A Study of Energy Optimisation of Urban Water Distribution Systems Using Potential Elements
A Study of Energy Optimisation of Urban Water Distribution Systems Using Potential Elements
A Study of Energy Optimisation of Urban Water Distribution Systems Using Potential Elements
Article
A Study of Energy Optimisation of Urban Water
Distribution Systems Using Potential Elements
Ioan Sarbu
Department of Building Services Engineering, Polytechnic University of Timisoara, Piata Bisericii 4A,
300233 Timisoara, Romania; [email protected]; Tel.: +40-256-403-991
Abstract: Energy use in water supply systems represents a significant portion of the global energy
consumption. The electricity consumption due to the water pumping represents the highest
proportion of the energy costs in these systems. This paper presents several comparative studies of
energy efficiency in water distribution systems considering distinct configurations of the networks
and also considers implementation of the variable-speed pumps. The main objective of this study
is the energy optimisation of urban systems using optimal network configurations that reduce
energy consumption and improve energy efficiency. The paper describes in detail four strategies for
improving energy efficiency of water pumping: control systems to vary pump speed drive according
to water demand, pumped storage tanks, intermediary pumping stations integrated in the network,
and elevated storage tanks floating on the system. The improving energy efficiency of water pumping
is briefly reviewed providing a representative real case study. In addition, a different approach for the
hydraulic analysis of the networks and the determination of the optimal location of a pumped storage
tank is provided. Finally, this study compares the results of the application of four water supply
strategies to a real case in Romania. The results indicate high potential operating costs savings.
1. Introduction
As a vital part of water supply systems, water distribution networks represent one of the largest
infrastructure assets of industrial society. According to Watergy [1], approximately 2% to 3% of the
worldwide electricity consumption is used for pumping in water supply systems, while 80%–90% of
this consumption is absorbed by motor-pump sets [2]. Coelho and Andrade-Campos [3] provides
several strategies to improve the energy efficiency of the water supply systems.
Most water distribution systems require the operation of pumps to deliver the necessary quantity
of water with the adequate pressure to the final consumers. As reported by Bene et al. [4] and Vilanova
and Balestieri [5], the electricity used to pump water is a significant part of the total operation in water
supply systems.
Water distribution systems equipped with pumping stations are characterised by energy
consumption greater than 60% of the energy consumed by the operation of the entire supply system
of large urban centres [6]. As a result, a great increase in the energetic system load occurs especially
during peak water consumption hours.
Pumping systems are found to have a significant potential for energy efficiency improvements [7–10].
In most cases, optimisation of operations has only considered fixed speed pumps and the cost savings
that may be obtained by exploiting a multi-pattern electric tariff [11–15]. Pump and motor upgrades
to more efficient solutions, either being technologically more advanced or because they are more
properly adjusted to the system, often allow significant energy savings [2].
Vogelesang [16] quantitatively discussed the energy saving potential of applying variable-speed
pumps and indicated a possible energy reduction of 27% only with a 10% of pump speed decrease.
Variable-speed drives (VSDs) have been shown to be an effective way to reduce the pumping energy,
especially in systems that require a wide range of flow rates [17] in absence of elevated tanks. Energy
optimisation of parallel-connected, rotational speed-controlled pumps has been studied to some
extent [18,19]. Viholainen et al. [20] developed a pumping control strategy for most of the scenarios
considered (two pumps in parallel, two frequency converters, and one programmable logic controller)
using frequency converters that close to high efficiency.
Several studies provide other alternatives to improve energy efficiency in water distribution
systems. A model for decision systems regarding the quantification, location and opening adjustment
of control valves in a distribution network, to minimize pressures and leakage levels in network is
developed in [21]. Carravetta et al. [22] present a real case study (flow rate less than 1440 m3 /h) and
suggest the installation of pumps in the supply pipes that act as micro-hydro turbines to generate
electric power. These turbines may be used to provide pressure control instead of using pressure
control valves.
Diniz et al. [23] present an analysis of energy efficiency in supply systems based on modelling
and optimisation. Other researchers have successfully applied genetic algorithms to control
hydraulic pressure in the water distribution network [24]. However, these models require that the
functions satisfy certain restrictive conditions that cannot be generally guaranteed for any water
distribution system.
The assessment of energy efficiency in water distribution systems is strongly influenced by the
site-dependent nature of the water-energy nexus in pressurised networks [25]. Understanding this
link requires a systematic energy analysis to separately evaluate the influence of pumping stations,
the network and water loss and to highlight inconsistencies in the design and management that are
reflected in both of the resources, namely water and energy.
The hourly variations in water demand during the day are much greater compared to the average
daily demand. For a domestic consumer water requirement is more during morning and evening hours
than the noon demand. The hourly variation in demand has also an influence on the residual pressures
in the system. In the case of water distribution for Romanian consumers, the available pressure is
greater at the periphery consumers, where the lower pressure is necessary, while in central zones, the
pressure is insufficient. Often, the absence of water at consumers can be observed during certain hours
in a 24-h period due to system under dimensioning, increased water consumption by some users,
inadequate operation of pumping stations, or a combination of these factors. These disadvantages are
amplified by the overlapping of peak hours for water, heat, and electricity consumption, especially
between 7:00 and 9:00 in the morning and between 17:00 and 21:00 in the evening, contributing to
increasing operation expenses.
During peak hours, the energy cost is 2–3 times more expensive than during the hours of minimum
consumption. Therefore, it is very interesting to provide a reduction of energy consumption during
peak hours. A technical solution for this reduction can be a decrease in the pumping power (even
stopping pumps if it is possible) during peak hours, along with an extensive delivery outside of these
hours. Consequently, distribution systems must be equipped with pumped storage tanks.
An important goal is the absolute reduction of pumping energy, which is possible by dividing the
system into zones. For this purpose, a special form of parallel zoning procedure or a vertical division
into zones with intermediary pumps mounted on the distribution mains, or a combined solution with
more potential elements, can be used [26].
In this context, this paper presents several comparative studies of energy efficiency in water
distribution systems considering distinct configurations of the networks and also considers utilisation
of the variable-speed pumps. The main aim of the paper is to search for possible optimal network
configurations that reduce electricity consumption and improve energy efficiency using potential
elements (pumped storage tanks, intermediary pumping stations integrated on distribution mains,
Water 2016, 8, 593 3 of 19
elevated storage tanks floating on the system) and control systems to vary pump speed drive according
to water demand. The improving energy efficiency of water pumping is briefly reviewed providing
a representative real case study. In addition, a hydraulic analysis of the optimisation strategies
with potential elements is performed and an analytical model is developed to estimate the optimal
location of a pumped storage tank. Finally, certain optimisation solutions to reduce pumping energy
are analysed in a detailed manner through the use of a case study to ascertain their energy and
economic efficiencies.
γQH p
P= (1)
η
W = PTp (2)
where γ is the water specific weight, in N/m3 ; Q is the pump discharge, in m3 /s; Hp is the pump head
for the operating point, in m; η is the global efficiency of the pumping station; and Tp is the operation
period, in h.
The specific energy consumption w, in %, for an optimal operation period Tp of the pumps can be
estimated as: R Tp
0 Pdt
w=
24
· 100 (3)
QH
∑ ηi i γTp
i
i =1
where Qi , Hi , and ηi are the pump characteristics in classical operation at the ith hour of a day; and
R Tp
0 P dt is the energy consumption during interval Tp at discharges different from Qi .
Most existing pumping stations requiring flow control make use of bypass lines, throttling valves,
or pump speed adjustments.
Most water distribution systems are fed through some type of centrifugal pumps characterized by
a head–flow (H-Q) curve. A centrifugal pump has a motor that spins a piece within the pump called
an impeller. If the pump used is a fixed-speed pump, the operating point is forced to move along the
pump curve corresponding to the constant nominal speed. There are two methods to adjust the water
flow rate in a pipe network with a fixed-speed pump:
Speed can be controlled in a number of ways, either the most popular type of VSD being the
variable frequency drive (VFD) or variable-speed controller.
Water 2016, 8, 593 4 of 19
Water 2016, 8, 12 4 of 19
Using VSDs
Using VSDs to to replace
replacefixed‐speed
fixed-speedpumps pumpshas the the
has possibility
possibilityto save electrical
to save energy.
electrical The
energy.
decreasing energy consumption can be reduced the cost related to pump operation. Variable‐speed
The decreasing energy consumption can be reduced the cost related to pump operation. Variable-speed
pumps can prevent over‐pressurising of the water distribution system that has no storage floating
pumps can prevent over-pressurising of the water distribution system that has no storage floating on
on the system (that is, no tank where the hydraulic grade line (HGL) in the tank is the same as the
the system (that is, no tank where the hydraulic grade line (HGL) in the tank is the same as the HGL in
HGL in the system) [6].
the system) [6].
Variable‐speed pumps are coupled with a motor that is controlled by a VFD. The most common
Variable-speed pumps are coupled with a motor that is controlled by a VFD. The most common
form ofof
form VFDVFD is the
is the voltage‐source,
voltage-source, pulse‐width
pulse-width modulated
modulated (PWM)(PWM)
frequency frequency
converter.converter. The
The principal
principal duty of the VFD is to alter the main supply to vary the speed of the motor while delivering
duty of the VFD is to alter the main supply to vary the speed of the motor while delivering the required
the required torque at higher efficiency. As a result, as the pump speed changes, the pump curve is
torque at higher efficiency. As a result, as the pump speed changes, the pump curve is adjusted for
adjusted for different operating conditions. The flow control (Figure 1) is achieved by changing the
different operating conditions. The flow control (Figure 1) is achieved by changing the pump curve
pump curve H (at different pump speeds n
H (at different pump speeds n1 and n2 ) on the 1 and n 2) on the fixed system curve H
fixed system curve Hr . Pipe workr. Pipe work curve H
curve Hr start fromr
start from point (0, H
point (0, Hg ), where Hg is the geodesic head. The operating point F2 corresponds tocorresponds
g), where H g is the geodesic head. The operating point F 2 to the
the reduced pump
reduced pump head H
head HF2 . F2.
Figure 1. Flow rate adjustment using pump speed control.
Figure 1. Flow rate adjustment using pump speed control.
The approximation introduced into the power‐speed relation implies that the efficiency will
The approximation introduced into the power-speed relation implies that the efficiency will
remain constant for speeds n1 and n2, i.e., that the efficiency curve will only be shifted to the left in
remain constant for speeds n1 and n2 , i.e., that the efficiency curve will only be shifted to the left in
the case of speed reduction. The efficiency variation depending of the pump speed is provided by
the case of speed reduction. The efficiency variation depending of the pump speed is provided by
following analytical relationship [29]:
following analytical relationship [29]:
0.1
n 0.1
η 1 (1 η )n 1 (4)
η2 = 21 − (1 − η1 )1 n1 (4)
n22
where n
where n11 and n
and n22 are two different speeds and η
are two different speeds and η11,, η η22 are the corresponding efficiencies.
are the corresponding efficiencies.
Therefore, as indicated in [30], for the particularly case ofcase
Therefore, as indicated in [30], for the particularly of the
the large large the
pumps pumps
changesthe inchanges in
efficiency
efficiency can be neglected if the changes in speed rate do not exceed 1/3 from the nominal pump
can be neglected if the changes in speed rate do not exceed 1/3 from the nominal pump speed. Figure 2
speed.
shows the Figure 2 shows
variation curvesthe variation
of pump headcurves
(H), flowof rate
pump
(Q),head
power(H),
(P), flow rate (Q), (η)
and efficiency power (P), and
for centrifugal
efficiency (η) for centrifugal pumps depending on pump speed n. It can be observed that a reduction
pumps depending on pump speed n. It can be observed that a reduction of 20% of the pump speed
of 20% of the pump speed will lead to the decreasing of power demand of 50% at constant pump
will lead to the decreasing of power demand of 50% at constant pump efficiency. Thus, the possibility
efficiency. Thus, the possibility exists to reduce the pumping energy consumption by using VSDs.
exists to reduce the pumping energy consumption by using VSDs.
Variable‐speed pumps are useful in applications requiring operational flexibility, such as when
Variable-speed pumps are useful in applications requiring operational flexibility, such as when
flow rates change rapidly,
flow rates change rapidly, but but the
the required
required pressure
pressure remains
remains constant
constant [6].
[6]. These
These pumps
pumps can can take
take
advantage of the different required operating conditions in water distribution systems. In particular,
advantage of the different required operating conditions in water distribution systems. In particular,
the reduction in energy consumption exploits the possibility of reducing the head or flow rate in the
the reduction in energy consumption exploits the possibility of reducing the head or flow rate in the
system. Figure 1 shows the case in which the required flow rate is smaller than the actual operating
system. Figure 1 shows the case in which the required flow rate is smaller than the actual operating
point. This situation can be the case of a water transmission system, where the pumps are used to
point. This situation can be the case of a water transmission system, where the pumps are used to
move water from a lower to an upper tank. Because the pumping at a particular time of the year may
move water from a lower to an upper tank. Because the pumping at a particular time of the year
be sized
may for a
be sized forpeak‐day
a peak-daydemand,
demand, the the
pump
pump will
will deliver
delivera aflow
flowrate
rateassociated
associated with
with thethe operating
operating
point, despite the fact that the required demand is decreased. However, this operating strategy can
Water 2016, 8, 593 5 of 19
Water 2016, 8, 12 5 of 19
point, despite the fact that the required demand is decreased. However, this operating strategy can be
be economically
economically convenient
convenient if theif system
the system has a sufficient
has a sufficient storagestorage
volumevolume so that can
so that pumps pumps can be
be switched
switched on only during the off‐peak‐tariff period.
on only during the off-peak-tariff period.
Figure 2. Variation of the centrifugal pump curves.
Figure 2. Variation of the centrifugal pump curves.
