Model: Maa: Lightning Surge Protectors For Electronics Equipment M-RESTER Lightning Surge Protector For Power Supply Use
Model: Maa: Lightning Surge Protectors For Electronics Equipment M-RESTER Lightning Surge Protector For Power Supply Use
Model: Maa: Lightning Surge Protectors For Electronics Equipment M-RESTER Lightning Surge Protector For Power Supply Use
Lightning Surge Protectors for •Green: The unit has received one or more surges.
•Amber: Replacement is recommended.
Electronics Equipment M-RESTER
•Red: The life span has ended.
Alarm output: The N.C. contact is on when the life span of
LIGHTNING SURGE PROTECTOR the discharge elements has ended, when the voltage limiter
FOR POWER SUPPLY USE has degraded, and/or when the power supply is removed.
(5 A; high discharge current capacity; life monitor) Rating: 125 V AC @ 0.5 A (cos ø = 1)
Functions & Features 30 V DC @ 1 A (resistive load)
•Designed specifically for AC power supplies up to 5 amps Maximum switching voltage: 125 V AC or 110 V DC
•Discharge current capacity 10000 A Maximum switching power: 62.5 VA or 30 W
•Life monitor function helps you to decide when you should Minimum load: 5 V DC @ 1 mA
replace the M-RESTER; reduces maintenance and prevents
downtime INSTALLATION
•LED display and alarm contact output indicate the Operating temperature: -5 to +55°C (23 to 131°F)
degradation and life span of the surge protection circuits Operating humidity: 30 to 90 %RH (non-condensing)
•No power supply interruption even when the unit is Mounting: Surface or DIN rail
degraded or at the end of its life Weight: 500 g (1.1 lb)
50 PERFORMANCE
[1.97]
Operational voltage range:
90 – 132 V AC (MAA-100)
80 180 – 264 V AC (MAA-200)
[3.15]
50/60 Hz, approx. 2 VA
Discharge voltage (peak voltage)
Line to line: 190 V min. (MAA-100)
123
[4.84] 410 V min. (MAA-200)
mm [inch]
Line to ground: 400 V min.
Maximum surge voltage
MODEL: MAA–[1] Line to line: 380 V max. (MAA-100)
700V max. (MAA-200)
Line to ground: 800 V max.
ORDERING INFORMATION Withstand voltage of protected equipment between the
• Code number: MAA–[1] circuit and the metal housing must be 1000 V AC or more.
Specify a code from below for [1]. Response time: ≤ 0.01 μsec.
(e.g. MAA-100) Leakage current
Line to line: ≤ 26mA at 100 V AC (MAA-100)
[1] OPERATIONAL VOLTAGE ≤ 13 mA at 200 V AC (MAA-200)
100: 100 V / 110 V / 120 V AC Line to ground: ≤ 0.1 mA at 300 V AC
200: 200 V / 220 V / 240 V AC Discharge current capacity: 10000 A (8/ 20 μsec.)
Maximum load current: 5 A
Internal series resistance: ≤ 0.5 Ω including return
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m) STANDARDS & APPROVALS
Screw terminal: Chromated steel EU conformity:
Housing material: Flame-resistant resin (black) EMC Directive
Alarm indicators EMI EN 61000-6-4
POWER: The green LED turns on while the circuit is alive EMS EN 61000-6-2
and the internal fuse is not blown; and is off when the Low Voltage Directive
power supply is removed or the fuse is blown. EN 61010-1
ALARM: Tricolor LED (green/amber/red) Measurement Category II (alarm output)
•Remains off when the power supply is first turned on. Installation Category II (power)
https://www.m-system.co.jp/
MODEL: MAA
Pollution degree 2
Alarm output to power: Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
POWER LED
ALARM LED
GROUNDING
M-RESTER PROTECTED
EQUIPMENT
G G
GROUNDING
(100 ohms or less) CROSSOVER WIRE
A crossover wire between M-RESTER ground and ground or metallic
housing of equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
DIN RAIL
35mm wide 6 5 4 3
80 [3.15]
80 [3.15]
https://www.m-system.co.jp/
MODEL: MAA
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Fuse
U 1 4 U
POWER SOURCE Discharge Discharge PROTECTED
(surge side) Element Element EQUIPMENT
V 8 5 V
POWER LED
CT
ALARM LED
2 Leakage Current
Surge Detector 3
7 Counter Ry ALARM OUTPUT
6
Base Socket