Setup Program

This document provides information about programming compact controllers and digital indicators using the ST editor and the Structured Text (ST) programming language. It describes the user interface of the ST editor, system variables, data types, operators, instructions, functions, and function modules that are supported. The ST code created with the editor is transmitted to the device to be continuously processed by the integrated ST module.

Uploaded by

Marek Duží
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views58 pages

Setup Program

This document provides information about programming compact controllers and digital indicators using the ST editor and the Structured Text (ST) programming language. It describes the user interface of the ST editor, system variables, data types, operators, instructions, functions, and function modules that are supported. The ST code created with the editor is transmitted to the device to be continuously processed by the integrated ST module.

Uploaded by

Marek Duží
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 58

JUMO diraTRON/diraVIEW 104/108/116/132

Compact controller/digital indicator

ST Editor Manual

70211000T96Z001K000

V2.00/EN/00688820
Contents
Contents

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Qualification of personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Content of this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 System variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Input variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Output variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Internal variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

4 Data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1 Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

5 Operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

6 Selection instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

7 Repeat instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

8 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.1 Type conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.2 Arithmetic functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.3 Numerical functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.4 Bit sequence functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.5 Logical functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8.6 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.7 Comparison. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8.8 Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.9 Other functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

9 Function modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.1 Software up/down counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.2 Impulse generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
9.3 Switch-on delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9.4 Switch-off delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Contents
9.5 Rising edge detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.6 Falling edge detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.7 Bistable function SR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9.8 Bistable function RS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.9 Set controller parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
1 Introduction

1 Introduction
1.1 Safety information
Note symbols
NOTE!
This symbol refers to important information about the product, its handling, or additional benefits.

REFERENCE!
This symbol refers to additional information in other sections, chapters, or other manuals.

1.2 Intended use


The device is designed for use in an industrial environment as specified in the technical data. Other uses
beyond those defined are not viewed as intended uses.
The device has been manufactured in compliance with applicable standards and directives as well as
the applicable safety regulations. Nevertheless, improper use may lead to personal injury or material
damage.
To avoid danger, only use the device:
• For the intended use
• When in good order and condition
• When taking the technical documentation provided into account
Risks resulting from the application may arise, e.g. as the result of missing safety provisions or wrong
settings, even when the device is used properly and as intended.

1.3 Qualification of personnel


This document contains the necessary information for the intended use of the device to which it relates.
It is intended for staff with technical qualifications who have been specially trained and have the appro-
priate knowledge in the field of automation technology.
The appropriate level of knowledge and the technically fault-free implementation of the safety informa-
tion and warnings contained in the technical documentation provided are prerequisites for risk-free
mounting, installation, and startup as well as for ensuring safety when operating the described modules.
Only qualified personnel have the required specialist knowledge to correctly interpret and implement the
safety information and warnings contained in this document in specific situations.

1.4 Content of this document


NOTE!
This document applies to devices from the 70211x series (compact controllers) as well as to devices from
the 70151x series (digital indicators).

This document describes the application of the ST editor with which users can create their own applica-
tions in the PLC programming language "Structured Text" (ST) for the device. The document is intended
for users with relevant programming knowledge.
The PLC programming language "Structured Text" (ST) is described in the standard DIN IEC 61131-3.
Detailed information about programming can be found in this standard. The ST module of the respective
device supports only a subset of the programming language described in the standard.

5
1 Introduction
In addition to this document, the operating manual of the respective device series must be observed:
• Types 701510, 701511, 701512, 701513, 701514 (digital indicators):
Document 70151000T90Z...K...
• Types 702110, 702111, 702112, 702113, 702114 (compact controllers):
Document 70211000T90Z...K...

6
2 User interface

2 User interface
The ST editor is part of the setup program and is started by clicking on the corresponding button in the
"ST code" window (see operating manual).
The finished application is transmitted to the device as ST code and continuously processed in the inte-
grated ST module.

Overview

The user interface consists of several toolbars and windows, which are briefly described in the following
sections.

Menu bar

The individual menus contain functions for editing and compiling a program, for troubleshooting, for dis-
playing and hiding toolbars and windows of the user interface, as well as ST editor version information.
Further information about the functions of the menu bar is displayed in the status bar when the mouse
pointer hovers over the individual function in the respective menu.

7
2 User interface
Toolbar

Some functions of the menu bar are also available in the toolbar and can be selected by a simple mouse
click. The meaning of the symbols is briefly described by a tool tip function (hover over the respective
symbol with the mouse pointer). In addition, further information about the relevant function is then also
displayed in the status bar.

