TN Nail Salon: 9270 S Rainbow BLVD CC Enterprise-89139 APN 176-23-210-006
TN Nail Salon: 9270 S Rainbow BLVD CC Enterprise-89139 APN 176-23-210-006
other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are sealed, signed, and
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for their use
[email protected]
702.749.0038
TN NAIL SALON
9270 S RAINBOW BLVD seal:
CC ENTERPRISE-89139
APN 176-23-210-006
04/13/2023
consultant:
TN NAILS SALON
SQ. SQUARE
CODES, REGULATIONS AND ORDINANCES OF THE GOVERNING INTERIOR FINISH APPLICATION. CONC. CONCRETE IN. INCH
STD. STANDARD ELECTRICAL LAYOUT
AGENCY HAVING JURISDICTION OVER THE PROJECT SUCH CONST. CONSTRUCTION INSUL. INSULATION
INT. INTERIOR STL. STEEL E000 ELECTRICAL NOTES AND SPECS
FIRE PROTECTION APPLICABLE CODES, ETC. ARE THOSE, WHICH ARE IN EFFECT AT THE 20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND CONT. CONTINUOUS
COVER SHEET
TIME THE PERMIT APPLICATION FOR THE PROJECT IS RECORDED. INSTALLING ANY "BUILDING STANDARDS" FIXTURES AND FINISHES IN DBL. DOUBLE INV. INVERT
J.B. JUNCTION BOX SUSP. SUSPENDED OCCUPANCY LOAD CALCULATIONS AS PER TABLE 1004.5 OF THE 2018 IBC E102 NEW POWER PLAN
ADDITION TO THOSE NOTED ON PLAN. DET. DETAIL TREADS
JT. JOINT T.
6. EACH SUB-CONTRACTOR IS CONSIDER A SPECIALIST IN HIS DIA.,R DIAMETER TOP AND BOTTOM S.F. PER OCC. OCCUPANT
DIAG. DIAGONAL LAM. LAMINATE T. & B. ROOM ROOM NAME
RESPECTIVE FIELD/TRADE AND SHALL (BEFORE SUBMISSION OF BID 21. CONTRACTOR SHALL INSTALL REQUIRED FIRE ALARM SYSTEM. T. & G. TONGUE AND GROOVE AREA GROSS/NET LOAD
DIM. DIMENSION LAV. LAVATORY
OR PERFORMANCE OF WORK) NOTIFY THE GENERAL CONTRACTOR LT. WT. LIGHT WEIGHT T.O.C. TOP OF CONCRETE 100 LOBBY 396.77 SQ FT 15 26.4
DISP. DISPENSER
CC ENTERPRISE-89139
DN. DOWN M.H. MAN HOLE 101 NAILS ROOM 1329.85 SQ FT 150 8.86
APN 176-23-210-006
DRAWINGS OR IN THE SPECIFICATIONS WHICH CANNOT BE FULLY DEPARTMENT. DWG. DRAWING M.O. MASONRY OPENING THRU. THROUGH 102 73.80 SQ FT 0 0
RESTROOM
GUARANTEED OR CONSTRUCTED AS DESIGNED AND/OR DETAILS. E.J. EXPANSION JOINT MACH. MACHINE TYP. TYPICAL 45.21 SQ FT 0
103 HALL 0
23. ALL EQUIPMENT AND FURNISHING SHALL BE AS NOTED. E.W. EACH WAY MANUF. MANUFACTURER UR. URINAL
104 HALL 40.08 SQ FT 0 0
7. DUE TO REPROGRAPHIC PROCESSES, THESE PLANS MAY NOT BE E.W.C. ELECTRIC WATER COOLER MAX. MAXIMUM V.C.P. VERIFIED CLAY PIPE
ACCURATE TO SCALE. ALL DIMENSIONS SHALL TAKE PRECEDENCE 24. INSTALL (ADDITIONAL) BLOCKING IN WALLS AS REQUIRED FOR EA. EACH MECH. MECHANICAL V.C.T. VINYL COMPOSITION TILE 105 WAX ROOM 78.27 SQ FT 150 0.52
AVER SCALE SHOWN AND IN NO CASE SHALL WORKING DIMENSION INSTALLATION OF ANY AND ALL ACCESSIBILITY DEVISES I.E. GRAB BARS ETC. EL. ELEVATION MET. METAL VERTICAL 106 LASH ROOM 83.11 SQ FT 150 0.54
Project Title :
VERT.
BE SCALED FROM PLANS, SECTIONS, ELEVATIONS OR DETAILS. PER CABO/ANSI A117.1. ELECT. ELECTRICAL MIN. MINIMUM W/ WITH 107 RESTROOM 73.80 SQ FT 0 0
sheet title:
ENAM. ENAMEL NEC'Y. NECESSARY W.C. WATER CLOSET 108 BREAK ROOM 309.07 SQ FT 15 20.6
8. THE STRUCTURAL, MECHANICAL PLUMBING AND ELECTRICAL EQ. EQUAL NOM. NOMINAL W.F. WIDE FLANGE
EQUIP. EQUIPMENT WATERPROOF TOTAL 2430 SF 56.92 OCC: 57 OCC
SCOPE OF WORK
DRAWINGS ARE SUPPLEMENTARY TO THE ARCHITECTURAL O.C. ON CENTER W.P.
DRAWINGS. SHOULD THERE BE ANY DISCREPANCY BETWEEN THE EX. EXISTING O.D. OUTSIDE DIAMETER W.W.F. WELDED WIRE FABRIC NEW CONSTRUCTION OF A NAIL SALON THAT IS LOCATED IN SUITE 220
VARIOUS DRAWINGS, IT SHALL BE BROUGHT TO THE DEVELOPER'S EXP. EXPANSION OPG. OPENING WATER-RES. WATER-RESISTANT AND 230. THIS INCLUDES A NEW LASH ROOM, NEW NAIL ROOM, WAX
ATTENTION FOR CLARIFICATION. EXP. JT. EXPANSION JOINT PARTN. PARTITON WD. WOOD
ROOM, BREAK, LOBBY AND RESTROOM. INCLUDES ARCHITECTURAL, Revisions :
MIN. FIXTURE REQUIRED MECHANICAL, PLUMBING, ELECTRICAL AND STRUCTURAL.
9. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER'S
REPRESENTATIVE FOR INSTALLATION OF SPECIAL MANUFACTURING AS PER SECTION 2902.1 OF THE 2018 IBC MINIMUM NUMBER OF PLUMBING LOCATION MAP NO SCALE
EQUIPMENT NOT SHOWN IN THESE DRAWINGS. THE CONTRACTOR BUILDING CODES : BUILDING CODE OF LAS VEGAS FACILITIES
SHALL VERIFY EQUIPMENT LOCATIONS WITH THE OWNER'S 2018 IBC, UPC, UMC, IECC 57 FOR MALE AND FEMALE
REPRESENTATIVE AND/OR EQUIPMENT MANUFACTURER PRIOR TO 2017 NEC MIN FIXTURE REQUIRED
FORMING THE SLAB, FOR PROPER SIZE AND LOCATION OF AND SOUTHERN NEVADA CODE AMENDMENTS FIXTURE MALE FEMALE PROVIDED/REQUIRED
FOUNDATION DEPRESSIONS, DRAINS, AND WARPS. WATER CLOSET 1 PER 50 1 PER 50 2/2
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD LAVATORIES 1 PER 80 1 PER 80 2/2 OND
RD
DIAM
10. UNLESS OTHERWISE NOTED, MANUFACTURER'S ITEMS SHALL SURVEY AND THE PLANS IN RECORDS. DRINKING FOUNTAINS - - - BLUE
BE PROVIDED. CONTRACTOR SHALL VERIFY ANY SUBSTITUTIONS EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN SERVICE SINK -
WITH THE OWNER AND DEVELOPER PRIOR TO BID AND/OR - -
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF
INSTALLATION. ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
REDWOOD ST
11. WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
Issued Date: 04/13/2023
RAINBOW BLVD
ARCHITECT TO COORDINATE SUCH DISCREPANCY.
FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME AS FOR
OTHER SIMILAR FIRST CLASS WORK; FOR THE TRADE INVOLVED THE PROJECT Project No.: 23060-TNS
DEVELOPER SHALL BE NOTIFIED IMMEDIATELY, IN WRITING, IF ANY
ALTERNATE NON-STANDARD OR UNTESTED METHOD(S) PROPOSED.
LOCATION Drawn By: AH
Checked By: EM
Sheet No:
dated.
SERENE AVE
A000
1 OF 1
and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are sealed, signed, and
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for their use
[email protected]
ZONING CLASSIFICATION: ZONING CLASSIFICATION:
GENERAL COMMERCIAL (C-2) GENERAL HIGHWAY FRONTAGE (H-2)
702.749.0038
JURISDICTION: CC ENTERPRISE - 89139 JURISDICTION: CC ENTERPRISE - 89139
REDWOOD ST
RAINBOW BLVD
PARCEL: 17623101040
OWNER NAME(S): USA
SITE ADDRESS: 0
ZONING CLASSIFICATION:
GENERAL HIGHWAY FRONTAGE (H-2)
PARCEL: 17623201017 PARCEL: 17623201002 JURISDICTION: CC ENTERPRISE - 89139
OWNER NAME(S): KULAR GULZAR SINGH OWNER NAME(S): NEEDHAM HOWARD J & CHRISTINE S
SITE ADDRESS: 0 SITE ADDRESS: 0
ZONING CLASSIFICATION: ZONING CLASSIFICATION:
seal:
GENERAL COMMERCIAL (C-2) GENERAL HIGHWAY FRONTAGE (H-2)
JURISDICTION: CC ENTERPRISE - 89139 JURISDICTION: CC ENTERPRISE - 89139
SERENE AVE
PROJECT
LOCATION N D RD
U E D IAMO
B L
04/13/2023
consultant:
REDWOOD ST
ZONING CLASSIFICATION:
LOCAL BUSINESS (C-1)
JURISDICTION: CC ENTERPRISE - 89139
△=77° 35' 40"
R=54.00'
L=73.13'
T=43.41'
RAINBOW BLVD
N 0° 16' 11" E
121.90'
PROYECT
LOCATION
PARCEL: 17623201019
TN NAILS SALON
OWNER NAME(S): RON AVI ETAL AND ZITRON ISAAC
SITE ADDRESS: 0
ZONING CLASSIFICATION:
633.21'
SITE PLAN
00°
Project Title :
sheet title:
PARCEL:
N 0° 16' 01" E
17623210006
159.06'
OWNER NAME(S):
RAINBOW & BLUE DIAMOND SOUTHEAST L L C
SITE ADDRESS: 9270 S RAINBOW Revisions :
ZONING CLASSIFICATION:
GENERAL COMMERCIAL (C-2)
JURISDICTION:
CC ENTERPRISE - 89139 PARCEL: 17623201012 PARCEL: 17623201013
OWNER NAME(S): DAVIS BROTHERS INVESTMENTS LTD OWNER NAME(S): DAVIS BROTHERS INVESTMENTS LTD
SITE ADDRESS: 6720 W SERENE AVE SITE ADDRESS: 6720 W SERENE AVE
△=90° 37' 46" ZONING CLASSIFICATION: ZONING CLASSIFICATION:
R=54.00'
△=89° 27' 35" LIGHT MANUFACTURING (M-1) LIGHT MANUFACTURING (M-1)
L=85.42'
R=20.00' JURISDICTION: CC ENTERPRISE - 89139 JURISDICTION: CC ENTERPRISE - 89139
T=54.60'
L=31.23'
499.87' T=19.81'
S 0° 21' 35" E
S 89° 35' 13" W 5.00'
Issued Date: 04/13/2023
Drawn By: AH
Sheet No:
dated.
