Millmate Roll Force Systems With Millmate Controller 400: User Manual
Millmate Roll Force Systems With Millmate Controller 400: User Manual
A B B M E A S U R E M E N T & A N A LY T I C S
3BSE023139R0401 en Rev A
Operator unit X2-40
Control unit 3.4-1
Use of DANGER, WARNING, CAUTION, and NOTE
This publication includes, DANGER, WARNING, CAUTION and NOTE information where appropriate to point out safety
related or other important information.
DANGER Hazards which could result in severe personal injury or death
WARNING Hazards which could result in personal injury
CAUTION Hazards which could result in equipment or property damage
NOTE Alerts user to pertinent facts and conditions
Although DANGER and WARNING hazards are related to personal injury, and CAUTION hazards are associated with
equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational
conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all
DANGER, WARNING, and CAUTION notices.
TRADEMARKS
®
Pressductor is a registered trademark of ABB AB.
NOTICE
The information in this document is subject to change without notice and should not be construed as a commitment by ABB
AB. ABB AB assumes no responsibility for any errors that may appear in this document.
In no event shall ABB AB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind
arising from the use of this document, nor shall ABB AB be liable for incidental or consequential damages arising from use of
any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without ABB AB’s written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized purpose.
The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance
with the terms of such license.
CE marking
Millmate Controller 401 fulfills the RoHS Directive 2011/65/EU, EMC Directive 2014/30/EU and Low Voltage Directive
2014/35/EU, provided that the installation is carried out in accordance with the installation instructions given in Chapter 3
Installation, included in this User Manual.
Template: 3BSE001286/D
3BSE023139R0401 Rev A
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
TABLE OF CONTENTS
Chapter 1 - Introduction
1.1 About This Manual .................................................................................................. 1-1
1.2 Cyber security disclaimer......................................................................................... 1-1
1.3 Disposal and Recycling............................................................................................ 1-1
1.3.1 Environmental Policy.............................................................................. 1-1
1.3.2 WEEE: Waste Electrical and Electronic Equipment............................... 1-2
1.3.3 Recycling the Transport Material............................................................ 1-2
1.3.4 Disposal of the Product ........................................................................... 1-2
1.3.4.1 Dismantling and Recycling of the Product....................... 1-2
1.3.5 Operator Unit HMI differences ............................................................... 1-3
1.4 Safety Information ................................................................................................... 1-3
1.4.1 Personal Safety........................................................................................ 1-3
1.4.2 Equipment Safety .................................................................................... 1-4
1.5 About This System................................................................................................... 1-4
3BSE023139R0401 Rev A 1
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
2.9 External Display QDIL 451 ................................................................................... 2-27
2.9.1 Technical Data....................................................................................... 2-27
2.9.2 Dimensions............................................................................................ 2-27
Chapter 3 - Installation
3.1 About this Chapter ................................................................................................... 3-1
3.2 General Installation Information .............................................................................. 3-1
3.3 Packaging and Delivery ........................................................................................... 3-1
3.4 Storage...................................................................................................................... 3-2
3.5 Mounting Load Cell Cabling and Accessories......................................................... 3-2
3.5.1 Cable Routing.......................................................................................... 3-2
3.5.2 Cable Protection ...................................................................................... 3-4
3.6 Installation of Matching Unit PFVO 142 and PFVO 143........................................ 3-4
3.7 Installing Junction Boxes PFXC 141 and PFBC 161............................................... 3-5
3.7.1 Junction Box PFXC 141.......................................................................... 3-6
3.7.2 Junction Box PFBC 161.......................................................................... 3-7
3.8 Electrical Connection of Load Cells ........................................................................ 3-8
3.8.1 Connecting PFVL 141 Load Cells to MC 400........................................ 3-8
3.8.2 Connecting QGPR 102/104 Load Cells to MC 400.............................. 3-12
3.8.3 Connecting QGPR 102/104 Load Cells with
Phase Matching Board PFBK 401 ........................................................ 3-17
3.9 Installing Millmate Controller 400......................................................................... 3-22
3.9.1 Mounting MC 400 Control Unit ........................................................... 3-22
3.9.2 Installing Wall Cabinet.......................................................................... 3-22
3.9.3 Installing MNS Select Floor Cabinet .................................................... 3-23
3.9.3.1 Mounting Cabinets Together .......................................... 3-23
3.9.3.2 Mounting Cabinets to the Floor...................................... 3-23
3.9.3.3 Space Requirements ....................................................... 3-24
3.9.4 Connecting Cables ................................................................................ 3-25
3.9.4.1 Power Supply Cables...................................................... 3-25
3.9.4.2 Signal Cables .................................................................. 3-26
3.9.4.3 Cable Specifications ....................................................... 3-26
3.9.4.4 Connection of Excitation Unit........................................ 3-28
3.9.4.5 Mains Connection........................................................... 3-28
3.9.4.6 Synchronisation (SYNC)................................................ 3-29
3.9.4.7 Connecting Millmate Operator Unit 410 to LAN. ......... 3-29
3.9.4.8 Connecting Redundant +24 V Supply to Millmate
Operator Unit 410 and Network switch.......................... 3-30
3.10 Installing Optional Units ........................................................................................ 3-31
3.10.1 Connecting Insulation Amplifier PXUB 201........................................ 3-31
3.10.2 Connecting Relay Board PFVK 128 ..................................................... 3-32
3.10.3 Mounting External Display QDIL 451 ................................................. 3-33
3.10.3.1 Dimensions ..................................................................... 3-33
3BSE023139R0401 Rev A 2
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
3.10.4 Connecting External Display QDIL 451............................................... 3-33
3.10.4.1 General ........................................................................... 3-33
3.10.4.2 Terminating RS-485 Cable Connected to QDIL 451 ..... 3-34
3.10.4.3 Power Supply for QDIL 451 .......................................... 3-34
3.10.5 Connecting Serial Ports......................................................................... 3-34
Chapter 4 - Commissioning
4.1 About This Chapter .................................................................................................. 4-1
4.2 Recommended Equipment ....................................................................................... 4-1
4.3 Actions Before Mains Supply is Switched On......................................................... 4-1
4.3.1 Visual Inspection..................................................................................... 4-2
4.3.2 Checking Connections ............................................................................ 4-2
4.3.3 Checking Power Supplies ....................................................................... 4-3
4.3.3.1 Millmate Controller 400 ................................................... 4-3
4.3.3.2 Millmate Operator Unit 410 ............................................. 4-3
4.3.3.3 Additional Supplies .......................................................... 4-3
4.4 Starting the Equipment............................................................................................. 4-3
4.4.1 Starting Millmate Controller 400 ............................................................ 4-3
4.4.2 Starting Millmate Operator Unit 410 ...................................................... 4-3
4.5 Commissioning the Control Unit ............................................................................. 4-4
4.5.1 Menu Map for Millmate Controller 400 ................................................. 4-4
4.5.2 Overview of Service Menus for the Control Unit................................... 4-5
4.5.3 Actions During the Commissioning........................................................ 4-6
4.5.4 Setting Up the Operator Unit .................................................................. 4-7
4.5.4.1 Set screen saver ................................................................ 4-7
4.5.4.2 Set Backlight Brightness .................................................. 4-8
4.5.4.3 Touch Screen Calibration ................................................. 4-8
4.5.5 Establishing Communication Between the Operator Unit and
the Control Unit, Millmate Controller 400 ............................................. 4-9
4.5.6 Setting Up Network Data For the Operator Unit .................................. 4-10
4.5.7 Setting Up Basic Data in the Control Unit............................................ 4-11
4.5.8 Defining a Measuring Object ................................................................ 4-12
4.5.8.1 Modifying an Existing Measuring Object ...................... 4-13
4.5.9 Objects Types ........................................................................................ 4-14
4.5.10 Changing Load Cell Data...................................................................... 4-15
4.5.11 Setting Force Measurement Parameters................................................ 4-17
4.5.11.1 Setting Filter Response Time ......................................... 4-18
4.5.11.2 Selecting Load Unit........................................................ 4-19
4.5.12 Setting Indication Parameters ............................................................... 4-20
4.5.12.1 Setting Up Level Detectors ............................................ 4-21
4.5.12.2 Setting Analog Output.................................................... 4-23
4.5.12.3 Setting Up Step Detector ................................................ 4-24
4.5.12.4 Object Information ......................................................... 4-27
3BSE023139R0401 Rev A 3
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
CONTENTS (continued)
Chapter 5 - Operation
5.1 About This Chapter .................................................................................................. 5-1
5.2 Safety........................................................................................................................ 5-1
5.3 Indications ................................................................................................................ 5-2
5.3.1 LED Indications ...................................................................................... 5-2
5.3.2 Fault Indications During Run.................................................................. 5-3
5.4 Start-up ..................................................................................................................... 5-4
5.5 Measurement During Normal Operation ................................................................. 5-5
