HA 35.41 ·
2022
MEDIUM-VOLTAGE SWITCHGEAR
Application:
Public power
supply system
and
offshore
R-HA3541-304 tif
R-HA3541-301 jpg
Application:
Industry and
offshore
Photo: Harald M. Valderhaug
R-HA35-185 tif
R-HA35-365 tif
2 Fixed-Mounted Circuit-Breaker Switchgear Type N XPLUS C up to 36 kV, Gas-Insulated · Siemens HA 35.41 · 2022
Contents Page
Fixed-Mounted Requirements
Circuit-Breaker
Features, safety, technology 6 and 7
Technical data
Switchgear Electrical data
Room planning
8 to 11
12 and 13
Type NXPLUS C Shipping data
Classification
14
15
up to 36 kV, Panel dimensions
Product range
Single-busbar panels 29 to 35
Double-busbar panels 36 and 37
Catalog HA 35.41 · 2022
Components
Invalid: Catalog HA 35.41 · 2020
Panel connection 38 to 40
siemens.com/nxplusc Standards
Standards, specifications,
guidelines 41 to 44
R-HA3541-305 png
R-HA3541-306 png
R-HA3541-307 png
Circuit-breaker panel 5) and bus sectionalizer 1000 A 5), 1250 A 5), 1600 A, 2000 A, 2500 A
Rated normal current 3) Ir at an ambient A 1000 1000 1000 1000 1000 1000 1000
air temperature of 40 °C A 1250 1250 1250 1250 1250 1250 1250
A 1600 1600 1600 1600 1600 – –
A 2000 2000 2000 2000 2000 – –
A 2500 2500 2500 2500 2500 – –
Rated short-time for switchgear with tk = 1 s kA 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 20 | 25 20 | 25
withstand current Ik for switchgear with tk = 3 s kA 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 20 | 25 20 | 25
Rated peak 50 Hz kA 50 | 63 | 80 50 | 63 | 80 50 | 63 | 80 50 | 63 | 80 50 | 63 50 | 63 50 | 63
withstand current Ip 60 Hz kA 52 | 65 | 82 52 | 65 | 82 52 | 65 | 82 52 | 65 | 82 52 | 65 52 | 65 52 | 65
Rated short-circuit 50 Hz kA 50 | 63 | 80 50 | 63 | 80 50 | 63 | 80 50 | 63 | 80 50 | 63 50 | 63 50 | 63
making current Ima 60 Hz kA 52 | 65 | 82 52 | 65 | 82 52 | 65 | 82 52 | 65 | 82 52 | 65 52 | 65 52 | 65
Rated short-circuit breaking current Isc kA 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 | 31.5 20 | 25 20 | 25 20 | 25
Electrical endurance of at rated normal current 10,000 operating cycles
vacuum circuit-breakers 30,000 5) operating cycles – –
at rated short-circuit 50 breaking operations
breaking current
Endurance classes according to IEC 62271‑100 M2, E2, C2, S2
Endurance classes DISCONNECTING M1 M1 M1 M1 M1 M1 M1
according to IEC 62271‑102 EARTHING M0, E0 M0, E0 M0, E0 M0, E0 M0, E0 M0, E0 M0, E0
The EARTHING function with endurance class E2 is reached by closing the circuit-breaker in combination with the earthing switch (endurance class E0).
