10080-1-ENGG-DBD-CI-007 - 0 - Design Basis For Fire and Gas System
10080-1-ENGG-DBD-CI-007 - 0 - Design Basis For Fire and Gas System
10080-1-ENGG-DBD-CI-007 - 0 - Design Basis For Fire and Gas System
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
RECORD OF REVISIONS
Contents
1. Purpose........................................................................................................................... 1
2. Scope .............................................................................................................................. 1
3. Cost competitive engineering and design ........................................................................ 1
4. Conflicts and Deviations .................................................................................................. 2
5. References ...................................................................................................................... 2
6. Terms and Definitions ..................................................................................................... 2
7. Abbreviations .................................................................................................................. 2
8. Environmental Conditions ............................................................................................... 4
9. Fire & Gas System Overview ........................................................................................... 4
10. Fire & Gas Field Devices .................................................................................................. 5
11. Technical Requirements & System Engineering Specification. ....................................... 10
12. Third Party Interfaces .................................................................................................... 13
13. Fibre Optic Network ...................................................................................................... 14
14. RISK Analysis ................................................................................................................. 15
15. Engineering Documentation.......................................................................................... 15
1. Purpose
This Design basis specifies requirements of various type of Fire, Gas & Smoke
detectors & other field devices design guidelines for F&G system, third party
interface requirements, and Risk Analysis for Process Plants F&G system.
2. Scope
The scope of the F&G System shall be to detect a fire or gas release and
automatically initiate audible and visual alarms in the respective designated
‘Emergency Response Areas, Central Control Room (CCR) and in the vicinity of the
hazard. Fire protection systems may be activated automatically for heat and fire
and by executive action for other alarms from the CCR.
By early detection of a potential hazardous event and carrying out predetermined
actions to mitigate the effects, the F&G System will help ensure:
• Protection of Personnel;
• Protection of the Environment;
• Protection of Plant;
• Protection of Production;
The F&G system shall be designed to:
• Provide visual and audible alarms in the CCR, Fire Stations, Site Shift Managers
Office, and local to the hazard;
• Initiate alarm only actions at an early stage in order to mitigate the
consequence of fire or gas release;
• Alert personnel to danger;
• Initiate protection systems (if required);
• In order to quickly assess the overall situation in the event of an alarm in
highly hazardous and low-manned areas with limited direct visibility, the
addition of remote plant surveillance by means of Close Circuit Television
(CCTV) may be considered based on type of Project. In case of Alarm
designated CCTV camera shall be zoomed to pre-assigned direction.
3. Cost competitive engineering and design
The engineering team shall maintain the cost focus throughout all phases of the
project. This should be done without compromising any specification and design
requirements.
10080-1-ENGG-DBD-CI-007 Page 1 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
7. Abbreviations
AC Alternating Current
DC Direct Current
10080-1-ENGG-DBD-CI-007 Page 2 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
IS Intrinsically Safe
PA Public Address
10080-1-ENGG-DBD-CI-007 Page 3 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
8. Environmental Conditions
The System will be located in an air conditioned environment which will be to ISA
S71.04, G1 classification.
Normal operating conditions will be:
22 ± 2 °C and 50 ± 6% Relative Humidity.
9. Fire & Gas System Overview
F&G system shall comprise of two systems. Fire Detection Alarm System and Gas
Detection Alarm system. Microprocessor based Intelligent Fire alarm system shall
be used with addressable detectors. Gas detection system shall be dual redundant
PLC based system. Fire alarm system shall be only data gathering system and will
be interfaced with dual redundant PLC on dual redundant serial link. All executive
actions, activation of outputs shall be carried out by PLC ONLY. Typical PIB F&G
architecture is attached as Annexure-X.
All the detection equipment and alarms shall be monitored by the operators in
the CCR and in the Fire Stations and Site Shift Managers Office via the F&G
network. All the monitoring networks shall give precise locations of the problem
areas.