Symbol Meaning Description


Undo (Ctrl+Z) Undo previous action

Restore Restore previously undone action

Cut (Ctrl+X) Remove selected data and transfer to clipboard

Copy (Ctrl+C) Copy selected data and transfer to clipboard

Paste (Ctrl+V) Insert data from the clipboard

Find (Ctrl+F) Search for entered text

Function text (F4) Insert function text from the browser window
See also section "Browse window ", page 11.
Compile (F7) Compile ST code

Start debugging Start debugging (cold start)


After starting, a program that is already on the device is termi-
nated. Instead, the current program is loaded onto the device.
See also section "Debugging ", page 13.
Terminate debugging Terminate debugging
After terminating, the current program remains on the device
and is run.
See also section "End ST editor ", page 13.
Start/continue (F5) Start program or continue running after interruption

Interrupt program Interrupt program

Single step (F11) Run program in a single step

Terminate Terminate program

Next bookmark (F2) Move insertion mark to the next bookmark

Toggle bookmark Toggle bookmark for the current line


(Ctrl+F2)
Previous bookmark Move insertion mark to the previous bookmark
(Shift+F2)
Delete bookmark Delete all bookmarks
(Shift+Ctrl+F2)

8
2 User interface
Symbol Meaning Description
Toggle breakpoint (F9) Toggle breakpoint for the current line

Edit window

The program is created in the edit window by declaring variables and constants, creating program code
and using commentary texts.
In order to assign a version name to the program, the keyword @VERSION followed by the version
name must be used in a comment line. If the program contains several comment lines with this keyword,
only the first comment line is evaluated. After the ST code has been permanently transferred to the de-
vice, the version name can be displayed on the device (Device info > Versions > ST code version).
It is possible to change the font size using Ctrl+Mouse wheel.

9
2 User interface
Output window
The output window consists of two parts (tabs).

The "Compiler" tab shows messages concerning the compilation of the program code.

The "Print" tab contains messages concerning the debug mode.

Status bar

The status bar is located at the bottom of the program interface and indicates whether the editor or debug
mode is active. In the case of debug mode, the individual states (STOP, RUN, PAUSE) are displayed.
Further information about the functions of the menu bar and the toolbar is also displayed in the status
bar (hover over the individual function in the respective menu or over the symbol in the toolbar with the
mouse pointer).

10
2 User interface
Browse window

The browse window lists all the instructions and functions that can be used in the editor. The use of the
instruction or function is shown in the bottom part of the window.
The function text displayed in the bottom part of the browse window can be inserted into the ST code in
the desired position by dragging and dropping (select text beforehand), by clicking on the "Function text"
icon, or using the F4 function key in the edit window (where the cursor is or instead of the selected text).
After inserting, the next placeholder is selected by clicking on the symbol again or pressing F4.

11
2 User interface
Force window
The force window consists of three parts (tabs). Only the "Bool" tab is shown here.

The "Bool" and "Real" input variables as well as date and time can be set by the user in the force window
in order to test the program code.

Variables window
The variables window consists of two parts (tabs).

The "Variables" tab lists all system variables and function outputs (outputs of the function blocks) as well
as the constants and variables (markers) declared by the user. They can be copied from the variable
window by dragging and dropping and pasted into the ST code at the desired position in the edit window.

12
2 User interface

Variables and constants can be displayed and observed during debugging in the "Monitoring" tab. To do
so, they must be copied from the edit window or the "Variables" tab by dragging and dropping and pasted
into the "Monitoring" tab.
Pasting and removing is only possible if the program is not running. Different functions are then also
available via the context menu (right mouse button).

Debugging
The following variants are available with the Debug > Start debugging (menu bar) function:
• Cold start: A program that is already running on the device is terminated and the current program
from the ST editor is loaded onto the device. All variables (retain and non-retain variables) are reset
to their default values.
• Warm start: The retain variables are not reset (70211x and 70151x device types do not support retain
variables).
• Service start: The program currently running on the device is used in the ST editor and can be ana-
lyzed. No variables are reset here. A prerequisite for the service start is that the code compiled in the
ST editor corresponds to the code on the device.

End ST editor
When ending the ST editor with Editor > Save and end (finish) (menu bar), there are the following options
(if debugging mode was active):

• Current program will remain loaded on the control.