Parallel‐connected centrifugal pumps are often implemented in the pumping systems with a
Parallel-connected centrifugal pumps are often implemented in the pumping systems with a
widely varying flow rate demand [31,32]. The output of the parallel‐connected centrifugal pumps in
widely varying flow rate demand [31,32]. The output of the parallel-connected centrifugal pumps in a
a system can be adjusted with an on–off, throttle, or rotational speed control methods. In the
system can be adjusted with an on–off, throttle, or rotational speed control methods. In the simplest
simplest case, parallel‐connected pumps are operated with an on–off control method, where
case, parallel-connected pumps are operated with an on–off control method, where additional parallel
additional parallel pumps are started and stopped according to the desired flow rate. In the systems
pumps are started and stopped according to the desired flow rate. In the systems where more accurate
where more accurate flow regulation is required, the adjustment can be performed by applying
flow regulation is required, the adjustment can be performed by applying throttling or rotational speed
throttling or rotational speed control for a single pump, while the other pumps are controlled with
control for a single pump, while the other pumps are controlled with the on–off method.
the on–off method.
VSDs have a motor that can change the pump speed in response to the system conditions.
VSDs have a motor that can change the pump speed in response to the system conditions. The
The majority of electric motors used in pump applications are of induction type. The most common
majority of electric motors used in pump applications are of induction type. The most common type
type of VFD controls the flow of electricity to the pump motor and therefore controls the rate at which
of VFD controls the flow of electricity to the pump motor and therefore controls the rate at which the
the pump rotates. Note that, in variable drive systems, additional losses are generated in the motor by
pump rotates. Note that, in variable drive systems, additional losses are generated in the motor by
the VFD. Another problem could be in the lower reliability of the pumps, both for the lower quality of
the VFD. Another problem could be in the lower reliability of the pumps, both for the lower quality of
the electric pulse and for operational conditions diverging from the best efficiency point (BEP) line.
the electric pulse and for operational conditions diverging from the best efficiency point (BEP) line.
The general expression of variable-speed pump system efficiency is given by Marchi et al. [29]:
The general expression of variable‐speed pump system efficiency is given by Marchi et al. [29]:
η ηmηηmVFD
η= ηVFDηηp p (5)
(5)
where η
where ηmm is the motor efficiency; η
is the motor efficiency; ηVFD VFD is the efficiency of the VSD; and η
is the efficiency of the VSD; and ηpp is the pump efficiency.
is the pump efficiency.
The flow variation in pumping systems may occur as a result of several situations, such as the
The flow variation in pumping systems may occur as a result of several situations, such as the
need to turn pumps on only when required (partial load operation), the use of a bypass to return a
need to turn pumps on only when required (partial load operation), the use of a bypass to return a
portion of the pumped discharge to the suction tank, the use of a suction tank with a variable level,
portion of the pumped discharge to the suction tank, the use of a suction tank with a variable level, the
the insertion
insertion of head
of head losseslosses
in thein system
the system through
through the throttling
the throttling of control
of control valves,valves,
changes changes in the
in the pump
pump speed by hydraulic or electrical coupling between the pump and motor, or the use of pumps
speed by hydraulic or electrical coupling between the pump and motor, or the use of pumps operating
operating in parallel [33].
in parallel [33].
According to Gibson [34], VSDs are an energy‐efficient alternative for controlling pump flow
According to Gibson [34], VSDs are an energy-efficient alternative for controlling pump flow rates.
rates. Author
Author reported reported
that the that the effectiveness
effectiveness of VSDs on of flow
VSDs on flow
control control
depends ondepends on the between
the interaction interaction
the
between the characteristic curve (H‐Q) and the system curve. This includes the use of the magnitude
characteristic curve (H-Q) and the system curve. This includes the use of the magnitude of required
of required speed variation to obtain the maximum and minimum required flow rates in addition to
speed variation to obtain the maximum and minimum required flow rates in addition to the unstable
the unstable regions in
regions in the pump curve, the which
pump are curve, which are usually
usually located
located in the range belowin the
33%range
of thebelow 33% of the
nominal flow.
nominal flow.
To correlate the pumped discharge with the water demand and to ensure the required pressure
usingTo correlate the pumped discharge with the water demand and to ensure the required pressure
minimum energy, an automatic control device of pump speed designed and described in [29]
using minimum energy, an automatic control device of pump speed designed and described in [29]
or a supervisory control and data acquisition (SCADA) system deployed in industry can be utilised.
or a supervisory control and data acquisition (SCADA) system deployed in industry can be utilised.
If several pumps are to operate in parallel connection, the rotational speed can be modified for a single
If several pumps are to operate in parallel connection, the rotational speed can be modified for a
single pump (while the other pumps operate at nominal speed and nominal discharge), and the
frequency converter automatically connects to the other pumps. Thus, the pumping station must be
Water 2016, 8, 593 6 of 19
pump (while the other pumps operate at nominal speed and nominal discharge), and the frequency
converter automatically connects to the other pumps. Thus, the pumping station must be equipped
with np = nc + nv number of pumps, where nc is the number of classical (fixed-speed) pumps (pf ) and
nv is the number of variable-speed pumps (pv ).
Table 1. The specific energy consumption and energy savings obtained with control methods.
Figure 3. Characteristic curves H-Q, η-Q and the operating points for different parallel-connected pumps.
Figure 3. Characteristic curves H‐Q, η‐Q and the operating points for different parallel‐connected pumps.
The results
The results show
show thethe potential
potential gain
gain in energy efficiency using
in energy efficiency using rotational speed control in
rotational speed control in the
the
pumping system.
pumping system.
ItIt should
should bebe noted
noted that
that thethe optimised
optimised operation
operation of pumping
of the the pumping station
station using using the rotational
the rotational speed
speed control leads to a specific energy consumption of 80% compared with 88% when valve control
control leads to a specific energy consumption of 80% compared with 88% when valve control is used.
is comparison
In used. In comparison with the
with the classical classical
pumping pumping
station station
operation, theoperation, the rotational
rotational speed speed energy
control ensures control
ensures energy savings of 2280 MWh/year (20%), and the valve control provides
savings of 2280 MWh/year (20%), and the valve control provides savings of 1345 MWh/year (11.6%). savings of 1345
MWh/year (11.6%).
In summary, the pump speed control ensures a supplementary energy savings of approximately
In summary,
9% compared the pump
to the throttle valve speed
control. control ensures a supplementary energy savings of
approximately 9% compared to the throttle valve control.