The F&G System in certain areas shall initiate trips and/or shutdowns via the ESD
system (if required/ specified).
The F&G system shall get Digital Input from DCS or any system for Beacon Black-
out. (if required/ specified) In case of Beacon Black-out signal ACTIVE/ON
command, beacons will NOT flash despite alarm in field devices.
Evacuation procedures shall be directed from Emergency Response areas which
shall be in communication with the Central Control Room.
10080-1-ENGG-DBD-CI-007 Page 4 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 5 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 8 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 9 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 10 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 11 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
The work stations quantity shall be decided based on Site / Project Organization
for specific project.
Deluge start should be possible from control room workstation (except from SSM
office & Fire station workstations)
Inhibit should be possible from control room workstation (except from SSM office
& Fire station workstations)
All detector locations shall be indicated and an indication of the detected medium
i.e. Toxic Gas (H2S) or Fire etc.
• H2S : Blue
• Flammable gas : Amber
• Fire : Red
• System fault : White
• Smoke : Red
• Healthy : Green.
• Healthy Detector inhibited : Grey and Pink box surrounding detector
• Detector in alarm Inhibited : Respective detector alarm colour and Pink Box
surrounding detector
• Fire Water Pump Running : Green
11.3. Alarm Management
• Basically Alarm will be segregated like:
− Fire Alarm
− LO / HI Gas Alarms
− Inhibit Alarms
− Fault Alarms
− System Alarms
− Maintenance / Test Alarms
11.4. Requirements For Circuit Integrity
F&G system shall be robust against spurious activation.
Electric circuitry shall be enhanced with line monitoring facilities. Line monitoring
shall be able to discriminate between safe condition, alarm condition, open loop
and short circuit.
10080-1-ENGG-DBD-CI-007 Page 12 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 13 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 14 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 15 of 16
J3 Program 10080-1-ENGG-DBD-CI-007
Design Basis for Fire & Gas System Date: 18/07/2012, Rev. 0
10080-1-ENGG-DBD-CI-007 Page 16 of 16
Annexure- I: Typical F&G Detection Layout
Annexure- II: Typical F&G Cable Block Diagram
Annexure- III: Typical F&G Cause & Effect Chart
NOTES
FIRE & GAS SYSTEM AUDIBLE
VISUAL ALARMS GASEOUS SYSTEM HVAC SYSTEM ELECTRICAL
ANNUNCIATION ALARMS $//7$*180%(5$5(6+2:1:,7+2877+(,535(),;7+(
35(),;)257+,6$5(,6
=
)25*(1(5$/127(6$1''(7$,/66((
,1'(;2)),5(
=21(6
6+((72)7+,6'2&80(17
7+,6'5$:,1*6+$//%(5($',1&21-81&7,21:,7+) *
/$<287'5$:,1*180%(5-5'=
,)36+,1387,612735(6(17:,7+,135(6(77,0($)7(5
(;7,1*8,6+$175(/($6(,6'(0$1'('$
)$,/('72
',6&+$5*(
$/$506+$//$1181&,$7(
7 $)7(5$7,0(('(/$<>7,0(56(&21'6
FUNCTION PERFORMED
$'-867$%/(@
'(0 25'(01(('72%(35(66('
72*(7+(5:,7+,1$63$12)6(&0$;72,1,$7(
(;7,1*8,6+$170$18$//<
EFFECT
AUDIBLE ALARM - FLAMMABLE GAS
TAG NO.
DXS 001
DXS 002
DXS 003
DAF 201, 202
DAGC 201,202
DAGT 201, 202
DES 201
XY 910,911
DEL 201, 204
DEL 202, 205
DEL 203, 206
DEL 203, 206
DXS 004
DXS 005
CAUSE
DESCRIPTION TAG NO. VOTING 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
1
FLAMMABLE GAS DETECTOR IN HVAC INTAKE DGC201, 202 1-O-O-2, 20% LEL 15 X X
1-O-O-2, 40% LEL 16 X X X X
CONFIRMED INPUT 2-O-O-2, 40% LEL 17 X X X
18
TOXIC H2S GAS DETECTOR IN HVAC INTAKE DGT201,202 1-O-O-2, 10ppm 19 X X HOLDS
1-O-O-2, 20ppm 20 X X X X
CONFIRMED INPUT 2-O-O-2, 20ppm 21 X X X
22 1. HVAC PHILOSOPHY.
