Sample of Residential Load Computation For Power System Analysis
Sample of Residential Load Computation For Power System Analysis
SECTION NO.1
TOTA 29 4 14 5 48 14 7 10 58.49
L
OTHER CUSTOMERS:
TRANSFORMER LOAD:
TRANSFORMER RATING:
LOAD CENTER:
TMD 28.29
1. Percent Loading ¿ ¿ x 100 ¿75.44%
Actual ¿ ¿ ¿ 37.5
37500
2. I fl = Actual¿ ¿ Primary Voltage= =2 .72 A ¿
13800
3. Maximum Setting of Overcurrent Protection in Primary
I =300 % of I fl =8.16 A ≅15 A
4. Short Circuit Current in the Primary (KVA)
37500
KVA SC= =797.87 KVA
0.047
37500
5. ISC (sym.) =57.82 A
4.7 % (13800)
6. ISC (assym.) ¿1.6 x 57.82A = 92.51A
The rating of the transformer shall be 37.5KVA, 13.8kV/230V, 60Hz single phase
distribution transformer with 4.7% impedance, the total expected load is
73.41%,
the rating of the fuse cutout shall be 15A fuse link. The maximum setting of load
is 8.16 A. The Lightning Arrester shall be line type rated at 12kV
POLE LOCATION:
MAXIMUM DEMAND BY POLE:
CM =97007.321 CM =136897.5939
CM ≈ 105,535.00 (From TABLE 8) CM ≈ 167800 (From TABLE 8)
SIZE OF CONDUCTOR TO BE USED IB BOTH SIDES: