Danfoss IOM APP 11 13 L
Danfoss IOM APP 11 13 L
Danfoss IOM APP 11 13 L
Lenntech
[email protected]
[email protected] Tel.
Tel. +31-152-610-900
+31-152-610-900
www.lenntech.com
www.lenntech.com Fax.
Fax.+31-152-616-289
+31-152-616-289
User manual
APP 11-13
User manual Installation, Operation and Maintenance APP Pumps (APP 11-13)
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Manufacturer and customer service address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Preferred system design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Commissioning and servicing the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Adhere to the following important points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 In case of doubt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Approved applications and operational limits for the pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Application range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Electric motor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Noise and vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.6 Space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.7 Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.8 Properties of water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.9 Air bubbles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.10 Chemicals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Subject index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Validity This manual is valid for APP pumps with the following code numbers/serial numbers:
This manual contains the necessary instructions It is important that these instructions are
for the installation, operation and service of the always available to the personnel concerned.
pumps used in a Sea Water Reverse Osmosis
(SWRO) system or Brackish Water Reverse
Osmosis (BWRO) system. 1.2 Symbols
Use of the pump in other applications that are Indicates a situation which will or could
not suitable for the pump unit can cause result in personal injury and/or damage
damages to the pump unit, with risk of personal to the pump
injury.
!
Protective
The pump must always be installed and used in garments Protective garments
accordance with existing national/local must be worn must be worn
sanitary, safety regulations and laws.
2. Safety
!
Protective
garments Use of this manual does not relieve operation
must be worn and maintenance personnel of the responsibil-
ity of applying good judgment when operating
and maintaining the pump and its compo-
nents.
Always wear suitable safety clothing when
handling the pump.
2.2 Preferred system design
When working near the pump system, safety Danfoss recommends to build systems with a
shoes, safety glasses, hearing protection and high degree of safety. Danfoss preferred system
safety helmet must always be worn. design and P&ID are found in appendix 1, Data
sheet, and appendix 2, Instruction.
It is always the system builders´ responsibility • o not try to lift the pump unit manually;
D
that the system design does not cause any kind most of the pumps weigh more than
of hazard and is adapted to local regulations and 20 kilos, see specific weight for the pump
standards. in the appendix 1, Data sheet.
• Always bleed the pump prior to initial
Proper installation, proper start up and shut- start-up.
down devices as well as high-pressure protection • Do not mount the pump without the bell
equipment is essential. housing and a flexible coupling.
• Do not try to start the unit before the
system components are mounted, bleeded
2.3 Commissioning and servicing the unit and adjusted.
It is recommended that commissioning and • Flush the system throughly before
servicing are carried out by a minimum of two connecting the pump or pump unit.
people, where one is acting as a supervisor. • Check rotation direction of the motor
before mounting the pump.
Danfoss recommends not to build a filter bypass All air must be bleeded from both the low-
function or to use filters with an integrated pressure and high-pressure side before the RO
bypass. If the above recommendation is not system is pressurised. Special consideration
followed the warranty for the pump will should be given in order to minimize air bubbles
automatically become void. in the feed flow. Air bubbles can cause cavitation.
4.2 Warning
Before any lifting operation is performed,
environmental conditions must be taken into
consideration (Ex-rated areas, wind speed, wet/
dry conditions, lifting height, etc.).
When the pump is mounted together with an How to mount the pump and the electric motor
electric motor, the pump unit always weigh more correctly, see appendix 1, Data sheet or appendix
than 20 kilos and must be handled by using 2, Instruction.
slings around the pump unit.
4.6 Storage
Each pump is tested before shipment, and will
therefore contain water. For storage temperature
and frost protection see appendix 2, Instruction.
5. Installation and
commissioning
5.1 Important dimensions 5.4 Electrical data
Physical dimensions and connections of the Check voltage, current frequency and rated
pump unit are described in appendix 1, Data power on the electric motor and VFD settings on
sheet. the name plate placed on both the motor and
the VFD.
5.2 Cleanliness
It is very important that the tubes and pipes are 5.5 Local regulations
completely clean: no dirt, chips or burrs are Commissioning must always be done in
allowed. Flush all piping before connecting the accordance with valid regulations and local
high-pressure pump to ensure the system is standards.
clean. Internal surfaces of the piping must not be
corroded. If dirt or rust is not removed, the pump
and the valves can be damaged. In worst case
the pump can be damaged beyond repair!
Media filter
PI
M
9 3 8
PI 1 PI 1 PI PT PI
Feed 2
7 Permeate
4
5
6 PT
Brine
Table 1: C
heck points when assembling and commissioning system
6. Operation of pump
unit
6.1 General safety information G) Drop in flow and/or pressure – may indicate
Before inspecting the pump unit, read the Safety wear on one or more parts inside the
chapter 2 in this user manual. pump. The pump must be stopped
immediately and inspected before it is
restarted. Contact the maintenance
6.2 What to listen and look for department.
If one or more of the following examples are
observed, please act as indicated: H) Other observations or troubles, please see
appendix 7, Right and Wrong or appendix
A) Loose bolts – check all bolts and, if 6, the Trouble shooting guide.
necessary, contact the maintenance Both appendices give good advises
department in order to have all bolts regarding design, installation, wiring and
tightened to the specified torque(s). troubleshooting.
See also service and warranty section in
B) Leakage – if a small leakage from the bell appendix 1, Data sheet and appendix 2,
housing is observed. Contact the mainte- Instruction.
nance department.
If the pump is not stopped for inspection as
C) Leakage – if there is a large leak, the unit recommended, it can lead to damage of the
should be stopped immediately. Contact pump or break-down. See also service and
the maintenance department. warranty section in the appendix 1, Data sheet,
in appendix 2, Instruction or appendix 4,
D) High frequency tones – safety/relief valves Instruction for recommended service intervals.
are either damaged or running very close
to their design pressure, stop the unit Danfoss offers service of the pump at the system
immediately. Contact the maintenance manufacturer’s location as well as we offer
department. training in how to service the pump. Quotes are
offered upon request.
E) Increased noise or vibration – requires the
unit to be stopped immediately. Contact Danfoss recommends simultaneously to check
the maintenance department. the filter and membrane condition and to
evaluate contamination; filter and membrane
F) Very high temperatures – may indicate that elements must be replaced if necessary.
one or more parts are damaged inside the
pump. The pump must be stopped
immediately and inspected before it is
restarted. Contact the maintenance
department.
7. Maintenance and
service of the pump
unit 7.1 General safety information Danfoss offers service of the pump at the system
Before servicing the pump unit, it is necessary to manufacturer’s location and training in how to
read and understand this user manual, especially service the pump. Quotes are offered upon
the Safety, chapter 2. Remember to wear suitable request.
safety equipment according to Safety, chapter 2.
For spare parts and service tools, please see E) Open bleeding and drain plugs. Wait until
appendix 3, Parts list. the pump and system are emptied for
water.