The program last loaded onto the device in debugging mode must be used.
• Load previous program onto the control.
The program last loaded onto the device in debugging mode must not be used. Instead, the previous
(continuously loaded onto the device) program is used, if available.
• Clear control.
Neither the program last loaded onto the device in debugging mode nor the previous program must
be used.

13
2 User interface
NOTE!
In debugging mode, the program is only temporarily loaded onto the device (no backup in case of a pow-
er failure). In order to make changes permanently effective on the device, the setup file must be trans-
ferred to the device after exiting the ST editor (close ST code window by pressing "OK", data transfer to
the device).

NOTE!
The source code created in the ST editor is transferred into the device in compiled form. It is therefore
necessary to save the source code separately in a setup file.

14
3 System variables

3 System variables
The system variables include the input and output variables as well as the internal variables.
The input and output variables can be used to exchange values of different data types between the de-
vice and the ST module integrated in the device. The internal variables are only relevant within the ST
module and can be used to implement certain functions.

3.1 Input variables


The input variables provide device values for use in the ST module.
The values are assigned to the input variables in the setup program by selecting the respective signals
from the selectors (analog selector or digital selector). In addition, there are some variables that are per-
manently assigned in the device and therefore do not occur in the selectors.

bool_in

Designation Designation in the setup Description


program
bool_in01 bool_in01 Boolean input variables; flexible assignment in the
to to setup program (digital selector)
bool_in04 bool_in04

real_in

Designation Designation in the setup Description


program
real_in01 real_in01 Real input variables; flexible assignment in the set-
to to up program (analog selector)
real_in06 real_in06

dword_in

Designation Designation in the setup Description


program
dword_in01 (no designation, no fixed as- (These double-word input variables are not used.)
dword_in02 signment)

rtc.cdt

Designation Designation in the setup Description


program
rtc.cdt (no designation, fixed assign- This type DT input variable returns the time since
ment) the device was switched on (date and time start
each time the device is switched on from
01.01.1970 00:00:00:00).

15
3 System variables
3.2 Output variables
The output variables are used to transfer the values generated in the ST module to the device.
The output variables are available for configuration in the setup program and in the selectors (analog
selector or digital selector) on the device, and can be used individually. In addition, there are some vari-
ables that have certain functions on the device (e.g. text display) and therefore cannot be selected using
the selectors.
For certain output variables there are associated variables in the variable window with the designations
"...conf" and "...sec". These variables can be used to implement a defined behavior in the ST code in the
event of an error.
• The variable "...conf" can be set in the ST code to decide which value the corresponding output
variable will accept in case of an error: FALSE = current value; TRUE = replacement value.
Default setting: FALSE
• The variable "...sec" contains the replacement value; it can be set to a certain value or to the default
value in the ST code.
In case of REAL variables, the replacement value is checked for compliance with the scaling limits.
If it is outside the limits, the default value is used.
The SET_DEFAULT function is available for setting the default value.
 8.9 "Other functions", page 42

Error control
(runtime error, calculation error)

no Error yes

Check the „...conf“ variable

Output ...conf = TRUE


the current value no yes

Output Output
the current the „...sec“
value variable

bool_out

Designation Designation in the setup Description


program and on the device
bool_out01 1. ST digital output Boolean output variables; flexible use in the setup
to to program and on the device (digital selector)
bool_out04 4. ST digital output A description text can be assigned to each variable
in the setup program.

16
3 System variables
real_out

Designation Designation in the setup Description


program and on the device
real_out01 1. ST analog output Real output variables; flexible use in the setup pro-
to to gram and on the device (analog selector)
real_out06 6. ST analog output A description text can be assigned to each variable
in the setup program. It also requires settings that
affect the variable (e.g. scaling).

alarm

Designation Designation in the setup Description


program and on the device
alarm ST alarm Boolean output variable; flexible use in the setup
program and on the device (digital selector)
Unlike the bool_out variables, this variable has a
special designation. However, it can be freely used
in the ST code.

error_out

Designation Designation in the setup Description


program and on the device
error_out ST error Boolean output variable; flexible use in the setup
program and on the device (digital selector)
This variable is set to TRUE if the ST code cannot
be processed further, such as in the following cas-
es:
• Division by 0
• Incorrect array access
• Runtime exceeded
The variable is set to FALSE again if the ST code
has been completely run through once after the er-
ror occurred.

dword_out

Designation Designation in the setup Description


program and on the device
dword_out01, (no designation, fixed assign- Double-word output variables of the application;
dword_out02 ment) fixed assignment: text display on the device dis-
play
The texts must be entered in the "Display/opera-
tion" dialog under "Display texts" in the setup pro-
gram.

