Multicore Unscreened Cable: Specifications
Multicore Unscreened Cable: Specifications
Multicore Unscreened Cable: Specifications
Specifications:
Conductor : Plain copper, solid, class 1 (cross-section ≤2.5mm2)
Plain copper, stranded wire, class 2 (cross-section ≥4mm2)
Insulation : PVC compound, CPC (circuit protective conductor) conductor insulated
Sheath : PVC compound, flat shape
Colour : Grey
Functional characteristics:
Rated voltage Uo/U : 300/500 V
Operating Temperature : -10°C to 70°C (without mechanical shocks)
Max. Short circuit temperature : 160°C
Standards:
Construction : BS 6004
Flame propagation : BS EN 60332-1-2
Installation conditions
Min. Installation Temperature : 5°C
Recommended min. Bending Radius : 4 times the cable diameter for the single pole type and 6 times the cable diameter for
the smaller dimension for the flat type
Recommended max. Tensile Stress : 50 N/mm² of the cross-section of the copper
Approx. Average Insulation Average Sheath Max. Max. Electrical Approx. Cable
Formation
Conductor Thickness Thickness External Resistance at 20°C weight
n° × mm²
mm mm mm mm Ω/km kg/km
1×1+1 1.1/1.1 0.6 0.9 4.8 × 6.0 18.1/18.1 45
1 × 1.5 + 1 1.4/1.1 0.7 0.9 5.3 × 6.6 12.1/18.1 49
2×1+1 1.1/1.1 0.6 0.9 4.8 × 8.7 18.1/18.1 68
2 × 1.5 + 1 1.4/1.1 0.7 0.9 5.3 × 9.7 12.1/18.1 83
2 × 2.5 + 1.5 1.8/1.4 0.8 1 6.2 × 11.7 7.41/12.1 121
2 × 4 + 1.5 2.4/1.4 0.8 1 6.9 × 13.1 4.61/12.1 170
www.element14.com
www.farnell.com
www.newark.com
www.cpc.co.uk
Page <1> 29/06/16 V1.0
Multicore Unscreened Cable
Approx. Average Insulation Average Sheath Max. Max. Electrical Approx. Cable
Formation
Conductor Thickness Thickness External Resistance at 20°C weight
n° × mm²
mm mm mm mm Ω/km kg/km
2 × 6 + 2.5 3.1/1.8 0.8 1.1 7.8 × 15.0 3.08/7.41 235
2 × 10 + 4 4/2.4 1 1.2 9.5 × 18.9 1.83/4.61 370
2 × 16 + 6 4.9/3.1 1 1.3 10.8 × 21.9 1.15/3.08 530
3×1+1 1.1/1.1 0.6 0.9 4.8 × 11.4 18.1/18.1 90
3 × 1.5 + 1 1.4/1.1 0.7 0.9 5.3 × 12.9 12.1/18.1 112
3 × 2.5 + 1.5 1.8/1.4 0.8 1 6.2 × 15.3 7.41/12.1 160
Important Notice : This data sheet and its contents (the “Information”) belong to the members of the Premier Farnell group of companies (the “Group”) or are licensed to it. No licence is granted
for the use of it other than for information purposes in connection with the products to which it relates. No licence of any intellectual property rights is granted. The Information is subject to change
without notice and replaces all data sheets previously supplied. The Information supplied is believed to be accurate but the Group assumes no responsibility for its accuracy or completeness, any
error in or omission from it or for any use made of it. Users of this data sheet should check for themselves the Information and the suitability of the products for their purpose and not make any
assumptions based on information included or omitted. Liability for loss or damage resulting from any reliance on the Information or use of it (including liability resulting from negligence or where the
Group was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict the Group’s liability for death or personal injury resulting from its negligence.
pro - POWER is the registered trademark of the Group. © Premier Farnell plc 2012.
www.element14.com
www.farnell.com
www.newark.com
www.cpc.co.uk
Page <2> 29/06/16 V1.0