H) For the small pumps, unscrew the bolts Returns without a return number will be
holding the pump to the bell housing. For rejected !!!
the bigger pumps, unscrew the bolts/nuts
from the pump and bell housing to the
motor. Afterwards unscrew the bolts/nuts 7.5 Assembling the pump unit
holding the pump and bell housing. Assemble the pump according to the Dis
assembling and Assembling Instruction
I) Carefully pull the pump out of the bell (available at www.ro-solutions.danfoss.com).
housing by using lifting equipment, if
necessary.
7.6 Procedure for mounting the pump onto
J) Hold the pump in different positions above the electric motor
a drip tray; this should allow most of the
water trapped in the pump to drain. Clean
and dry the pump surface and plug the
bleeding and draining plugs.
Mount the flexible coupling and bell housing
K) Move the pump to a clean and safe location according to appendix 2, Instruction.
where the pump can be inspected/
serviced.
7.7 Getting the pump unit back into
operation
7.4 Disassembling and assembling the Find instructions of how to put the pump unit
pump unit back into operation in chapter 4, Arrival inspec-
A) Remove all connections from the pump. tion, transportation, handling, lifting and storage
and Installation and commissioning, chapter 5.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction
(available at www.ro-solutions.danfoss.com) 7.8 Storage of the pump
If the pump has to be shut down for a longer
Clean all parts and surfaces with a fluid period, instructions can be found in appendix 2,
compatible with the materials found in the Instruction.
pump. Wipe the parts clean and dry with a
lint-free clothing.
8. Troubleshooting and
scrapping criteria
8.1 General safety information If water is leaking into the electric motor; it can
Before inspecting the pump unit, it is necessary cause electric shock, fire, short circuit or even
to read and understand this user manual, death. When mounting the pump vertically
especially the Safety chapter 2. always mount the motor above the pump to
avoid water leaking into the electric motor.
Remember to wear suitable safety equipment
according to Safety chapter 2.
Electrical
hazard
8.2 Operational conditions which can cause 8.4 Electrical failure
pump failures If the wiring of the electric motor is incorrect or
The following conditions can cause a pump the ground connection is missing, it can cause
failure : electric shock, burn damages, fire or even death.
• The pump is running dry. If a VFD is used and wrongly programmed, it can
• The inlet pressure is too high. damage the pump and lead to high tempera-
• The inlet pressure is too low. tures or other dangers.
• The temperature of the fluid is too high.
• The ambient temperature is too high. All electrical installation must be carried out by
• The pump is running against a blocked authorized personnel in accordance with
port/closed manual valve. EN60204-1 and/or local regulations.
• The pump is operating at a pressure out of
specification.
• The pump is running with a non-specified/ 8.5 Responsibility
approved fluid. Danfoss takes no responsibility for any abnormal
• The pump is running in the wrong injuries, risks or damages that could arise caused
direction. by abnormal conditions, vibrations, corrosion,
• The filtration is insufficient. abrasives, foreign objects or excessive tempera-
• The pump is not being serviced according tures and shall not be liable for any consequen-
to Danfoss specifications (end of life). tial or incidental damages.
• There is excessive mechanical load on the
shaft coupling and piping.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be
scrapped, depends on in which conditions the
internal parts are, or how damaged the whole
8.3 Mechanical failure unit is. Please use appendix 6, Trouble shooting
If the pump is running dry, the temperature will guide as guideline or send the pump to Danfoss
quickly increase which can cause burns. headquarter in Denmark for evaluation.
If there is any leakage at start-up or during For other observations or troubles, please see
operation, a high pressure jet can cause eye or appendix 7, Right and Wrong which gives good
skin damage. advises regarding design, installation, wiring and
troubleshooting.
Leakage can result in flooding, which can cause
slipping, tripping or falling. In case the pump needs to be scrapped, please
follow your local environmental rules.
Subject index
A G S
Address . . . . . . . . . . . . . . . . . . . .7, 8, 15 General information . . . . . . . . . . . . . . . 7 Safety . . . . . . . . . . . 6, 7, 8, 9, 12, 13, 14, 16
Air bubbles . . . . . . . . . . . . . . . . . . . . . 9 Guideline . . . . . . . . . . . . . . . . . . . . . 16 Safety valve . . . . . . . . . . . . . . . . . . . . 7
Appendix . . . . . . . . 7, 8, 9, 10, 11, 14, 15, 16 Scrapping criteria . . . . . . . . . . . . . . . . 16
Application range . . . . . . . . . . . . . . . . . 8 H Serial number . . . . . . . . . . . . . . . . . . . 4
Approval . . . . . . . . . . . . . . . . . . . . . . 6 Handling . . . . . . . . . . . . . . . . . 7, 9, 12, 15 Servicing . . . . . . . . . . . . . . . . . . . 6, 8, 14
Arrival . . . . . . . . . . . . . . . . . . . . 9, 12, 15 Shut down . . . . . . . . . . . . . . . . . . . 14, 15
Assembling . . . . . . . . . . . . . . . . . . 12, 15 I Space requirement . . . . . . . . . . . . . . . . 8
Inspection . . . . . . . . . . . . . . . . . . . 13, 14 Spare part . . . . . . . . . . . . . . . . . . . . . 14
B Installation . . . . . . . 6, 7, 8, 11, 12, 14, 15, 16 Start up . . . . . . . . . . . . . . . . . . . . . . . 8
Bleed . . . . . . . . . . . . . . . . . . . 8, 9, 13, 15 Instruction . . . . . . . . 6, 7, 8, 9, 10, 12, 14, 15 Storage . . . . . . . . . . . . . . . . . 9, 10, 12, 15
Instrumentation . . . . . . . . . . . . . . . . 6, 12 Symbols . . . . . . . . . . . . . . . . . . . . . . . 6
C Introduction . . . . . . . . . . . . . . . . . . . . 6 System . . . . . . . . . . . 6, 7, 8, 9, 11, 12, 13, 14
Checklist . . . . . . . . . . . . . . . . . . . . . . 11 Systems . . . . . . . . . . . . . . . . . . . . . . 7, 8