Variable Value Function


dword_out01 0 No text display
1 to 10 Devices in formats 108H, 108Q, 104:
The respective text (1 to 10) is displayed in line 3.
Devices in formats 132, 116:
The respective text (1 to 10) is displayed in line 1.

17
3 System variables
Variable Value Function
dword_out02 0 No text display
1 to 10 Devices in formats 108H, 108Q, 104:
The respective text (1 to 10) is displayed in line 4.
Devices in formats 132, 116:
The respective text (1 to 10) is displayed in line 2.

18
3 System variables
3.3 Internal variables
The internal variables can be used in the ST code to implement certain functions.

ext_error

Designation Description
ext_error Integer variable
The variable is 0 if the function Set_CP (set controller parameter) was executed
without errors. If an error occurs, the variable returns a value > 0.

reset_flag

Designation Description
reset_flag Boolean variable
The variable is set to TRUE after power on.
If the ST code is completely run through once without an error after power on, the
variable is set to FALSE. Otherwise, it stays as TRUE.
Debug mode: The first time the program is started in debug mode or after a program
stop, the variable is TRUE. After a second run through, it is set to FALSE.

sys_error

Designation Description
sys_error Real variable
The variable returns an error value if an error occurs during program execution:
1.00E+37 = general error value
1.0E+37 = underrange (underflow)
2.0E+37 = overrange (overflow)
3.0E+37 = invalid input value
4.0E+37 = division by zero
5.0E+37 = incorrect math value
7.0E+37 = invalid value (general)

week_day

Designation Description
week_day Integer variable
The variable includes the current day:
0 = Sunday, 1 = Monday, 2 = Tuesday, 3 = Wednesday, 4 = Thursday, 5 = Friday,
6 = Saturday
The day is derived from the input variable rtc.cdt.

19
3 System variables

20
4 Data types

4 Data types
The ST module supports the following data types:
• Boolean value (BOOL)
• Integer without prefix sign, 2 bytes (UINT)
• Double integer without prefix sign, 4 bytes (UDINT)
• Floating-point number (REAL)
• Date and time (DT or DATE_AND_TIME)
NOTE!
No range monitoring of the data types takes place during operations.
Exceptions: square root function (SRQT), reciprocal (1/x)

NOTE!
The ST module does not support variables that are stored via power off (retain variables).

Boolean value
Keyword: BOOL
Value range: TRUE (1) or FALSE (0)
Declaration of a variable (example):
VAR
bExample : BOOL;
END_VAR
Declaration of a constant (example):
VAR CONSTANT
bConstExample : BOOL := FALSE;
END_VAR
Assignment (example):
bExample := TRUE;

Integer (2 bytes)
Keyword: UINT
Value range: 0 to 65535 (0 to 216-1)
Declaration of a variable (example):
VAR
uiExample : UINT;
END_VAR
Declaration of a constant (example):
VAR CONSTANT
uiConstExample : UINT := 0;
END_VAR
Assignment (example):
uiExample := 1;

21
4 Data types
Double integer (4 bytes)
Keyword: UDINT
Value range: 0 to 4294967295 (0 to 232-1)
Declaration of a variable (example):
VAR
udExample : UDINT;
END_VAR
Declaration of a constant (example):
VAR CONSTANT
udConstExample : UDINT := 100000;
END_VAR
Assignment (example):
udExample := 200000;

Floating-point number
Keyword: REAL
Value range: -1.5E-45 to 1.0E37
(Values ≥ 1.0E37 are interpreted as error values.)
Declaration of a variable (example):
VAR
rExample : REAL;
END_VAR
Declaration of a constant (example):
VAR CONSTANT
rConstExample : REAL := 0.0;
END_VAR
Assignment (example):
rExample := 1.0;

Date and time


Keywords: DT or DATE_AND_TIME
Value range: yyyy-mm-dd-hh:mm:ss
Declaration of a variable (example):
VAR
dtExample : DT;
END_VAR
Declaration of a constant (example):
VAR CONSTANT
dtConstExample : DT := dt#2017-12-31-23:59:59;
END_VAR
Assignment (example):
dtExample := dt#2017-01-01-08:00:00;

22
4 Data types
4.1 Fields
All data types can also be declared as a one-dimensional or two-dimensional field (array) (see standard
DIN IEC 61131-3). The following sections use the data type REAL as an example.