GASOUS FIRE EXTINGUISHING SYSTEM 23 2. FEEDER SHUTDOWN PHILOSOPHY.
( NOTE 5) EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 201 1-O-O-1 24 X X
EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 202 1-O-O-1 25 X X
EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 201,202 2-O-O-2 26 X X X X XT X X
EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 203 1-O-O-1 27 X X
EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 204 1-O-O-1 28 X X
EXTINGUISHING CONTROL STATION( MANUAL RELEASED) DEM 203,204 2-O-O-2 29 X X X X XT X X
(NOTE 3 ) RELEASE CONFIRMED PSH 912 1-O-O-1 30 X X X X X
NORMAL/INHIBITED SWITCH INHIBITED DHS 201 1-O-O-1 31 X X X
NORMAL DHS 201 1-O-O-1 32 X X X
33
1. TRIP ONLY WHEN ANALYSER PLC PURGE FAILED & FLAMABLE GAS OR
HYDROGEN GAS INSIDE ANALSYER HOUSE IS IN HIGH ALARM.
2. TRIP ONLY WHEN LOW HOUSE PRESSURE DETECTED & FLAMABLE GAS OR
HYDROGEN GAS INSIDE ANALSYER HOUSE IS IN HIGH ALARM.
3 TRIP ONLY WHEN PURGE FAILURE & ANALYSER HOUSE PRESSURE LOW.
EFFECT
5 WHEN NO DETECTOR IS IN ALARM, THEN ONLY DALG WILL BE GREEN
FUNCTION PERFORMED
6 RESET(ANALSYER HOUSE POWER):- RESET BUTTON/SWITCH WILL BE
LOCATED OUTSIDE ANALSYER HOUSE ( WITH SHROUDING COVER) . THIS
SWITCH WEHN PRESSED AND IF NO DETECTOR IS IN ALARM THEN F&G PLC
WILL ENERGISE CONTACT DXS 812 & 813.
IF SINGLE ALARM EXISTS FOR ANY ANALYSER HOUSE DETECTOR EIXSTS ,
AND RESET SWITCH IS PRESSED DXS 812 & 813 WILL NOT ENERGISE.
EFFECT
TAG NO.
CAUSE
LIKELYHOOD CONSEQUENCE
Sl.N RISK SEVERITY BEFORE TREATMENT RISK TREATEMENT RISK SEVERITY AFTER TREATMENT
o. RISK AREA Risk Description Likelyhood Consequence Severity PLAN MANAGEMENT /ACTION PLAN Likelyhood Consequence Severity
Consequence
Risk Map Insignificant Minor Moderate Major Catastrophic
Before Treatment 1 2 3 4 5
< $2000 < $20000 < $200,000 <$ 500,000 >$1000,000
A Almost Certain
B Likely
Likelihood
C Moderate
D Unlikely
E Rare
Consequence
Risk Map Insignificant Minor Moderate Major Catastrophic
After Treatment 1 2 3 4 5
< $2000 < $20000 < $200,000 <$ 500,000 >$1000,000
A Almost Certain
B Likely
Likelihood
C Moderate
D Unlikely
E Rare
ANNEXURE- VII
RISK SUMMARY
BEFORE AFTER
Sl.No. RISK AREA Risk Description TREATMENT TREATMENT
Project Execution
centers(UK, Holland,India)
1 Project Execution synergy failure.
Under development products
(IS MCP, IS Heat )
certfication not available in
2 Conceptual Design time
Develeopment of serail link
3 Conceptual Design bet. FAP & PLC failure
UV/IR Detectors (DFX) shall be provided for all Compressor UV/IR minimum two
houses handling hydrocarbons (in addition to point detectors). numbers per compressor.