5.6 Shutdown.................................................................................................................. 5-5
5.7 Operation.................................................................................................................. 5-6
5.7.1 Operation from the Operator Unit........................................................... 5-6
5.7.1.1 General ............................................................................. 5-6
5.7.1.2 Operator Unit Buttons ...................................................... 5-7
5.7.1.3 Operator Unit Display ...................................................... 5-8
5.7.2 Operation from an Optional Web Browser ............................................. 5-9
5.7.3 Selection List (List of Connected Objects) ........................................... 5-11
5.7.4 Service Menus....................................................................................... 5-11
5.7.4.1 Service Menu Settings for the Control Unit ................... 5-12
5.7.5 Settings for the Operator Unit ............................................................... 5-12
5.7.5.1 Set Screen saver.............................................................. 5-12
5.7.5.2 Set Backlight Brightness ................................................ 5-13
5.8 Connecting to a Measuring Object......................................................................... 5-14
5.8.1 Selecting an Object from the Selection List.......................................... 5-14
5.8.2 Changing to an Object in Another Control Unit ................................... 5-14
5.9 Operation Menus for Roll Force Measurement ..................................................... 5-15
5.9.1 Standard Measurement (720, 730, 740) ................................................ 5-15
5.9.1.1 Key Functions................................................................. 5-16
5.9.1.2 Operation Messages........................................................ 5-16
5.9.2 Single Input Measurement (710)........................................................... 5-17
5.9.2.1 Key Functions................................................................. 5-17
5.9.2.2 Operation Messages........................................................ 5-18
5.10 Multi View (750).................................................................................................... 5-18
5.11 Sub Functions for Operation Menus ...................................................................... 5-19
5.11.1 System Test (761, 762, 763).................................................................. 5-19
5.11.2 Changing to Single Cell Operation (775, 776, 777).............................. 5-20
5.11.3 Setting Load Cell Set Number .............................................................. 5-21
5.11.3.1 Key Functions................................................................. 5-21
5.11.4 Error Inspection..................................................................................... 5-22
Chapter 6 - Maintenance
6.1 About This Chapter .................................................................................................. 6-1
6.2 Periodical Maintenance............................................................................................ 6-1
3BSE023139R0401 Rev A 5
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
6.3 Operator Unit ........................................................................................................... 6-2
6.4 Cabinets.................................................................................................................... 6-2
6.5 Load Cells ................................................................................................................ 6-2
6.6 Changing Battery in the Control Unit ...................................................................... 6-3
6.7 Replacing Battery in the Operator unit .................................................................... 6-4
3BSE023139R0401 Rev A 6
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
A.3.3 Strip Tensiometer and Roll Force Meter Communication ..................... A-6
A.3.3.1 Input Package Sent to MST and MRF............................. A-6
A.3.3.2 Output Package Produced by MST and MRF ................. A-7
A.3.4 Strip Scanner Communication ............................................................... A-8
A.3.4.1 Input Package Sent to MSS ............................................. A-8
A.3.4.2 Output Package Produced by MSS ................................. A-9
3BSE023139R0401 Rev A 7
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Table of Contents
CONTENTS (continued)
Appendix C - Drawings
C.1 Millmate Controller 400 in Wall Cabinet, Dimension Drawing,
3BSE017454, Rev. B............................................................................................... C-1
C.2 Wall Cabinet Cylmate/Millmate Controller, Dimension Drawing,
3BSE022232D0064, Rev. C.................................................................................... C-2
C.3 MNS Select Cabinet, Dimension Drawing, 3BSE017052D64, Rev. B .................. C-3
C.4 Millmate Controller 400, Dimension Drawing, MC 400 on 19” Mounting Plate,
3BSE017453D0064, Rev. A ................................................................................... C-4
C.5 Millmate Controller 400, Dimension Drawing, 3BSE017585, Rev. A................... C-5
C.6 PFVI 401 Excitation Unit, Dimension Drawing, 3BSE028251, Rev. - .................. C-6
C.7 Vibration Isolators for Millmate Controller 400, Erection Drawing,
3BSE017462D0090, Rev. - ..................................................................................... C-7
C.8 Millmate Operator Unit 410 (PXAH 411), Dimension Drawing,
3BSE086846, Rev. - ................................................................................................ C-8
C.9 Relay Board, PFVK 128, Circuit Diagram, 3BSE010547D0002, Rev. B .............. C-9
C.10 Relay Board, PFVK 128, Arrangement Drawing, 3BSE010547D0004, Rev. E .. C-10
C.11 Matching Board, PFBK 401, Circuit Diagram, 3BSE027078D0002, Rev. -.........C-11
C.12 Matching Device, PFVO 142, Circuit Diagram, 3BSE023732D2, Rev. A .......... C-12
C.13 Matching Device, PFVO 143, Circuit Diagram, 3BSE023150D2, Rev. A .......... C-13
8 3BSE023139R0401 Rev A
Millmate Roll Force Systems with Millmate Controller 400, User Manual
Section 1.1 About This Manual
Chapter 1 Introduction
The crossed – out wheeled bin symbol on the product(s) and / or accompanying documents
means that used electrical and electronic equipment (WEEE) should not be mixed with general
household waste.
If you wish to discard electrical and electronic equipment (EEE), in the European Union, please
contact your dealer or supplier for further information.
Outside of the European Union, contact your local authorities or dealer and ask for the correct
method of disposal.
Disposing of this product correctly will help save valuable resources and prevent any potential
negative effects on human health and the environment, which could otherwise arise from
inappropriate waste handling.
Junction box
PFXC 141 or
PFBC 161
Analog PLC
inputs
Ethernet
Figure 2-1. Overview Diagram for a Millmate Roll Force System with Millmate Controller 400
2.3.1 General
The Millmate Roll Force Systems with MC 400 use Pressductor® load cells.
2.4.1 Overview
PFVL 141
Matching units
PFVO 142/143
1) Excitation unit
PFVI 401
Load cell
Power excitation
supply
PFVL 141
Mains
85 - 264 V
47 - 63 Hz
Control unit
PFXA 401
Junction box
PFXC 141 or Load cell
QGPR 102/104 Power excitation
PFBC 161
supply
+24 V
1)
AI AO
CPU
(4) (4)
1) Alternative DI DO
depending on (8) (8)
load cell type
2) Serial link
2) 3)
RS-232
RS-485
Operator unit
3) Fieldbus PXAH 411
CPU Display
Voltage Key-
converter board
The Millmate Controller 400 control unit supplies the load cells with power, processes signals
from the load cells and transfers measured values to the operator unit or external units.
The control unit is supplied with mains voltage.
The following additional connections exist:
• Excitation current to the load cells
• 2 or 4 analog inputs for load cells signals
• 4 analog outputs for measured values, voltage or current, insulated as one group.
• 8 digital inputs for control signals, insulated in two groups of four inputs each.
• 8 digital outputs for status signals and alarms, insulated in two groups with four outputs
each.
• +24 V output to power the Millmate Operator Unit 410 and external units, if any.
• Network connection for operator unit, Ethernet 10Base2, 10Base-T and AUI1.
• 2 serial interfaces type RS-232 for external displays, external control, etc.
• 1 serial interface type RS-485 for external displays.
• 1 “SYNC” connection for synchronisation of the load cell excitation frequency of several
control units.
Each Millmate Controller 400 control unit can handle up to four objects. The number of objects
is limited by the number of signal inputs and the power of the load cell power supply unit.
Load cells requiring different types of excitation cannot be mixed in the same control unit.
The control unit is encapsulated according to IP 20 and is intended for vertical mounting in an
external enclosure. The external enclosure is normally required to fulfil the demands for
electrical safety and environmental conditions.
Type Data
Mains voltage 85 - 264 V AC (100 V –15% to 240 V +10%)
Mains fuses (F1, F2)
in PFXA 401 2 A, slow blow
in PFVI 401 6.3 A, slow blow
Mains frequency 47 - 63 Hz
Power consumption
only PFXA 401 Max. 140 W with QGPR 102/104 load cells
PFXA 401 and PFVI 401 Max. 600 W with PFVL 101/141 load cells
Power factor Min. 0.95 at 140 W / 600 W
Type Data
Heat dissipation
PFXA 401 (Control unit) Max. 60 W with QGPR 102/104 load cells
Max. 40 W with PFVL 101/141 load cells
Type Data
Analog outputs (4)
Output level
Voltage output 0 ± 10 V
Current output 0 ± 20 mA or 4 - 20 mA
Max. load
Voltage output 5 mA
Current output 500
Rated insulation voltage 50 V AC
Digital inputs (8)
Input level 0 Nominal 0 V, –40 - +6 V
1 Nominal +24 V, +15 - +40 V
Current consumption Max. 5 mA at +24 V
Rated insulation voltage 50 V AC
Digital outputs (8)
Output level 0 Open contact
1 Current driving from external common supply,
protected by a parallel diode
Max. load 0.2 A, over current protection
Max. voltage drop 2 V at 0.2 A
Max. operating voltage (output not active) 50 V
Rated insulation voltage 50 V AC
External outputs (2)
Output, supply to operator unit (X8) +24 V DC (+22 - 28 V) max. 0.5 A (1)
Output, supply to external units (X18) +24 V DC (+22 - 28 V) max. 0.5 A (1)
Clock backup battery
Lithium, 3.6 V, 1.75 Ah, Size R6 SAFT type LS14500 CNA, or equivalent
ABB Ordering No. 3BSC790006R1
4943 013 - 4 (old number)
Environmental data
Degree of protection IP 20, according to IEC 529, EN 60-529
Temperature range 0 to +70°C operation
-40 to +70°C storage
Operating pressure Min. 80 kPa
Storage pressure Min. 70 kPa
Type Data
Mechanical data
Size (l × w × d)
PFXA 401 (Control unit) 380 × 235 × 90 mm
PFVI 401 (Excitation unit) 380 × 235 × 90 mm
Weight
PFXA 401 (Control unit) 5 kg
PFVI 401 (Excitation unit) 7.4 kg
(1) Max total current on X8 + X18 = 0.8 A
2.4.3 Connections
Connections to the Millmate Controller 400 control unit with the
Millmate Excitation Unit PFVI 401 are shown in Figure 2-5 and table 2-2.
X31 X23 X27 X26
X29
X22
Run Fault
Syserr Profibus
LAN ControlNet
10Base-T
RS-485 RS-232 RS-232:2 RS-232:1
X29
X27 X26
DO1 DO5
DO2 DO6
DO3 DO7
DO4 DO8
X34
X24
X30
AUI Profibus
X34 X35
X22 X31 X25
X24
T2A T2A Digital in Digital out
F1 F2 X35
85-264V~ X21 X30 X23
47-63Hz 140W 10Base2 Profibus RS-485 X25
X21 12 3 4 5 1 2 3 4 5
PFVI 401
X11 X4
Figure 2-5. Millmate Controller 400 - Connections
MC 400
X18
1 +24 V (internal supply)
X34
1
DI1
2
DI2
24 V
external 3
supply DI3
4
DI4
5
X18
2 0V
X18
1 +24 V (internal supply)
X24
1
DI5
2
DI6
24 V
external 3
supply DI7
4
DI8
5
X18
2 0V
MC 400
X18
+24 V (internal supply) 1
X35
5
Output 24 V
DO1 load external
1 supply
DO2
2
DO3
3
DO4
4
X18
0 V (internal supply) 2
X18
+24 V (internal supply) 1
X25
5
Output 24 V
DO5 load external
1 supply
DO6
2
DO7
3
DO8
4
X18
0 V (internal supply) 2
MC 400
X6
1 +
± 15 V RL
2
Voltage
U –
I 3
AO1 5
AO2 U RL
I 6
D/A- Current
converter
X16
AO3 1
14
bits
AO4 2
0VAO U
I 3
U
I 6
2.4.7 LAN-connections
MC400 uses TCP/IP protocol on Ethernet for communication between control units, operator
units and other systems.
MC400 control and operator units use fixed IP-addresses. How to adjust IP-addresses is
described in Section .
MC400 uses twisted pairs cables from control unit to operator unit or ethernet switch.
External network connection is as an option possible with an opto switch.