3. Energy Optimisation Methodology
3. Energy Optimisation Methodology
3.1. Pumped Storage Tanks
3.1. Pumped Storage Tanks
A pumped storage tank requires a buried tank coupled with a pump (repumping station) to
deliverA water
pumped from the tank
storage torequires
tank the distribution
a buried system and a control
tank coupled with a valve
pump to(repumping
gradually fillstation)
the tankto
without seriously affecting the pressure in the surrounding system. These buried tanks
deliver water from the tank to the distribution system and a control valve to gradually fill the tank are known as
“zone tanks”, and the repumping stations are known as “internal pumping stations”. With pumped
without seriously affecting the pressure in the surrounding system. These buried tanks are known as
storage, the distribution storage has a head lower than the hydraulic grade line (HGL) required by the
“zone tanks”, and the repumping stations are known as “internal pumping stations”. With pumped
system, so the water must be pumped out of the zone tank to be used.
storage, the distribution storage has a head lower than the hydraulic grade line (HGL) required by
The pumped storage pump pressurises water from the storage facility for delivery to customers
the system, so the water must be pumped out of the zone tank to be used.
within the pressure zone. This procedure consists of the optimal spacing of a few buried storage
The pumped storage pump pressurises water from the storage facility for delivery to customers
tanks on some
within the of the distribution
pressure mains of the
zone. This procedure distribution
consists of the system.
optimal These tanks
spacing of are supplied
a few buried with the
storage
required discharge for downstream consumers through some low pressure transmission mains, even
tanks on some of the distribution mains of the distribution system. These tanks are supplied with the
by means of gravity, for
required discharge if possible. From consumers
downstream these storage tanks, the
through required
some discharge
low pressure is repumped
transmission into
mains,
the distribution network at the relatively low pressure of the transmission mains in
even by means of gravity, if possible. From these storage tanks, the required discharge is repumped the junction point.
This process does not incur a considerable energy loss, which would occur if the tanks are filled from
into the distribution network at the relatively low pressure of the transmission mains in the junction
the distribution network.
point. This process does not incur a considerable energy loss, which would occur if the tanks are
Using this procedure, a subdivision of pumped discharge Qp and pump heads Hpe,j of external
filled from the distribution network.
pumping stations is achieved as follows.
Using this procedure, a subdivision of pumped discharge Q p and pump heads Hpe,j of external
From the total discharge Q delivered
pumping stations is achieved as follows.
p by NP external pumping stations, a part Qpn is transported
through the distribution mains of
From the total discharge Q pressurised network, and another part Qpa is transported
p delivered by NP external pumping stations, a part Q through
pn is transported
transmission mains at NT buried storage tanks, according to the following equation:
through the distribution mains of pressurised network, and another part Qpa is transported through
transmission mains at NT buried storage tanks, according to the following equation:
NP NP NT
∑Q
NPp,j = ∑NP
Q pn,j + ∑
NTQ pa,k (6)
j =1
j 1
j 1
Q p,j j=1 Q pn,j k=1 Q pa,k
k 1
(6)
Water 2016, 8, 593 8 of 19
Pump heads Hpe,j of the external pumping stations are decreased at the values hpe,j . The total
pump station power P is computed using Equation (7) if the transmission mains are operated by
gravity or using Equation (8) if the transmission mains operate by pumping:
γ NP NT
P= ( ∑ Q pn,j h pe,j + ∑ Q pa,k H pi,k ) (7)
η j =1 k =1
γ NP NT NT
P= ( ∑ Q pn,j h pe,j + ∑ Q pa,k H pa,k + ∑ Q pa,k H pi,k ) (8)
η j =1 k =1 k =1
where γ is the water specific weight; η is the aggregated and averaged efficiency of the pumping
stations; Qpa,k is the discharge of the pumped storage pump (internal pumping station) k; Hpi,k is the
pump head corresponding to the pressure zone served by the internal station k; and Hpa,k is the pump
head at the external station for water delivery through transmission mains at storage tank k.
Pump heads hpe,j are much lower than pump heads Hpe,j because the head losses are changing
in proportion with the square of the ratio Qpn,j /Qp,j < 1. Thus, the power of the external pumping
stations decreases by reducing the discharge as well as by reducing the pressure, and total power is
decreased by:
γ NP
∆P = ( ∑ Q p,j H pe,j − P) (9)
η j =1
where x is the abscissa of the computing section, reported at an upstream extremity of the distribution
main; Q(x) is the pipe discharge in section X; R0 (x) is the specific (per unit length) hydraulic
resistance [6,35] of the distribution main in section X; and β is an exponent with values in the range of
1.85 to 2.0, that depends on the Reynolds number and the relative pipe roughness [36].
The variations of the discharge Q(x) and the hydraulic resistance R0 (x) are estimated as:
Q( x ) = q0 + axα (11)
R0 ( x ) = r0 − bx2 (12)
where the real constants q0 , r0 , and b are computed from the boundary conditions: x = 0, Q(0) = q0 ,
R0 (0) = 8λ/(π 2 gDm
5 ), and x = L, R ( L ) = 8λ/ ( π 2 gD5 ) in which λ is the pipe friction factor, R (x)
0 M 0
Water 2016, 8, 593 9 of 19
Water 2016, 8, 12 9 of 19
is the
the hydraulic resistanceper
hydraulic resistance perlength
lengthunit
unitof
ofthe
thepipe,
pipe,and
andthe
theparameters andα α
parametersa aand are
are determined
determined
statistically [37] based on the discharge distribution along the distribution main.
statistically [37] based on the discharge distribution along the distribution main.
TheThe optimal solution for the location of a pumped storage tank coupled with SP
optimal solution for the location of a pumped storage tank coupled with SP i is determined
i is determined
byby the value of x , for which the total power P expressed by Equation (Appendix A, A6) becomes
the value of x0 , 0for which the total power P expressed by Equation (Appendix A, A6) becomes
minimum (Figure 4d):
minimum (Figure 4d):
γ α α 1 3 α 3 βα 1 α βα 1 βα 3 α βα 3
min
minP = Pγ (c c x αc2 xc03 x0αc+31x+0 c4x03c+
η ( c0 + c10 x0 +1 c20 x0 + 4 xc05
x0αc+53x0+ c6x0βα
c6 x+01 +
c7 c cc88 xx0βα
x07αx+0βα+1 + 0
+3 c x α+βα)+3
+ 9c9 x0 0 )(13)
(13)
η
where c0 . 0. … c
where c . c9 9are the coefficients of the objective function depending on the parameters a, b, α, β,0, r0 ,
are the coefficients of the objective function depending on the parameters a, b, α, β, r
q0 ,qand L as shown in [38].
0, and L as shown in [38].
Figure
Figure 4. 4. Optimal
Optimal location
location of
of aa pumped
pumped storage
storage tank.
tank. (a)
(a)Schematic
Schematicof ofthe
thedistribution
distributionmain;
main;
(b) Discharge distribution; (c) Head loss variation; (d) Power variation of the external and internal
(b) Discharge distribution; (c) Head loss variation; (d) Power variation of the external and internal
pump stations.
pump stations.
The minimum of the objective Equation (13) is evaluated using an interpolation numerical
The minimum of the objective Equation (13) is evaluated using an interpolation numerical method,
method, based on a searching algorithm with an accelerated step coupled with square interpolation
based on a searching
(modified algorithm with an accelerated
Broyden‐Fletcher‐Goldfarb‐Shann step
general coupled[39],
method) with square
which interpolation
were (modified
implemented in a
Broyden-Fletcher-Goldfarb-Shann general method) [39], which were implemented in a computer
computer program. The flow chart of this algorithm is illustrated in Figure 5, where: X(1) is the start
program. The flow chart of this algorithm is illustrated in Figure 5, where: X(1) is the start point;
point; S is the step; R is the reduction coefficient of step; ε is the critical value of convergence; and X 0
S isis the interpolation result.
the step; R is the reduction coefficient of step; ε is the critical value of convergence; and X0 is the
interpolation result.
