 3 phase supply. What is the angle between
early phase?
3.What is going to be angle between each phase of a (a) 10 phase supply (b) 12
phase supply and (c) 2 phase supply. (d) 1 phase supply.
Apparatus Required: -
Theory: -
Procedure: -
(a) Connect two single phase transformers as shown above. Make V ab=Vcd,
measure primary voltage and secondary voltage Vab, Vcd and Vad (with c & b
connected) tabulate the observations as follows.
(b) Now connect a unity power factor load to terminals ‘cd’ only, terminals ‘ab’
being kept open. Take ammeter readings.
(c) Connect a unity power factor load to terminals ‘ab’ only. Terminals ‘cd’
being kept open. Take ammeter readings.
(d) Connect equal unity power factor load to both ‘ab’ &‘cd’, now take ammeter
readings.
Observations for run b, c & d
I1 I2 I3 I4 I5
Run b
Run c
Run d
Questions
1. Why 86.6 tap of teaser & 50% tap of main transformer are used & how do we
get 2 phase supply from 3 phase by Scott connection?
3. If we apply the same single phase supply to both ab and cd what will be the
nature of voltage available at terminals 1, 2, 3. Illustrate your answer by
corresponding vector diagram (magnitude of voltage may be arbitrary)
Discussion & Precautions: - Discuss the reason if you find any discrepancy in
computed and test result.
Note: - Auto transformer is connected to get 230 V supply from 400 V available
supply, as primary winding main transformer is rated for 230 V only. Draw all
phasor diagrams on L.H.S
Reduced (by auto transformer) voltage across primary secondary 3 phase supply
to both transformer winding of both trans-side voltage (2 phase out put).
(a) Voltage across teaser transformer is 220cos 30. This voltage is across 86.6%
turns of primary. Hence secondary voltage of teaser transformer will be
220cos30 x 1/0.86 = 220V