Check points . . . . . . . . . . . . . . . . . . . 12 M
Chemicals . . . . . . . . . . . . . . . . . . . . . . 9 Maintenance . . . . . . . . . . . . 6, 7, 10, 13, 14 T
Cleanliness . . . . . . . . . . . . . . . . . . 11, 14 Mechanical failure . . . . . . . . . . . . . . . . 16 Table of Contents . . . . . . . . . . . . . . . . . 2
Commissioning . . . . . . 6, 8, 11, 12, 13, 15, 16 Mounting . . . . . . . . . . . . . . . .8, 11, 13, 15 Technical data . . . . . . . . . . . . . . . . . . . 8
Connections . . . . . . . . . . 7, 9, 10, 11, 12, 15 Temperature . . . . . . . 7, 10, 11, 12, 13, 14, 16
Coupling . . . . . . . . . . . . . . 8, 12, 13, 15, 16 N Transportation . . . . . . . . . . . . . 6, 9, 12, 15
Name plate . . . . . . . . . . . . . . . 9, 11, 12, 13 Trouble shooting . . . . . . . . . . . . . . 14, 16
D Noise . . . . . . . . . . . . . . . . . . . . . . . 8, 14
Danger . . . . . . . . . . . . . . . . . . 6, 7, 13, 16 V
Data sheet . . . . . . . . . . 7, 8, 9, 10, 11, 12, 14 L Valve . . . . . . . . . . . . . . 7, 11, 12, 13, 14, 16
Declaration of Conformity . . . . . . . . . .5, 7 Leaking . . . . . . . . . . . . . . . . . . . . . . . 16
Design . . . . . . . . . . 7, 8, 9, 11, 12, 13, 14, 16 Lifting . . . . . . . . . . . . . . . . 6, 9, 10, 12, 15 W
Distributor . . . . . . . . . . . . . . . . . 6, 7, 8, 9 Local regulations . . . . . . . . 6, 7, 8, 11, 12, 16 Warning . . . . . . . . . . . . . . . . . . . . . .6, 9
Dimensions . . . . . . . . . . . . . . . . . . . 8, 11
Disassembling . . . . . . . . . . . . . . . . . . 15 O
Operation . . . . . . . . . 6, 7, 8, 9, 13, 14, 15, 16
E Operational conditions . . . . . . . . . . . 7, 16
EC Declaration of Conformity . . . . . . . .5, 7
Electric motor . . 6, 7, 8, 9, 10, 11, 12, 13, 15, 16 P
Electrical failure . . . . . . . . . . . . . . . . . 16 Piping . . . . . . . . . . . . . . . . . . 9, 11, 12, 16
Electrical hazard . . . . . . . . . . . . . . . . 6, 7 Positioning . . . . . . . . . . . . . . . . . . . . 12
Electrics . . . . . . . . . . . . . . . . . . . . . . 12 Preferred system design . . . . . . . . . . 7, 11
Pre mounting . . . . . . . . . . . . . . . . . . . 11
F Protection . . . . . . . . . . . . . . . . 6, 7, 8, 10
Failure . . . . . . . . . . . . . . . . . . . . . . 8, 16
Filter condition . . . . . . . . . . . . . . . . . . 13 R
Filtration . . . . . . . . . . . . . . . . 9, 12, 14, 16 Relief valve . . . . . . . . . . . . . . . . 12, 13, 14
Flow . . . . . . . . . . . . . . . . . . . 7, 9, 13, 14 Responsibility . . . . . . . . . . . . . . 6, 7, 8, 16
Fluid . . . . . . . . . . . . . . . . . . 11, 12, 15, 16 Return . . . . . . . . . . . . . . . . . . . . . 10, 15
Flush . . . . . . . . . . . . . . . . . . . . . 8, 11, 13 Rotation . . . . . . . . . . . . . . . . . . . . . 8, 13
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
User manual
APP 11-13
User manual Appendices for IOM Manual for APP Pumps (APP 11-13)
Data sheet
APP 11-13
ro-solutions.com
Data sheet APP 11-13
4. Variants
6. Flushing valve
7. Power requirements
9. Noise level
10. Filtration
11. Dimensions
13. Installation
13.1 Mounting
13.2 Open-ended system with direct water supply
13.3 RO system with APP pump
14. Service
14.1 Warranty
14.2 Maintenance
14.3 Repair
4
2 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
Data sheet APP 11-13
1. Introduction APP 11-13 pumps are designed to supply low All parts included in the pumps are designed to
viscosity and corrosive fluids under high provide long service life, i.e. long service life with
pressure, eg. in seawater reverse osmosis a constantly high efficiency and minimum
filtration applications and for high pressure salt service required.
water pumping.
The pumps are fixed displacement pumps in
The pumps are based on the positive displace- which the flow is proportional to the number of
ment principle (axial piston design) which revolutions of the input shaft and the pump
enables a very light and compact design, and displacement.
they are designed so that the lubrication of the
moving parts in the pumps is provided by the
fluid itself. No oil lubrication is thus required.
1: Shaft Sealing
2: Bolts for bell
housing
3: Flushing valve
4: Port plate
5: Bleeding plug
6: Valve/thrust plate
7: Piston/shoe
8: Cylinder barrel
9: Retainer ring
10: Swash plate
with bearing
11: Port flange
with bearing
12: Drain plug
13: Housing
14: Springs
2. Benefits • O
ne of the smallest and lightest pumps on • No oil lubricant required.
the market. • Integrated flushing valve.
• Can be powered by a combustion engine • All parts of the pump are made of non-corro-
provided that a special coupling is used. sive materials, e.g. Duplex (EN1.4462/UNS
• Long service life / no preventive maintenance S31803-S32205) and Super Duplex (EN1.4410/
required in the warranty period. UNS S32750) stainless steel and carbon
• Generates insignificant pulsations in the reinforced PEEK.
pressure line. • High efficiency.
180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013 5
3
Data sheet APP 11-13
3. Technical data APP Pumps APP 11 / 1200 APP 11 / 1500 APP 13 / 1200 APP 13 / 1500
Code number 180B3212 180B3211 180B3214 180B3213
Geometric displacement cm³/rpm 166 137 197 166
in³/rpm 10.1 8.4 12.0 10.1
Rated flow at max. speed 1) m³/h 11.0 11.1 13.1 13.5
gpm 48.4 49 57.7 59.3
Outlet min. pressure 2) bar 30 30 30 30
psi 435 435 435 435
Outlet max. pressure, cont. 3) bar 80 70 80 70
psi 1160 1015 1160 1015
Inlet min. pressure bar 2 2 2 2
psi 29 29 29 29
Inlet max. pressure, cont. bar 5 5 5 5
psi 72.5 72.5 72.5 72.5
Inlet max. pressure, peak bar 10 10 10 10
psi 145 145 145 145
Max. speed cont. rpm 1200 1500 1200 1500
Min. speed cont. rpm 700 700 700 700
Power requirement at kW 23 24 27 29
max. speed and 60 bar
hp 30.8 32.2 36.2 38.9
outlet pressure
Torque at 60 bar Nm 179 148 212 179
outlet pressure
lbf-ft 132 109 157 132
Weight Kg 75 75 75 75
lb 165 165 165 165
Integrated flushing valve YES YES YES YES
4. Variants • A
vailable as ATEX certified. Category 2, zone 1 For more details on the variants, please contact
and category 3, zone 2. the Danfoss RO Solutions Sales Organisation.
• Available with material certificates on wetted
parts.