Water 2016, 8, 593 10 of 19
Water 2016, 8, 12 10 of 19
Figure 5. Flow chart of searching algorithm with an accelerated step.
Figure 5. Flow chart of searching algorithm with an accelerated step.
3.2. Intermediary Pumping Stations Integrated on the Distribution Mains
3.2. Intermediary Pumping Stations Integrated on the Distribution Mains
Direct integration of pumps on the network main pipes is a rational possibility for preservation
Direct integration of pumps on the network main pipes is a rational possibility for preservation of
of the energy used in the water distribution process.
the energyOn usedthe in the water mains
distribution distribution
where process.
a repumping station is mounted with parallel‐connected
pumps, water is taken over
On the distribution mains where a repumpingpstation
at a lower pressure 1 and repressed
is mountedat a with
higher pressure p2, and the
parallel-connected pumps,
pump head is H pi = (p2–p1)/γ.
water is taken over at a lower pressure p1 and repressed at a higher pressure p2 , and the pump head is
Use of serial‐connected intermediary pump stations on some distribution mains amplifies the
Hpi = (p2 –p 1 )/γ.
discharge through these pipes. These pump stations also generate a low pressure zone upstream in
Use of serial-connected intermediary pump stations on some distribution mains amplifies the
the suction node but ensures an important increase in pressure downstream in the pressure node. In
discharge through these pipes. These pump stations also generate a low pressure zone upstream in
this mode, favourable local increases in the piezometric head (HGL) in the system are generated. The
the suction node but ensures an important increase in pressure downstream in the pressure node.
In this mode, favourable local increases in the piezometric head (HGL) in the system are generated.
The repumping station is located almost at the suction node, and connection of the service lines at
Water 2016, 8, 593 11 of 19
the upstream pipes is not made from the suction node but rather immediately downstream from
the pump.
Considering that in a distribution system served by NP external pump stations (SPe ) intermediary
pump stations are directly serial-connected on a number of NA distribution mains, the total power in
the system is:
γ NP NA
P = ( ∑ Q p,j h pe,j + ∑ Q pa,k H pi,k ) (14)
η j =1 k =1
where Qp,j and hpe,j are the discharge and pump head, respectively, for external pump station j, and
Qpak and Hpi,k are the discharge and pump head, respectively, for intermediary pump station k.
Because the pump heads of the external pump stations are decreased (hpe,j << Hpe,j ) and the
discharges of the intermediary pump stations became equal to the local discharges of the distribution
mains on which they are integrated, a power reduction ∆P occurs according to Equation (9). As a result,
electrical energy consumption in the system is reduced with ∆W.
The optimal solution for the location of the intermediary pump stations and the choice of their
number, as well as the pumps from each of them, is determined by minimising the total installed power.
9.81
W= Q p H pe Tp (15)
η
where Qp is the pumped discharge in the system; Hpe is the maximum pump head (for a network
supplied by one-sided pumping from the exterior); Tp is the pumping time; and η is the efficiency of
the pump station.
The pump head is established as a function of the elevated tank location related to the pump
station, the required pressure and the head losses in the transport pipes.
The cost economy obtained by the transfer of energy consumption from peak hours to base hours
can be evaluated using the following equation:
9.81
C= Q p H pe Tp (e1 − e2 ) (16)
η
where e1 , and e2 are the estimated electric energy tariffs during peak hours and base hours, respectively.
Water 2016, 8, 593
Water 2016, 8, 12 12 of 19
12 of 19
Because of higher level oscillations, the advantages of peak energy savings could be lost by
Because of higher
increasing global level
energy oscillations, As
consumption. the a
advantages ofnecessary
result, it is peak energy savings
to study could
the be lost
elevated by
tank
increasing global energy consumption. As a result, it is necessary to study the elevated tank behaviour
behaviour in different constructive solutions and to study the way in which their potential
incharacteristics influence the energy balance of the distribution.
different constructive solutions and to study the way in which their potential characteristics influence
the energy balance of the distribution.
3.4. Economic Indicators
3.4. Economic Indicators
Incorporating potential elements into the water distribution system requires an additional
Incorporating potential elements into the water distribution system requires an additional
investment, and its efficiency can be evaluated by the simply pay back time (SPBT), calculated as follows:
investment, and its efficiency can be evaluated by the simply pay back time (SPBT), calculated
I
as follows: SPBT ∆I RTn (17)
SPBT = Ce C<i RTn (17)
Ce − Ci
where
where ∆Iis
I the
is the additional investment for the optimised system; C
additional investment for the optimised system; Ce ise is the annual operation cost for
the annual operation cost for the
the reference system with the network supplied by one‐sided pumping from the exterior; C
reference system with the network supplied by one-sided pumping from the exterior; Ci is the i is the annual
annual operation
operation cost for thecost for the
system withsystem with
internal internal
potential potential
elements; elements;
and and
RTn is the RTn is
normal the normal
recovery time
ofrecovery time of 10–12 years
10–12 years.
Equation (17) can be reformulated in the following form [38]:
Equation (17) can be reformulated in the following form [38]:
I
SPBT ∆I RTn (18)
SPBT = C r< I RTn (18)
∆Cw − r∆I
w
where ∆C
where Cwis is the difference between the energy cost C
the difference between the energy cost Cwewe for the reference system and the energy
for the reference system and the energy
w
cost Cwiwi for the optimised system and r is the repair, maintenance and periodic testing rate for the
cost C for the optimised system and r is the repair, maintenance and periodic testing rate for the
distribution system.
distribution system.
4.4. Case Studies
Case Studies
4.1. Potential Characteristics Influence of the Elevated Tanks on Distribution Energy Balance
4.1. Potential Characteristics Influence of the Elevated Tanks on Distribution Energy Balance
Table 2 provides the hourly variations in water demand and pumped water during the day by
Table 2 provides the hourly variations in water demand and pumped water during the day by
relative amounts (the per cents αd dand
relative amounts (the per cents α and α and cumulative per cents Σαd and Σα
αpp,, and cumulative per cents Σα and Σαpp). Starting from this
). Starting from this
table,
table, the compensatory
the compensatory function willwill
function be analysed
be analysed for two types
for two oftypes
elevated tanks: taper
of elevated tanktaper
tanks: optimised,
tank
with generatrix angle of inclination 45◦ from the horizontal
optimised, with generatrix angle of inclination 45 line, diameters of 36 m and 16 m, and
from the horizontal line, diameters of 36 m and
16 m, and maximum height of 10 m, and a rectangular (flat) tank with a height of 2 m. These water
maximum height of 10 m, and a rectangular (flat) tank with a height of 2 m. These water towers are
towers inare
located thelocated in the system
distribution distribution system
of a large urban of a large from
centre urban centre from
Romania Romania
and have and have
an average an
hourly
load equal to the maximum-day discharge Qd max = 3.59 m3 /sdmax
average hourly load equal to the maximum‐day discharge Q = = 3.59 m
301,536 m 3 /day.
