Prosensesubleveltrans
Prosensesubleveltrans
Prosensesubleveltrans
Transmitters
Submersible Level Transmitters
The ProSense SLT series submersible level sensors provide continuous liquid level measurement by
sensing the hydrostatic pressure produced by the height of liquid above the sensor and providing a
4-20 mA output signal compatible with PLCs, panel meters, data loggers, and other electronic
equipment. The shielded cable with atmospheric vent tube and a tough polyurethane jacket
incorporating an exclusive “water block” liner beneath the jacket is attached to the sensor using an
over-molding process that prevents moisture intrusion. The SLT1 series has a slim 1-inch diameter housing and a ported
bullet nose cap for protection of the sensor diaphragm. The SLT2 series features a large 2.75 inch diameter PTFE flexible
diaphragm surrounded by a 316 stainless steel non-fouling protective cage. Accessories include a desiccant vent filter,
aneroid bellows, junction boxes, and replacement nose caps.
Applications
•• Lift station monitoring •• Pump control
•• Liquid level in vented tank •• Slurry tank liquid level
•• Landfill leachate monitoring •• • Wastewater
•• Construction by-pass pumping
Part No. SLT2-005-L30 •• Dewatering
SLT1-015-L60 0–15 psig (34.6 ftWC) 60ft (18.3 m) 316 Stainless steel diaphragm / 3.4
Ported POM (polyoxymethylene)
SLT1-020-L60 0–20 psig (46.1 ftWC) 60ft (18.3 m) nose cap 3.4
* It is required that any excess cable length be accommodated in a service loop and that the cable NOT be shortened as this will void the warranty. If longer transmitter cable is needed,
terminate the sensor in an SLT-JB1 or SLT-JB2 junction box and run standard non-vented instrumentation cable between the junction box and the measuring electronics.
Thermal Error ±0.1% FS/°C (maximum allowable deviation from the best fit straight line due to a change in temperature)
Conductor Size 22AWG (0.33 mm²) spiral tinned copper wire foil shield with 20AWG (0.52 mm²) drain wire
Vent Tube PUR (polyethylene) 0.016 in (0.41 mm) ID
Cable Seal Molded PUR (polyurethane)
Certifications / Agency
UL (E197886), CE, RoHS, FM (3036412)
Approvals
* Combined effects of non-linearity, hysteresis and repeatability, best fit straight line method.
Dimensions
inches [mm]
SLT1 Series
SLT2 Series
Wiring
1500
(V+) – 9V
1250 RL max =
20 mA
1000
SLT1 & SLT2 Series Wiring Connection
750
4–20 mA output (22AWG conductors in a shielded cable with vent tube)
500
250 Operating + Excitation Red
9V
Area
0 - Excitation Black
0 10 20 30
Loop Power Supply Voltage Shield Drain Wire
Dimensions
inches [mm]
Always install a vent filter (desiccant) or aneroid bellows immediately after transmitter installation. Failure to use one or the other could result in
premature failure of the transmitter, which would not be covered by warranty.
Application
•• If longer transmitter cable is needed, terminate the sensor in an SLT-JB1 or
SLT-JB2 junction box and run standard instrumentation cable between the
junction box and the measuring electronics.
Dimensions
inches [mm]
Part No. SLT-JB1
Dimensions
inches [mm]
Dimensions
inches [mm]