6
4 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
Data sheet APP 11-13
5. Flow at different rpm When using the diagrams shown below, it is easy best if the flow required and the rotation speed
to select the pump which fits the application (rpm) of the pump are known.
m3/h 10,00
9,00
8,00
7,00
6,00
5,00
700 800 900 1000 1100 1200
rpm
10,00
9,00
8,00
7,00
6,00
5,00
700 800 900 1000 1100 1200 1300 1400 1500
rpm
Furthermore, these diagrams shows that the flow the “required “ flow can be obtained by chang-
can be changed by changing the rotation speed ing the rotation speed to a corresponding value.
of the pump. The flow/rpm ratio is constant, and Thus, the required rpm can be determined as:
180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013 7
5
Data sheet APP 11-13
6. Flushing valve
Flushing Valve characteristic
2,00
1,80
1,60
The power requirements can be determined using one of the following guiding equations:
3
l/min x bar 16.7 x m /h x bar 0.26 x gpm x psi
Required power= Calc. factor [kW] or Calc. factor [kW] or Calc. factor [kW]
8
6 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
Data sheet APP 11-13
80 º C Duplex
70
Super Duplex
60
50
316L
40
30
20 -
100 1000 10 000 100 000 CI
ppm
160 1600 16000 160000 NaCI
ppm
9. Noise level The sound pressure levels, L PA, 1 m*) db(A) for The noise level is influenced by:
APP 11-13 pumps are typically 81 dB(A) at • The speed of the pump, high rpm create more
60 bar/1500rpm and 85 dB at 80 bar/1500rpm. noise than low rpm
• R igid mounting of the pump generates more
Generally, noise will be reduced if speed is noise than flexible mounting
reduced and vice versa. Use flexible hoses in • P ipe mounting direct to the pump increases
order to minimize vibrations and noise. the noise level compared to a flexible hose
• If using a VFD the motors can produce higher
Since the pump is typically mounted on a bell noise values depending on the operation
housing or frame, the noise level must be point.
determined for the complete unit (system).
180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013 9
7
Data sheet APP 11-13
10. Filtration As water has very low viscosity, the APP pumps cartridges typically have only 50% filtration
have been designed with very narrow clearance efficiency. This means that for each 100,000 parti-
in order to control internal leakage rates and cles reaching the filter, 50,000 particles pass
improve component performance. Therefore it is through it compared to only 20 particles in a
important that the inlet water is filtered properly filter with an efficiency of 99.98%.
to minimize the wear of the pump.
For more information on the importance of
The main filter must have a filtration efficiency of proper filtration, please consult our publication
99.98% at 10 µm. We recommend to use “Filtration” (code number 521B1009), which also
precision depth filter cartridges rated 10µm abs. will provide you with an explanation of filtration
ß10>5000 (equivalent to a filtration efficiency of definitions and a guidance on how to select the
99.98%). Bag filters and string wound filter right filter.
11. Dimensions
Inlet
Outlet
10
8 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
Data sheet APP 11-13
12. Dimensions,
complete unit
180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013 11
9
Data sheet APP 11-13
Note: Examples of different pump/motor sizes motors and couplings. Please always check
and drawing dimensions are only for IEC required motor power and dimensions.
13. Installation 13.1 Mounting To ensure easy mounting of the flexible coupling
The figure below illustrates how to mount the without using tools, the tolerances must be
pump and connect it to the electric motor/ dimensioned accordingly.
combustion engine.
Note: Any axial and radial loads on the pump
If alternative mounting is required, please shaft must be avoided.
contact Danfoss RO Sales Organization for
further information.
A B C
A: Flexible coupling
B: Bell housing
C: Motor shaft
3. Install a low pressure safety valve or a Note: If a non-return valve is mounted in the
pressure relief valve (3) in order to avoid inlet line, a low pressure relief valve is also
system or pump damage in case the pump required between non return valve and pump
stops momentarily or is spinning backwards. as protection against high pressure peaks.
12
10 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
Data sheet APP 11-13
13.3 RO system with APP pump 6. For easy system bleeding and flushing, a
1. Dimension the inlet line to obtain minimum bypass non-return vavle (6) is integrated in
pressure loss (large flow, minimum pipe the APP pump.
length, minimum number of bends/connec- 7. A non-return valve (7) in outlet can be
tions, and fittings with small pressure losses). installed in order to avoid backspin of the
2. Place an inlet filter (1) in front of the APP pump. The volume of water in the membrane
pump (2). Please consult section 10, “Filtra- vessel works as an accumulator and will send
tion” for guidance on how to select the right flow backwards in case of the pump stops
filter. Thoroughly clean pipes and flush momentarily.
system prior to start-up. 8. A safety valve or a pressure relief valve (8) can
3. Place a monitoring pressure switch (3) set at be installed in order to avoid system damage
min. inlet pressure between filter and pump as the Danfoss APP pump creates pressure
inlet. The monitoring switch must stop the and flow immediately after start-up, regard-
pump at pressures lower than minimum less of any counter-pressure.
pressure.
4. Use flexible hoses (4) to minimize vibrations
and noise. Note: If a non-return valve is mounted in the
5. In order to eliminate the risk of damage and inlet line, a low pressure relief valve is also
cavitation, a positive pressure at the inlet (5) is required between non return valve and pump
always to be maintained at min. inlet pressure as protection against high pressure peaks.
and max. inlet pressure. Recommend to install
safety valve or a pressure relief valve (9) in
order to avoid high pressure peaks in case the
pump stops momentarily or is spinning
backwards.
14. Service 14.1 Warranty breakdown of the pump. If the parts are not
Danfoss APP pumps are designed for long replaced, more frequent inspection is recom-
operation, low maintenance and reduced mended according to our guidelines.
lifecycle costs.
180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013 13
11
Data sheet Water pumps APP 11-13
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
14
12 180R9264 // DKCFN.PD.013.E2.02
521B1215 IOM APP 11-13 Appendices - v04 / 11.2013
/ 02.2013
MAKING MODERN LIVING POSSIBLE
www.ro-solutions.com
Instruction APP pump instruction APP 11-13 and APP 16-22
4. Initial start-up
5. Operation
5.1 Temperature
5.2 Pressure
5.3 Dry running
5.4 Disconnection
5.5 Storage
5.5.1 Recommended procedure
6. Service
6.1 Warranty
6.2 Maintenance
6.3 Repair
7. EC Declaration of Conformity
16
2 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
Instruction APP pump instruction APP 11-13 and APP 16-22
2. System design The design of the system must ensure that 2. Place a monitoring pressure switch (3)
self-emptying of the pump during standstill is between filter and pump inlet - set at min.
avoided. 2 bar (29 psi) inlet pressure. The monitoring
The inlet pressure of the pump must never pressure switch must stop the pump at
exceed the outlet pressure. This may typically pressures lower than 2 bar (29 psi ) inlet
occur in boosted or open-ended systems with pressure.
direct water supply. 3. Install a low pressure safety valve or a low
pressure relief valve (4) in order to avoid
system or pump damage in case the pump
2.1 Open-ended systems with direct stops momentarily ( high pressure peaks )
water supply or starts spinning backwards.
The pump is supplied with water direct from a
feed pump.
In order to eliminate the risk of cavitation, a Note: If a non return valve (2) is mounted in the
positive inlet pressure of at least 2 bar(29 psi) is inlet line, a low pressure relief valve is also
always to be maintained, but it must not exceed required between non return valve and pump
5 bar (72.5 psi) continuously. as protection against high pressure peaks.