8 Fixed-Mounted Circuit-Breaker Switchgear Type N XPLUS C up to 36 kV, Gas-Insulated · Siemens HA 35.41 · 2022
Technical data
Electrical data, filling pressure, temperature for single-busbar switchgear
Ring-main panel
Rated voltage Ur kV 7.2 12 15 17.5 24 36 38
Rated at an ambient A 630 630 630 630 630 – –
normal current 3) Iload air temperature of 40 °C
Rated short-time for switchgear with tk = 1 s kA 20 | 25 20 | 25 20 | 25 20 | 25 20 | – – –
withstand current Ik for switchgear with tk = 3 s kA 20 | – 20 | – 20 | – 20 | – 20 | – – –
Rated peak 50 Hz kA 50 | 63 50 | 63 50 | 63 50 | 63 50 | – – –
withstand current Ip 60 Hz kA 52 | 65 52 | 65 52 | 65 52 | 65 52 | – – –
Rated short-circuit 50 Hz kA 50 | 63 50 | 63 50 | 63 50 | 63 50 | – – –
making current Ima 60 Hz kA 52 | 65 52 | 65 52 | 65 52 | 65 52 | – – –
Endurance class according to IEC 62271‑103 M1, E3 M1, E3 M1, E3 M1, E3 M1, E3 – –
Rated short-duration
power-frequency withstand
voltage Ud
– phase-to-phase, phase-to-
earth, open contact gap kV 20 1) 28 2) 36 38 50
– across the isolating distance kV 23 1) 32 2) 40 45 60
Rated lightning impulse
withstand voltage Up
– phase-to-phase, phase-to-
earth, open contact gap kV 60 1) 75 2) 95 95 125
– across the isolating distance kV 70 1) 85 2) 110 110 145
Rated frequency fr Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Rated normal current 3) Ir for the busbar up to A 2500 2500 2500 2500 2500
Rated filling level pre for gas-insulated kPa 150 150 150 150 150
switchgear vessels
Minimum for gas-insulated kPa 130 130 130 130 130
functional level pme switchgear vessels
Gas leakage rate % < 0.1 per year
Ambient air temperature °C −5 to +55 6)
Switchgear installation
Switchgear installation
with lateral cable connection as end panels
*** ≥ 500 mm aisle for installation and maintenance
(according to IEC 61936‑1)
≥ 800 mm aisle for operation (according to IEC 62271‑200)
* Control aisle depending on national specifications;
for extension/panel replacement:
≥ 1400 mm recommended (450 mm, 600 mm panels)
≥ 1600 mm recommended (900 mm panels)
** Lateral wall distance ≥ 50 mm optionally possible on the
left or on the right:
≥ 500 mm for installation and maintenance
(according to IEC 61936‑1)
≥ 800 mm for operation (according to IEC 62271‑200)
≥ 800 mm for panel replacement
(450 mm, 600 mm panels)
≥ 1100 mm for panel replacement (900 mm panels)
Transport
NXPLUS C switchgear is delivered in form of individual panels. Please observe the following:
• Transport facilities on site
• Transport dimensions and transport weights
• Size of door openings in building.
In case of double-busbar panels the A and B sides are supplied separately.
Packing
Means of transport: Rail and truck Means of transport: Ship and airplane
– Panels on pallets – Panels on pallets
– Open packing with PE protective foil. – In closed crates (cardboard)
with sealed upper and lower PE protective foil
– With desiccant bags
– With sealed wooden base
– Max. storage time: 6 months.
Dimensions, weights
Transport Panel spacing Transport dimensions Transport weight
Single busbar
Truck 1 x 450 1100 2460 1450 800 700
or
1 x 600 1100 2460 1450 900 800
rail
1 x 900 1100 2460 1450 1500 1400
1 x 450 1100 2460 2100 800 700
(cable connection from rear)
1 x 600 1100 2460 2100 900 800
(cable connection from rear)
1 x 900 1100 2460 2100 1500 1400
(cable connection from rear)
Auxiliary power transformer 800 1200 1200 500 425
Ship 1 x 450 1130 2550 1450 800 700
or
1 x 600 1130 2550 1450 900 800
airplane
1 x 900 1130 2550 1450 1500 1400
1 x 450 1130 2550 2100 800 700
(cable connection from rear)
1 x 600 1130 2550 2100 900 800
(cable connection from rear)
1 x 900 1130 2550 2100 1500 1400
(cable connection from rear)
Auxiliary power transformer 800 1200 1200 500 425
Double busbar
Truck 1 x 450 1100 2460 1450 800 700
or
1 x 600 1100 2460 1450 900 800
rail
1 x 900 1100 2460 1450 1500 1400
Auxiliary power transformer 800 1200 1200 500 425
Ship 1 x 450 1130 2550 1450 800 700
or
1 x 600 1130 2550 1450 900 800
airplane
1 x 900 1130 2550 1450 1500 1400
Auxiliary power transformer 800 1200 1200 500 425
630 A, 800 A
Legend see page 28
Legend see page 28
1) 2650 mm for higher low-voltage compartment
Legend see page 28
Legend see page 28
Legend see page 28
18 Fixed-Mounted Circuit-Breaker Switchgear Type N XPLUS C up to 36 kV, Gas-Insulated · Siemens HA 35.41 · 2022