3/s = 301,536 m 3/day.
The hour-compensatory
The hour‐compensatory volume volume of of an
an elevated
elevated tanktank isis given
given byby αvα·vQ
∙Qd dmax
max/100
/100 and
and total
total
compensatory capacity is defined as α
compensatory capacity is defined as αvmax vmax∙Q· Q
dmax /100. The water height h was computed every hour
d max /100. The water height h was computed every
for both
hour types
for both of tanks,
types as shown
of tanks, as shownin in
Figure
Figure 6. 6.
On Onthis
thisbasis,
basis,the
thecomparative
comparativevalues
valuesof ofelectricity
electricity
consumption for both types of elevated tanks are reported in Table 3.
consumption for both types of elevated tanks are reported in Table 3.
Figure 6. Water level fluctuation in elevated tanks.
Figure 6. Water level fluctuation in elevated tanks.
Water 2016, 8, 593 13 of 19
Table 3. Computation of energy consumption for water distribution using elevated tanks.
A large urban industrial centre from Romania with the water distribution network illustrated in
4.2. Energy–Economic Efficiency of Optimisation Solutions
4.2. Energy–Economic
Figure 7 is considered. Efficiency of Optimisation
In this section, a Solutions
comparative energy–economic analysis of the four
A large urban industrial centre from Romania with the water distribution network illustrated in
optimisation solutions with internal potential elements proposed for water distribution is
A large urban industrial centre from Romania with the water distribution network illustrated in
Figure 7 is considered. In this section, a comparative energy–economic analysis of the four
performed:
Figure 7 is considered. In this section, a comparative energy–economic analysis of the four optimisation
optimisation solutions with internal potential elements proposed for water distribution is
(1) First solution represents the classic reference case with an exterior pump station SP
solutions with internal potential elements proposed for water distribution is performed: e at the
performed:
water plant (direct pumping), which delivers a maximum‐hour discharge Q
First solution represents the classic reference case with an exterior pump station SP
(1)(1) First solution represents the classic reference case with an exterior pump station SP hmax = 4.30 m 3/s and an
e at the
e at the
average pump head H
water plant (direct pe = 60 m. Taking into account the schedule of the hourly pumped discharge
pumping), which delivers a maximum-hour discharge Q = 4.30 m 3 /s and an
max = 4.30 m3/s and an
water plant (direct pumping), which delivers a maximum‐hour discharge Qhhmax
(Figure 8), the daily energy consumption W is determined.
average pump head Hpe pe= = 60 m. Taking into account the schedule of the hourly pumped discharge
60 m. Taking into account the schedule of the hourly pumped discharge
average pump head H
(2) 8),
(Figure Second solution
the daily assumes
energy partition
consumption Wof
(Figure 8), the daily energy consumption W is determined. the town into seven distinct pressure zones, with a
is determined.
pumped storage
Second
(2)(2) Second tank
solution located
assumes
solution in
assumes each
partition zone
of the
partition centre.
of town The seven
into
the town external
into pump
distinct
seven station
pressure
distinct SPe supplies
zones,
pressure with a with
zones, buried
pumped a
tanks R
storage
pumped k (k = 1 ... 7) of pumped storage through a low pressure looped transmission network (Figure
tankstorage
located in each
tank zone
located centre.
in each The
zone external
centre. The pump station
external pump SP e supplies
station tanks Rk
buried buried
SPe supplies
9).
(k = In this
1 ...
tanks R k7)way, outside storage
of pumped of the through
peak energy
a lowconsumption
pressure looped hours, the maximum‐day
transmission
(k = 1 ... 7) of pumped storage through a low pressure looped transmission network (Figure discharge
network (Figure 9).
Q
9). =
In 3.94
this m 3/s and the average pump head hpe = 15 m are continuously assured. The pumped
way, outside of the peak energy consumption
In this way, outside of the peak energy consumption hours, the maximum-day discharge
dmax hours, the maximum‐day discharge
storage
Qd max pump
Qdmax= = 3.94
3.94 3stations
mm/s/s and
3 generate
and the
the average via
average pump the buried
pump head
head hpetanks
pe = = 15 the
15 m hourly
m are discharge
are continuously Q,
continuouslyassured. according
assured.The Thepumped to
pumped the
pumping schedule from Figure 10, and the required pressure for the pressure zones.
storage
storage pump pump stations
stations generate
generate via buried
via the the buried
tankstanks the hourly
the hourly discharge
discharge Q, according
Q, according to the
to the pumping
The average pump heads corresponding to the pressure zones k have the following values, in
pumping schedule from Figure 10, and the required pressure for the pressure zones.
schedule from Figure 10, and the required pressure for the pressure zones.
The The average pump heads corresponding to the pressure zones k have the following values, in
m: 30.2, 40.8, 33.7, 43.6, 31.1, 37.5, and 29.6. The total daily energy consumption W for this solution is
average pump heads corresponding to the pressure zones k have the following values,
m: 30.2, 40.8, 33.7, 43.6, 31.1, 37.5, and 29.6. The total daily energy consumption W for this solution is
evaluated.
in m: 30.2, 40.8, 33.7, 43.6, 31.1, 37.5, and 29.6. The total daily energy consumption W for this solution
evaluated.
is evaluated.
Figure 7. Schematic of the analysed distribution network.
Figure 7. Schematic of the analysed distribution network.
Figure 7. Schematic of the analysed distribution network.
Figure 8. Pumping schedule of SPe for the reference solution.
Figure 8. Pumping schedule of SP
Figure 8. Pumping schedule of SPee for the reference solution.
for the reference solution.
Water 2016, 8, 593
Water 2016, 8, 12 15 of 19
15 of 19
Water 2016, 8, 12 15 of 19
Figure 9. Schematic of the supply network of pumped storage tanks.
Figure 9. Schematic of the supply network of pumped storage tanks.
Figure 9. Schematic of the supply network of pumped storage tanks.
Figure 10. Pumping schedule for pumped storage tanks.
Figure 10. Pumping schedule for pumped storage tanks.
Figure 10. Pumping schedule for pumped storage tanks.