1
2
3
PS
Inlet
Outlet
180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013 17
3
Instruction APP pump instruction APP 11-13 and APP 16-22
18
4 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
Instruction APP pump instruction APP 11-13 and APP 16-22
A: Elastic coupling
B: Bell housing
C: Motor shaft
D: Pump flange
3
2
C
1
1. Mount the coupling flush or maximum 6. Adjust respectively, verify the measure-
1 mm offset from the pump shaft end. ment, and secure both couplings with the
Ensure an air gap between coupling and right torques on the locking screws (see
pump flange of min. 4 mm (0.16 inch). coupling operation & mounting instruc-
2. Mount the bell housing on pump. Secure tion).
nuts with the right torque. 7. Mount the elastic gear ring and mount the
3. Measure the longest distance “A” from top bell housing/pump on the motor. After
of bell housing to the button of coupling mounting it must be possible to move the
claw. elastic gear ring 3-5 mm (0.12 - 0.2 inch)
4. Mount the coupling on motor shaft. Ensure axial “C”. The check can be done through
the coupling and motor flange are not in the inspection hole of bell housing. Secure
contact with each other. flange bolts with the right torque.
5. Measure from motor flange to the top of
the coupling. That measurement “B” shall
be 3-5 mm (0.12 - 0.2 inch) shorter than the
measurement “A”.
180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013 19
5
Instruction APP pump instruction APP 11-13 and APP 16-22
NESSIE © Pump
Type APP
Serial no.
Code no.
MADE IN DENMARK
3.3 Orientation
The pump can be mounted/orientated in any
horizontal direction with the inlet and the outlet
pointing upwards, downwards or to either side.
CC C
C
C - Bleeding
C
C
CC
20
6 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
Instruction APP pump instruction APP 11-13 and APP 16-22
3.4 Protection against too high Both the inlet and outlet lines must be flexible
outlet pressure soft hoses.
The pump should be protected against too high
outlet pressure by means of a safety valve or a The valve outlet must not be connected
pressure relief valve. The valve should be placed directly to the pump suction line. It must be
as close to the pump as possible. The opening connected directly to the drain.
characteristics of the valve must not result in
peak pressures higher than 80 bar (1,160 psi).
Inlet
Inlet
Outlet
Outlet
3.5 Connections
I : Inlet C
O : Outlet
C : Bleeding I
D : Parallel key
180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013 21
7
Instruction APP pump instruction APP 11-13 and APP 16-22
APP 11 - APP 13
APP 16 – APP 22
22
8 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
Instruction APP pump instruction APP 11-13 and APP 16-22
180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013 23
9
Instruction APP pump instruction APP 11-13 and APP 16-22
80 º C Duplex
70
Super Duplex
60
50
316L
40
30
20 -
100 1000 10 000 100 000 CI
ppm
160 1600 16000 160000 NaCI
ppm
24
10 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
Instruction APP pump instruction APP 11-13 and APP 16-22
6. Service 6.1 Warranty of the pump. If the parts are not replaced, more
Danfoss APP pumps are designed for long frequent inspection is recommended according
operation, low maintenance and reduced to our guidelines.
lifecycle costs.
180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013 25
11
Instruction APP pump instruction APP 11-13 and APP 16-22
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
26
14 180R9264 / 521B1184
180R9223 IOM APP 11-13 Appendices - v04/ /12.2012
/ DKCFN.PI.013.T1.02 11.2013
3. IOM Electric motors
(180R9230)
Electric Motors
Motor Manual
hoyermotors.com
Manual
Motor Manual
Lifting eyebolts must be tightened before use. Damaged Connections must be made in such a way as to ensure that
eyebolts must not be used, check before use. Lifting eyes at a permanently safe electrical connection is maintained,
motor must not be used to lift the motor when it is attached both for the main supply and the earth connection.
to other equipment. We recommend that crimped connections are made in
accordance with IEC 60352-2.
Before commissioning, measure the insulation impedance.
If values are ≤ 10MΩ at 25°C, the winding must be oven dried. Tightening torques for terminal board screws:
The insulation resistance reference is halved for each 20°C Thread M5 M6 M8 M10 M12 M16 M20
rise in motor temperature.
T.(Nm) 2.5 3.5 7 12 18 35 55
It is recommended that shafts are rotated periodically by
hand to prevent grease migration.
Ensure that the terminal box is clean and dry.
Unused glands must be closed.
3. Installation Check the terminal box gasket before it is remounted.
The motor must be fixed on a stable, clear and flat founda-
tion. It must be sufficiently rigid to withstand possible short 5. Maintenance
circuit forces.
It is important to ensure that the mounting conditions do Inspect the motor at regular intervals, keep it clean and
not cause resonance with the rotational frequency and the ensure free ventilation air flow, check the condition of
doubled supply frequency. shaft seals and replace if necessary. Both electrical and
Only mount or remove drive components (pulley, coupling, mechanical connections must be checked and tightened if
etc.) using suitable tools, never hit the drive components necessary.
with a hammer as this will cause damage to the bearing.
The motor are balancing with half key, ensure that the drive
components are also the same.
2
28
Hoyer Motors, Motor Manual, October 2011
180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
Motor Manual
Bearing size and type are specified on the rating plate. The table values are based on an ambient temperature of
Motor types HMA2 and HMC2 is as standard with lifetime 25°C. The values must be halved for every 15K increase in
greased bearing with motor size ≤225. bearing temperature.
Motor types MS and Y2E is as standard with lifetime greased Higher speed operations, e.g. frequency converter drive will
bearing with motor size ≤160. require shorter greasing intervals. Typically, doubling the
speed will reduce the values by 50%.
Typical duty hours for lifetime lubricated bearings.
Correct alignment
alignment is is essential
essential to
to avoid
avoid bearing,
bearing, vibration
vibration
1. General Correct
and shaft
shaft failure.
failure.
and
This manual
This manual concerns
concerns thethe following
following types
types of
of standard
standard Use appropriate
appropriate methods
methods forfor alignment.
alignment.
Use
induction motors
induction motors from
from Hoyer:
Hoyer: Re-check the alignment after the final
final tightening
tightening of
of the
the
Re-check the alignment after the
HMA2, HMC2,
HMA2, HMC2, HMD,
HMD, HMT,
HMT, MS,
MS, Y2E1,
Y2E1, Y2E2,
Y2E2, YDT
YDT bolts or
or studs.
studs.
bolts
These motors
These motors are
are manufactured
manufactured in in accordance
accordance with
with IEC/EN
IEC/EN Check that
that drain
drain holes
holes and
and plugs
plugs face
face downwards.
downwards. WeWe
Check
60034-4 and
60034-4 and IEC/EN
IEC/EN 60072.
