DVP-SX Multi-Function, Built-In Analog I - O, Multiple
DVP-SX Multi-Function, Built-In Analog I - O, Multiple
Control Method Stored program, cyclic scan system POWER Clear all M1031 Clear all M1032 Factory
Memory Type STOPÖRUN RUNÖSTOP
Batch processing method (when END instruction is
I/O refresh instruction is OffÖOn non-latched area latched area Setting
I/O Processing Method M1033=Off, clear
executed) available Non-latched Clear Unchanged Clear Unchanged 0
Application Instructions M103=On, unchanged
http://www.delta.com.tw/products/plc.asp Execution Speed Basic instructions (several us)
(10~hundreds us) Latched Unchanged Unchanged Clear 0
DVP-SX Analog I/O, Multiple Instructions 32 Basic sequential instructions (including STL/RET) 168 Application instructions File register Unchanged 0
Correspond to external input
X External input relay X0~X177, octal number system, 128 points Total 4 BUILT-IN ANALOG I/OAND 7-SEGMENT DISPLAY
Instructions PLC
point
256
Correspond to external output Built-in 2-CH 12-bit A/D and 2-CH 12-bit D/A are bipolar. It can read A/D converted digital value and get designated
Y External output relay Y0~Y177, octal number system, 128 points points
point analog output by reading special D or writing into special D. Refer to the table below for corresponding special D.
Instruction Sheet General M0~M511, 512 points (*1)
Total
Device
Function
■ Built-in Display This built-in display corresponds to special D
Auxiliary M512~M999, 488 points (*3) Contacts can switch to On/Off in No. directly. User can use it to display error code or station
1 WARNING M Latched 4096 when executing PLC LINK. It is fairly convenient for
Relay M2000~M4095, 2096 points (*3) program Present value of AD card
points D1056 system maintenance. Refer to the table below for
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & Special M1000~M1999, 1000 points (some are latched) channel 0 (CH0)
wiring, troubleshooting and peripherals. Other detail infromation about programming and instructions is compatible T0~T199, 200 points (*1) Present value of AD card corresponding special D.
D1057
with EP series; please see PLC Application Manual. For more information about the optional peripherals , please 100ms T192~T199 for Subroutine When the timer that set by TMR channel 1 (CH1) 2-digital
7-segment display
Device No. Function
see individual product manual. Total Average value of AD card Number system setting for display (Off:
T250~T255, 6 points Accumulative (*4) instruction reaches the preset D1110 M1196
T Timer 256
Interrupt Service
◎ DVPACAB215: 1.5M Cable (PC (DB9+DB25) Ù PLC) I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 (X4), Voltage Below 250VAC,
External interrupt Off→On, above16VDC 30VDC
◎ DVPACAB230: 3.0M Cable (PC (DB9+DB25) Ù PLC) I501 (X5); 6 points (all are rising-edge trigger) Specification 30VDC
The location pointer of interrupt Active Level
◎ DVPACAB2A30: 3.0M Cable (PC (DB9) Ù PLC) I On→Off, below When the output of Y0 and
Time interrupt I6□□ (1ms), I7□□ (1ms), (□□=1~99ms) subroutine Maximum 75VA (Inductive) Y1 is high-speed pulse, Y0
2.2 Product Profile and Outline 14.4VDC 9W/1 point
Hi-speed counter I010, I020, I030, I040, I050, I060; 6 points About 10ms (An Loading and Y1 = 0.9W (Y0 =
1 Status indicator: POWER, RUN, Communication I150, 1 point 90 W (Resistive) 32kHz, Y1 = 10kHz)
ERROR, BAT.LOW adjustment range of
K-32,768 ~ K32,767 (16-bit operation) Responding
Y0 and Y1 are specified
Constant
4 Digital I/O terminal Programming port COM1: RS-232, COM2: RS-485 (Master/Slave), They can be used at the same time. 6 MODEL NAME & I/O CONFIGURATION
5 DIN rail clip Analog Volume / RTC MPU built-in bipolar 2-CH A/D, D/A, 12 bits, 2-digital 7-segment display, built-in RTC
Input Output
Y0
Use the same modules (AD, DA, PT, TC, XA, RT) of SS series. (Max. 8 Extension Unit
C1
Y2
Y3
points) Point Type Point Type
7 I/O point indicators DO AO DO AO DO AO DO AO
*1: The non-latched area is fixed, and can’t be changed.