SITE PLAN A101
1 NTS 1 OF 1
architecture - planning - 3d imagination
LEGEND
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
GENERAL NOTES
EXISTING WALL NOT TO BE MODIFIED
1. GRAY SCALE ELEMENTS REPRESENTS OBJECTS NOT TO BE MODIFIED
[email protected]
OR ARCHITECT TO RESOLVE SUCH DISCREPANCY
4. INSTALL, PATCH AND REPAIR NEW DRYWALL, WHERE REQUIRED, GENERAL
702.749.0038
CONTRACTOR MUST IDENTIFY
SUCH AREAS PRIOR ISSUE A PROPOSAL TO CLIENT TO AVOID OMMITIONS IN THE
ESTIMATE
seal:
04/13/2023
CONSULTANT:
SUITE 240
TN NAILS SALON
SUITE 220 & 230
9270 S RAINBOW BLVD
DEMO PLAN NOTES THE EXISTING BUILDING IF THE INSPECTION INDICATES THAT THE STRUCTURAL NON-RATED) AS REQUIRED TO ALL AREAS WITHIN THE CONSTRUCTION LIMIT LINES
CC ENTERPRISE-89139
APN 176-23-210-006
INTEGRITY MAY BE IMPAIRED, NOTIFY THE GENERAL CONTRACTOR/ENGINEER DURING THE CONSTRUCTION PROCESS. LOCATIONS AND PROVISIONS TO CONTROL
*THESE NOTES APPLY TO ALL DEMOLITION DRAWINGS AND TO ALL CONTRACTOR AND/OR IMMEDIATELY. AIRBORNE DUST SHALL BE COORDINATED WITH THE OWNER, FACILITIES-BUILDING
SUB-CONTRACTORS THAT WORK ON THIS PROJECT. 8. PRIOR TO ANY DEMOLITION, THE CONTRACTOR SHALL COORDINATE BRACING AND MANAGER, AND GENERAL CONTRACTOR PRIOR TO START OR WORK. COORDINATE
MAINTAIN THE STRUCTURAL INTEGRITY OF THE REMAINING ELEMENTS OF THE ADDITIONAL FILTRATION OF EXTERIOR AIR INTAKES TO MECHANICAL SYSTEMS.
1. ALL WORK SHALL CONFORM WITH ALL THE PROVISIONS OF THE 2018 IBC BUILDING AND ITS SYSTEMS AS REQUIRED THE CONTRACTOR SHALL BE RESPONSIBLE 14. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL
(INTERNATIONAL BUILDING CODE), NEC (NATIONAL ELECTRICAL CODE), UPC (UNIFORM FOR THE SUPPORT OF ADJACENT STRUCTURES DURING DEMOLITION AND NEW PROTECTION FOR POLLUTION CONTROL. THOROUGHLY CLEAN ADJACENT AREAS OF
project title :
PLUMBING CODE), UMC (UNIFORM MECHANICAL CODE), INTERNATIONAL FIRE CODE, CONSTRUCTION WORK THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING, DUST, DIRT AND DEBRIS CAUSED BY DEMOLITION WORK. BEFORE NEW WORK BEGINS,
IECC (INTERNATIONAL ENERGY CONSERVATION CODE) AND ALL APPLICABLE CODE SCAFFOLDING, ETC. WHICH ARE NECESSARY TO PREVENT COLLAPSE, SUBSIDENCE, RETURN ADJACENT AREAS TO CONDITION FOUND PRIOR TO START OF DEMOLITION
sheet title :
ORDINANCES HAVING JURISDICTION. DEFLECTION OR ANY OTHER TYPE OF DAMAGE REPAIR SPRAY FIREPROOFING DAMAGED WORK.
2. GRAYSOLID LINES ON DEMO PLANS REPRESENT WALLS, DOORS, SOFFITS, CASEWORK, DURING DEMOLITION WORK TO ITS REQUIRED ASSEMBLY AND FIRE RATING. 15. ALL CONSTRUCTION AREAS, REMOVAL TRAFFIC PATTERN AREAS AND ASSOCIATED
ETC TO BE REMOVED. (UNLESS NOTED OTHERWISE) PATCH & REPAIR EXISTING 9. PROVIDE A SECURE PROJECT SITE AT ALL TIMES. MAINTAIN ACCESS TO EXITS AND EXIT WORK AREAS SHALL BE KEPT CLEAN OF DEBRIS BY THE CONTRACTOR DAILY.
ADJOINING AREAS TO REMAIN. STAIRS AT ALL TIMES. MAINTAIN ALL EXISTING LIFE SAFETY ITEMS THROUGHOUT 16. PROTECT FROM DEMOLITION AND RECONSTRUCTION DEBRIS, ALL "EXISTING TO
3. UNLESS NOTED OTHERWISE "SOLID DARK ITEMS" ARE EXISTING AND ARE TO REMAIN. DEMOLITION AND NEW CONSTRUCTION. FIRE ALARM AND SMOKE DETECTION SYSTEM REMAIN" FIXTURES, EQUIPMENT, AND ITEMS REQUIRED TO REMAIN IN PLACE DURING
4. CONTRACTOR SHALL COORDINATE ARCHITECTURAL DEMOLITION DRAWINGS AND
NOTES WITH MECHANICAL, ELECTRICAL, FIRE PROTECTION AND PLUMBING DRAWINGS
SHALL REMAIN OPERATIONAL AT ALL TIMES. PROTECT SMOKE DETECTORS AS
REQUIRED AND IN CONFORMANCE WITH CODES AND LOCAL AUTHORITIES HAVING 17.
AND THROUGHOUT CONSTRUCTION.