Flammable Gas Point Point Gas Detection shall be provided as follows: Point Devices to have 5 to Gas detector type to be Process Areas: Calibration to take into account
Detection - To cover pumps, including flare K.O.drum pumps, handling light 10m pitches. determined by checking the 1ooN - 20%LEL differing gas sensitivities of
hydrocarbons (C1 to C5 more than 25% of the stream). stream data. Once this is 1ooN - 60% LEL Catalytic and IR detectors.
- Process Cooling Towers- Top Platform. 2 devices in each HVAC done the detector/s should 2ooN - 60%LEL The gas that each detector
- Fuel Knock-Out Drums. intake. be calibrated for the HVAC Intakes: should be calibrated for, should
- Suction side of draft air blowers. predominant gas in the 1ooN - 20%LEL clearly be shown on the F&G
- LPG Pumps, Loading and Unloading Areas etc. location. 1ooN - 40%LEL detection layouts as well as on
- Gas Compressor Sheds. 2ooN - 40%LEL the Cause and Effect Charts.
- To cover HVAC intakes. (where N is more than 2) Wind rose to be taken into
account.
NB. 1. For distances >20m open path could be considered as an In HVAC application, length of
alternative, if clear line of sight can be obtained. the HVAC duct should be
2. Do not provide gas detectors in fin-fan cooler areas. considered for dumber closing
3. Do not provide gas detectos if mixture of gases present times.
contains C6+prod more than 75% of the stream).
Flammable Gas Detection- Optimum use would be on groups of pumps which are handling Short range: 5 to 40 meters. Gas detector type to be 1 LEL/m Final position to be confirmed
Open Path similar hydrocarbons (this would help on calibrating the detector for Medium Range: 40 to 120 determined by checking the 3 LEL/m with reference to the 3D model.
a specific gas). meters. stream data. Once this is
Long Range: 120 to 200 done the detector/s should
NB. For optimal use Open path gas detection should not be placed meters. be calibrated for the
for groups of just two pumps handling hydrocarbons. Point Gas predominant gas in the
detection should be used instead. location.
Hydrogen Gas Detection To be used in enclosed areas, where hydrogen would be expected Towards HVAC extract in Low Alarm: 10% LEL
to accumulate, rather than disperse. (i.e. battery rooms and battery rooms. High alarm: 25% LEL
compressor shelters).
To be used on the PSA unit on the Platformer.
2 detectors to be placed adjacent to each manway on the CCR
reactors.
Hydrogen compression Unit.
H2S Gas Detection On rotating equipment that are a potential source of H2S release. Electrochemical cell type. 2 detectors to each 10ppm LTEL Locations to be checked in
Stream data to determine requirements for any other areas. appropriate HVAC 20ppm STEL detail with a view to maximising
Detection to be considered for situations with more than 1000ppm intake. efficient spacing, but ensuring
(0.1% of stream). For all other areas, as adequate coverage.
Toxic Gas Detection requirements shall be suitably reviewed and dictated by leak source. Data sheets, detail layouts and
deleted if deemed so (this applies to repeat units). the 3-D model may be helpful.
Other Toxic Gas Detection According to appropriate studies carried out within the group.
Smoke Detection Indoor locations (Sub-stations, PIBs). Multisensor (HPO) detectors The sensitive elements of 1ooN - Alarm Ref. Departmental Work
within a horizontal 7.5m the detectors should lie 2ooN - Executive Instruction Doc. No. 25194-DWI-
Smoke detectors to be installed in rooms and air pockets. radius. within the range of 25mm 00106 for details.
Beam Detector coverage to to 600mm from the
be 7m radius from centre line ceiling.
of beam.