RS-232
RS-485
8 COM1 (RS-232) (Rx) indicator *2: The non-latched area can be changed to a latched area with parameter setting. DVP10SX11R 4 2 DC24V/5 mA -20~20mA 2 2 Relay -20~20mA
9 COM2 (RS-485) (Tx) indicator *3: The latched area can be changed to a non-latched area with parameter setting. Sink or or or
DVP10SX11T 20.4-28.8 4 2 2 2 Resistor
*4: The latched area is fixed, and can’t be changed. Source -10~+10V -10~+10V
10 COM1 (RS-232) programming port VDC
Units: mm General Latched Special auxiliary relay Latched
7 INSTALLATION & WIRING
11 Nameplate M M0~M511 M512~M999 M1000~M1999 M2000~M4095
Auxiliary 7.1 PLC Mounting Arrangements and Wiring Notes
※ Battery replacement: the replacement must be finished within 3 12 Extension port Latched (default) Latched (default)
Relay Some are latched and Installation of the DIN rail When install the DVP series PLC,
minutes, or the internal data of the PLC (including the program Non-latched (fixed) Start: D1200 (K512) Start: D1202 (K2000)
13 Mounting hold of the extension unit can’t be changed The DVP-PLC can be secured to a cabinet by using the DIN make sure that it is installed in an
area, RTC and latched registers) could be lost or destroyed. End: D1201 (K999) End: D1203 (K4095)
rail that is 35mm high with a depth of 7.5mm. When mounting enclosure with sufficient space
14 DIN rail (35mm) 100 ms 10 ms 10ms 1 ms 100 ms
T the PLC on the DIN rail, be sure to use the end bracket to (as shown below) to its
15 Extension unit clip T0 ~T199 T200~T239 T240~T245 T246~T249 T250~T255 stop any side-to-side motion of the PLC, thus to reduce the
Timer surroundings so as to allow heat
Non-latched (fixed) Non-latched (fixed) Accumulative Latched (fixed) chance of the wires being pulled loose. At the bottom of the
16 COM2 (RS-485) Communication port dissipation.
16-bit count up 32-bit count up/down 32-bit high-speed count up/down PLC has a small retaining clip. To secure the PLC to the DIN
17 DC Power input
C0~C95 C96~C199 C200~C215 C216~C234 C235~C245 C246~C255 rail, place it onto the rail and gently push up the clip. To
D
C D DVP D
18 RS-485 Cable (standard accessory) Latched (default) Latched (default) Latched (default) remove it, pull down the retaining clip and gently pull the PLC MP
19 Power input cable (standard accessory) Start: D1208 (K96) Start: D1210 (K216) Start: D1212 (K235) away from the DIN rail. As shown on the right: D > 50 mm
(fixed) (fixed)
End: D1209 (K199) End: D1211 (K234) End: D1213 (K255)
20 Battery Cover Wiring Notes:
General Latched Special registers Latched 22-16AWG 1. Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for I/O
21 Battery socket connection
D D0~D199 D200~D999 D1000~D1999 D2000~D4999 wiring terminals. The specification for the terminals is as shown on the left. PLC
22 Battery mount Register Factory setting is latched. Factory setting is latched. terminal screws should be tightened as a torque 1.95 kg-cm (1.7 in-lbs).
Some are latched and 2. I/O signal wires or power supply should not run through the same multi-wire
Non-latched (fixed) Start: D1216 (K200) Start: D1218 (K2000)
3 FUNCTION SPECIFICATIONS can’t be changed.
End: D1217 (K999) End: D1219 (K4999) <1.5mm cable or conduit.
File Register K0~K1599, Latched (fixed) 3. Use copper conductor only, 60℃.