60072. recommend opening the drain hole for motors placed
recommend opening the drain hole for motors placed
Motors are
Motors are rated
rated for
for the
the ambient
ambient temperature
temperature range
range -20°C
-20°C outdoors and
and not
not running
running 2424 hours
hours // day,
day, so
so that
that the
the motor
motor
outdoors
to +40°C
to +40°C and
and site
site altitudes ≤1000 m
altitudes ≤1000 m above
above sea
sea level.
level. can breathe,
breathe, thus
thus ensuring
ensuring a a dry
dry motor.
motor.
can
Low-voltage motors
Low-voltage motors are are components
components for for installation
installation in
in
machinery. They are CE marked according
machinery. They are CE marked according to the Low to the Low
Voltage Directive
Voltage Directive 2006/95/EC
2006/95/EC 4. Electrical connection
Work is
Work is only
only permitted
permitted to to be
be carried
carried out
out by
by qualified
qualified
2. Transport and storage specialists
specialists and
and must
must toto be
be carried
carried out
out in
in accordance
accordance with
with
Check thethe motor
motor forfor external
external damage
damage immediately
immediately upon
upon local
local regulations.
regulations.
Check
receipt and,
and, ifif found,
found, inform
inform the
the forwarding
forwarding agent
agent right
right Before work
Before work commences,
commences, ensure
ensure that
that all
all power
power is
is switched
switched
receipt
away. Check
Check allall rating
rating plate
plate data,
data, and
and compare
compare itit with
with the
the off
off and
and cannot
cannot be
be switched
switched on on again.
again. This
This also
also applies
applies to
to the
the
away.
requirement of the motor. auxiliary power circuits, e.g. anti-condense heaters.
auxiliary power circuits, e.g. anti-condense heaters.
requirement of the motor.
Turn the
the shaft
shaft byby hand
hand toto check
check free
free rotation,
rotation, remove
remove Check that
Check that supply
supply voltage
voltage and
and frequency
frequency are are the
the same
same as
as
Turn
transport locking
locking ifif used.
used. rated data.
rated data.
transport
Transport locking
locking must
must be
be used
used again
again for
for internal
internal transport
transport Motors
Motors can
can be
be used
used with
with aa supply
supply deviation
deviation ofof ±
± 5%
5% voltage
voltage
Transport
also. It
It is
is also
also important
important that
that transport
transport locking
locking is
is used
used when
when and ± 2% frequency, according to IEC60034-1
and ± 2% frequency, according to IEC60034-1
also.
motors are
motors are transported
transported mounted
mounted onon equipment.
equipment.
All motors
motors should
should be be stored
stored indoors,
indoors, in
in dry,
dry, vibration-
vibration- and
and Connection
Connection diagrams
diagrams for
for main
main supply
supply and
and accessory
accessory as
as PTC
PTC
All
dust-free conditions. or heater are located inside the terminal box.
or heater are located inside the terminal box.
dust-free conditions.
Lifting eyebolts
eyebolts must
must be
be tightened
tightened before
before use.
use. Damaged
Damaged Connections
Connections must
must bebe made
made inin such
such a
a way
way as
as to
to ensure
ensure that
that
Lifting
eyebolts must not be used, check before use. Lifting eyes at
at a permanently safe electrical connection is maintained,
a permanently safe electrical connection is maintained,
eyebolts must not be used, check before use. Lifting eyes
motor must
must not
not be
be used
used to
to lift
lift the
the motor
motor when
when it
it is
is attached
attached both for
both for the
the main
main supply
supply and
and the
the earth
earth connection.
connection.
motor
to other
other equipment.
equipment. We recommend
We recommend that that crimped
crimped connections
connections are
are made
made inin
to
accordance
accordance with
with IEC
IEC 60352-2.
60352-2.
Before commissioning,
Before commissioning, measure
measure the
the insulation
insulation impedance.
impedance.
If values
values are ≤ 10MΩ
are ≤ 10MΩ at
at 25°C,
25°C, the
the winding
winding must
must be
be oven
oven dried.
dried. Tightening torques
Tightening torques for
for terminal
terminal board
board screws:
screws:
If
The insulation
The insulation resistance
resistance reference
reference is
is halved
halved for
for each
each 20°C
20°C Thread M5 M6 M8 M10 M12 M16 M20
Thread M5 M6 M8 M10 M12 M16 M20
rise in motor temperature.
rise in motor temperature. T.(Nm)
T.(Nm) 2.5
2.5 3.5
3.5 7
7 12
12 18
18 35
35 55
55
It is
It is recommended
recommended thatthat shafts
shafts are
are rotated
rotated periodically
periodically by
by
hand to
hand to prevent
prevent grease
grease migration.
migration.
Ensure
Ensure that
that the
the terminal
terminal box
box is
is clean
clean and
and dry.
dry.
Unused glands
Unused glands must
must be
be closed.
closed.
3. Installation Check the
Check the terminal
terminal box
box gasket
gasket before
before it
it is
is remounted.
remounted.
The motor
The motor must
must bebe fixed
fixed on
on aa stable,
stable, clear
clear and
and flat
flat founda-
founda-
tion. It
tion. It must
must be
be sufficiently
sufficiently rigid
rigid to
to withstand
withstand possible
possible short
short 5. Maintenance
circuit forces.
circuit forces.
It is
is important
important to to ensure
ensure that
that the
the mounting
mounting conditions
conditions do
do Inspect the
Inspect the motor
motor at
at regular
regular intervals,
intervals, keep
keep it
it clean
clean and
and
It
not cause
cause resonance
resonance with
with the
the rotational
rotational frequency
frequency andand the
the ensure
ensure free
free ventilation
ventilation air
air flow,
flow, check
check the
the condition
condition ofof
not
doubled supply
supply frequency.
frequency. shaft
shaft seals
seals and
and replace
replace if
if necessary.
necessary. Both
Both electrical
electrical and
and
doubled
Only mount
mount or or remove
remove drive
drive components
components (pulley,
(pulley, coupling,
coupling, mechanical connections
mechanical connections must
must bebe checked
checked and
and tightened
tightened if
if
Only
etc.) using
using suitable
suitable tools,
tools, never
never hit
hit the
the drive
drive components
components necessary.
necessary.
etc.)
with a
with a hammer
hammer as as this
this will
will cause
cause damage
damage to to the
the bearing.
bearing.
The motor
The motor areare balancing
balancing with
with half
half key,
key, ensure
ensure that
that the
the drive
drive
components are
components are also
also the
the same.
same.
2
30 4
2 Hoyer Motors,
Hoyer Motors, Motor
Motor Manual,
Manual, October
180R9264October
2011
/ IOM APP2011
11-13 Appendices - v04 / 11.2013
180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013 31
SVEND HØYER A/S
Chains · Gears · Motors
Tlf. (+45) 86 98 21 11
Lenntech
[email protected]
[email protected] Tel.
Tel. +31-152-610-900
+31-152-610-900
www.lenntech.com
www.lenntech.com Fax.