REFER TO REMAINING DRAWINGS FOR RECONSTRUCTION ALL CONTRACTORS SHALL
Revisions :
AND NOTES. JURISDICTION. NOTIFY OWNER AND GENERAL CONTRACTOR 48 HOURS PRIOR TO COORDINATE THE DEMOLITION AND RECONSTRUCTION WORK TO BE ASSURED THAT 1
5. CONTRACTOR AND SUB-CONTRACTORS SHALL BE RESPONSIBLE FOR VISITING THE SITE TURNING OFF ANY UTILITY ITEMS OR LIFE SAFETY ITEMS. THEIR WORK IS COMPLIMENTARY TO THE WORK OF ALL OTHER CONTRACTORS AND
TO BECOME FAMILIAR WITH AND VERIFY THE EXISTING CONDITIONS PRIOR TO 10. SUB-CONTRACTOR SHALL REMOVE ALL WIRING DETERMINED TO BE DISCONNECTED COMPLETE IN ALL RESPECTS. 2
DEMOLITION THESE DEMOLITION DRAWINGS SHALL SERVE TO AID THE AND/OR ABANDONED, AND REMOVE ALL CONDUIT AND JUNCTION BOXES 18. CONTRACTOR SHALL REVIEW ALL ITEMS TO BE DEMOLISHED WITH OWNER TO IDENTIFY
SUB-CONTRACTOR IN THE EVALUATION OF THE EXTENT OF DEMOLITION-BUT SHALL NOT DETERMINED TO BE EMPTY AND NOT INTENDED TO BE USED DURING THE ANY ITEMS TO BE SALVAGED PRIOR TO START OF DEMOLITION. 3
BE HELD TO BE ALL INCLUSIVE NOTIFY THE ARCHITECT IMMEDIATELY IN WRITING OF RECONSTRUCTION PHASE. IF SUCH ITEMS ARE TO BE RE-USED, PATCH, REPAIR, 19. CONTRACTOR TO PATCH AND REPAIR ANY AND ALL DAMAGES CREATED BY
ANY DEVIATION FROM CONTRACT DOCUMENTS NECESSITATED BY FIELD CONDITIONS RE-ROUTE & RE-WIRE AS REQUIRED FOR CONTINUED USE. DEMOLITION. COORDINATE WITH OWNER/TENANT THE REMOVAL, STORAGE AND 4
OR ITEMS NOT COVERED. 11. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH AND MATCH SURFACES RE-USE OF EXISTING FURNITURE.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION, FOR INSTALLATION OF DISTURBED BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES. INSTALL 20. THE CONTRACTOR RESPONSIBLE FOR GENERAL DEMOLITION WORK SHALL COORDINATE 5
NEW CONSTRUCTION, AND AS NECESSARY TO FULFILL THE PURPOSE AND INTENT OF PARCHING TO MATCH ADJACENT WORK IN FINISH, STRUCTURAL QUALITIES, COURSING ANY AND ALL HAZARDOUS MATERIAL REMOVAL WITH THE OWNER. CONTRACTOR
THE FINISHED WORK WHETHER OR NOT IT IS SPECIFICALLY SHOWN OR NOTED IN OF MASONRY, AND/OR OTHER CHARACTERISTICS. PATCH SURFACES. SHALL STOP WORK AND INFORM OWNER IMMEDIATELY IN WRITING OF ANY 6
BUILDING CODES : BUILDING CODE OF LAS VEGAS THESE DOCUMENTS. THE SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ITEMS 12. CONTRACTOR TO COMPLY WITH FIRE RATINGS, SMOKE-TIGHT RATINGS, ACOUSTICAL HAZARDOUS MATERIAL ENCOUNTERED OR THOUGHT TO BE HAZARDOUS MATERIAL
2018 IBC, UPC, UMC, IECC CALLED TO BE REMOVED THROUGHOUT THE ENTIRE SET OF DOCUMENTS REPORT ANY CRITERIA AND OTHER PERFORMANCE CRITERIA INDICATED OR REQUIRED BY LOCAL THE OWNER, AFTER RECEIVING WRITTEN NOTICE SHALL INSTRUCT THE CONTRACTOR
2017 NEC
AND SOUTHERN NEVADA CODE AMENDMENTS
DISCREPANCIES WHICH MAYBE FOUND TO ARCHITECT BEFORE PROCEEDING WITH
WORK IN SUCH AREA(S). 13.
CODES.
ALL WORK SHALL BE DONE IN PROTECTED SPACE. SUBCONTRACTORS SHALL BE
ON HOW TO PROCEED. ALL HAZARDOUS MATERIAL REMOVAL WILL BE PERFORMED BY
A LICENSED REMOVAL CONTRACTOR. Issued Date: 04/11/2023
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
GENERAL NOTES
EXISTING WALL NOT TO BE MODIFIED
1. GRAY SCALE ELEMENTS REPRESENTS OBJECTS NOT TO BE MODIFIED
[email protected]
OR ARCHITECT TO RESOLVE SUCH DISCREPANCY INDICATES ROOM/SPACE NAME.
4. INSTALL, PATCH AND REPAIR NEW DRYWALL, WHERE REQUIRED, GENERAL ROOM/SPACE NUMBER
702.749.0038
CONTRACTOR MUST IDENTIFY
SUCH AREAS PRIOR ISSUE A PROPOSAL TO CLIENT TO AVOID OMMITIONS IN THE 0 KEY NOTE FLOOR
ESTIMATE
RESTROOM 07
107
NEW WALL SCHEDULE
KEYNOTES 06
WALL TYPE WALL IMAGE DESCRIPTION NEW LUMINOUS SPA PEDICURE MEITHA (OR SIMILAR)
02 HALL
A 104
EXISTING WALL. NOT TO BE MODIFIED NEW WATER CLOSET
NEW CHAIR 3
NAILS ROOM
DOOR SCHEDULE
A501 101
BREAK ROOM
NEW HAND SINK 108
DOOR FRAME REMARKS
NEW DECORATIVE WALL 5X8'
WD
y las columnas decorativas?
