Example 23.1: E E E E E
Example 23.1: E E E E E
------------------------------------------------------------------------------------------------------------
Example 23.1
The phase sequence of the Y-connected generator in Fig. 23.13 is ABC.
a. Find the phase angles θ2 and θ3.
b. Find the magnitude of the line voltages.
c. Find the line currents.
Fig. 23.13
Example 23.1 – Solutions
c. Vø = Eø.
Therefore, Van = EAN Vbn = EBN Vcn = ECN
Example 23.2
For the three-phase system in Fig. 23.15:
Fig. 23.15
Example 23.2 – Solutions
b. Vø = EL.
Therefore, Vab = EAB Vca = ECA Vbc = EBC
c. I L = 3I = (1.73)(15A ) = 25.95A
Therefore, IAa = IBb = ICc = 25.95 A
Example 23.3
For the Δ-Δ system shown in Fig. 23.20:
a. Find the phase angles θ2 and θ3 for the specified phase sequence.
b. Find the current in each phase of the load.
c. Find the magnitude of the line currents.
Fig. 23.20
b. Vø = EL
Therefore, Vab = EAB Vca = ECA Vbc = EBC
Z = Z ab = Z bc = Z ca
=
Z R ZC
=
(50)(5 − 90) = 25 − 90 = 3.54 − 45
Z R + ZC 5 − j5 7.071 − 45
Vab 120V0
Iab = = = 33.9A45
Z ab 3.54 − 45
c. I L = 3I = (1.73)(34A ) = 58.82A
Therefore, IAa = IBb = ICc = 58.82 A
Example 23.4
For the Δ-Y system shown in Fig. 23.21:
Fig. 23.21
a. IøL = IL
Therefore
Ian = IAa = 2A0
Ibn = IBb = 2A − 120
Icn = ICc = 2A + 120
Example 23.5
For the Y-connected load in Fig. 23.23:
a. Find the average power to each phase and the total load.
b. Determine the reactive power to each phase and the total reactive power.
c. Find the apparent power to each phase and the total apparent power.
d. Find the power factor of the load.
Fig. 23.23
OR P =
VR
2
=
(60V )2 = 1200W
R 3
S = V I = (100V)(20A) = 2000 VA
PT 3600W
Fp = = = 0.6 lagging
S T 6000VA
Example 23.6
For the Δ-Y connected load in Fig. 23.25:
Fig 23.25
Example 23.6 – Solutions
For the Δ:
Z = 6 − j8 = 10 - 53.13
E 200 V
I = L = = 20 A
Z 10
PT = 3I 2 R = 3(20) (6) = 7200 W
2
For the Y:
Z Y = 4 + j3 = 5 36.87
EL 200 V
3 3 116 V
I = = = = 23.12 A
ZY 5 5
PTY = 3I 2 R = 3(23.12) (4) = 6414.41 W
2
PT 13,614.41W
Fp = = = 0.943 leading
S T 14,432.20VA
Example 23.7
Each transmission line of the three-wire, three-phase system in Fig. 23.36 has an
impedance of 15 Ω + j 20 Ω. The system delivers a total power of 160 kW at 12,000 V to
a balanced three-phase load with a lagging power factor of 0.86.
Fig. 23.26
VL 12,000 V
a. V (load) = = = 6936.42 V
3 1.73
Since = cos−1 0.86 = 30.68 , assigning V = V 0 , a lagging power factor results
in
I = 8.94 A - 30.68
For each phase, the system will appear as shown in Fig. 23.27, where
Fig. 23.27
The loading on each phase of the system in Fig. 23.26.
E AN = I Z line + V
= (8.94 − 30.68)(2553.13) + 6936.420
= 223.522.45 + 6936.420
= 206.56 + j85.35 + 6936.42
= 7142.98 + j85.35
= 7143.5 V0.68
Then
E AB = 3Eg = (1.73)(7143.5) = 12,358.26 V
b.
PT = Pload + Plines
= 160 kW + 3(I L ) Rline
2
= 160 kW + 3 (8.94) 15
2
= 160,000 W + 3596.55W
= 163,596.55W
And PT = 3V L I L cos T
PT 163,596.55
cos T = =
3V L I L (1.73)(12,358.26)(8.94)
FP = cos T = 0.856 0.86 of the load
Po Po 160 kW
= = = = 0.978
c. Pi Po + Plosses 160 kW + 3596.55W
= 97.8%