One-dimensional field
Declaration of variables (example):
VAR
rArrayExample : ARRAY [0..2] OF REAL; (* field with 3 variables *)
END_VAR
Declaration of constants (example):
VAR CONSTANT
rArrayConstExample : ARRAY [0..2] OF REAL := [0.0, 0.1, 0.2]; (* field with 3 constants *)
END_VAR
Assignment (example):
rArrayExample[0] := 0.0;
rArrayExample[1] := 0.1;
rArrayExample[2] := 0.2;

Two-dimensional field
Declaration of variables (example):
VAR
rArrayExample : ARRAY [0..2, 0..1] OF REAL; (* field with 3 x 2 variables *)
END_VAR
Declaration of constants (example):
VAR CONSTANT
rArrayConstExample : ARRAY [0..2, 0..1] OF REAL :=
[0.0, 0.1, 0.2,
1.0, 1.1, 1.2]; (* field with 3 x 2 constants *)
END_VAR
Assignment (example):
rArrayExample[0,0] := 0.0;
rArrayExample[1,0] := 0.1;
rArrayExample[2,0] := 0.2;
rArrayExample[0,1] := 1.0;
rArrayExample[1,1] := 1.1;
rArrayExample[2,1] := 1.2;

23
4 Data types

24
5 Operators

5 Operators
All operators supported by the ST module are shown in the following table. The order in the table de-
pends on the ranking of the operators, starting with the highest rank.

Operation Symbol Admissible data types Example


Brackets (expression) a := 3.0 * (b - 1.0);
Function Identifier (argument list) i := MIN (3, j);
Negation - REAL a := -a;
Complement NOT BOOL, UINT, UDINTa a := NOT b;
Multiplication * UINT, UDINT, REAL i := 5 * j;
Division / a := 5.0 / b;
Modulo MOD UINT, UDINT j := i MOD 10;
Addition + UINT, UDINT, REAL i := 5 + j;
Subtraction - a := b - 5.0E20;
Comparison <, >, <=, >= UINT, UDINT, REAL, bExample := 5 <= j;
DATE_AND_TIME
Equality = BOOL, UINT, UDINT, bExample := 5 = i;
Inequality <> REAL, bExample := 5 <> j;
DATE_AND_TIME
AND & or AND BOOL, UINT, UDINTa bExample := x AND y;
Exclusive OR XOR BOOL, UINT, UDINT a bExample := x XOR y;
OR OR BOOL, UINT, UDINTa bExample := x OR y;
a Boolean variables are logically linked, integer variables are linked bit-by-bit.

25
5 Operators

26
6 Selection instructions

6 Selection instructions
A selection instruction executes an instruction or group of instructions based on a specified condition.

IF instruction
The IF instruction specifies that a group of instructions is only executed if the corresponding Boolean
expression returns the value TRUE. If the condition is incorrect, either no instruction may be executed
or the instruction group following the keyword ELSE (or the keyword ELSIF, if its associated Boolean
condition is true) must be executed.
Keywords:
IF, THEN, ELSIF, ELSE, END_IF
Example:
VAR
i : UINT;
END_VAR

IF reset_flag THEN
bool_out01 := false; (* after the reset, the outputs bool_out01 and *)
bool_out02 := false; (* bool_out02 are reset first and *)
i := 1; (* i set to 1 *)
END_IF;

if i>0 and i<=100 then


bool_out01 := true; (* in run through 1 to 100, the output bool_out01 is set ... *)
bool_out02 := false; (* and bool_out02 reset *)
elsif i>100 and i<=200 then
bool_out01 := false; (* in run through 101 to 200, the output bool_out01 is reset ... *)
bool_out02 := false; (* and bool_out02 set *)
else
i := 1; (* in run through 201, i is set to 1 and ... *)
bool_out01 := false; (* the outputs bool_out01 and ... *)
bool_out02 := false; (* bool_out02 are reset; it starts again from the beginning *)
end_if;

i := i + 1; (* i is increased by 1 *)

27
6 Selection instructions
CASE instruction
The CASE instruction combines several conditional instructions. It consists of an expression that con-
tains an integer variable and a list of instruction groups. Each group is identified by a mark consisting of
one or more integers (separated by commas). The value of the variable determines the mark and thus
the instruction group to be executed. The keyword ELSE can also be used as an option. If no value ap-
plies, the instruction group following the keyword ELSE is executed.
Keywords:
CASE, OF, ELSE, END_CASE
Example:
CASE i OF (* variable i must be UINT or UDINT *)
1: b1 := TRUE;
2, 3, 4: b2 := TRUE;
ELSE
b1 := FALSE;
b2 := FALSE;
END_CASE;