TN NAIL SALON
SUITE 220 & 230
9270 S RAINBOW BLVD
CC ENTERPRISE-89139
APN 176-23-210-006
project title :
sheet title :
Revisions :
1
Drawn By: AH
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD
SURVEY AND THE PLANS IN RECORDS. Checked By: EM
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF Sheet No:
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY. A202
2 OF 4
architecture - planning - 3d imagination
LEGEND
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
GENERAL NOTES
EXISTING WALL NOT TO BE MODIFIED
1. GRAY SCALE ELEMENTS REPRESENTS OBJECTS NOT TO BE MODIFIED
[email protected]
5'-8 11/32"
OR ARCHITECT TO RESOLVE SUCH DISCREPANCY
4. INSTALL, PATCH AND REPAIR NEW DRYWALL, WHERE REQUIRED, GENERAL
7'-5 3/16"
7'-11 3/32"
8'-9 1/32"
702.749.0038
9'-0 11/16"
CONTRACTOR MUST IDENTIFY
SUCH AREAS PRIOR ISSUE A PROPOSAL TO CLIENT TO AVOID OMMITIONS IN THE
ESTIMATE 7'-5 13/32"
8'-11 1/8"
4'-6"
3'-5 1/32"
20'-0"
12'-0"
4'-3 19/32"
1'-3 29/32" 6'-0 5/8"
4'-6"
7'-6 1/16"
9'-9 3/32"
seal:
11'-11 15/16"
39'-4 15/16"
28'-0 1/4"
16'-8 1/2"
8'-4 3/16"
4'-0 1/4"
9'-9 3/32"
7'-6 1/16"
04/13/2023
6'-5 11/32"
4'-11 31/32"
4'-6 1/4"
CONSULTANT:
3'-5 9/32"
CREATIVE BULDERS, INC
20'-0"
4'-6"
32'-7 17/32"
9'-0 11/16"
7'-11 3/32"
7'-5 3/32"
5'-8 11/32"
LICENSE #0060836 B-2
42'-3 7/32" LICENSE LIMIT $600,000
TN NAILS SALON
SUITE 220 & 230
9270 S RAINBOW BLVD
CC ENTERPRISE-89139
APN 176-23-210-006
project title :
sheet title :
Revisions :
1
Drawn By: AH
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD
SURVEY AND THE PLANS IN RECORDS. Checked By: LFP
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF Sheet No:
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY. A203
2 OF 4
and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are sealed, signed, and
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for their use
[email protected]
WOMEN MEN REST ROOMS
A CLEAR FLOOR SPACE AT WATER CLOSET PER
esta simbologia acomodala ICC/ANSI A 117.1-2009 604.3
702.749.0038
NOTE: B CLEAR FLOOR SPACE AT DOOR PER ICCI/ANSI A
ENTRY DOORS TO HAVE A SYMBOL 117.1-2009 sect. Fig. 404.2.3.1
INDICATING SEX, MEN: EQUILATERAL
TRIANGLE 12" PER SIDE, WOMEN: 12" C CLEAR FLOOR SPACE AT LAVATORY 30"X48" FOR
DIA. CIRCLE - SYMBOL TO BE |" FORWARD APPROACH AND MAY EXTEND A
THICK, CONTRASTING COLORS AND MAXIMUM OF 25" UNDER THE LAVATORY
D
MOUNTED @ 60" ABOVE FINISHED 48"
C
FLOOR.
30" Cmin. D WHEEL CHAIR TURNING SPACE 60" DIAMETER
2/A204
1/A204
A A
60"
C
C
A
A
CIRCLE OR T-SHAPE PER ICCI/ANSI A 117 .1-2009
60"
60" Fig. 303.3
R/R 30" min.
D D
B
SIGN 60" 48" NOTE: THE MEASUREMENTS HERE PROVIDED ARE THE
SOLID RESULT OF A FIELD SURVEY AND THE PLANS IN
CORE B B
RECORDS. EACH CONSULTANT IS RESPONSIBLE TO
TAKE THEIR OWN MEASUREMENTS TO AVOID ANY
PULL CONFLICTS WITH THEIR WORK. IF ANY DISCREPANCY
HANDLE
IS FOUND IN THE MEASUREMENTS, IS THE seal:
KICKPLATE
ON PUSH cúal es el a y el b CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY
THE ARCHITECT TO COORDINATE SUCH
SIDES, DISCREPANCY.
1
P-LAM. COUNTER TOP W/ P-LAM.
END BRACE SUPPORT, COLOR BY
OWNER
04/13/2023
6 1
54" MIN 2
42" MIN 12" MAX
39"-41" 12"
18"
17" 3
MIN MIN 24" MIN CREATIVE BULDERS, INC
4
MIN
36" MAX.
18"
96"
18"
96"
8
96"
6
96"
21"
39"-41"
48"
34" MAX
33"-36"
5
29" MIN.
39"-41"
48"
27" MIN.
33"-36"
MAX
MAX
34"
MIN.
32"
MIN.
29"
15"-48"
27"
19"
17"-19"
8" MIN
9" MIN.
7 TOE HEALTH DEPARTMENT
CLEARANCE PIPING BELOW LAV. TYP.
RECOMENDATION
LICENSE #0060836 B-2
ELEVATION ELEVATION ELEVATION ELEVATION LICENSE LIMIT $600,000
A B C D
1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"
1 6
54" MIN 2
RESTROOM ENLARGEMENT
12" MAX 42" MIN
39"-41" 12"
18"
MIN
18"
36" MAX.
18"
96"
8 6
96"
96"
96"
21"
39"-41"
48"
34" MAX
33"-36"
5
29" MIN.
39"-41"
27" MIN.
48"
33"-36"
MAX
MAX
34"
MIN.
32"
MIN.
15"-48"
29"
19"
27"
17"-19"
8" MIN
9" MIN.
NOTE: INSUL. ALL EXPOSED
TN NAILS SALON
TOE 7 HEALTH DEPARTMENT
PIPING BELOW LAV. TYP. CLEARANCE RECOMENDATION
Project Title :
EXISTING AND UNCOVERED SITE AND BUILDING CONDITIONS MAY
VARY FROM THE PREPARED DOCUMENTS, THE CONTRACTOR OR
sheet title:
ACCESSORIES SUCH AS GRAB BARS, TOWEL BARS, PAPER DISPENSERS AND SOAP DISHES, PROVIDED ON OR WITHIN WALLS, SHALL BE
OWNER SHALL REPORT ANY ERRORS, OMISSIONS, OR INCONSISTENCY
INSTALLED AND SEALED TO PROTECT STRUCTURAL ELEMENTS FROM MOISTURE.
THAT MAY BE DISCOVERED. THE CONTRACTOR AND OWNER ARE TO
RESOLVE ANY DISCREPANCIES TROUGH APPROPIATE DRAWINGS
AND DETAILS.