External network
Opto fiber
Ethernet switch
Opto switch (Optional)
Figure 2-10. Connection to local and external Network with Ethernet switch
X1 PFVK 128 X1
13 2
14
3
15 5
16
6
17 8
18
9
19 11
10
20
12
Type Data
Dimensions (l × w) 80 × 120 mm
Cable dimensions:
– control signals max 2.5 mm2
– relay outputs max 4 mm2
Weight 200 g
No. of channels 4
Operating voltage, coil 24 V AC or DC
Current consumption, coil 20 mA / relay
Contact function Changeover
Rated voltage, contacts 250 V AC
Breaking current
at 250 V AC max. 8 A
at 48 V DC max. 1.2 A
at 220 V DC max. 0.2 A
Rated insulation voltage 250 V AC
Switch time max. 8.5 ms
Temperature range 0 to +70°C operation
-40 to +70°C storage
Mounting ABB mounting rail
+
+
Input Output
–
–
+24VV
+24
Type Data
Power supply +24 V (20 - 253 V AC/DC)
Current consumption 10 mA + external load, at 24 V
Signal range Input Output
0 ± 10 V 0 ± 10 V
0-5V 4 - 20 mA
0 - 10 V 4 - 20 mA
0 - 5V 0 - 20 mA
0 ± 10 V 0 ± 20 mA
Input resistance 1 M at 10 V input
500 k at 5 V input
Max. load 10 mA for voltage output
500 for current output
Rise time 50 s or 50 ms, selectable
Ripple 10 mVp-p
Bandwidth (-3 dB) 10 kHz or 10 Hz
Rated insulation voltage 600 V, basic insulation
Insulation test voltage 4 kV
Temperature range -10 to +70°C operation
-40 to +85°C storage
Dimensions (l × w × d) 99 × 12.5 × 111 mm
Type Data
Weight 150 g
Type Data
10Base2 10Base-T
Coaxial cable Twisted Pair
PXUB 231
+24 V
Type Data
Cable dimension max 2.5 mm2
Power supply +24 V (18-36 V DC)
Current consumption Typical 160 mA at 24 V
Network standards IEEE 802.3, 10Base-T, 10base2
Data rate 10 Mbits/s, half duplex mode
Connectors
Supply Screw terminals
10Base2 BNC
10Base-T RJ-45
Dimensions 10 x 8 x 3 cm
Temperature range -40 to +75°C operation
-40 to +85°C storage
Weight 150 g
Mounting DIN-rail 35 mm
Note
This system has been updated with a new Touch screen Operator Unit.
This manual has not yet been updated with the new HMI layout on all descriptive
figures. The functions on the system is basically the same, and can be followed as
described.
Type Data
Power supply voltage +24 V DC (18 - 32 V DC)
Power consumption Max 14 W
Degree of protection Sealing front: IP65, NEMA 4X/ 12 and UL Type
4X/ 12
Sealing back: IP20
Dimensions (l × w × d) 204x143x50 mm
Weight 0.8 kg
Temperature range -10 to +60°C (operation)
-20 to +70°C (storage)
2.5.2 Connections
Table 2-7. Connections for Millmate Operator Unit 410
1.95 A 5 A / 25 A
Figure 2-15. Block Diagram of Matching Units PFVO 142 and PFVO 143
Type Data
Dimension (h × l × w) 300 × 250 × 150 mm
Weight 8 kg
Temperature range 0 to +55°C operation
-40 to +70°C storage
Degree of protection IP 65 IEC 529, EN 60-529
Type Data
Dimensions (l × w × d) 220 × 120 × 80 mm
Weight 2.0 kg
Degree of protection IP 65 IEC 529, EN 60-529
[mm]
80
16 37
30 60 90 120
150
110
110
(4 x) D = 10.5 - 13.5
Cable gland PR22.5
Type Data
Dimensions (l × w × d) 150 × 150 × 80 mm
Weight 1.7 kg
Temperature range 0 to +70°C operation
-40 to +70°C storage
Degree of protection IP 65 IEC 529, EN 60-529
Type Data
Supply voltage 24 V DC (18 - 30 V)
Power consumption Max 4 VA
Operation temperature 0 to 50 °C
Degree of protection IP 40 by front
Input interface Serial RS-232 or RS-485
selected from menu
2.9.2 Dimensions
Table 2-13. Dimensions for External Display QDIL 451
Digits Dimensions
Type
No. of height width height depth
4 72 48 68
QDIL 451 14 mm
6 96 48 68
Chapter 3 Installation
3.4 Storage
Limits for various combinations of temperature and humidity when storing electronic
equipment during prolonged periods are shown in Figure 3-1.
If, for any reason, the control unit must be stored prior to the installation, the relative humidity
in the storage area must not exceed the values indicated in Figure 3-1. If the humidity is higher
the units must be stored in air-tight packaging, or in shielded and air conditioned rooms with
filtered air.
Relative
Relativ
humidity (%) (%)
luftfuktighet
100
100
90
90
80
80
70
70
66 months
månader ell
60
60 or longer
längre
50
50 1-2
1 -2 månader
months
40
40
30
30
Best
Bästastorage
20 environment
lagringsmiljö
20
10
10 Unsuitable
Olämplig
storage
lagringsmiljö
environment
-60
-60 -50
-50 -40
-40 -30
-30 -20
-20 -10
-10 00 +10
+10 +20
+20 +30
+30 +40
+40 +50
+50
Temperature (°C)
Temperatur (oC)
Figure 3-1. Permissible Values Regarding Temperature/Humidity at
Prolonged Storage of Electronic Equipment
Modem
10Base-T
X29
DI DO PFVL 141
RS-485
Mains load cell
Mains X23 X24/X34 X25/X35
voltage excitation
voltage
LC exc. LC signals AO
X3/X13 X5/X15 X6/X16 X11 X4
X1
> 50 mm
Power supply cables >250 V and inductive non suppressed loads
< 50 mm
> 0.3 m
Note:
The 10Base-T cable
is only approved for
Mains
use inside the cabinet
filter
10Base-T
RS-485
AO
DO
AI
DI
Cables to be connected to control units mounted on rubber dampers must be run to allow for a
degree of movement, e.g. in a loop or a curve, see Figure 3-3.
Figure 3-3. Cable run for Control Unit Mounted on Rubber Dampers
NOTE
If the matching unit is earthed at the place of installation, the earth cable must not
be connected between terminal 4 in the matching unit and the earth terminal in the
control unit.
All components in the matching unit are mounted on one plate. This plate is easy to remove and
can be mounted in a locally supplied box, if required
Holes not used must be plugged.
(6 x)
D = 6–12 mm (Cable gland Pg16)
[mm]
80
16 37
30 60 90 120
150
110
110
PFVI 401 X4
1 2 3 4
1
Not connected if the matching units are
properly earthed at the installation site.
1
Matching unit A
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell A Black
D 11
B Blue
12
A 1
13
C 2
14
15
16 17 18 19 20 21
1
Matching unit B
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell B Black
D 11
B Blue
12
A 1
13
C 2
14
15
Figure 3-8. Connecting Two PFVL 141V/C Load Cells or Two PFVL 141R 25 A Load Cells
PFVI 401 X4
1 2 3 4
1
Not connected if the matching units are
properly earthed at the installation site. 1
Matching unit A
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell A
D Red 11
B Blue 12
A Black 13
C White 14
15
16 17 18 19 20 21
Matching unit B 1
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell B Red
D 11
B Blue
12
A Black
13
C White
14
15
PFVI 401 X4
1 2 3 4
1
Not connected if the matching units are
properly earthed at the installation site. 1
Matching unit A1
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell A1 Black
D 11
B Blue
12
A 1
13
C 2
14
15
16 17 18 19 20 21
1
Matching unit B1
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell B1 Black
D 11
B Blue
12
A 1
13
C 2
14
15
1
Matching unit A2
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell A2 Black
D 11
B Blue
12
A 1
13
C 2
14
15
16 17 18 19 20 21
1
Matching unit B2
1 2 3 4 5 6 7 8 9
PFVO 142
25 A 1.95 A
Load cell B2 Black
D 11
B Blue
12
A 1
13
C 2
14
15
Figure 3-10. Connecting Four PFVL 141V/C Load Cells or Four PFVL 141R 25 A Load Cells
PFVI 401 X4
1 2 3 4
1
Not connected if the matching units are
properly earthed at the installation site. 1
Matching unit A1
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell A1
D Red 11
B Blue 12
A Black 13
C White 14
15
16 17 18 19 20 21
Matching unit B1 1
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell B1
D Red 11
B Blue 12
A Black 13
C White 14
15
1
Matching unit A2
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell A2
D Red 11
B Blue 12
A Black 13
C White 14
15
16 17 18 19 20 21
1
Matching unit B2
1 2 3 4 5 6 7 8 9
PFVO 143
5A 1.95 A
Load cell B2
D Red 11
B Blue 12
A Black 13
C White 14
15
Control unit
Load cell A Cable Junction box MC 400 (PFXA 401)
with matching unit No. PFXC 141 X3
1
1 17 1 1 LC EXC
3
2 18 2 2
2 1)
3 19 3
4
4 20 4 LC EXC
Load cell B 6
with matching unit X5
1 21 3 1
LC Signal 1, A
2 22 4 2
3 23 7 3
LC Signal 2, B
4 24 8 4
2)
1) Built-in relays used to disconnect either load cell A or load cell B in Single Cell Operation Mode
2) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-12. Connecting Two QGPR 102/104 Load Cells with PFXC 141
Control unit
Load cell A Cable Junction box MC 400 (PFXA 401)
with matching unit No PFBC 161 X3
1
1 9 1 1 LC EXC
3
2 10 2 2
2 1)
3 11 3
4
4 12 4 LC EXC
Load cell B 13 3
with matching unit X5
1 14 4 1
LC Signal 1, A
2 15 5 2
3 16 6 3
LC Signal 2, B
4 17 7 4
18 8
1) Built-in relays used to disconnect either load cell A or load cell B in Single Cell Operation Mode
Figure 3-13. Connecting Two QGPR 102/104 Load Cells with PFBC 161
Control unit
Load cell A Cable Junction box MC 400
with matching unit No. PFXC 141 X3
1
1 17 1 1 LC EXC
3
2 18 6 2
2
3 19 3
4
4 20 4 LC EXC
Load cell B
with matching unit X5
1 21 1
1 3 LC Signal 1, A
3
2 22 4 2
2 23 3
3 7 LC Signal 2, B
4 4 24 8 4
1)
1)
1) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-14. Connecting four QGPR 102/104 Load Cells with Two PFXC 141
Control unit
Load cell A Cable Junction box MC 400
with matching unit No. PFXC 141 X3
1
1 17 1 1 LC EXC
3
2 18 6 2
2
3 19 3
4
4 20 10 4 LC EXC
Load cell B
with matching unit X5
1 1
1 21 3
3 LC Signal 1, A
2 22 4 2
2 3
3 23 7 LC Signal 2, B
4 4 24 4
8
25
26
X15
27 11 1
LC Signal 3, A
28 12 2
31 15 3
LC Signal 4, B
32 16 4
1)
1)
1) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-15. Connecting four QGPR 102/104 Load Cells with Two PFXC 141 Connected in Series
Control unit
Load cell A Cable Junction box MC 400
with matching unit No. PFXC 141 X3
1 17 1 1 LC EXC
1
3 6
2 18 2
2 3
3 19
4 20 14 4 LC EXC
4
Load cell B
with matching unit X5
1 1 21 3 1
LC Signal 1, A
3 22 4 2
2
2 23 7 3
3 LC Signal 2, B
4 4 24 8 4
1)
1) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-16. Connecting four QGPR 102/104 Load Cells with One PFXC 141
Figure 3-17. Connecting Four QGPR 102/104 Load Cells with Two PFBC 161
1) Built-in relays used to disconnect either load cell A or load cell B in Single Cell Operation Mode
2) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-18. Connecting Two Large QGPR 102/104 Load Cells with Matching Board PFBK 401 and One PFXC 141
1) Built-in relays used to disconnect either load cell A or load cell B in Single Cell Operation Mode
Figure 3-19. Connecting Two Large QGPR 102/104 Load Cells with Matching Board PFBK 401 and One PFBC 161
1)
Junction box
STAND 2 Load cell A Cable PFXC 141
with matching unit No.