28
7 Repeat instructions

7 Repeat instructions
With repeat instructions (iterations), instructions and groups of instructions are executed repeatedly.
There are three types of repeat instructions:
• FOR
• WHILE
• REPEAT UNTIL

EXIT
With EXIT, a repeat instruction is terminated before the end condition of the iteration is fulfilled. If EXIT
is executed within a nested repetition construct, the innermost loop is exited within the EXIT.
NOTE!
For repeat instructions, you must ensure that there are no endless loops or very long running loops. The
runtime is monitored.

FOR instruction
The FOR instruction is used if the number of repeats is fixed.
Keywords:
FOR, TO, BY, DO, END_FOR
Examples:
FOR i := 10 TO 100 BY 10 DO (* control variable must be UINT *)
j := j + i; (* i runs from 10 to 100 in steps of 10 (10, 20, 30, …, 100) *)
END_FOR;

FOR i := 1 TO 5 DO (* without specification of "BY x", the ... *)


a := a + b; (* control variable increases by 1 in each run through (1, 2, 3, 4, 5) *)
a := a * 3.0;
END_FOR;

WHILE instruction
The WHILE instruction causes a group of instructions to be repeatedly executed until the associated
Boolean expression is incorrect (FALSE, untrue). If the Boolean expression is incorrect from the begin-
ning, the group of instructions is not executed at all.
Keywords:
WHILE, DO, END_WHILE
Example:
WHILE j < 100 DO
j := j + 2;
END_WHILE;

29
7 Repeat instructions
REPEAT instruction
The REPEAT instruction causes a group of instructions up to the keyword UNTIL to be repeatedly exe-
cuted until the associated Boolean condition is true (TRUE).
Keywords:
REPEAT, UNTIL, END_REPEAT
Example:
REPEAT
i := i - 2;
a := a + 2.0;
UNTIL i = 0 END_REPEAT;

30
8 Functions

8 Functions
The ST module supports the following functions:
• Type conversion
• Arithmetic functions
• Numerical functions
• Bit sequence functions (shift functions)
• Logical functions
• Selection (statistics)
• Comparison
• Date and time
• Specific functions (not part of the standard/norm)

8.1 Type conversion


Admissible data types
Argument: UINT, UDINT
Result: BOOL, UINT, UDINT, REAL

INT_TO_REAL
Converts an INTEGER into a REAL number.
Example:
a := INT_TO_REAL(10); (* a := 10.0 *)

INT_TO_DINT
Converts an INTEGER into a DOUBLE INTEGER.
Example:
a := INT_TO_DINT(10); (* a := 10 *)

INT_TO_BOOL
Converts an INTEGER into a BOOL value.
The result is FALSE if the argument is 0. In all other cases, the result is TRUE.
Examples:
a := INT_TO_BOOL(0); (* a = FALSE *)
b := INT_TO_BOOL(1); (* b = TRUE *)
c := INT_TO_BOOL(8); (* c = TRUE *)

DINT_TO_REAL
Converts a DOUBLE INTEGER into a REAL number.
Examples:
a := DINT_TO_REAL(100000); (* a = 100000.0 *)

31
8 Functions
DINT_TO_INT
Converts a DOUBLE INTEGER into an INTEGER.
Only the lower two bytes are evaluated (bit 0 to bit 15).
Examples:
a := DINT_TO_INT(1); (* a = 1; 1 = 0000 0000 0000 0001 = 0x0001 *)
b := DINT_TO_INT(65535); (* b = 65535; 65535 = 1111 1111 1111 1111 = 0xFFFF *)
c := DINT_TO_INT(65536); (* c = 0; 65536 = 0001 0000 0000 0000 0000 = 0x10000 *)
d := DINT_TO_INT(65537); (* d = 1, 65537 = 0001 0000 0000 0000 0001 =0x10001 *)

DINT_TO_BOOL
Converts a DOUBLE INTEGER into a BOOL value.
The result is FALSE if the argument is 0. In all other cases, the result is TRUE.
Examples:
a := DINT_TO_BOOL(0); (* a = FALSE: *)
b := DINT_TO_BOOL(1); (* b = TRUE *)
c := DINT_TO_BOOL(100000); (* c = TRUE *)