TOILET ACCESSORY SCHEDULE TEH CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH Revisions :
No. DESCRIPTION MANUF. OR EQUAL FINISH REMARKS THE PROJECT AND SHALL FIELD VERIFY ALL CONDITIONS PRIOR TO
1 TOWEL DISP. W/ WASTE DISPOSAL BOBRICK #B-36903 SATIN BARRIER FREE ANY WORK.
2 SOAP DISPENSER BOBRICK #B-190 """ THE CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS AND METHODS
3 TOILET PAPER DISPENSER BOBRICK #B-304 """ OF CONSTRUCTION - JOB SITE SAFETY AND SUPERVISION.
4 GRAB BAR 36" BOBRICK """
THE CONTRACTOR SHALL PROVIDE TEMPORARY BARRICADES DURING
5 GRAB BAR 36" BOBRICK """ CONSTRUCTION TO ENSURE PUBLIC SAFETY.
6 MIRROR J.S.M. 24" X 36" S.S. SERIES 1907
7 TOILET MANUF. OR EQUAL KOHLER K-3427 T WHITE OR SIMILAR THE CONTRACTOR IS RESPONSISBLE FOR ALL PERMITS AND FEES.
8 LAVATORY MANUF. OR EQUAL KOHLER K-2035-1 WHITE OR SIMILAR
THE CONTRACTOR IS RESPONSIBLE TO PROVIDE NOISE AND DUST
CONTROL PER CITY AND COUNTY CODES.
NOTE: 1.- ALL BATH RM. ACCESSORYS SHALL BE INSTALLED AS PER ANSI 4.15 THRU 4.19 Issued Date: 04/13/2023
2. ALL PLUMBING FIXTURES TO COMPLY WITH UPC SECTION 402 AND 409
Project No.: 23060-TNS
1
Checked By: LFP
Sheet No:
dated.
A204
4 OF 4
architecture - planning - 3d imagination
LEGEND
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
GENERAL NOTES
[email protected]
NEW GYP BOARD CEILING
OR ARCHITECT TO RESOLVE SUCH DISCREPANCY
4. INSTALL, PATCH AND REPAIR NEW DRYWALL, WHERE REQUIRED, GENERAL
NEW LED STRIP LIGHT
702.749.0038
CONTRACTOR MUST IDENTIFY
SUCH AREAS PRIOR ISSUE A PROPOSAL TO CLIENT TO AVOID OMMITIONS IN THE
ESTIMATE
EXIT
NEW SLIM DOWN LIGHT
calidad de dibujo
EXIT
24"x24" HVAC RETURN
seal:
NEW 24"X24" SUPPLY AIR DIFFUSER
04/13/2023
CONSULTANT:
EXIT
EXIT
y el led ribbon que te marque por que no LICENSE #0060836 B-2
LICENSE LIMIT $600,000
esta representado aqui
1
A301
TN NAILS SALON
SUITE 220 & 230
9270 S RAINBOW BLVD
CC ENTERPRISE-89139
APN 176-23-210-006
project title :
sheet title :
altura? podria quedar mas abajo no?
Revisions :
1
BOTTOM OF CEILING 2
este es el crown molding
11'-0"
dondé esta el moulding? 4
3
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD Issued Date: 04/13/2023
SURVEY AND THE PLANS IN RECORDS. si esta a escala la silla?
FIN. FLOOR
+0'-0" Sheet No:
el wall base son de 4"
A301
2 OF 2
architecture - planning - 3d imagination
LEGEND
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
EXISTING WALL NOT TO BE MODIFIED (E) EXIT
#2
[email protected]
WIDTH
X-1 OCCUPANCY CLASSIFICATION 30" min. 180 OCC
72"
NET OR GROSS NET OR GROSS AREA
60"
CAPACITY
702.749.0038
150 SF AREA (SQ. FT.)
X.15 OLF NAILS 60"
1/XXX OLF OCCUPANT LOAD FACTOR ROOM
360 OCC 48"
XXX OCC MINIMUM OCCUPANT LOAD 101 (E)EXIT
2 REQUIRED NUMBER OF EXITS B #2
GROSS
1329.85 SF
RM NAME EGRESS PATH FUNCTION 1/150 OLF
101 AND NUMBER 9 OCC
(E)EXIT 26
WIDTH
#1
XX" CLEAR WIDTH AS PERMITTED BY CODE
CAPACITY
1/XXX OLF OCCUPANT LOAD FACTOR
LASH BREAK
XXX OCC MAX. OVERALL CAPACITY ROOM ROOM
106 108
B B
GROSS GROSS
EXIT NAME EXIT NUMBER 83.11 SF 309.07 SF
seal:
EXIT# 01
1/150 OLF 1/15 OLF
1 OCC 20 OCC
WAX
XX EXISTING LOAD 22 ROOM
105
B
01
GROSS
78.27 SF
EXISTING / EGRESS PATH OF 1/150 OLF
TRAVEL-FIRST FLOOR 1 OCC (E) EXIT
20
#4 04/13/2023
WIDTH
57 36" CONSULTANT:
(E)EXIT 09
CAPACITY
#3
X.15 OLF CREATIVE BULDERS, INC
180 OCC
LOBBY
100
B (E)EXIT
GROSS 48" #4
(E) EXIT 396.77 SF
60"
#3 1/15 OLF
26 OCC
WIDTH 30" min. LICENSE #0060836 B-2
60"
72" LICENSE LIMIT $600,000
CAPACITY
X.15 OLF
360 OCC
TN NAILS SALON
SUITE 220 & 230
EGRESS PLAN
Drawn By: AH
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD
SURVEY AND THE PLANS IN RECORDS. Checked By: EM
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF Sheet No:
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY. A401
1 OF 1
architecture - planning - 3d imagination
LEGEND
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
FINISH SCHEDULE
EXISTING WALL NOT TO BE MODIFIED
FLOOR DESCRIPTION
WF-02
WF-02
INDICATES ROOM/SPACE NO. FINISH FLOOR TILES AS PER OWNER SELECTED
102 FC-01 CL-01
SALES AREA
[email protected]
INDICATES ROOM/SPACE NAME. WF-02 WF-01 30" min.