1
1 17 1
3 6
2 18
2
3 19
4 4
20
STAND 2 Load cell B
with matching unit
1 X15
1 21 3 1
3 LC Signal 3, A
2 22 4 2
2
3 23 7 3
4 LC Signal 4, B
4 24 8 4
1)
1) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-20. Connecting Four Large QGPR 102/104 Load Cells and Matching Board PFBK 401 with Two PFXC 141
1)
1) Copper bar for connecting cable shields (insulated from metal case of junction box)
Figure 3-21. Connecting Four Large QGPR 102/104 Load Cells and Matching Board PFBK 401 with One PFXC 141
Junction box
STAND 2 Load cell A Cable PFBC 161
with matching unit No.
1 9 1
1
3 10 3
2
2 11
3
4 4 12
13
STAND 2 Load cell B
with matching unit X15
1 14 4 1
1 LC Signal 3, A
3 15 5
2 2
2 16 6 3
3 LC Signal 4, B
4 17 7 4
4
18 8
Figure 3-22. Connecting Four Large QGPR 102/104 Load Cells and Matching Board PFBK 401 with Two PFBC 161
1
2
3
4
Load cell
QGPR 102/104 Matching unit QIPZ 127
A Red X1:1 X2:1
B Blue X1:2 X2:2
C Black X1:3 X2:3
To control unit
D White X1:4 X2:4
Figure 3-23. Connection between Load Cell QGPR 102/104 and Matching Unit QIPZ 127
NOTE
The incoming mains voltage must be provided with fuses and a means outside the
control unit for disconnection.
NOTE
Vibration isolators shall be used when mounting the control unit
in a harsh environment.
Figure 3-25. Position of the Holes for fixing the Cabinet(s) to the Floor
Symbol Distance
X 69 mm (2.7”)
W3 602 mm (23.7)
W 700 mm (27.6”)
Y 56 mm (2.2”)
D3 544 mm (21.4”)
Dtot 655 mm (25.8”)
X34 X35
X24 X25
T2A T2A MC 400 (PFXA 401) Digital in Digital out
F1 F2
85-264V~ X21 X30 X23
47-63Hz 140W 10Base2 Profibus RS-485
1 2 3 4 5 1 2 3 4 5
S1 X2 X3 X5 X6 X8
X1
1) 12) 3) 11)
Mains SYNC Load cell excitation External supply
(X1) (X2) to junction box +24 V DC
(X13, X3) (X18, X8)
PFVI 401
X11 X4
1) 3)
Mains Load cell excitation
(X11) to matching units
(X4)
3) 4)
3) 4)
Matching units
Junction
box
RS-232
Ethernet to (X27, X26)
9)
Operator unit
(X29) 5)
Run Fault
10Base-T Syserr Profibus
LAN C
X29 RS-485 RS-232 RS-232:2 RS-232:1
X27 X26
DO1 DO5
DO2 DO6
DO3 DO7
DO4 DO8
AUI
X22
Profibus
X31
X34 X35 6) Digital in
X24 X25
T2A T2A Digital in Digital out (X34, X24)
F1 F2
85-264V~ X21 X30 X23
47-63Hz 140W 10Base2 Profibus RS-485
Digital out
1 2 3 4 5 1 2 3 4 5 7)
(X35, X25)
X13 X15 X16 X18
S1 X2 X3 X5 X6 X8
X1
10) 4) 8)
For
PFVL 141:
Load cell excitation circuit (in 1.95 A loop) - max. 5 ohm cable
resistance. 5 ohm corresponds to approx. 350 m of 2.5 mm2 cable.
For
QGPR 102/104:
Excitation unit PFVI 401 is controlled by control unit PFXA 401 via a ribbon cable.
Ribbon cable
X39 X49
PFXA 401 PFVI 401
control unit excitation unit
X2
1 2 3
From To
previous next
unit unit
3.9.4.8 Connecting Redundant +24 V Supply to Millmate Operator Unit 410 and Network
switch
One Millmate Operator Unit can be redundantly supplied with +24 V DC from several Millmate
Controller 400 control units, see Figure 3-26.
+24 V + -
X8 1 2
MC 400 (2)
0V
The Operator Unit and the Network switch
+24 V will be supplied if at least one of the control
units is switched on.
X8 1 2
+ –
MC 400 (n)
Network
Switch
0V
+24 V
X8 1 2
Figure 3-30. Connection of Redundant +24 V Supply to Millmate Operator Unit 410
and Network switch
+24 V X18:1 7
+
X18:2 8 –
0V
PFVK 128
MC 400
X18
+24 V (internal supply) 1
X25
5
PFVK 128
DO5
X1 X1
1 13 2
1
14
DO6 3
2 15 5
4
16
DO7 6
3 17 8
7
18
DO8 9
4 19 11
X18 10
0 V (internal supply) 2 20
12
3.10.3.1 Dimensions
Table 3-4. Dimensions for External Display QDIL 451
Digits Dimensions
Type
No. of height width height depth
4 72 48 68
QDIL 451 14 mm
6 96 48 68
3.10.4.1 General
External display QDIL 451, mounted in cabinet doors or panels, can be connected either to the
RS-232 or RS-485 outputs.
RS-485 is normally recommended since longer communication cables can be used.
• RS-485, max 500 m
• RS-232, max 15 m
Another advantage with RS-485 is that several external displays indicating different measured
signals simultaneously can be connected to the same RS-485 cable (max cable area 0.75mm2).
DB 9
Male
Chapter 4 Commissioning
NOTE
Check that the load cells are connected to give a positive output signal change for
increased roll force. See cable diagram for actual type of load cell in Appendix C
Drawings.
Home menu
System Error Lc exc Next Settings Check Next Define Comm. MC 400 Next
test inspect ON/OFF I/O system setup data
Modify or Modify or set up Adjust measuring Settings Settings for Settings for
add new analog and digital sensitivity for LAN RS-232, and VIP and Profibus
measuring inputs/outputs See 4.5.24 See 4.5.16 RS-485 comm. See 4.5.17 and 4.5.18
objects See 4.5.14 Zero adjustment See 4.5.19
See 4.5.8 or See 4.5.25
4.5.13
After selecting screen saver, it will automatically start when your computer is idle for the time
interval specified in Wait. Select one of the specified wait intervals and press Save. The
available wait intervals are 5 seconds up to 10 hours. It is also possible to set the screen saver to
OFF, this disables the screen saver.
To clear the screen saver after it has started, touch the screen.
A screen that is continuously updated will redirect to Startup Object on Home menu when
screen saver has been activated to avoid data traffic during time out. If Startup Object has not
been activated, the Home menu is shown.
Set Backlight brightness level. Intensity is set in levels 10 (brightest) to 1 (dullest). When
approaching level 1 backlight, changes in brightness level may no longer be noticeable in the
panel.
Complete dimming (to level 0) is not possible. Backlight brightness level is maintained after
reboot of panel.
NOTE
If the units are to be used in a wide area network where other equipment is
present, the IP addresses in the operator unit and the control unit must be adapted
to the network address range. To accomplish this, the IP address in the control
unit must be altered first. This is best done using an operator unit in a temporary
local area network where no other equipment is present. When the IP address in
the control unit is altered, the IP address in the operator unit can be changed.
After that, the units can be connected in the wide area network.
Listing of control units, adds the designated controller device (Millmate controller or other) for
this particular operator unit. It is also a way to see if a particular controller is off line.
To save a control unit to the list:
• Slide the toggle switch “In List” to the right and press “Apply”
To set an object as Startup menu see Section 4.5.26.
“
Subnet Mask” is used to decide if the connection
should be done within the local network or through
a router. Default is ffff0000.