8 TRIAL RUN Power Module Digital I/O Extension Unit
7.2 Wiring Notes DVPPS01 DVPPS02 DVP08SM DVP08SN DVP08SP DVP16SP
☼ Power Indication
Power Input Wiring The “POWER” LED at the front of the MPU or the Extension Units will be lit (in green) if power is on. If the indicator is S/S C0 S/S S/S
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX. Series. not on when the MPU is powered up, it means that the 24V DC power supply of the PLC is overloaded. It is thus
X0
X1
X2
Y0
Y1
Y2
X0
X1
X2
X0
X1
X2
DVP-PS01 DVP-PS02
1. Please make sure the power is at terminals 24VDC and 0V (power range is 20.4VDC~28.8VDC). When voltage necessary to remove the wiring on terminals +24V and 24G, and use a 24VDC power supply instead. If the ERROR X3
X4
X5
Y3
Y4
Y5
X3 X3
X4
X5
is lower than 20.4VDC, PLC will stop operation, all outputs will be off and ERROR LED will flash continuously. LED is blinking swiftly, it suggests that the +24V power supply of the PLC is not enough. X6
X7
Y6
Y7
X6
X7
2. Please use wires of 1.6mm or above for the MPU ground. ☼ Low Voltage Indication C0
Y0
C0
Y0
C1 Y1
3. PLC operation has no affect if the power-off time is less than 10ms. However, if the power-off time is too long or The “LOW V.” LED on the Extension Unit is an indication that the input power voltage is not enough, thus all outputs Y1
C2
Y2
Y3
the power voltage drops, the PLC will stop operation and all the outputs will be off. Once the power is restored, of the extension unit should be turned off. Y2
C3
Y4
Y5
Y3 Y6
the PLC will return to operation automatically. (There are latched auxiliary relays and registers inside of the PLC, ☼ Low Battery Voltage Indication Y7
please be aware when programming.) There is also a “BAT.LOW” LED at the front of the MPU. When the LED is on, it indicates that the battery voltage is
POWER POWER
DC Input Type not enough. Please change the batter (within 3 minutes) immediately; otherwise the user programs and the data in
latched area may be lost.
Preparation
n Prior to applying power, please verify that the power lines and the input/output wiring are correct. DO NOT
10 TROUBLESHOOTING
20.4V~28.8V
24V 0V S/S X0 X1 X2 supply AC110V or AC220V to the I/O terminals, or it might cause the wire short and would direct damage the ) Judge the errors by the indicators on the front panel. When errors occurred on DVP PLC, please check:
PLC. ☼ “POWER” LED
2A
o After using the peripheral devices to write the program into the MPU and that the ERROR LED of the MPU is not There is a “POWER” LED at the front of the MPU. When the MPU powered on, the green LED light will be on. If the
5V on, it means that the program in use is legitimate, and it is now waiting for the user to give the RUN instruction. indicator is not on after the input power to MPU is normal, it indicates that the PLC is out of order. Please have this
DC/DC
p Use HPP to execute the forced On/Off test of the output contact. machine replaced or repaired at a dealer near you.
Operation & Test ☼ PLC “RUN” LED
Identify the status of the PLC. When the PLC is in operation, this light will be on, and users could thus use HPP or the
Safety Wiring If the “ERROR” LED of the MPU is not blinking, use RUN/STOP switch or the peripheral devices (HPP or WPLSoft)
editing program of the ladder diagram to send instructions to PLC for “RUN” or “STOP”.
Since the PLC is used to control numerous devices, motion of one device could affect the motion of other devices, to send the RUN instruction, and the RUN indicator will then be on. If the “RUN” LED is not on, it means no ☼ “ERROR” LED
therefore the breakdown of either one device would consequently be detrimental to the whole auto control system, program inside the PLC. If incorrect programs are input to the MPU, or the instructions and the components exceed the allowable range, the
and damage could be significantly. Please use the recommended wiring below for the power input: HPP could be utilized to monitor the settings and the registered values of the timer (T), the counter (C) and the data indicator will blink. In this case, the user should check both the error codes saved in the MPU data register D1004 and
c Power supply for AC loads register (D) during operation. Moreover, HPP forces the output contacts to conduct the On/Off action. If the ERROR the Error Code Table below to correct the programs. The address that the error occurs will be stored in data register
5 d Power Circuit Protection Fuse (3A) LED is on (but not blinking), it means that the setting of the user’s program exceeded the preset overtime limit, thus D1137 (the address saved in D1137 is invalid in case of common loop error).
MC
1 e Power On pilot indicator users have to double check the program and perform the On/Off function again. (The PLC is at this moment back to When the ERROR LED is on (not blinking), users should make a judgment from the special relay M1008 of the MPU.
4
f Emergency stop If it is on, it indicates that the execution time of the program loop has exceeded the time-out setting (set by D1000).
STOP automatically)
8
The machinery must provide a quick manual method PLC Input/Output Response Time Please place the PLC RUN/STOP switch to STOP, and find out the address of the time-out program via special data
Guard 2 disconnecting all system power. The total response time from the input signal to the output operation is calculated as follows: register D1008. ”WDT” instruction can be used to solve the problem.