CEILING DESCRIPTION
60"
ROOM/SPACE NUMBER WF-01 WF-02
702.749.0038
60" FC-01
FINISH CEILING GYPSUM W/ SOFFITS SUSPENDED
WF-01
CL-01 RESTROOM
48"
CEILING AND PAINTED. SEE A602 FOR CEILING DETAILS
107
WF-02 WF-02
WF-02
HALL
CL-01
WF-02
CL-01 104
WF-01 FINISH WALL 58" GYPSUM BOTH SIDE AND PAINT LOBBY
WF-02
OWNER SELECTED COLOR FC-01
100
WF-02
CL-01
FC-01
NAILS ROOM
BREAK ROOM
101
LEVEL 2 108
18'-0"
WF-02
CL-01 FC-01
WAX ROOM
WF-02 105 WF-02
WF-02
WF-02
WF-02
WF-02
BOTTOM OF CEILING 04/13/2023
11'-0"
CONSULTANT:
WF-02
CL-01
HALL
agrega las columnas
WF-02
103
decorativas CREATIVE BULDERS, INC
CL-01 WF-02 WF-02
WF-01
RESTROOM
102
WF-01 48"
WF-02
60"
WF-02 WF-01
CL-01
FC-01
30" min. WF-02
LICENSE #0060836 B-2
WF-02
60"
WF-01
WF-02
WF-02
FC-01
WF-02 LICENSE LIMIT $600,000
WD
FIN. FLOOR WF-02
+0'-0"
TN NAILS SALON
LEVEL 2
18'-0"
11'-0"
calidad de linea
project title :
BOTTOM OF CEILING
9'-6" donde pasa la linea de corte debe verse mas intensa
sheet title :
CL-01
y la proyeccion mas ligera
Revisions :
1
4
FC-01
FIN. FLOOR
+0'-0" 5
4" 6
Drawn By: AH
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD
SURVEY AND THE PLANS IN RECORDS. Checked By: EM
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF Sheet No:
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY. A501
1 OF 1
architecture - planning - 3d imagination
their use and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for
[email protected]
agrega tambien el wallschedule
8'-0"
702.749.0038
DOOR - SEE SCHEDULE
PREFINISHED KNOCK DOWN
FRAME
DRYWALL SCREW, NEXT TO EACH
RETAINER CLIP
DRYWALL SCREW, NEXT TO EACH
A RETAINER CLIP
REFER TO WALL TYPES
CONSULTANT:
ARCHITECTURAL DETAILS
TN NAILS SALON
9'-0 3/4"
project title :
sheet title :
indica de que es
Revisions :
1
8'-0"
Drawn By: AH
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD
SURVEY AND THE PLANS IN RECORDS. Checked By: LFP
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN
MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF Sheet No:
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY. A601
1 OF 2
48" SHEETROCK BRAND
and for occupying the project for which they were prepared, and not for construction of any other projects. any use or reproduction of this drawing in whole or part by any means whatsoever is strictly prohibited. these documents are not final and ready for use, and therefore not valid, unless they are sealed, signed, and
As instruments of service these drawings and specifications are the property of XPC Architectural Studio, LLC. and may not be reproduced or used for any purpose without the XPC Architectural Studio, LLC. Written consent. Copies of the drawings and specifications retained by the client may be utilized only for their use
COMPASSO TRIM
18"- 60" CONCRETE DECK MAIN TEE GYPSUM PANEL
[email protected]
SECTION TYPE VARIES
DETERMINED BY
MAIN TEE
702.749.0038
PLENUM DEPTH CROSS
TEE
MAIN TEE
TEE
SHEETROCK BRAND
1/2" OR 5/8" EXTERIOR PANELS
GYPSUM PANEL
*NOTE: ONLY SHEETROCK BRAND EXTERIOR CEILING BOARD,
FIBEROCK BRAND AQUA-TOUGH SHEATHING, AND
seal:
DUROCK CEMENT BOARD ARE SUITABLE FOR EXTERIOR APPLICATIONS.
SEE DRYWALL SUSPENSION SYSTEM LITERATURE AC3152 FOR DETAILS.
TEE
EXTERIOR APPLICATION COMPASSO TRIM-PARALLEL TO TEE 90 DEGREE CORNER CHANNEL MOLDING 90 DEGREE CORNER FIELD CUT
SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS
COMPASSO TRIM
04/13/2023
COMPASSO CLIP
CREATIVE BULDERS, INC
TRANSITION CLIP
MAIN/CROSS
TEE
LICENSE #0060836 B-2
LICENSE LIMIT $600,000
MAIN/CROSS TEE TEE
TRANSITION CLIP
ANGLE MOLDING
ANGLE MOLDING
SHEETROCK BRAND
ANGLE MOLDING SHEETROCK BRAND GYPSUM PANEL
GYPSUM PANEL
90 DEGREE CORNER TRANSITION CLIP DEGREE OUTSIDE CORNER MAIN TEE DEGREE OUTSIDE CORNER FIELD COMPASSO TRIM-PERPENDICULAR TO TEE
SCALE: NTS SCALE: NTS SCALE: NTS SCALE: NTS
TN NAILS SALON
CEILING DETAILS
CC ENTERPRISE-89139
· SUSPENDED CEILING INSTALLATIONS SHALL MEET THE REQUIREMENTS 1. A “HEAVY DUTY” T-BAR GRID SYSTEM IS REQUIRED TO BE USED IN HAVE SEISMIC SEPARATION JOINTS PER APPROVED PLAN DESIGN.
APN 176-23-210-006
AND SOUTHERN NEVADA CODE AMENDMENTS
OF SEISMIC CATEGORY D UNLESS SPECIFICALLY NOTED AS CATEGORY ALL APPLICATIONS.
C ON THE STRUCTURAL AND/OR ARCHITECTURAL GENERAL NOTE 14. ALL FIXTURES SHALL BE POSITIVELY ATTACHED TO THE CEILING
THE MEASUREMENTS HERE PROVIDED ARE THE RESULT OF A FIELD PAGE(S). 2. CEILING AREAS OF 144 SQUARE FEET OR LESS, DO NOT SYSTEM. THE ATTACHMENT DEVICE SHALL BE ABLE TO WITHSTAND
SURVEY AND THE PLANS IN RECORDS. REQUIRE SEISMIC BRACING AND STRUTS. 100% OF THE WEIGHT OF THE FIXTURE ACTING IN ANY
EACH CONSULTANT IS RESPONSIBLE TO TAKE THEIR OWN · APPROVED ARCHITECTURAL PLANS SHALL REFLECT COMPRESSION DIRECTION.