Fax.+31-152-616-289
+31-152-616-289
MAKING MODERN LIVING POSSIBLE
4. Recommended service
intervals for APP
pumps (180R9199)
Instruction
1. General information This guideline provides information on the The recommendation is for guidance only.
recommended service intervals. The recommen-
dation is based upon good engineering practice
and on experience gained from operation even
under extreme conditions.
2. Design/features Danfoss APP pumps are designed for long If the Danfoss recommendations concerning
operation and low maintenance and life cycle system-design (see our data sheet) are not
costs. followed, the service life of the APP pumps might
be affected.
Danfoss guarantees 8,000 hours service free
operation, however max. 18 months from date of The recommended service intervals on the
production. After 8,000 operation hours it is different parts in the APP pumps appear from the
recommended to inspect the pump and replace table below:
worn parts, if any.
34
2 180R9264 / 521B1135
180R9199 IOM APP 11-13 Appendices - v04/ /01.2013
/ DKCFN.PI.013.C1.02 11.2013
Instruction Recommended service intervals for APP pumps
180R9264 / 521B1135
180R9199 IOM APP 11-13 Appendices - v04/ /01.2013
/ DKCFN.PI.013.C1.02 11.2013 35
3
Instruction Recommended service intervals for APP pumps
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
36
4 180R9264 / 521B1135
180R9199 IOM APP 11-13 Appendices - v04/ /01.2013
/ DKCFN.PI.013.C1.02 11.2013
MAKING MODERN LIVING POSSIBLE
APP Pumps
APP 0.6-43
11-13 / APM 0.8-2.9 /
APP W 5.1- 10.2
APP 11-13
Parts list APP 0.6-43 / APM 0.8-2.9 / APP W 5.1-10.2
Parts list APP 21-43 2. Parts list APP 0.6 - 1.0 Compact
(521B0941)
3. Exploded view APP 0.6 - 1.0 Compact
38
2 180R9264 // DKCFN.PC.073.A13.02
521B0941 IOM APP 11-13 Appendices - v04 / 11.2013
/ 10.2013
Parts list APP 0.6-43 / APM 0.8-2.9 / APP W 5.1-10.2
180R9264
521B0941 // DKCFN.PC.073.A13.02
IOM APP 11-13 Appendices - v04 / 11.2013
/ 10.2013 39
3
Parts list APP 0.6-43 / APM 0.8-2.9 / APP W 5.1-10.2
(APP 11-13)
(APP 11-13)
(APP 11-13)
(APP 11-13)
(APP 11-13)
(APP 11-13)
1 1 Housing Duplex / PEEK
2 2 Pin (Ø6x10) AISI 316 x
3 2 Bleeding plug Super Duplex x
4 2 O-ring (Ø11x2) NBR x
5 12 Screw (M8x30) AISI 316 x x
9 1 O-ring (Ø182x4) NBR x x
10 2 O-ring (Ø9.19x2.62) NBR x x x x
11 1 End flange Duplex
12 1 Lifting eye AISI 316
31 1 Swash plate Super Duplex / PEEK x x x
34 2 Pin (Ø10.5x20) Super Duplex x x x x
61 1 Cylinder barrel Super Duplex / x
Duplex / PEEK
62 7 Spring Duplex x
63 1 Spring guide PP x
64 1 Retainer ball Super Duplex / DLC x
65 1 Retainer plate Super Duplex x
66 7 Piston Super Duplex / PEEK x
67 1 Key (10x8x45) AISI 316 x
81 3 Pin (Ø6.4x40) Duplex x
91 1 Port plate Super Duplex / PEEK x
92 1 Valve plate Super Duplex x
93 7 Back-up ring PTFE x x
94 7 O-ring (30.2x3.0) NBR x x
121 1 Port flange Duplex / PEEK
122 1 O-ring (Ø68x2) NBR x
123 1 O-ring (Ø182x4) NBR x
124 1 Shaft seal (Ø35) Hastelloy / NBR x
125 1 Cover for shaft seal Super Duplex
126 2 Pin (Ø10.5x20) Duplex x x
127 4 Screws (M6x16) AISI 316 x
128 10 Screws (M8x65) AISI 316 x
129 1 Lifting eye AISI 316
142 1 Stop for shaft seal PP x
144 4 Tailstock screw (M12x60) AISI 316
145 4 Check nut (M12) AISI 316 x
151 1 O-ring (Ø29x3) FPM 75 x x
152 1 Valve cone Super Duplex x
153 1 Spring (Ø1.9xØ25x33.7) Duplex x
154 1 Plug/guide Super Duplex x
155 1 O-ring (Ø38x3.7) NBR x x
Instruction x x x x x x x x x
40
16 180R9264 // DKCFN.PC.073.A13.02
521B0941 IOM APP 11-13 Appendices - v04 / 11.2013
/ 10.2013
15.
Parts list
APP 11 - 13
Exploded view
180R9264
[22.13 lbf ft
± 2.21 lbf ft]
[1.47 lbf ft
± 0.74 lbf ft] [22.13 lbf ft ± 2.21 lbf ft]
521B0941 // DKCFN.PC.073.A13.02
IOM APP 11-13 Appendices
[1.47 lbf ft
± 0.74 lbf ft]
/ 10.2013
- v04 / 11.2013
[22.13 lbf ft
± 2.21 lbf ft]
APP 0.6-43 / APM 0.8-2.9 / APP W 5.1-10.2
17
41
Parts list APP 0.6-43 / APM 0.8-2.9 / APP W 5.1-10.2
Shaft bush x
Press bush x
Drift x
Torx (T30) x
Shaft bush (Ø18) x x
Press bush (Ø18) x x
Allen key (4 mm) x
Allen key (5 mm) x
Allen key (6 mm) x x x x
Shaft bush (Ø35) x
Shaft seal extractor (Ø35) x x
Press bush (Ø35) x x
Adjustable pin wrench x x x x
Combination wrench (10 mm) x x x x
Combination wrench (13 mm) x x x
Nut (M8x6.5x13) x x x
Guide bolt (M8x140) x x
Shaft seal extractor (Ø45) x x
Press bush (Ø45) x x
Eye bolt (M8) x x
Press bush for valve plate x x
Stop for retainer plate x
Screw (M8x20) x x x
Screw (M8x70) x x
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
42
26 180R9264 // DKCFN.PC.073.A13.02
521B0941 IOM APP 11-13 Appendices - v04 / 11.2013
/ 10.2013
MAKING MODERN LIVING POSSIBLE
Guideline
44
2 180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
08.2013
Instruction
08.2013
1. No flow/pressure 2. Reduced flow/pressure
2.1.5 Pre-treatment
PUMP FAILED
3. High torque on el. motor 4. Noise from pump 5. Noise from installation
45
3
Instruction Trouble shooting guide for APP, APP S and APP S 674 pumps
1. No flow/no pressure
1.3 No rotation of electric motor 1.3.1 Check that main switch is switched on. If motor-type relay or the electrical fuse is
1.3.2 Check the electricity at the facility. blown, check that electric motor is sized
1.3.3 Ensure that motor relay is switched on. correctly.
1.3.4 Ensure that fuse is not blown.
1.3.5 Ensure that booster pump is started.
1.3.6 Check that the monitor switches are
working correctly.