REAL_TO_INT
Converts a REAL number with rounding into an INTEGER.
Examples:
a := REAL_TO_INT(1.378); (* a = 1 *)
b := REAL_TO_INT(1.897); (* b = 2 *)

REAL_TO_DINT
Converts a REAL number with rounding into a DOUBLE INTEGER.
Examples:
a := REAL_TO_DINT(100000.378); (* a = 100000 *)
b := REAL_TO_DINT(100000.897); (* b = 100001 *)

32
8 Functions
8.2 Arithmetic functions
Admissible data types
Argument: UINT, UDINT, REAL (only REAL for negation, only UINT or UDINT for modulo)
Result: UINT, UDINT, REAL

Addition
Addition is an expandable function. The sum of the arguments is returned as the result.
Example:
OUT := IN1 + IN2 + ... INn;

Subtraction
The second argument is subtracted from the first argument as a result.
Example:
OUT := IN1 - IN2;

Multiplication
Multiplication is an expandable function. The result is obtained by multiplying the arguments.
Example:
OUT := IN1 * IN2 * ...INn;

Division
The quotient of the two arguments is returned as the result.
The result of the division of integers (UINT or UDINT) is an integer with truncation of the decimal places
(example: 7/3 = 2).
Example:
OUT := IN1 / IN2;

Negation
REAL numbers can be negated.
Example:
OUT := -IN;

Modulo
The arguments of the modulo function (%) must be integers (UINT or UDINT). The result of the modulo
function is the same as processing the following instruction:
IF (IN2 = 0) THEN OUT := 0;
ELSE OUT := IN1 - (IN1 / IN2) * IN2;
END_IF
The result of the division of integers (UINT or UDINT) in the ELSE branch of the above IF selection in-
struction is an integer with truncation of the decimal places.
Example:
IN1 := 17;
IN2 := 3;
OUT := IN1 % IN2; (* OUT := 2 *)

33
8 Functions
8.3 Numerical functions
Admissible data types
Argument: REAL
Result: REAL

ABS (IN)
Returns the absolute value of IN.
Example:
IN := -2.3;
OUT := ABS(IN); (* OUT = 2.3 *)

SQRT (IN)
Returns the square root of IN.
If IN is negative, the error value 5.0E+37 is returned.
Example:
IN := 4.0;
OUT := SQRT(IN); (* OUT = 2.0 *)

LN (IN)
Returns the natural logarithm of IN.
Example:
IN := 2.718282; (* number e (rounded) *)
OUT := LN(IN); (* OUT = 1.0 (rounded) *)

LOG (IN)
Returns the base 10 logarithm of IN.
Example:
IN := 100.0;
OUT := LOG(IN); (* OUT = 2.0 *)

EXP (IN)
Returns the natural exponential function of IN.
Example:
IN := 2.0;
OUT := EXP(IN); (* OUT = 7.389056 *)

34
8 Functions
SIN (IN)
Returns the sine of IN (radian).
Example:
IN := 1.5708; (* corresponds to 90° *)
OUT := SIN(IN); (* OUT = 1.0 *)

COS (IN)
Returns the cosine of IN (radian).
Example:
IN := 0.0; (* corresponds to 0° *)
OUT := COS(IN); (* OUT = 1.0 *)

TAN (IN)
Returns the tangent of IN (radian).
Example:
IN := 0.7854; (* corresponds to 45° *)
OUT := TAN(IN); (* OUT = 1.0 *)

ASIN (IN)
Returns the arc sine of IN (radian).
Example:
IN := 1.0;
OUT := ASIN(IN); (* OUT = 1.5708; corresponds to 90° *)

ACOS (IN)
Returns the arc cosine of IN (radian).
Example:
IN := 1.0;
OUT := ASIN(IN); (* OUT = 0.0; corresponds to 0° *)

ATAN (IN)
Returns the arc tangent of IN (radian).
Example:
IN := 1.0;
OUT := ATAN(IN); (* OUT = 0.7854; corresponds to 45° *)

35
8 Functions
8.4 Bit sequence functions
Admissible data types
Argument: UINT, UDINT
Result: UINT, UDINT

SHL (IN, n)
Moves the bit sequence of the IN argument to the left by n bits. Subsequent digits are filled with 0 from
the right.
Example:
IN := 255; (* bit sequence: 0000 0000 1111 1111 *)
OUT := SHL(IN, 4); (* OUT = 4080; bit sequence: 0000 1111 1111 0000 *)