Limit
g Circuit isolation device (System Power Disconnect) Reaction Time = input delay time + program scan time + output delay time ☼ “BAT.LOW” LED
Utilize the electromagnetic contactor and the relay to be When the battery voltage is low, the “BAT.LOW” LED will be on, and the battery should be replaced as soon as
MC 3
MC the isolation unit of the power circuit to prevent the 10ms (factory default), 0~15ms adjustable. Please refer to the possible; otherwise the user program and the data in latched area will be lost. (On the unplugged PLC, please change
Input delay time
1
possible instability of the system when the power is usage of special registers D1020~1021. the battery within 3 minutes to retain the PLC internal user programs and data).
supplied on and off. Program scan time Please refer to the usage of special register D1010. ☼ “Input” LED
h DVP PLC MPU (main processing unit) Output delay time Relay module: 10ms. Transistor module: 20~30us. The On/Off signals of the input point could be displayed through the “Input” LED, or the status of the input point could
Basic Instructions and Application Instructions of the PLC: be monitored through the device monitoring function of HPP.
L N 7
i Grounding
◎ The basic instructions and the application instructions of the MPU of this series are totally applicable to the ☼ “Output” LED
6
j Power supply: Output LED indicates the output signals are on or off. Please check the following items when the LED On/Off
DELTA DVP-PLC EP Series MPU. Refer to the DELTA PLC Technique Application Manual for the basic
AC: 100~240VAC, 50/60Hz indication does not correspond to the instructions: 1. Output contacts may be melted and stuck together due to a short
instructions and application instructions.
DC: 24VDC circuit or overload current. 2. Check wiring and verify that the screws are tight.
◎ All Delta DVP-PLC series can use DVPHPP handheld programming panel and the WPLSoft (Windows version)
Input Point Wiring to edit program. A specific transmission wire is used for PLC connects to DVP12SX MPU in order to execute the ) Error Code (D1004, Hexadecimal Number) Table
DC power is used for input signals. program transmission, the MPU control, the program monitor, etc.
◎ Two types of DC wiring are used: SINK and SOURCE, defined as follows: Code Explanation Code Explanation Code Explanation
Sink = Current flows into the common terminal S/S Source = Current flows out of common terminal S/S Device S exceeds the usage C register exceeds the usage
9 EXTENSION UNIT INFORMATION 0001 0E04 C404 FOR-NEXT exceeds 6 levels
limit limit
S/S X0 DVP-SX series is capable to handle different more I/O points (input point X and output point Y) via extension units. Misused operand CXXX of
Extension units can handle the combination signals of AI/AO and DI/DO. Max DI/DO points (including MPU DI/DO) can 0002 Misused Label P 0E05 C405 Misused STL/RET
DCNT
Sinking up to 128/128 points. Error LED on PLC MPU will be blinking when DI or DO point exceeds 128 points. Index registers E and F exceed
0003 KnSm exceeds the usage limit 0E0F Misused SRET/IRET
◎ Digital I/O Extension unit the usage limit
X0 S/S Input / Output 0102 Misused Label I 0E18 BCD conversion error Misused MC/MCR
Model Input Unit Input Unit Profile reference 0202 Misused MC 0E19 Division Error (divisor=0) Misused END/FEND
Sourcing Power Component exceeds the usage STL has been used for more
Point Type Point Type 0302 Misused MCR 0E1A C407
Loop Equivalent Circuit of Input Point Wiring Loop limit (including E and F error) than 9 times consecutively
DVP08SM11N 8 0 None Device X exceeds the usage
+24V 0401 0E1B The root is negative C408 MC/MCR used within STL
24VDC limit
DC Type DVP08SN11R 0 8 Relay
0403 KnXm exceeds the usage limit 0E1C FROM/TO communication error I/P used within STL
24G
DVP16SP11T 8 8 limit
DC Type 24VDC
24G
Device M exceeds the usage MC/MCR does not begin from
(DC Signal IN) 0801 0F08 Misused REF operands C40B
+5V
SOURCE
◎ Analog / Temperature Module Extension Unit limit N0 nor of continuous status
Profile Misused WSFR, WSFL
+24V OV S/S X0 X1 X2
Model Power Input / Output 0803 KnMm exceeds the usage limit 0F09 C40C Misused MC/MCR
operands
S/S
24VDC
reference
Misused TTMR, STMR
X0