(3) Third solution replaces the buried tanks R
(3) Third solution replaces the buried tanks Rkkk with the elevated tanks C
with the elevated tanks Ckkk (k = 1 ... 7) with smaller
(k = 1 ... 7) with smaller
(3) Third solution replaces the buried tanks R with the elevated tanks C (k = 1 ... 7) with smaller
levels
levels of fluctuation, which ensures a gravitational distribution in the respective zones. The
levels ofof fluctuation,
fluctuation, which ensures
which a gravitational
ensures distribution
a gravitational in the respective
distribution zones. The
in the respective discharge
zones. The
discharge Q
Q d max = 3.94 dmax
3 = 3.94 m
m = 3.94 m
dmax 3/s is pumped from external pump station SPe with an average pump head
/s is pumped from external pump station SPe with an average pump head hpe = 49 m,
discharge Q 3/s is pumped from external pump station SP e with an average pump head
hpe = 49 m, according to the pumping schedule presented in Table 2, which sets a reduced pumping
according to the pumping schedule presented in Table 2, which sets a reduced pumping during peak
hpe = 49 m, according to the pumping schedule presented in Table 2, which sets a reduced pumping
during peak hours of electricity consumption.
hours of electricity consumption.
during peak hours of electricity consumption.
(4) Fourth solution
(4) Fourth solutionconsists
consistsof ofdirect
directwater
water pumping
pumping through
throughintermediary
intermediary pump pumpstations SP
stationsi1i1
(4) Fourth solution consists of direct water pumping through intermediary pump stations SP
and SP
SP i1 and
i2 (Figure 7), assuming that the service pipes are connected immediately downstream of these
SPi2 (Figure 7), assuming that the service pipes are connected immediately downstream
and SP i2 (Figure 7), assuming that the service pipes are connected immediately downstream of these
stations. The intermediary pump stations are integrated on water mains M
of these stations. The intermediary pump stations are integrated on water 1 and M 2. External pump
mains M1 and M2 .
stations. The intermediary pump stations are integrated on water mains M 1 and M2. External pump
station SPe delivers discharge Qhmax = 4.30 m 3/s, with an average pumping head hpe = 40.5 m, and
3
station SPe delivers discharge Qhmax = 4.30 m /s, with an average pumping head hpe = 40.5 m, and
intermediary pump stations equipped with two sets of three parallel‐connected pumps operating
intermediary pump stations equipped with two sets of three parallel‐connected pumps operating
Water 2016, 8, 593 16 of 19
External pump station SPe delivers discharge Qh max = 4.30 m3 /s, with an average pumping head
hpe = 40.5 m, and intermediary pump stations equipped with two sets of three parallel-connected
pumps operating with discharges of 0.94 m3 /s and 1.78 m3 /s, for average pump heads Hpi,1 = 13.0 m
and Hpi,2 = 11.4 m, respectively.
The supply network design of the buried tanks and the computation of the discharge and
pressure distribution in the network for all of the analysed solutions were performed using computer
programmes OPNELIRA [41] and ANOREC [35].
Solution
No. Indicator
(1) (2) (3) (4)
Additional investment, 10−3 ∆I [€]
– transmissions mains – 1240 1240 –
1 – tanks – 157 625 –
– pump stations – 52 – 63
Total – 1449 1865 63
Average pump head, Hp [m]
2 – external pump station 60 15 49 40.5
– internal pump stations – 35 – 12
Consumed energy, W [MWh/year]
– external pump station 25,300 6600 21,600 19,600
3 – internal pump stations – 13,400 – 3600
Total 25,300 20,000 21,600 23,200
Peak 7300 2700 3400 5400
Operation cost, 10−3 Cw [€/year]
–energy cost difference, 10−3 ∆Cw – 170 135 67
4
–pay-off rate, 10−3 r∆I – 29 38 1
Costs difference, 10−3 (∆Cw − p∆I) – 141 97 66
5 SPBT [years] – 10 19 1
(MWh/year) 5300 3700 2100
6 Energy saving, ∆W
(%) 21 15 8
In general, for urban industrial centres with other technological characteristics, the absolute values
vary over a very large range, but the proportions at the level of comparable parameters are maintained
and the results of comparative computations remain available.
The distribution system with zone pumped storage has an important advantage of reducing
energy consumption by 5300 MWh/year, from which 4600 MWh/year occurs during peak hours,
although the economic efficiency is near the limit (SPBT = 10 years) (Table 4).
Solution 4 of repumping with intermediary stations requires primarily small additional
investments, but it ensures decreased energy consumption only under the assumption that service
lines are supplied from the high pressure zone downstream of the integrated pump stations. If this
Water 2016, 8, 593 17 of 19
condition is not realised due to constructive reasons, the HGL must be raised to 9 m to ensure the
required pressure. As a result, the energy consumption increases, which reduces the energy efficiency
of this solution, which is smaller than that of the solution with pumped storage tanks.
In this analysis, the optimal solution is considered to be Solution 2, with a convenient SPBT
of 10 years and the greatest energy savings of 21% compared with the energy consumption in a
reference unzoned distribution system.
6. Conclusions
Major findings of this study are concluded as follows:
Using potential elements can be replacing the doubling of distribution mains or increasing the
diameters of the distribution mains, which are expensive solutions. In addition to the energy-efficient
flow control in pumping, the rotational speed control using VSDs for each parallel-connected pump
can open new opportunities for the advanced control of the pumping processes.
This study confirmed the favourable energy–economic efficiency for the procedure of determining
the optimal location of pumped storage supply via low pressure transmission mains and the use of
buried tanks and internal pump stations. This procedure leads to energy savings of 8%–21% and
provides the possibility of chlorine step dosage for water disinfection, enabling a smaller dose of
chlorine at the water plant tanks.
The case of distribution networks with elevated tanks usually does not result in an absolute
reduction of electricity, but, generally, the energy cost is diminished because of the scheduling of the
more intense pumping outside of the peak hours of energy consumption. The absolute decrease in
energy consumption in the case of elevated rectangular tanks of low water height demands these
structures in a water distribution system.
The use of intermediary pump stations integrated on distribution mains has the advantages
of making the pressure more uniform in large networks, avoiding the zones with exaggerated high
pressure. However, some low pressure zones appear at the initial node of the distribution main on
which the repumping station is located. This deficiency can be completely eliminated by connecting
the service lines upstream of a pump.
Because water supply systems are executed sequentially, the proposed solutions for energy
optimisation of the water distribution can be combined while respecting the essential principles in the
structural development of the system.
Appendix A
Substituting Equations (11) and (12) into Equation (10) and integrating, the resulting equation
until section X0 is obtained:
To describe the hydraulic regime upstream of section X0 , the discharge equation can be written
under a simple form:
Q0 ( x ) = Q( x ) − Q( x0 ) = a( xα − x0α ) (A2)
This equation results in the piezometric head (HGL) in the supply node of the distribution main:
References
1. Watergy. 2009. Available online: http://www.watergy.net/-overview/why.php (accessed on 5 June 2015).
2. Moreira, D.F.; Ramos, H.M. Energy cost optimization in a water supply system case study. J. Energy 2013.
[CrossRef]
3. Coelho, B.; Andrade-Campos, A. Efficiency achievement in water supply systems–A review. Renew. Sustain.
Energy Rev. 2014, 30, 59–84. [CrossRef]
4. Bene, J.G.; Selek, I.; Hös, C. Neutral search technique for short-term pump schedule optimization. J. Water
Resour. Plan. Manag. 2010, 136, 133–137. [CrossRef]
5. Vilanova, M.R.N.; Balestieri, J.A.P. Energy and hydraulic efficiency in conventional water supply systems.
Renew. Sustain. Energy Rev. 2014, 30, 701–7014. [CrossRef]
6. Walski, T.M.; Chase, D.V.; Savic, D.A.; Grayman, W.; Beckwith, S.; Koelle, E. Advanced Water Distribution
Modeling and Management; Haestad Press: Waterbury, CT, USA, 2003.