See 4.5.10
Service Object parameters 320
Name Std1@ABB225
Options -
LC type PFVL 141
LC size 20.00 MN
Service Port No of LC/port Select load cell type 324
Load cell A 1 1 PFVL 141
Load cell B 2 1 PFVL 101
QGPR 102 (d)
QGPR 102 (c)
QGPR 102 (b)
Change Change Next QGPR 102 (a)
Next lc name lc type QGPR 104 (d)
QGPR 104 (c)
QGPR 104 (b)
QGPR 104 (a)
Next
See 4.5.11
Next Measurement parameters 330
Name Std1@ABB225
See 4.5.11.2
Filter response time 1 ms
20.00 MN
Define Measuring range
Load unit MegaNewton Newton
Select unit
(N)
338
(kN)
system kiloNewton
MegaNewton (MN)
kiloPond (kp)
tons (t)
Setup US pound (lb)
(T)
object Change Change
filter unit
Next US Tons
Next
Select object
See 4.5.11.1
Setup See 4.5.12 Set filter response time 336
0 - 90%
Indication parameters 351 1 ms
2 ms
Unfiltered
Level detectors 5 ms
1 Not defined 12 ms
24 ms
Object information 305 2 Not defined
3 Not defined 50 ms
100 ms
4 Not defined 200 ms
Name Std1@ABB225 Analog OUT 400 ms
Application Standard measurement 1 Fixed value 0V Next
Lc type PFVL 141 2 Fixed value 0V
Lc size 20.00 MN 3 Fixed value 0V
Lc at port 1, 2 4 Fixed value 0V
Load division 0.005 MN Level Analog Step Next
detect. OUT detect. See 4.5.12.3
Setup step detector 353
Modify End Active
Label SD
H1 Step up height 1.0000 MN
D1 Step up time 0.10 s
D2 Step up hold time 0.10 s
Pending object setup 306 D3 Step up lock time 0.10 s
H2 Cut-off offset -0.1000 MN
Name Std1@ABB225 D4 Step down hold time 0.10 s
D5 Step down lock time 0.10 s
Application Standard measurement Step counter 0 times
Lc type PFVL 141 Next
See 4.5.12.2
Lc size 20.000 MN Analog output 355
Lc at port 1, 2 Port 1 Tot Diff A B
Load division 0.005 MN Measurement value
Fixed value
800 ms Filter
Modify Discard Check Low High
changes object Measurement 0.00 10.00 MN
Output 0.000 10.000 V
Setup object 301 Limit -11.000 11.000 V
See 4.5.12.1 Volt or Default Default Next
1 Std1@ABB225 Object checked 307 Ampere All AO
2 Not defined
Setup level detector 352
Active
3 Not defined Std1@ABB225 Label
4 Not defined Result SUCCESSFUL
Level 0.00 MN
Hysteresis 0.00 MN
Multi view Counter 0 times
Not defined Digital out port 0 Invert
High Low
Tot Diff A B
Setup Remove End Measurement value
Next
Modify Discard Store
changes
+
MC 400 MC 400 MC 400
Define
system
Next
Parameter Description
Name Enter an object name. This object name will be shown in the
headline of the operation menus.
Lc name Select sub menu “Change lc name” to change the load cell
names.
Enter a load cell name for each load cell. The names will be
shown in operation menus.
For the load cell names to be displayed, this function must be
activated.
Lc type Select sub menu “Change lc type” to alter the load cell type. A
list of load cells which can be selected is shown.
Load cells QGPR 102/104 exist in four types, depending on
size; a, b, c and d. Check the calibration certificate for the load
cells for correct gain setting.
Lc size The nominal load of the load cell in MegaNewton. If more than
one load cell is connected, enter the measuring range for the
individual load cell, not the total.
Lc at port Load cell inputs (port numbers) connected to the object.
No of Lc / port The number of load cells connected to the same input port is
stated here.
Service
Next
Select unit 338
Newton (N)
kiloNewton (kN)
MegaNewton (MN)
Define See Table 4-2 and 4.5.11.2 kiloPond (kp)
(t)
system tons
(lb)
US pound
US Tons (T)
Setup
object Next
Setup
Menu 351
Parameter Description
Filter response time The filter response time is set in sub menu 336 “Set filter
response time”. All presentation and indication will be filtered
with the selected filter. The time corresponds to 0-90% step
response.
Load unit The load unit is selected in sub menu “Select unit”.
Note.
1 US ton = 2000 US pound
1 ton (metric) = 2205 US pound
Measuring range The nominal measuring range for the object is stated here.
Modify
Next
Change
filter
Select unit 338 Use “Select” to mark the desired unit, and exit
Service Newton (N) with “Next”.
kiloNewton (kN)
MegaNewton (MN) Note.
kiloPond (kp)
tons (t) 1 US ton = 2000 US pounds
Service
US pound (lb) 1 ton (metric) = 2205 US pounds
US Tons (T)
Next Next
Next
Define
system
Setup
object
Setup
Modify
Next
Change
unit
Next
Next
Setup level detector 352
Active
Label
Define Level 0.00 MN See Table 4-3.
Hysteresis 0.00 MN
system Counter 0 times
Digital out port 0 Invert
Setup High Low
object Tot Diff A B
Measurement value
Setup Next
Modify
Indication parameters 351
Level detectors
1 LABEL VALUE
Next 2 Not defined
Activated level detectors for the current object
3 Not defined are shown with set level and label.
4 Not defined
Analog OUT
Next 1 Fixed value 0V
2 Fixed value 0V
3 Fixed value 0V
4 Fixed value 0V
Level Analog Step Next
detect. OUT detect.
To menu 306
Total 50.0 MN
Side A 26.0 MN Run Fault
Syserr Profibus
Side B 24.0 LAN C
Difference 2.0 MN RS-485 RS-232
The level detector Digital OUT
indicates on the set to 1.
DO1 DO5
OVERLOAD DO2 DO6
display when the DO3 DO7
set level is reached. Zero System LC-exc Settings DO4 DO8
set test ON/OFF
Parameter Description
Label The label is shown on the object operation menu when the set
level for the level detector is reached.
Level Trigger level for the level detector.
Hysteresis Hysteresis for the trigger level.
Digital OUT Enter the desired digital output number (1 - 8), or 0 if no digital
out is used.
Counter Counts the number of times the level detector has been active.
To zero set the counters (max. 4) for one object:
Press “Service”, “Service”, “Next” and “Settings”.
Select object and press “Level detect.”
Press “Zero set” in menu 172 “Level detector counter”.
This command zero sets all displayed level detector counters
for the selected object.
Active / Not active Use “Select” to state if the level detector should be activated or
not. An activated level detector is shown with its label on higher
menu levels, where a not activated level detector is shown as
“Not defined”.
High / Low Use “Select” to state whether the level detector should respond
to high or low level. This affects the hysteresis function.
Load
High
Hysteresis
Time
LD ON LD OFF
Load
LD = Level detector
Hysteresis
Low
Time
LD ON LD OFF
Tot, Diff, A or B Use “Select” to state if the level detector should be connected to
Total (Tot), Difference (Diff), A or B signals. The level detector
for “Diff “ works on the absolute value A – B .
Next
Next
MR is the Measuring Range choosen on Ten-
sion Parameter menu 330.
The key “Default All AO” will set up all four ana-
Output log outputs according to the table above. This
V/A
only works for a standard object.
High limit
High
Low
Low limit
Low High Measurement value
MN (t, T, lb., kp)
Next
Setup step detector 353
Active See Table 4-4.
Label SD
Define H1 Step up height 1.0000 MN
system D1 Step up time 0.10 s
D2 Step up hold time 0.10 s
D3 Step up lock time 0.10 s
Setup H2 Cut-off offset -0.1000 MN
D4 Step down hold time 0.10 s
object D5 Step down lock time 0.10 s
Step counter 0 times
Setup Next
Modify
Indication parameters 351
Level detectors Activated level detectors for the current object
1 Not defined
Next 2 Not defined
are shown with set level and label.
3 Not defined
4 Not defined
Analog OUT
Next 1 Fixed value 0V
2 Fixed value 0V
3 Fixed value 0V
4 Fixed value 0V
Level Analog Step Next
detect. OUT detect.
To menu 306
Parameter Description
Label The label is shown on the object operation menu when the set
level for the step detector is reached.
H1 Step up height Trigger level for activating step detector output.
.
Signal level
L1 L1 L1
L2 H2 L2
H1
H2
Time Time
D1 D2 D3 D4 D5 D4 D5
SD=ON
SD=OFF SD=OFF
Figure 4-2. Time intervals and levels for adjusting the step detector
An alternative type of step down function of the step detector was introduced in release 3.3-2. It
works as the step detector in the 1986-1988 version of PFVA101 using processor board
PFVK105.
It reacts on fast step down only.
To switch between the standard step detector of PFVA401 and this additional type a negative
sign of D4 is used.
Signal
U1 } h2
Time
}
}
D4 D5 (S)
A step down is detected when the signal has decreased the force H2 in a time less than D4 and
stayed below the value U1 the time D5.
The input parameters at the Step detector meny 351 will have different meaning depending on
the sign in front of D4. Note that the menu will always show the text for the standard step
detector function.
Parameter 3.3-0 logic PFVK105 logic (minus sign on D4)
H2 Cut-off offset/Level Step down height (=h2 in PFVK105)
D4 Step down hold time Step down time (=t3 in PFVK105)
D5 Step down lock time Step down hold time (=t4 in PFVK105)
E.g:
D4= 0.1s ->standard logic with step down hold time of 0.1s
D4= -0.1s -> logic from PFVK105 with a step down time of 0.1s
Object information 305 The settings shown in this menu can be altered
Service or accepted.
Name Std1@ABB225
Application Standard measurement
Lc type PFVL 141 “Modify” changes to the first setup menu for al-
Service Lc size 20.00 MN
Lc at port 1, 2 tering the settings, see Section 4.5.8.1.
Load division 0.05 MN
Next
Detailed settings about inputs, outputs and level
Modify End
detectors will still remain.
Setup
Next
Define
system
Select Order in Next
Setup MC 400 menu
object
Select MC 400 314 View order in menu 315 Mark the desired
Mark MC 400 that has presentation order
Name: MultiView5@ABB203 Active 1 2 Combined objects
the desired objects. ABB226 Entry x Std1@ABB203
for the multi view
Std2@ABB203
objects in the op-
eration menu.
Search for
Search Next Next
more MC 400. MC 400
Rougher
Rougher 720
Total 38 MN
Side A 20 MN
Side B 18 MN
Difference 2 MN
MC 400 MC 400
A
B
Stand F2
F2 720
Total 6.0 MN
Side A 3.5 MN
Side B 2.5 MN
Difference 1.0 MN
Operation menu for
multi view object
MC 400
A
B
system End
End
4 Fixed value 0V
End
The eight digital inputs can be configured for a number of signals in the control unit.
See Table 4-5.
Service
Digital Digital End
IN OUT
Digital
I/O
Next
End
Service
Analog Analog End
IN OUT
Next
Service
Analog Analog End
IN OUT
Next
Next
Note
Next Double-check that the correct IP address has
been entered before pressing “End”. It will be
impossible to get contact with the control unit if
Comm.
the two first parts of the address are incorrect.
setup
LAN
Default values are:
IP address: 172.16.x.y (x and y are between 1
and 255 and y is decimal value from the two last
digits from the hexadecimal value of the Ether-
net address).
NOTE
The IP-address is included in the startup message Subnet mask:ffff0000
from port RS232:1. But only If this port is
set up as “Printer”, the default setting. It is sent Gateway address: 172.16.1.1
with 9600 Baus, 8 databits, No parity, 1 stop bit.