Project Title :
CROSS TEE MEASUREMENTS TO AVOID ANY CONFLICTS WITH THEIR WORK. IF STRUT CONSTRUCTION WHEN STRUTS ARE REQUIRED. 3. WALL MOLDING SHALL HAVE A MINIMUM 2 INCH WIDE
ANY DISCREPANCY IS FOUND IN THE MEASUREMENTS, IS THE
sheet title:
CONSULTANT RESPONSIBILITY TO IMMEDIATELY NOTIFY THE HORIZONTAL FLANGE. 15. CABLE TRAYS, ELECTRICAL CONDUIT AND WIRING SYSTEMS
· SEISMIC BRACING LAYOUT SHALL START WITHIN 6 FEET FROM TWO SHALL BE SUPPORTED AND BRACED INDEPENDENTLY OF THE
ARCHITECT TO COORDINATE SUCH DISCREPANCY.
ADJACENT WALLS AND SHALL BE SPACED A MAXIMUM OF 12 FEET ON 4. WALL MOLDING IS NOT STRUCTURAL, BUT MUST BE ATTACHED CEILING.
CENTER ACROSS THE SPACE IN BOTH DIRECTIONS. (PER CISCA SEISMIC TO THE WALL.
ZONES 3&4, #3 LATERAL FORCE BRACING, PAGE 2). THE 12 FOOT 16. MECHANICAL SERVICES SHALL BE POSITIVELY ATTACHED TO
SPACING WILL CONTINUE ACROSS THE SPACE WITH NO REMAINING 5. THE CEILING GRID SHALL BE RIGIDLY ATTACHED TO THE THE CEILING SYSTEM MAIN BEAMS OR TO CROSS TEES WITH THE Revisions :
AREA OR LINEAR MEASUREMENT TO BE GREATER THAN 12 FEET. MOLDING AT TWO ADJACENT WALLS. SAME LOAD CARRYING CAPACITY
SPLICE CLIP · TEE SECTIONS 6 INCHES OR LESS IN LENGTH ALONG THE WALL ANGLE SEISMIC CATEGORY “C” REQUIREMENTS
6. THE UNATTACHED ENDS OF THE GRID SYSTEM SHALL HAVE
DO NOT REQUIRE PERIMETER WIRES. MINIMUM ¾ INCH CLEARANCE FROM THE WALL AND REST ON ALL WORK SHALL BE IN ACCORDANCE WITH THE CLABD AND CISCA 0-1 STANDARD.
THE WALL MOLDING. LISTED BELOW ARE THE SPECIFIC REQUIREMENTS:
VAULT · ITEMS WEIGHING LESS THAN 20 POUNDS SHALL BE SUPPORTED FROM THE OBJECTIVE OF THIS STANDARD IS TO CREATE AN UNRESTRAINED CEILING.
MAIN TEE THE GRID AND MAY HAVE A SINGLE SLACK WIRE. 7. ALL TERMINAL ENDS AROUND THE PERIMETER SHALL BE
SUPPORTED WITHIN 8 iNCHES OF THE WALL. 1. THE ACTUAL CEILING WEIGHT INCLUDING ALL FIXTURES AND AIR TERMINALS SHALL
· TRAPEZE SUSPENSIONS SHALL BE A MINIMUM OF BACK-TO-BACK 1 ¼ BE LESS THAN 2.5 POUND PER SQUARE FOOT. THIS SHALL BE NOTED ON THE PLANS.
INCH COLD-FORMED CHANNELS FOR SPANS EXCEEDING 48 INCHES. 8. UNRESTRAINED TERMINAL ENDS SHALL BE SECURED TOGETHER
TO PREVENT THEIR SPREADING. SPREADER BARS SHALL BE 2. WALL MOLDINGS MAY HAVE A 7/8 INCH MINIMUM WIDE HORIZONTAL FLANGE.
· SUSPENSION HANGER WIRES SHALL BE A MINIMUM 12 GAUGE, INSPECTED AS PART OF THE BUILDING FINAL INSPECTION.
SPACED 4 FEET ON CENTER. 3. THE TERMINAL ENDS OF THE GRID MUST REST ON THE MOLDING WITH AT LEAST 3/8
9. SEISMIC SPLAY WIRE BRACING SHALL BE CLUSTERS OF FOUR INCH CLEARANCE FROM THE WALL AND AT LEAST 3/8 INCH SUPPORT ON THE Issued Date: 04/13/2023
MOLDING.
· SUSPENSION HANGER WIRES SHALL HAVE THREE FULL TURNS WITHIN 3
INCHES OF CONNECTION POINTS.
WIRES, OF A MINIMUM 12 GAGE, ATTACHED WITHIN 2 INCHES OF
THE CROSS TEE INTERSECTION. WIRES SHALL BE ARRAYED 900
Project No.: 23060-TNS
SHEETROCK BRAND FROM EACH OTHER AT AN ANGLE NOT EXCEEDING 450 FROM 4. PERIMETER ATTACHMENT IS NOT ALLOWED ON ANY SIDE.
Drawn By: LRE
GYPSUM PANEL · SUSPENSION WIRES SHALL NOT HANG MORE THAN 1 IN 6 HORIZONTAL.
OUT-OF-PLUMB UNLESS COUNTER SLOPING WIRES ARE PROVIDED. 5. PARTITIONS SHALL BE BRACED INDEPENDENT OF THE CEILING; ANY ATTACHMENT Checked By: LFP
10. AN APPROVED COMPRESSION STRUT SHALL BE ATTACHED TO TO THE CEILING MUST ALLOW 3/8 INCH MOVEMENT OF THE CEILING IN ANY
· FIXTURES 56 POUNDS OR LESS SHALL HAVE TWO SLACK WIRES THE CEILING AT EACH BRACING LOCATION, IN ACCORDANCE DIRECTION. Sheet No:
ATTACHED TO THE STRUCTURE. WITH THE APPROVED PLAN DETAILS.
dated.
6. ALL TERMINAL ENDS SHALL BE SECURED TOGETHER TO PREVENT THEIR SPREADING.