Panel dimensions
Disconnector panel, bus sectionalizer, single busbar
Legend see page 28
1000 A, 1250 A
Legend see page 28
1) 2650 mm for higher low-voltage compartment
Legend see page 28
1000 A, 1250 A
Legend see page 28
1) 2650 mm for higher low-voltage compartment
Legend see page 28
1) 2650 mm for higher low-voltage compartment
Legend see page 28
Legend see page 28
Legend see page 28
Legend see page 28
Panel dimensions
Metering panel, ring-main panel, single busbar
24 kV Air-insulated metering panel without / with three-position disconnector 900 mm
without three-position disconnector
1) 2
650 mm for
higher low-voltage
compartment
24 kV Ring-main panel 630 A 450 mm
1) 2650 mm for higher low-voltage compartment
1) 2
650 mm for higher
low-voltage compartment
300 mm 600 mm
Legend see page 28
1) 2
650 mm for higher
low-voltage compartment
Legend see page 28
Legend see page 28
1) 2650 mm for higher low-voltage compartment
1) 2650 mm for higher low-voltage compartment
28 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated · Siemens HA 35.41 · 2022
Product range
Single-busbar panels
Three-position
disconnector
Vacuum
or or circuit-breaker
or or
Current transformer
and/or or and/or or
Solid-insulated bar
Surge arrester
or limiter
Disconnectable
and plug-in
voltage transformer
or or
and/or or
and/or or
or or
Busbar
earthing switch
Three-position
disconnector
Vacuum
circuit-breaker
or
Current transformer
detecting system
and/or or
Solid-insulated bar
and/or or
Plug-in
voltage transformer
600 mm
Surge arrester
or limiter
Disconnectable
and plug-in
voltage transformer
or or or or
and/or or and/or or
outside-cone plug
(not included in the
scope of supply) or or
L1 L2 L3
L3 L2 L1
Inverted phases
600 mm 900 mm
Three-position
disconnector
Current transformer
Capacitive voltage
or detecting system
or or
Solid-insulated bar
and/or or
Plug-in
voltage transformer
and/or and/or or
Surge arrester
or limiter
600 mm
Disconnectable
and plug-in
voltage transformer
Three-position
disconnector
Vacuum
circuit-breaker
Capacitive voltage
detecting system
600 mm 900 mm
Solid-insulated bar
36 kV Bus sectionalizers 1000 A, 1250 A
Plug-in
voltage transformer
Surge arrester
or limiter
Longitudinal panel
and/or and/or
interconnection
900 mm
or and/or
and/or
Three-position
disconnector
or
Three-position
switch-disconnector
or
Current transformer
and/or or
Capacitive voltage
detecting system
and/or or
Solid-insulated bar
600 mm
Plug-in
voltage transformer
24 kV Auxiliary transformer panel
or Surge arrester
or limiter
HV HRC fuses
or and
Cable connection with
or outside-cone plug
(not included in the
scope of supply)
and/or
40 kVA
Auxiliary
transformer,
and/or three-phase
10 kVA
Auxiliary
transformer,
900 mm single-phase
24 kV Metering panel
Three-position
disconnector with
make-proof
earthing switch
or
Current transformer
or
Capacitive voltage
detecting system
and/or
Solid-insulated bar
and/or
Plug-in
voltage transformer 600 mm
HV HRC fuses
Three-position or and
disconnector
Voltage or
transformer
connection bolt)
900 mm
Three-position
switch-disconnector
or
Current transformer
or
Capacitive voltage
detecting system
and/or or
Solid-insulated bar
and/or or
Plug-in
voltage transformer
450 mm
Three-position
or disconnector with
make-proof
earthing switch
and/or or
HV HRC fuses
and/or or
Vacuum contactor
600 mm
24 kV Circuit-breaker panel
Three-position BB1
disconnector BB2
Vacuum
circuit-breaker
or or
Current transformer
or and/or or or
Capacitive voltage
detecting system
and/or or and/or
Solid-insulated bar
HA35-2500h x eps
and/or or and/or
Plug-in
voltage transformer or
Surge arrester
or limiter
24 kV Incoming sectionalizer
BB1
BB2
or and/or or
Transverse panel
interconnection
or or or
Disconnectable
and plug-in and/or or and/or
voltage transformer
HA35-2502m x eps
and/or or and/or
or
Abbreviations:
BB1 = Busbar 1
BB2 = Busbar 2
24 kV Bus coupler
BB1 Three-position
BB2 disconnector
Vacuum
circuit-breaker
or or
Current transformer
or or
Capacitive voltage
detecting system
and/or and/or
Solid-insulated bar
HA35-2503d x eps
and/or and/or
Plug-in
voltage transformer
Surge arrester
or limiter
Transverse panel
interconnection
Abbreviations:
BB1 = Busbar 1
BB2 = Busbar 2
interface type C according to
EN 50181
• For cable connection heights,
see table on the right
• Max. connection depth:
H1
See side views on p ages 16
to 28
H2
• With cable bracket type C40
according to DIN EN 60715
• Option: Access to the cable
compartment only if the Panel width 450 mm Panel width 600 mm Panel width 900 mm
feeder has been isolated and
earthed
Cable connection heights
• For thermoplastic-insulated
Height of Distance between Distances
cables
Panels cable compart- bushing and cable cable – cable
• For shielded cable T-plugs or
ment bracket cable – separation wall
cable elbow plugs with bolted
contact (H2) (H1) D1 D2 D3
• For connection cross-sections mm mm mm mm mm
up to 1200 mm2 450 mm 700 500 90 135 –
• Larger cross-sections on 600 mm 700 500 105 195 –
request 900 mm 570 430 115 185 100
• Cable routing downwards, Switch-disconnector panel
cable connection from the and vacuum contactor panel
front with HV HRC fuses 420 250 – – –
• Option: Cable connection
rear-top, cable connection
rear-bottom
• For rated normal currents
Connectable cables
up to 2500 A
Cable T-plug with coupling insert
• Cable T-plugs are not included
a) Panel width 450 mm
in the scope of supply.
b) Panel width 600 mm
c) Panel width 900 mm
Surge arresters
• Pluggable on cable T-plug
Solid-insulated bar Cable T-plug with coupling T-plug
• Surge arresters recommended
if, at the same time
– the cable system is directly
connected to the overhead
line,
– the protection zone of the
surge arrester at the end
tower of the overhead line
does not cover the switch-
gear.
Surge limiters
• Pluggable on cable T-plug a) Connection with b) Connection with b) Connection with
2 cables per phase 3 cables per phase 4 cables per phase
• Surge limiters recommended
b) Connection with c) Connection with c) Connection with
when motors with starting
2 cables per phase 6 cables per phase 8 cables per phase
currents < 600 A are c) Connection with
connected. 4 cables per phase
Legend
1C able T-plug
2C oupling T-plug
3 End adapter
38 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated · Siemens HA 35.41 · 2022
Components
Panel connection
short-circuit making capacity according to IEC 62271‑102 and
EN 62271‑102.
Dielectric strength
The dielectric strength is verified by testing the switchgear
with rated values of short-duration power-frequency with-
stand voltage and lightning impulse withstand voltage
according to IEC 62271‑1 (see Technical data).
The gas insulation at a relative gas pressure of 50 kPa permits (Only for panels with HV HRC fuse)
switchgear installation at an altitude of up to 4000 m
For site altitudes above 1000 m, the altitude correction factor Ka is
above sea level without the dielectric strength being
recommended, depending on the site altitude above sea level.
adversely a
ffected. This also applies to the cable connection Curve m = 1 for rated short-duration power-frequency withstand voltage
when plug‑in sealing ends are used. and rated lightning impulse withstand voltage according to IEC 62271‑1
Standards
NXPLUS C switchgear complies with the relevant standards
and specifications applicable at the time of type tests.
In accordance with the harmonization agreement reached
by the countries of the European Union, their national
specifications conform to the IEC standard.
Standards
Furthermore, the high-voltage part of the NXPLUS C For secondary devices in the low-voltage door, the
switchgear can be used in environmental conditions of stipulations of the IP degree of protection apply a
ccording to
the climatic category 3C2 according to the standard the definitions for the switchgear enclosure.
IEC 60721‑3-3.
1) Secondary devices (e.g. protection devices, meters, measuring transducers, etc.) must be suitable
for the given service c onditions
2) Heater in the low-voltage compartment and operating mechanism box of the circuit-breaker
For the U.S. published by It helps our customers to thrive, communities to progress
Siemens Industry Inc. and supports sustainable development to protect our planet
100 Technology Drive for the next generation.
Alpharetta, GA 30005
United States siemens.com/smart-infrastructure
Medium-
voltage
systems
Status 01/2022
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may not
always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens AG, its affiliated companies or other companies whose use by third parties for
their own purposes could violate the rights of the respective owner.