Communication 120
Service Setup
Local area network,
Serial port or
FieldBus
Service
Next
Fieldbuses 121
Comm. Profibus Active - 123
Address
Profibus 270
None Profibus Address 123 Enter unit Address.
Output Object Signal
1 Entry Load cell A
2 Entry Load cell B
3 Not defined -
4 Not defined -
Input
1 Not defined -
2 Not defined -
Select value
End
Valid GSD-file can be dumped from MC 400 directly. See Section 4.5.29.2.
For more information about Profibus, see Appendix B Profibus-DP Fieldbus Communication.
Communication 120
Service Setup
Local area network (LAN),
Serial port or
Fieldbus
Service
Next
IP address is the IP address of
Fieldbuses 121 the PLC.
Comm. Profibus Not active - -
Next
Change device 281
RS232:1
Comm. None
Printer
setup
External display
Console
Serial Serial comm.
ports
Setup End
device
Note.
Setup device 282
“Setup device”
Display type QDIL 410/430/450 5d
is valid only for Addressing mode
“External display” Leading zeroes
Object / Signal Tot Diff A B C D
Object name 1
Object name 2
Object name 3
Object name 4
Protocols for External Displays Setup End
(QDIL 410/420/430/440/450) display
NOTE: Select QDIL 450 for QDIL 451
Protocol in: Setup display 284
- Unaddressed mode: <STX>VALUE<ETX> Digits
4 5 6
- Addressed mode: <STX> ADDRESS VALUE<ETX> QDIL 410/430/450
QDIL 420/440
Service
Lc exc YES NO
ON/OFF
Number of load cells Load cell size, Fnom Cable length Power range
1 x x 1
2 35 MN 2x10 m 2
2 > 35 MN x 3*
2 x > 2x10 m 3*
3 or 4 x x 3*
* For operation in Power range 3, additional phase compensation should be
performed, see Section 4.5.21.2.
Check load cell exc. 164 – If “Excitation level” with both load cell sections
Service Excitation level 138 V selected is between 80 and 140 V, no further
Power range 2 adjustment is necessary.
Load cell excitation on – Changing of Power range is done by entering
Service
a new range (1, 2 or 3) and pressing “Apply”.
Excitation, 1st Lc sect On
Excitation, 2nd Lc sect On
The excitation level corresponds to the internal
Next Apply Change Lc exc End
section ON/OFF voltage “UR”, see Section 3.8.1.
Check
Excitation of lc sect 166
I/O
Excitation, 1st Lc sect On
First load cell section (1st Lc sect): Excitation
Check Excitation, 2nd Lc sect On circuit connected to X4, terminals 1-2.
lc-exc
Second load cell section (2nd Lc sect): Excitation
circuit connected to X4, terminals 3-4.
End
As low power range as possible is preferred as it gives lower power losses in the excitation unit.
The excitation level should not exceed 150 V.
Additional phase compensation is introduced in the load cell excitation circuit by connecting the
additional capacitor C2 of 3 F in series with the capacitor C1 of 1 F in the PFVO 142
matching unit.
In the PFVO 143 matching unit the capacitor C3 of 3 F is connected in series with the
capacitors C1 and C2.
Phase compensation should be adjusted for minimum excitation level.
Over voltage No
Alarm?
Yes
Disconnect
2nd Lc sect.
Yes Yes
Add phase compensation Add phase compensation
in 2nd matching unit in 2nd matching unit
Disconnect latest
in 1st Lc sect. in 2nd Lc sect.
added phase
compensation.
Is new Is new
No No
excitation level excitation level
lower? lower? Is
No
Yes Disconnect latest Yes Disconnect latest excitation level
added phase added phase <80 V?
compensation. compensation.
Yes
Change to
Connect 2nd Lc sect and Connect both Lc-sections.
Power range 2
disconnect 1st Lc sect.
End
S1
Capacitor value 1-2 3-4 5-6 7-8
16 F - - X X
24 F X - - X
32 F X X - -
Adjust the capacitor value based on the excitation level presented in menu 164, “Check load cell
excitation”. Use the following procedure:
Note.
The selection “Reference” is available, when the
reference test has been saved the first time.
All data are sent as plain ASCII-text and can be handled in a terminal program as a text file for
later processing.
Serial port RS-232:1 (X26) is set up as default printer port, with 9600 Baud, 8 data bits, no
parity and 1 stop bit. No handshake is used.
For connection to a PC a standard crossed RS-232 cable (“Null modem cable”) should be used.
NOTE
Line ends are sent as <CR> (ASCII 0D16) only and some terminal programs work
better if they are set up to add <LF> (ASCII 0A16) to incoming <CR>.
201
ABB201
Language
201
ABB201
Language
• Select object and click “Show” to display the complete object setup.
• Store a backup copy of the complete object setup (for example, use the Internet Explorer
command “Save as”).
• Click “End”.
ABB201
Language
• Select type of application (Roll Force Meter) and object and click “Store”.
Setup object 301 1. Use “Select” and then “Setup” to select the
Service object to remove.
1 Rougher
2 Not defined
3 Not defined
4 Not defined
Service Multi view
Not defined
Next
Object remove 302 2. Verify the removal of the object.
Define Rougher
NOTE
system Verify Detailed settings about inputs and outputs
Setup will still remain.
object To remove all settings, see Section 4.5.32.
Remove NO
Verify
The unit will clear the memory and restart the program.
It will take several seconds and communication with the
operator unit will be lost.
YES NO Check indications on control unit MC 400:
When the clearing function is going on, indication “Run”
is switched OFF and indications “Fault”, “Syserr”, “LAN”
Wait for.... 139
and “Profibus are switched ON.
Clearing the memory
When clearing is finished, “Run” is switched ON and
and
the restart “Fault”, “Syserr”, “LAN” and “Profibus” are switched
OFF.
Check that “Run” is ON (lit).
MC 400
service Press “MC 400 service” to continue.
S2
ON
1 2 3
Snap-lock Snap-lock
S1
ON
1 2 3
PXUB 201
3 Output: 0 to ± 10 V
Signal +
0V 4 - Input: 0 to ± 10 V
5
7 +
+ S1 S2
+24 V
0V 8 - – 6
ON ON
1 2 3 1 2 3
Earth
+24 V + 1 2 3 1 2 3
0V 8 -
Earth
Range S1 S2
Default
Input Output 1 2 3 1 2 3
× 0 to ±10 V 0 to ±10 V × ×
0 to 5 V 4 to 20 mA ×
0 to 10 V 4 to 20 mA ×
0 to 5 V 0 to 20 mA × ×
0 to 10 V 0 to 20 mA ×
0 to ±10 V 0 to ±20 mA x
S2, position 3
Default Bandwidth
(× = ON)
× 10 kHz
10 Hz ×
Standard
• For external termination
Internal Termination Switch
50 Internal termination
Standard
• Straight cable to hub, switch
or router
• Cross-over cable to PC
Uplink (Cross-over) Switch
• Cross-over cable to hub,
switch or router
• Straight cable to PC
PWR
Link / L / LK
Indicator Function
PWR (Power) Indicates power applied
Link / L / LK Indicates proper connection on 10Base-T segment
Chapter 5 Operation
5.2 Safety
The safety instructions given in Section 1.4 should always be followed to minimize the risk of
personal injury, and also the risk of damaging the equipment when operating the measuring
objects. However, local regulations, if stricter, always take precedence.
5.3 Indications
Status for the measurement equipment is indicated by LEDs on the control unit, the operator
unit and the excitation unit through messages on the operator unit display, or via the RS-232 and
RS-485 serial ports.
Control unit LEDs Marking Color Indicates when lit that ...
Run green the control unit is working normally.
Run Fault
Syserr Profibus a serious fault in the control unit has
LAN C Fault red been detected, see Chapter 7, Fault
RS-485 RS-232 Tracing.
a system fault is detected by the self
DO1 DO5 Syserr red test, or by the continuous monitoring
DO2 DO6 function, see Chapter 7, Fault Tracing.
DO3 DO7
DO4 DO8 communication in progress on the
Profibus yellow
fieldbus.
LAN yellow communication in progress on Ethernet.
C yellow Not used.
communication in progress on the
RS-485 yellow
RS-485 port.
communication in progress on any of
RS-232 yellow
the RS-232 ports.
activity in progress on the digital outputs
DO1 - DO8 yellow
DO1 - DO8.
Operator unit LEDs Marking Color Indicates when lit that ...
Power supply voltage is present in the
blue
Operator Unit
purple Command to Control Unit on Ethernet
.
NOTE
Serious faults, which cannot be detected by the normal fault handling in the
control unit are indicated by illuminating the LED “Fault” on the control unit.
5.4 Start-up
1. Switch the mains switch on the front of the control unit to position “1”.
a. The green LED “Run” on the control unit should be lit,
indicating that the equipment is powered.
b. The red LED “Fault” should be extinguished..
Fault (red)
Run (green)
Mains switch
in position “1”
The operation menu for the pre-selected object is shown when measurement is started.
Example of an operation menu:
ROUGHER 720
Total 15 MN
Side A 8 MN
Side B 7 MN
Difference 1 MN
5.6 Shutdown
1. Switch the mains switch to position “0” to switch off the control unit and the
operator unit.
Mains switch
in position “0”
Normally, the operator unit is powered from the control unit, and is shut-down automatically
when the control unit is shut-down.
5.7 Operation
5.7.1.1 General
Corresponding
old HMI function
buttons
P1
P2
P3
P4
Button Function
http;//
Connection to other device than MC400.
Operator unit works as a standard web browser.
S ROUGHER 720 1 2 3
abcd efgh ijkl
C
Total 15 MN
F Side A 8 MN 4 5 6
Side B 7 MN mnop qrst uvwx
Difference 1 MN
Select 7 8 9
yz%& åäöü ()<>
Clear - 0 +
Zero set System Lc exc Single
+=/* _#@‘ ,:;$
test ON/OFF cell
P1 P2 P3 P4
Menu number
Total 15 MN
Side A 8 MN
Side B 7 MN Menu area
Difference 1 MN
Message area
Zero set System Lc exc Single
test ON/OFF cell Function line
P1 P2 P3 P4
Figure 5-2. The Operator Unit Display. The Example Shows the Operation Menu for a Standard Object
NOTE
It is not possible to use the X29/X22 and X21 connectors at the same time. X29 has priority
over X22. X22 has priority over X21.
If the operator unit uses a LAN 10Base2 cable, connected to X21, this cable will be
disconnected when X22 or X29 is used.