1.3.7 Disconnect pump from electric motor and
check that the motor is capable of running
with no load.
1.4 No rotation of pump 1.4.1 Ensure that coupling between electric
motor and pump is connected.
1.4.2 Check if coupling is damaged.
1.4.3 Check that electric motor is sized correctly.
1.4.4 Check that the electrical installation is
correctly sized.
1.4.5 Contact Danfoss Sales office for guidelines
in how to troubleshoot internal pump
parts.
1.5 Axial load on pump shaft 1.5.1 Ensure that the air gap between the two To ensure easy mounting of the flexible
(may cause high internal leakage) coupling parts is min 5 mm. It should coupling without using tools, the tolerances
Only applying to always be possible to move the plastic part must be dimensioned accordingly.
APP 0.6 to APP 3.5 and on the coupling at least 3 mm.
APP 21 to APP 26 only. WARNING:
Also applying to APP S and APP S 674 pumps. Any axial and/or radial loads on the shaft
must be avoided. Any axial or radial load will
cause breakdown.
A - Bell housing
B - Flexible coupling
C - Motor shaft
A B C
1.6 Pump damage 1.6.1 Contact Danfoss sales office for guidelines Instructions on internal elements
(the internal parts may be damaged) in how to troubleshoot internal pump 180R9092/180R9085 for APP 0.6-1.0
parts. 180R9091/180R9147/180R9089 for APP 1.5-3.5
180R9093/180R9090 for APP 5.1-10.2
180R9228/180R9227 for APP 11-13 and APP 16-22
180R9121/180R9139 for APP 21-43
180R9281 for APP S 674 3.0-3.5 / APP S 3.0-3.5
180R9280 for APP S 674 5.1-9.0 / APP S 5.1-9.0
180R9278 for APP S 674 21-38 / APP S 21-38
– are available on www.ro-solutions.com.
46
4 180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
08.2013
Instruction Trouble shooting guide for APP, APP S and APP S 674 pumps
48
6 180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
08.2013
Instruction Trouble shooting guide for APP, APP S and APP S 674 pumps
50
8 180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
08.2013
Instruction Trouble shooting guide for APP, APP S and APP S 674 pumps
Picture 1 A normally worn valve plate has no marks/scratches but only a slightly
polished surface.
No scratches or marks should be felt. The surface must be flat and level.
Picture 2 A worn valve plate has scratches, and/or a polished surface. Even small
scratches will give a loss of flow.
Scratches
Picture 3 A good way to identify a worn valve plate is to hold a straight knife edge
over the valve plate. When holding it up to the light, it will be possible to
see any space between the knife edge and the valve plate. See picture 3.
If any light can be seen between the two arrows on the picture, the valve
plate is worn.
If any scratches or marks can be felt by running a fingernail over the surface,
the valve plate is worn.
Picture 1 If the port plate has scratches, level differences or both between the arrows,
the port plate must be replaced.
L ev
dul el diff
l an e re
d sh nce
inin s b e
g P t we
EEK e n
The surface of the swash plate must be plane and even at same level all
over. To check this, please see item 6.1, picture 3.
Please contact Danfoss High Pressure Pumps sales office for further infor-
mation.
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
52
10 180R9264 / IOM APP 11-13 Appendices - v04 / 11.2013
08.2013
MAKING MODERN LIVING POSSIBLE
180R9042
4. Pump location
Design
Pump always to be placed below water Pump location above water surface
surface level level will cause damage
. Iron
. Rubber . Copper
. Plastic . Brass
. Stainless steel . Aluminium
Always use system components made Non-corrosion proof materials System to be dimensioned to provide Poor suction conditions will cause
of corrosion proof materials may cause damage a suction pressure of the pump inlet of malfunction and damage the pump
max. 0.1 bar vacuum
Install a 10 micron absolute filter with Return filter with bypass valve and Pressure relief valve to be mounted Coupling the pressure relief valve outlet
pressure switch poorer filterability than 10 m will vertically or with vertical outlet and directly to the pump inlet may damage
damage the system connected to return hose or tank the pump
Locate the return filter in the return line Placing the return filter upstream of the System to be filled via filter Filling system with unfiltered
immediately before the tank final load may damage the pump water causes damage
Installation
Assembly of coupling
8. Impurities 11.
Prior to installation, burrs and chips and Chips or other impurities in the system The coupling must be easy and simple Never use force when assembling the
other impurities must be removed from may cause damage to assemble (see product instruction) coupling parts, as this will damage the
pipes and hoses, eg with a felt plug motor/pump
Coupling
9. Sealing 12.
= min. 3 mm 0 mm
Fittings in screwed components to be Using teflon tape or packing yarn in Ensure always to have 3 mm distance Insufficient distance and/or misalign-
sealed with O-rings or bonded seals joints may cause damage between coupling flanges ment between the coupling flanges
will damage the pump
Correctly limited quantities of grease Too much grease may develop Fill system with water before starting Starting without water will cause
prevent seizing biofilm causing operational failures to ensure lubrication and cooling damage
Wiring
Starting procedure
Cleaning procedure
Level indicator 1. Fill cold water into the system via the return filter and
14. bleed the pump (Power Packs PPH 4 - 6.3 - 10 and 12.5 are
self-bleeding)
Level and temperature indicators Missing or incorrectly connected level 5. Empty the system of the cleaning agent solution
must be fitted. Follow installation and temperature indicators cause
instructions damage
Flushing procedure
6. Fill cold water through the return filter and bleed the
15. Rotation direction pump (Power Packs PPH 4 - 6.3 - 10 and 12.5 are
self-bleeding)
1 ? 2
7. Run the system for 30 min. and activate all components as
often as possible
Bleeding
16. Starting procedure
60 min. 2-3
days
Bleeding the pump will ensure correct Insufficient bleeding may cause dam- Observing the starting procedure will If the system is not cleaned before
cooling and lubrication age (not applicable to Power Packs) ensure problem-free operation starting, the filter will clog
Trouble shooting
Open ended water systems
No water supply
Yes
. Is water coming . Is the electric motor of . Is the water in the tank . Lower inlet
No o Yes temperature or
No out of the tap? the pump unit rotating? very hot? Ie above 50
provide better cooling
. Are all taps open?
Yes No
Yes
No
Contact serviceman
The system
does not work
Yes
Yes No
. At temperatures
o
higher than 50 the
. Is the power supply ok? pump drive cuts out.
No Consequently the
. Are control lights on?
cooler must be
checked/cleaned
Yes
No
Contact serviceman
Stamp
Lenntech
[email protected]
[email protected] Tel.
Tel. +31-152-610-900
+31-152-610-900
www.lenntech.com
www.lenntech.com Fax.
Fax.+31-152-616-289
+31-152-616-289
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.