Point Heat Detection Generally rate compensated, used in buildings throughout the plant.50m2 per device. Where smoke detection is 1ooN - Alarm
ineffective, e.g. paint stores, 2ooN - Executive
kitchens, labs and soldering
rooms.
Linear Heat Electrical Rim seal on floating roof petrochemical storage tanks of less than Linear heat detection cable Alarm only
Detection 60m in diameter. on petrochemical storage
Alarm annunciation to be set for 100°C. tanks of less than 60m
diameter.
Pneumatic Heat Rim seal on floating roof tanks. To automatically initiate rim N/A
Automatic deluge on: seal foam system on tanks
- Storage tanks and spheres. of more than 60m in
- Deluge skids i.e. on pumps. diameter.
MAC Along central piperack and unit perimeters. External: 90m max. MACs should be coordinated
Other possible locations are: high level piperack walkways, some Internal: By main exit on with hydrant/safety equipment
escape routes (including door exits), hydrant/safety equipment right hand side (not on locations and escape routes as
locations as per engineer's judgment. hinge side of door) far as possible.
In cases where perimeter hydrants are sited at edge of paved area Elevation to be 1500mm They should also be coordinated
MACs should be located adjacent to these. above paving or as noted with those on adjacent process
otherwise. units, where appropriate.
F&G Beacon To be located in high noise areas (compressor shelters, Elevation to be 2400mm
intersections of escape routes etc.) above paving or as noted
otherwise by the
manufacturer or the local
conditions.
Gaseous Extiguishant Outside all points of entry to the protected area. All areas protected by Elevation to be 1400mm Ref. Departmental Work
Manual Discharge Gaseous Extiguishing above finished floor level. Instruction Doc. No. 25194-DWI-
Stations system. 00106 for details.
Gaseous Extiguishant Outside all points of exit from the protected area. Warning for gaseous Elevation to be 1500mm Ref. Departmental Work
Status Light systems. above finished floor level. Instruction Doc. No. 25194-DWI-
00106 for details.
Gaseous Extiguishant Pre- To be located in the protected area. All areas protected by Elevation to be 2400mm Ref. Departmental Work
Discharge Audible Alarm Gaseous Extiguishing above finished floor level. Instruction Doc. No. 25194-DWI-
system. 00106 for details.
PIB NETWORK
UCOM 1 UCOM 2 CABINET
RS30
ETHERNET/TCP-IP RS30
ETHERNET/TCP-IP
MODBUS
MODBUS SYSTEM
CABINET
MODBUS
MODBUS PORT 2
PORT 2 PORT 1
PORT 1
C U P C U P
P S S P S S SM(PLC) DCOM 2
1 I U 2 I U DCOM 1
1 2
1 2 Modbus
Modbus
RS232
RS232
Sixnet