Ethernet switch
CU name
Select language
Press Home
Press Home to get to the Home menu. Click the name of desired Millmate
ABB225
Date 12 jan 2004, 12:00
Load cell excitation On
After selecting screen saver, it will automatically start when your computer is idle for the time
interval specified in Wait. Select one of the specified wait intervals and click Save. The
available wait intervals are 5 seconds up to 10 hours. It is also possible to set the screen saver to
OFF, this disables the screen saver.
To clear the screen saver after it has started, touch the screen.
A screen that is continuously updated will redirect to Startup Object on Home screen when
screen saver has been activated to avoid data traffic during time out. If Startup Object has not
been activated, the Scan Controller screen is shown.
Set Backlight brightness level. Intensity is set in levels 10 (brightest) to 1 (dullest). When
approaching level 1 backlight, changes in brightness level may no longer be noticeable in the
panel. Complete dimming (to level 0) is not possible. Backlight brightness level is maintained
after reboot of panel.
Object name
Press Home
Rougher 720
Total 15 MN
Side A 8 MN
Side B 7 MN
Difference 1 MN
If there are more than four function keys, settings are moved to a separate menu.
To menu 761
(See Section 5.13.1)
Function
Description See section
key
Zero sets measuring signals from both load cells. The
Zero function must be acknowledged before it is executed.
set
Set
number Changing load cell set number in menu 760. 5.11.3
To menu 760
(See Section 5.13.3)
After
completed
System test finished 763 test
Test completed successfully
Reference saved: 12 feb 2004, 10:45
After the test is finished, detected errors can be read and acknowledged by pressing “Error
inspect”. The result of the tests can be printed by pressing “Print result”, see 4.5.29.
ROUGHER 720
Total Actual operation menu (example)
15 MN
Side A 8 MN
Side B 7 MN
Difference 1 MN
Settings 760
ROUGHER
LC set number 2
ROUGHER ROUGHER
Verify Verify
Single cell operation Double cell operation
Settings 760
ROUGHER
LC set number 2
Previous
operation
menu
Table 5-6. Function Keys for Setting Load Cell Set Number
End
Stores the entered value and leaves the menu.
ROUGHER 720
Total 15 MN
Side A 8 MN
Side B 7 MN
Difference 1 MN
Std1@ABB225
Chapter 6 Maintenance
Maintenance interval
Equipment Action 3 6 1
months months year
Enclosures and Cleaning x
cabinets
Checking cables x
Operator unit Cleaning x
Load cells Cleaning x
Visual inspection x
Cabling Visual inspection x
Junction box Check terminals x
Matching Units Check terminals x
It is also recommended that the System Reference Test (Self Test) is performed on a regular
basis, see Section 4.5.27, Performing a System Reference Test (Self Test).
CAUTION
Only use a damp cloth when cleaning the operator unit.
6.4 Cabinets
Check that:
• all screw terminals are well tightened.
• all units are securely fastened.
• no cables or conductors are damaged.
7.2 Interchangeability
Confirm End
Fault (error) inspection can also be done from operation menus, see 5.11.4.
Error
Fault Description Measures
Code
101 +5V supply voltage supervision alarm Replace control unit PFXA 401
102 +15V supply voltage supervision alarm
103 -15V supply voltage supervision alarm
104 +24V supply voltage supervision alarm
105 Analog in 1 offset voltage, supervision alarm If the system has been running:
• Replace control unit PFXA 401
106 Analog in 2 offset voltage, supervision alarm Error detected at commissioning:
• Try to restart the control unit.
• If error remains, remove all setup, see 4.5.32.
107 Analog in 3, offset voltage, supervision alarm
• Load the complete object setup, see 4.5.30, or do
the object setup manually.
108 Analog in 4, offset voltage, supervision alarm • Start the system. If not OK, replace control unit.
109 AD1 reference voltage supervision alarm Replace control unit PFXA 401
110 AD2 reference voltage supervision alarm
112 Load cell excitation loop impedance too high Check excitation circuit, see 4.5.21
114 Excitation unit under voltage alarm These alarms interrupt load cell excitation:
• Run system test, see 7.6, to check if error
diagnostics identifies cause of error.
116 Excitation unit loop impedance too high
• Use “Checking of load cell excitation in
PFVI 401”, see 4.5.21, for fault tracing.
117 Excitation unit over current alarm Note. Intermittent cable break in excitation circuit
can cause both error 116 and error 117.
121 Digital output 1 overload
122 Digital output 2 overload
123 Digital output 3 overload
124 Digital output 4 overload
Check wiring on Digital output
125 Digital output 5 overload
126 Digital output 6 overload
127 Digital output 7 overload
128 Digital output 8 overload
129 Analog in 1 amplification alarm If the system has been running:
• Replace control unit PFXA 401
130 Analog in 2 amplification alarm Error detected at commissioning:
• Try to restart the control unit.
• If error remains, remove all setup, see 4.5.32.
131 Analog in 3 amplification alarm
• Load the complete object setup, see 4.5.30, or do
the object setup manually.
132 Analog in 4 amplification alarm • Start the system. If not OK, replace control unit.
Error
Fault Description Measures
Code
136 Analog in 1 signal overflow
137 Analog in 2 signal overflow
Check setting on analog input
138 Analog in 3 signal overflow
139 Analog in 4 signal overflow
141 Analog in 1 voltage overload
142 Analog in 2 voltage overload
Check wiring on analog input
143 Analog in 3 voltage overload
144 Analog in 4 voltage overload
145 Analog inputs transient voltage overload Check wiring on analog input
149 Excitation unit PFVI401 power supply Excitation unit PFVI 401 is not working.
Check fuses and mains voltage connections.
If error remains, replace PFVI 401.
150 Excitation unit PFVI401 not connected Check ribbon cable between PFXA 401 and
PFVI 401. If error remains, replace PFVI 401.
151 Communication failure to the other MC 400 Check LAN wiring
152 Illegal system configuration Check settings
181 DSP communication failure
182 DSP to excitation synchronisation error
185 CPU bus error
186 CPU address error
188 Illegal instruction
189 Divide by zero detected Contact ABB
191 Other exception type
192 Boot sector memory checksum fault
195 Application checksum error
197 DSP interrupt missing
198 Watchdog time out
1 Load cell excitation level supervision warning Excitation level is changed compared to reference
301 )
test. The current is however still correct so meas-
urement is working correctly.
This indicates a change in excitation wiring and
matching units. Check wiring and matching unit.
3031) Saving on Boot FLASH fault Contact ABB
3041) Saving on PXAK401 FLASH fault Replace control unit PFXA 401
Error
Fault Description Measures
Code
3071) Low battery voltage Replace battery, see 6.6
Battery only supplies clock. Control unit works well
as long as it is switched on. Date and time will be
wrong after next power down if battery has not
been changed.
3201) Cannot setup IP-port for http communication
3491) Excitation unit PFVI 401 cooling fan Cooling fan is not working. Replace PFVI 401
or make sure that ambient temperature around
PFVI 401 is lower than 30°C.
1) Does not affect Ready and Ready all
7.4.1.2 Errors Detected when Running the System Test, (Error Types No 201-264)
The system test can be activated in different ways.
• From operation menu See 5.11.4 and 5.11.1
• From service menu See 7.6.1
NOTE
Measurement is interrupted when running the system test.
Press “Error inspect”, read error messages in menu “Stored errors” and take necessary actions to
correct detected faults.
Error types No 201-264 affect system status signals Healthy and Syserr (System error).
Syserr = System error (fault) that must be corrected.
Healthy = No unconfirmed system errors in the system
NOTE
The System Test can also be run from the operation menus, see 5.9 and
5.11.
Manual test 150 1. Enter the part test number and press “Start
Service Test no 1 test”. The part test is run continuously.
+5V Supply During the test, the previously stored test re-
Previous 5.03 V sults and approved limits are shown.
Service Reference 5 V
Low limit 4.75 V 2. Terminate the part test by pressing “Stop
High limit 5.25 V
Not performed test” - otherwise the part test is automatically
System Start Check Next End terminated after 30 minutes.
test values test
test 3. Press “Check values” to show all stored val-
ues without starting a part test.
Manual Repeated test 151
test Test no 1
4. Press “Next test” to step to the next part test.
+5V Supply 5. Analog outputs and digital inputs/outputs can
Value 5.03 V
Previous 5.03 V be tested manually using “Check I/O”.
Reference 5 V
Low limit 4.75 V
High limit 5.25 V
Running, OK
Stop Next
test test
Test
Description
No.
1 Power supply + 5 V
2 Power supply +15 V
3 Power supply –15 V
4 Power supply +24 V (for internal use and for external equipment)
5 Offset voltage, analog input 1
6 Offset voltage, analog input 2
7 Offset voltage, analog input 3
8 Offset voltage, analog input 4
9 Internal reference voltage, A/D-converter 1
10 Internal reference voltage, A/D-converter 2
11 Relative gain, analog input 1
12 Relative gain, analog input 2
Test
Description
No.
13 Relative gain, analog input 3
14 Relative gain, analog input 4
15 Insulation in the signal circuit connected to analog input 1.
16 Insulation in the signal circuit connected to analog input 2.
17 Insulation in the signal circuit connected to analog input 3.
18 Insulation in the signal circuit connected to analog input 4.
19 Resistance in the signal circuit connected to analog input 1.
The measured value is compared with the reference test value.
20 Resistance in the signal circuit connected to analog input 2.
The measured value is compared with the reference test value.
21 Resistance in the signal circuit connected to analog input 3.
The measured value is compared with the reference test value.
22 Resistance in the signal circuit connected to analog input 4.
The measured value is compared with the reference test value.
23 Output level of load cell supply for the first half of load cell excitation circuit.
The measured value is compared with the reference test value.
24 Over voltage alarm for supply of the first half of load cell excitation circuit.
25 Over current alarm for supply of the first half of load cell excitation circuit.
26 Under voltage alarm for supply of the first half of load cell excitation circuit.
27 Not in use.
28 Not in use.
29 LC sensitivity on load cells connected to analog input 1
30 Zero voltage, load cells at analog input 1.
The measured value is compared with the reference test value.
The test is only performed if load cells are connected.
31 Output level of load cell supply for the second half of load cell excitation circuit.
The measured value is compared with the reference test value.
32 Over voltage alarm for supply of the second half of load cell excitation circuit.
33 Over current alarm for supply of the second half of load cell excitation circuit.
34 Under voltage alarm for supply of the second half of load cell excitation circuit.
35 Not in use.
36 Not in use.
37 LC sensitivity on load cells connected to analog input 2
Test
Description
No.
