Model ESFR-17 16.8 K-Factor Pendent Sprinkler Early Suppression, Fast Response General Description
Model ESFR-17 16.8 K-Factor Pendent Sprinkler Early Suppression, Fast Response General Description
www.tyco-fire.com
Contacts
Model ESFR-17
16.8 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General compared to ESFR Sprinklers having
a nominal K-factor of 14.0. This feature
Description offers flexibility when sizing system
piping, as well as possibly reducing or
TYCO Model ESFR-17 Pendent Sprin- eliminating the need for a system fire
klers are Early Suppression, Fast pump.
Response (ESFR) sprinklers having a
nominal K-factor of 16.8 (See Figure 1). WARNING
They are suppression mode sprinklers Sprinkler bulb protector must NOT be
that are especially advantageous as a removed until sprinkler is to be placed
means of eliminating in-rack sprinklers in service. The W-Type 35 Sprinkler
when protecting high-piled storage. Wrench MUST be used for proper
Model ESFR-17 Pendent Sprinklers are installation of the sprinkler. Failure to
primarily used for ceiling-only sprinkler do so may result in equipment damage
protection of (but not limited to) the fol- or failure.
lowing storage applications:
NOTICE
• most encapsulated or non-encap-
sulated common materials including The Model ESFR-17 Pendent Sprinklers Sprinkler
described herein must be installed and
cartoned, unexpanded plastics
• cartoned, expanded plastics
maintained in compliance with this Identification
document, as well as with the appli-
• uncartoned, unexpanded plastics cable standards of the National Fire
Protection Association (NFPA), in addi-
Number (SIN)
• uncartoned, expanded plastics See Table A for sprinkler identification
tion to the standards of any authorities number.
• some storage arrangements of having jurisdiction, such as FM Global.
rubber tires, roll paper, and aerosols
For more specific criteria, refer to Table
Failure to do so may impair the perfor-
mance of these devices. Technical
B in this technical data sheet as well as
the applicable design standard.
The owner is responsible for main-
taining their fire protection system
Data
and devices in proper operating con- Approvals
The Model ESFR-17 Pendent Sprin- dition. Contact the installing contrac- UL and C-UL Listed
klers provide the system designer tor or product manufacturer with any FM Approved
with hydraulic and sprinkler place- questions.
ment options not presently available Finish
to traditional ESFR Sprinklers having In all cases, the appropriate NFPA or Natural Brass
a nominal K-factor of 14.0. In particu- FM Global installation standard, or Physical Characteristics
lar, Model ESFR-17 Pendent Sprinklers other applicable standard, must be ref- Frame ���������������������������������������������������������Brass
are designed to operate at substan- erenced to ensure applicability and to Deflector ���������������������������������������������������Bronze
obtain complete installation guidelines. Compression Screw �����������������������������������Brass
tially lower-end head pressures, as Button. . . . . . . . . . . . . . . . . . . . Phosphor Bronze
The general guidelines in this technical Bulb(3mm) ������������������������������������������������� Glass
data sheet are not intended to provide Sealing Assembly. . Beryllium Nickel w/TEFLON
IMPORTANT complete installation criteria.
Additional Technical Data
Refer to Technical Data Sheet See Table A for additional technical data.
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Operation
Sheet TFP700 for the “INSTALLER The glass bulb contains a fluid which
WARNING” that provides cautions expands when exposed to heat. When
with respect to handling and instal- the rated temperature is reached, the
lation of sprinkler systems and com- fluid expands sufficiently to shatter the
ponents. Improper handling and glass bulb, allowing the sprinkler to
installation can permanently damage activate and water to flow.
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Solid Pile or Palletized Storage of Refer to NFPA 13 Refer to FM 2-0 and 8-9
Class I-IV and Group A or B Plastics Chapters 14 and 15
Refer to NFPA 13
Idle Pallet Storage Refer to FM 2-0, 8-9, and 8-24
Chapter 12
Refer to NFPA 13
Rubber Tire Storage Refer to FM 2-0 and 8-3
Chapter 18
Installation WARNING
Sprinkler bulb protector must NOT be
"FITTING SIDE"
TOWARD
TYCO Model ESFR-17 Early Suppres- removed until sprinkler is to be placed SPRINKLER
sion, Fast Response 16.8K Pendent in service. The W-Type 35 sprinkler FITTING
Sprinklers must be installed in accor- wrench MUST be used for proper
dance with this section. installation of the sprinkler. Failure to
General Instructions do so may result in equipment damage
Do not install any bulb type sprinklers or failure.
if the bulb is cracked or there is a loss Note: Install the Model ESFR-17
of liquid from the bulb. With the sprin- Pendent Sprinkler only in the pendent
WRENCH
kler held horizontally, a small air bubble position (See Figure 2).
RECESS
should be present. The diameter of the
Step 1. With pipe-thread sealant
air bubble is approximately 1/16 inch FIGURE 2
applied, hand-tighten the sprinkler into
(1,6 mm) for both 155°F (68°C) and W-TYPE 35
the sprinkler fitting. Do not apply pres-
205°F (96°C) temperature ratings. SPRINKLER WRENCH
sure to the bulb assembly, and handle
A leak-tight 3/4 inch NPT sprinkler joint the Model ESFR-17 Sprinkler only by
should be obtained by applying a min- the Frame arms.
imum-to-maximum torque of 10 to 20
Step 2. Wrench-tighten the Model
ft.-lbs. (13,4 to 26,8 Nm), or by hand-
ESFR-17 Sprinkler using only the
tightening and applying an additional
W-Type 35 Sprinkler Wrench (See
1-1/4 to 1-1/2 revolutions of the wrench.
Figure 2), and by fully engaging
Higher levels of torque can distort the
(seating) the wrench on the sprinkler
sprinkler inlet with consequent leakage
wrench flats (See Figure 1).
or impairment of the sprinkler.
Step 3. After installation, inspect the
bulb of each Model ESFR-17 Sprinkler
for damage. In particular, verify that the
bulb is not cracked. Replace damaged
sprinklers.
TFP322
Page 4 of 4