Sixnet
Secondary
A A D D
Primary OP
D
I I I O O
RS-485
RS-485 Connection
Connection
Modbus
Modbus
NON IS Marshalling NON IS Marshalling DA1 Loop 1 DA2
IS Marshalling Cabinet XY(EXTINGUISHANT
Cabinet Cabinet SKID) RS485 RS485
Loop 2 RS232
DAS RS232
DA4
RS485 DA3
DES RS485
RS232 RS232
4-20mA
DAB
XY(DELUGE SKID) DA5 DA6
RS485 RS485
RS232
RS232
DAL
EBUS LON
CONTACT SIGNAL
DEL
DEM
DFI
NON-IS ADDREESSABLE LOOP
4-20mA DAF/DAGC/DAGT
IS ADDREESSABLE LOOP
4-20mA DSO DHS TO DA
TO DA
DFX NON IS MARSHALLING
CABINET
PSL(Used for deluge skid, RIM DAF/DAGC IS MARSHALLING LOOP OUT LOOP IN
4-20mA WSM * CABINET
seal/Foam skid
LOOP IN DMC
4-20mA DHF
LOOP OUT
DGH/DGT DMC
4-20mA
4-20mA
DHE DSO
DMC DHF
DGC
DMC
LEGENDS FOR NON ADDRESSABLE DEVICES: TYPES OF SM CARDS LEGENDS FOR ADDRESSABLE DEVICES:
SR.NO ABBREVIATION DESCRIPTION MODEL MAKE NON-IS IS SR NOS CARD TYPE DESCRIPTION SR.NO ABBREVIATION DESCRIPTION MODEL MAKE NON-IS ADD IS/NIS
1 DFI IR3 HC FLAME DETECTOR X3301 DETTRONICS NON-IS(Exd) 1 SAI-1620 ANALOG INPUT CARD FOR IS/NIS 1 DMC NON-IS MANUAL CALL POINT 55100-905APO APOLLO NON-IS
2 DFX UVIR FLAME DETECTOR X5200 DETTRONICS NON-IS(Exd) 2 SDI-1624 DIGITAL INPUT CARD FOR IS DEVICES 2 DMC IS MANUAL CALL POINT 55000-940APO APOLLO IS
3 DAB SOUNDER ASSERTA MEDC NON-IS(SAFE) 3 SDIL-1608 DIGITAL INPUT CARD FOR NIS DEVICES 3 DMC WHETHER PROOF MANUAL CALL 55000-950APO APOLLO NON-IS
4 DGT TOXIC GAS DETECTOR APEX ZELLWEGER NON-IS(Exd) DIGITAL OUTPUT CARD FOR NIS DEVICES 4 DSO NON-IS OPTICAL SMOKE 55000-600APO APOLLO NON-IS
5 DGH HYDROGEN GAS DETECTOR APEX ZELLWEGER NON-IS(Exd) 4 SDO-1624 BEACONS/SOUNDERS 5 DSO IS OPTICAL SMOKE 55000-640APO APOLLO IS
6 DGC COMBUSTIBLE IR GAS DETECTOR OPTIMA PLUS ZELLWEGER NON-IS(Exd) 5 SDOL-0424 DIGITAL OUTPUT CARD FOR NON IS -- XY 6 DSM MULTISENSOR 55000-885APO APOLLO NON-IS
7 DGX OPEN PATH GAS DETECTOR EXCEL ZELLWEGER NON-IS(Exd) 6 SDO-0824 DIGITAL OUTPUT CARD FOR IS DEVICES 7 DSX BEAM DETECTOR(5-50 MTRS) 55000-268APO APOLLO NON-IS
8 DMC MANUAL CALL POINT WR4072IS KAC IS 7 CP CONTROL PROCESSOR 8 DSX BEAM DETECTOR(50-100 MTRS) 55000-273APO APOLLO NON-IS
9 DSO IS OPTICAL SMOKE DETECTOR ORBIS APOLLO IS 8 USI UNIVERSAL SAFETY INTERFACE 9 DHF FIELD HEAT DETECTOR HD1BD190NG MEDC NON-IS
10 DHC IS HEAT DETECTOR HD1BI190NN MEDC IS 9 PSU POWER SUPPLY UNIT 10 DHF HEAT DETECTOR 55000-400APO APOLLO NON-IS
11 WSM WIND SPEED & DIRECTION OMC-150 PLUS MUIR MATHERSON IS 11 DA DETECTOR DELTA MODULE 251247.51 ELTEK
12 DHE LINEAR HEAT SENSING CABLE(DIGITAL) H9650 KIDDE IS 12 OP FIRE ALARM DISPLAY PANEL 251261.1 ELTEK
13 DAGT ONE WAY TOXIC BEACON-BLUE SM87HXBA MEDC NON-IS(EXD)