38 Zero voltage, load cells at analog input 2.
The measured value is compared with the reference test value.
The test is only performed if load cells are connected.
39 LC sensitivity on load cells connected to analog input 3
40 Zero voltage, load cells at analog input 3.
The measured value is compared with the reference test value.
The test is only performed if load cells are connected.
41 LC sensitivity on load cells connected to analog input 4
42 Zero voltage, load cells at analog input 4.
The measured value is compared with the reference test value.
The test is only performed if load cells are connected.
43 Output level of load cell supply for the entire load cell excitation circuit.
The measured value is compared with the reference test value.
44 Over voltage alarm for the supply of the entire load cell excitation circuit.
45 Over current alarm for the supply of the entire load cell excitation circuit.
46 Under voltage alarm for the supply of the entire load cell excitation circuit.
47 Not in use.
48 Not in use.
49 Not in use.
50 PFVI 401 presence check.
51 Analog in 1, calibration check.
52 Analog in 2, calibration check.
53 Analog in 3, calibration check.
54 Analog in 4, calibration check.
55 Not in use.
56 Not in use.
57 Not in use.
58 Not in use.
59 Not in use.
60 Not in use.
61 Not in use.
62 Not in use.
63 Not in use.
64 Not in use.
Is the
“Syserr” LED on Yes Carry out a system test.
the control unit Correct any faults according
lit? to the fault list.
Carry out a new system test.
No
Is the
“Fault” LED on Yes
Contact service.
the control unit
lit?
No
Carry out a
system test.
ROUGHER 720
Operation Total Actual operation menu (example)
15 kN
Side A 8 kN
Side B 7 kN
Difference 1 kN
Operation
Settings 760
ROUGHER
ROUGHER ROUGHER
Verify Verify
Single cell operation Double cell operation
A.1.1 Terminology
Term Definition
VIP Vendor Internet Protocol
IP Internet Protocol
TCP Transmissions Control Protocol
Retransmission of lost or damaged data packages.
MC 400 Control unit Millmate Controller 400
MST Millmate Strip Tensiometer Systems with MC 400 (PFCA 401/PFXA 401)
MRF Millmate Roll Force Systems with MC 400 (PFXA 401 only)
MSS Millmate Strip Scanner Systems with MC 400 (PFXA 401 only)
4 bytes 0 - n bytes
Header Data
Header Data
packed packed
int16 int16 int16 int16 int16 int16 int16 int16 bool 16 bool 16
1 2 3 4 5 6 7 8 1 2
Figure A-2. Order of Data Types in the Data Block
A.3.1 Overview
Millmate Strip Tensiometer (MST), Millmate Roll Force Meter (MRF) and
Millmate Strip Scanner (MSS) are based on a common platform designated
Millmate Controller 400 (MC 400).
MC 400 comprises the necessary hardware and software infrastructure to realize the products
including communication facilities.
The following sections outline the required functionality that are provided by the VIP protocol.
1)
Ready all is recommended output for indication of working (measuring) system.
Slave – MC400
B.2.5 Blocks
Compact blocks for fast data exchange only. These blocks are optimized for fast control.
Bit No.
Data Byte No.
7 6 5 4 3 2 1 0
01 MSB
Value 1
02 LSB
03 MSB
Value 2
04 LSB
05 MSB
Value 3
06 LSB
07 MSB
Value 4
08 LSB
Boolean in 09 No. 8 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1
10 Spare for future use
Bit No.
Data Byte No.
7 6 5 4 3 2 1 0
01 MSB
Variable 1
02 LSB
03 MSB
Variable 2
04 LSB
Boolean out 05 No. 8 No. 7 No. 6 No. 5 No. 4 No. 3 No. 2 No. 1
06 Not used
Name Std1@ABB225
Application Standard measurement
Lc type PFVL 141
Lc size 20.00 MN
Lc at port 1, 2
Load division 0.05 MN
To menu 320
Modify End
Input variables
The resolution for input variables is the same as the unit used for the rest of the mechanical
settings. The variable should be given as an integer value (without decimals).
The GSD-file can also be output from the MC 400 control unit. For further information,
B.3 Installation
This section describes the cabling and setup of the Profibus in the MC 400.
Line type B
Parameter Line type A
(Avoid if possible)
Impedance in 135 to 165 100 to 130
Capacitance per unit length (pF/m) <30 <60
Loop resistance ( /km) 110 ---
Core diameter (mm) 0.64 > 0.53
Core cross section (mm2) > 0.34 > 0.22
The specified line parameters result in the following lengths of a bus segment.
X 31 X 30
Pin Pin Signal Designation
No. No.
1 Shield Shield/protective ground
2 N.C NOT USED
3 1 RxD/TxD-p*) Receive data/transmission data plus
4 CNTR-P Control signal for repeaters (direction control)
5 DGND Data Transmission potential (Ground to 5 V)
6 VP Supply voltage of the terminating resistance-P, (P5V)
7 N.C. NOT USED
8 2 RxD/TxD-N*) Receive data/transmission data negative
9 CNTR-N Control signal for repeaters (direction control)
The line shield should be led to the protective ground (usually the electrically conductive
housing) of the connected device to prevent EMC interference from penetrating the device.
Data transmission of the serial bus system using twisted wire pair lines with connected shield
is defined in the specifications of the RS 485 interface which is not susceptible to interference.
In accordance with EN 50 170, the plug connector allocation on the Profibus cable is specified
for a 9-pin, sub D plug connector. (This gives a slave a socket connection.)
MC 400 provides 5 volts and GND to pins 5 and 6 so that the bus can be terminated with
terminating resistors.
If the protection rating prevents use of the recommended 9-pin, sub D plug connector,
connection can be made to X30, use only the mandatory signals RxD/TxD-P and RxD/TxD-N.
Since the data lines are connected through in the Profibus connection plug, the failure
of one station does not affect other stations.
The failure of a slave is detected by the Profibus master during the next data cycle,
and indicated.
Line type A
Typical connection capacity of a bus station (e.g., plug connectors, line length to
the RS 485 driver, RS 485 driver, components, etc.): 15 to 25pF.
Stub lines should not be used at high transfer rates.
The tolerance of the capacitive load of the station should be in the range of 15 to 25 pF.
Otherwise, a repeater must be used for the bus connection to prevent errors.
To bridge longer distances and bypass EMC interference, transmission with optical fiber
conductors (glass or plastic) is also specified.
Standard bus plug connectors are available for transmission with optical fiber conductors.
These connectors convert RS 485 signals to optical fiber conductor signals and vice versa.
(OLP = optical link plug).
In addition, repeaters are available to handle this signal conversion.
This gives you the option of switching between the two transmission techniques within
one system if necessary.
You can connect up to 126 stations to one Profibus system.
To be able to handle this number of participants on the bus, the bus system must be divided
into individual segments, containing maximum 32 stations each.
These segments are linked by repeaters.
Run Fault
Profibus indication
Syserr
LAN
Profibus
C
lamp
RS-485 RS-232 RS-232:2 RS-232:1
X27 X26
DO1 DO5
DO2 DO6
DO3 DO7
DO4 DO8
Profibus DP
(X31)
(X30)
Profibus X35
X34
X31 X24 X25
T2A T2A Digital in Digital out
F1 F2
85-264V~ X30 X23
47-63Hz 140W Profibus RS-485
1 2 3 4 5 1 2 3 4 5
S1 X2 X3 X5 X6 X8
X1
Termination switch R
R
in ON position
Termination switch
R
in OFF position
R
B.4 Commissioning
This section contains:
Safety information
Setting up the Fieldbus
Selecting measurement values (signal values) Section B.4.2
Configuring digital inputs Section B.4.3
Configuring digital outputs Section B.4.4
Error handling Section B.4.5
DANGER
Be careful when working with the measurement system with mains voltage
applied to it. The voltage in the equipment can injure, or even kill.
Comm.
setup
Fieldbus
Select value
Profibus
A
Enter the function to be executed when
the selected input port is activated.
– The selected digital input No is
Booleans to MC400 from PLC 273 disconnected if “Signal” is set to “-”.
No Invert Signal Object
1 Zero set Inlet – The input function can be inverted
2 - -
3 - - by marking the “Invert” column.
4 - - Return to the main menu and save
5 - -
6 - - the modifications with “End”.
7 - -
8 - -
Signal Select End
list object
End
Select desired input signal to be
connected to the digital input bit.
“Not active” disconnects the input bit,
selected in menu 273.
Input Signal List 274
Not active Not active
EXON Lc exc on
EXOFF Lc exc off
LOCK Lock sys
SYTEST Sys. test
ZS Zero set
SCCA Single cell A
SCCB Single cell B
DCC Double cell
SDON Step det on
End
All these signals, except “Lock System”, are flank triggered. They react when the bit is changed
from “0” to “1”. The bit has to be “1” for at least 50 ms before it can be changed back to “0”
again.
Next
End
MC 400
Object 1
Signal input
A
MC 400
Object 1
Signal input
A
Object 2
Signal input
A
MC 400
RS-485
Boolean in No 8 Syserr
3BSE023139R0401 Rev A
B
C.9 Relay Board, PFVK 128, Circuit Diagram, 3BSE010547D0002, Rev. B
We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Appr. PAMP/FMGS F Norlund PFVK 128
Resp.dept. Relay Board -
PAMP/FMGS
Document number Lang. Rev. Sheet
Tuesday, April 21, 2015, 08:27:14 ABB Automation and Drives 3BSE010547D0002 en B 1
1 2 3 4 5 6
C-9
Millmate Roll Force Systems with Millmate Controller 400,
Appendix C- Drawings
Millmate Roll Force Systems with Millmate Controller 400,
Appendix C- Drawings C.10 Relay Board, PFVK 128, Arrangement Drawing, 3BSE010547D0004, Rev. E
3BSE023139R0401 Rev A
C.11 Matching Board, PFBK 401, Circuit Diagram, 3BSE027078D0002, Rev. -
We reserve all rights in this document and the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Appr. ATCF/FM/GF E Wadman PFBK 401
Resp.dept. Matching Board -
ATCF/FM/GF
Document number Lang. Rev. Sheet
Tuesday, December 4, 2001, 18:23:10 ABB Automation Products AB 3BSE 027 078 D0002 en - 1
C-11
Millmate Roll Force Systems with Millmate Controller 400,
Appendix C- Drawings
Millmate Roll Force Systems with Millmate Controller 400,
Appendix C- Drawings C.12 Matching Device, PFVO 142, Circuit Diagram, 3BSE023732D2, Rev. A
3BSE023139R0401 en Rev A