7. Binder, A. Potentials for energy saving with modern drive technology: A survey. In Proceedings of the
International Symposium on Power Electronics, Electrical Drives, Automation and Motion, Ischia, Italy,
11–13 June 2008.
8. Pemberton, M.; Bachmann, J. Pump systems performance impacts multiple bottom lines. Eng. Min. J. 2010,
211, 56–59.
9. Ferreira, F.J.T.E.; Fong, C.; de Almeida, T. Eco-analysis of variable-speed drives for flow regulation in
pumping system. IEEE Trans. Ind. Electron. 2011, 58, 2117–2125. [CrossRef]
10. Zhang, H.; Xia, X.; Zhang, J. Optimal sizing and operation of pumping systems to achieve energy efficiency
and load shifting. Electr. Power Syst. Res. 2012, 86, 41–50. [CrossRef]
11. McCormick, G.; Powell, R.S. Optimal pump scheduling in water supply systems with maximum demand
charges. J. Water Resour. Plan. Manag. 2003, 129, 372–379. [CrossRef]
12. Van Zyl, J.E.; Savic, D.A.; Walters, G.A. Operational optimization of water distribution systems using a
hybrid genetic algorithm. J. Water Resour. Plan. Manag. 2004, 130, 160–170. [CrossRef]
13. Salomons, E.; Goryashko, A.; Shamir, U.; Rao, Z.; Alvisi, S. Optimizing the operation of the Haifa: A water
distribution network. J. Hydroinf. 2007, 9, 51–64. [CrossRef]
14. Lopez-Ibáñez, M.; Prasad, T.D.; Paechter, B. Ant colony optimization for optimal control of pumps in water
distribution networks. J. Water Resour. Plan. Manag. 2008, 134, 337–346. [CrossRef]
15. Broad, D.R.; Maier, H.R.; Dandy, G.C. Optimal operation of complex water distribution systems using
metamodels. J. Water Resour. Plan. 2010, 136, 433–443. [CrossRef]
16. Vogelesang, H. Two approaches to capacity control. World Pumps 2009, 511, 26–29. [CrossRef]
17. Pemberton, M. Intelligent variable speed pumping. Plant Eng. 2003, 57, 28–30.
18. Bortoni, E.; Almeida, R.A.; Viana, A.N.C. Optimization of parallel variable-speed-driven centrifugal pumps
operation. Energy Effic. 2008, 1, 167–173. [CrossRef]
19. Yang, Z.; Borsting, H. Energy efficient control of a boosting system with multiple variable-speed pumps
in parallel. In Proceedings of the 49th IEEE Conference on Decision and Control, Atlanta, GA, USA,
15–17 December 2010.
20. Viholainen, J.; Tamminen, J.; Abhonen, T.; Ahola, J.; Vakkilainen, E.; Soukka, R. Energy-efficient control
strategy for variable speed-driven parallel pumping systems. Energy Effic. 2013, 6, 495–509. [CrossRef]
Water 2016, 8, 593 19 of 19
21. Araujo, L.S.; Ramos, H.; Coelho, S.T. Pressure control for leakage minimisation in water distribution systems
management. Water Resour. Manag. 2006, 20, 133–149. [CrossRef]
22. Carravetta, A.; Del Giudice, G.; Fecarotta, O.; Ramos, H.M. Energy production in water distribution networks:
A PAT design strategy. Water Resour. Manag. 2012, 26, 3947–3959. [CrossRef]
23. Diniz, A.M.F.; Fontes, C.H.; da Costa, C.A.; Costa, G.M.N. Dynamic modeling and simulation of water
supply system with applications for improving energy efficiency. Energy. Effic. 2014, 8, 417–432. [CrossRef]
24. Nazif, S.; Karanouz, M.; Moridi, A. Pressure management model for urban water distribution networks.
Water Resour. Manag. 2010, 24, 437–458. [CrossRef]
25. Lenzi, C.; Bragalli, C.; Bolognesi, A.; Artina, S. From energy balance to energy efficiency indicators including
water losses. Water Sci. Technol. Water Supply 2013, 13, 889–895. [CrossRef]
26. Sarbu, I.; Ostafe, G. Energetically optimization of water distribution systems in large urban centers.
Period. Polytech. Mech. Eng. 2008, 52, 93–102. [CrossRef]
27. Feldman, M. Aspects of energy efficiency in water supply systems. In Proceedings of the 5th IWA Water
Loss Reduction Specialist Conference, Cape Town, South Africa, 26–30 April 2009.
28. Rishel, J.B. Water Pumps and Pumping Systems; McGraw-Hill: New York, NY, USA, 2002.
29. Marchi, A.; Simpson, A.R.; Ertugrul, N. Assessing variable speed pump efficiency in water distribution
systems. Drink. Water Eng. Sci. 2012, 5, 15–21. [CrossRef]
30. Sarbu, I.; Borza, I. Energetic optimization of water pumping in distribution systems. Period. Polytech.
Mech. Eng. 1998, 42, 141–152.
31. Hooper, W. Advantages of parallel pumping. Plant Eng. 1999, 31, 4–6.
32. Volk, M. Pump Characteristics and Applications; Taylor & Francis Group: Boca Raton, FL, USA, 2005.
33. Kaya, D.; Yagmur, E.A.; Yigit, K.S.; Kilic, F.C.; Eren, A.S.; Celik, C. Energy efficiency in pumps.
Energy Convers. Manag. 2008, 49, 1662–1673. [CrossRef]
34. Gibson, I.H. Variable-speed dives as flow control elements. ISA Trans. 1994, 33, 165–169. [CrossRef]
35. Sarbu, I. Nodal analysis of urban water distribution networks. Water Resour. Manag. 2014, 28, 3143–3159.
[CrossRef]
36. Sarbu, I. Analysis of looped water supply networks. La Houille Blanche 2001, 3–4, 138–142.
37. Démidovitch, B.; Maron, I. Elements de Calcul Numerique; Mir: Moscou, Russia, 1979.
38. Sarbu, I. Energy Optimization of Water Distribution Systems; Romanian Academy Publishing House: Bucharest,
Romania, 1997.
39. Polak, E. Computational Methods in Optimization; Academic Press: New York, NY, USA, 1971.
40. Walski, T.M. Hydraulic design of water distribution storage tanks. In Water Distribution System Handbook;
McGraw Hill: New York, NY, USA, 2000.
41. Sarbu, I.; Kalmar, F. Optimization of looped water supply networks. Period. Polytech. Mech. Eng. 2002,
46, 75–90.
© 2016 by the author; licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC-BY) license (http://creativecommons.org/licenses/by/4.0/).