14 DAF/DAGC TWO WAY BEACON SM87SL2 MEDC NON-IS(EXD)
15 DAF/DAGC/DAGT 3 WAY BEACON SM87SL3 MEDC NON-IS(EXD)
16 DEL EXTINGUISHANT STATUS LIGHT SM87LU3 MEDC NON-IS(EXD)
17 DAL HIGH NOISE AREA BEACON XB4BE MEDC NON-IS(EXD)
18 DAS FIRE ALARM BELL SD 03SB MEDC NON-IS(EXD)
19 DES EXTINGUISHING SOUNDER DB3 MEDC NON-IS(EXD)
20 PSL PRESSURE SWITCH LOW IS
21 PSH PRESSURE SWITCH HIGH IS
EXTINGUISHANT SKID VENDOR
22 DEM MANUAL RELEASE PUSHBUTTON-FM200 IS
SCOPE OF SUPPLY
23 DHS AUTO/MANUAL SWITCH-FM200 IS
24 XY SOLENOID VALVE-EXTINGUISHANT SKID NON-IS (EXD)
DELUGE SKID VENDOR
25 XY
SOLENOID VALVE-DELUGE SKID SCOPE OF SUPPLY IS
NOTES:
1 NO OF DA SHALL BE AS PER THE PIB BOM
*NOTE: WIND SPEED DETECTOR IS INSTALLED ONLY IN CCC. 2 NO OF DETECTORS/OUTPUT DEVICES SHALL BE AS PER THE PIB BOM.
Customer : RELIANCE PETROLEUM LIMITED TITLE : TYPICAL PIB F&G SYSTEM ARCHITECTURE SH. 1 of 1 REV
Honeywell Project : JERP F&G AND CCTV SYSTEM
Honeywell Automation India Limited
Consultant : BECHTEL LIMITED DOC. NO. : 10/3/2008 0
Annexure- XI: Typical Overall F&G FO Network Architecture
Network Network
Color Network IMAC Server Plant Historian BackUp Server Management PC 2
Management PC 1 FO Switch
Printer
GPS 200.0.2.162
200.0.0.44
200.0.0.47 200.0.0.46 200.0.0.48
200.0.1.44
200.0.0.49 200.0.1.47 200.0.1.46 200.0.1.48
200.0.0.41 200.0.1.41
Dell Power Edge 2950 Dell Power Edge 2950 Dell Power Edge 2950 200.0.0.45
Dell Power Edge 2950 200.0.3.162 SSM Office
200.0.1.45
L STP
Operator
I cable
Station
200.0.2.171
U
FO
switch
200.0.0.19
STP 200.0.1.19
cable
200.0.3.171
RGB
Cable
Scada Server - L
Scada Server - Redundant I
Primary 200.0.0.129
U LVS
Operator Station's
Firewall
STP Operator
200.0.0.6 L Station 1
200.0.1.121 cable
200.0.0.121 I F
200.0.0.5 200.0.1.6
200.0.0.6
200.0.2.169
U 200.0.0.23
200.0.1.5 200.0.1.6 S
200.0.0.130
FO Switch 200.0.1.23
200.0.0.13 200.0.0.14 FO
200.0.0.15 Dell Power Edge 2950 Backbone 1
200.0.1.13
Backbone To Switch for CCTV switch
200.0.1.14 200.0.1.15 Dell Power Edge 2950 Dell Power Edge 2950
Redundant Primary IP based Modem for 200.0.2.163
Dell Precision 490 network LVS
200.0.3.169
200.0.1.24
L STP
200.0.3.163 Operator
FO Switch cable
I Station 2
U
200.0.1.50 Redundant Terminal
Server for PA STP Operator
200.0.3.4
L Station 1
cable
200.0.0.50 system interface I F
200.0.2.170
200.0.2.4
FO Switch U 200.0.0.27 S
200.0.1.27
FO 2
switch
LVS
200.0.0.28
200.0.3.170
200.0.1.28
L STP
Operator
cable
I Station 2
U
LEGENDS
LIU LIU LIU LIU LIU LIU
200.0.4.42
RS30
switch
STP
cable
200.0.0.103
200.0.1.103
FAP
with DA
Remote I/O
Remote Node
SH. 1 of 1 REV