SHR (IN, n)
Moves the bit sequence of the IN argument to the right by n bits. Subsequent digits are filled with 0 from
the left.
Example:
IN := 255; (* bit sequence: 0000 0000 1111 1111 *)
OUT := SHR(IN, 4); (* OUT = 15; bit sequence: 0000 0000 0000 1111 *)

ROL (IN, n)
Rotates the bit sequence of the IN argument to the left by n bits in a circle.
Example:
IN := 43690; (* bit sequence: 1010 1010 1010 1010 *)
OUT := ROL(IN, 1); (* OUT = 21845; bit sequence: 0101 0101 0101 0101 *)

ROR (IN, n)
Rotates the bit sequence of the IN argument to the right by n bits in a circle.
Example:
IN := 21845; (* bit sequence: 0101 0101 0101 0101 *)
OUT := ROR(IN, 1); (* OUT = 43690; bit sequence: 1010 1010 1010 1010 *)

36
8 Functions
8.5 Logical functions
Boolean variables are linked logically, UINT and UDINT variables are linked bit-by-bit.
If there are more than two parameters, each pair is always linked from left to right.

Admissible data types


Operand: BOOL, UINT, UDINT
Result: BOOL, UINT, UDINT

AND
AND link
Examples:
Logical link:
x := TRUE;
y := FALSE;
z := x AND y; (* z = FALSE *)
Bit-by-bit link:
a := 5;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0101 = 5
b := 6;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0110 = 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._______
c := a AND b; (* c = 4 *) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0100 = 4

OR
OR link
Examples:
Logical link:
x := TRUE;
y := FALSE;
z := x OR y; (* z = TRUE *)
Bit-by-bit link:
a := 5;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0101 = 5
b := 6;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0110 = 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._______
c := a OR b; (* c = 7 *) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0111 = 7

XOR
Exclusive OR link
Examples:
Logical link:
x := TRUE;
y := FALSE;
z := x XOR y; (* z = TRUE *)
Bit-by-bit link:
a := 5;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0101 = 5
b := 6;. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0110 = 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._______
c := a XOR b; (* c = 3 *) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0011 = 3

37
8 Functions
NOT
Inversion (form complement)
Examples:
IN := 1;
OUT := NOT IN; (* OUT = 0 *)
IN := 43690; (* IN = 1010 1010 1010 1010 *)
OUT := NOT IN; (* OUT = 21845; OUT = 0101 0101 0101 0101 *)

38
8 Functions
8.6 Selection
Admissible data types
Argument: UINT, UDINT, REAL (with SEL, additionally BOOL for the selector)
Result: UINT, UDINT, REAL

MAX
Returns the biggest argument as a result.
Example:
OUT := MAX(8, 9, 10, 11, 12); (* OUT := 12 *)

MIN
Returns the smallest argument as a result.
Example:
OUT := MIN(8, 9, 10, 11, 12); (* OUT := 8 *)

LIMIT
Checks whether a value (IN) is within a certain range (MIN, MAX). If the value is within the range, the
value itself is returned. If the value is below the range, the lower range limit is returned. If the value is
above the range, the upper range limit is returned.
Examples:
OUT := LIMIT(IN, MIN, MAX);
OUT := LIMIT(15, 10, 20); (* OUT = 15 *)
OUT := LIMIT(5, 10, 20); (* OUT = 10 *)
OUT := LIMIT(25, 10, 20); (* OUT = 20 *)

SEL
Selects one of two values (IN0, IN1) depending on a Boolean variable (G). The data type of the values
IN0 and IN1 must be identical.
Examples:
OUT := SEL(G, IN0, IN1);
OUT := SEL(G, 10, 20); (* G = FALSE: OUT = 10 *)
OUT := SEL(G, 10, 20); (* G = TRUE: OUT = 20 *)

39
8 Functions
8.7 Comparison
Admissible data types
Argument with LT, LE, GT, GE: UINT, UDINT, REAL, DT
Argument with EQ and NE: BOOL, UINT, UDINT, REAL, DT
Result: BOOL

< (LT)
Compares arguments on whether one is smaller than another.
Examples:
bOUT := IN1 < IN2; (* bOUT := TRUE, if IN1 is smaller than IN2 *)
bOUT := (IN1 < IN2) & (IN2 > IN3) & ... & (INn-1 > INn);

<= (LE)
Compares arguments on whether one is smaller than or equal to another.
Examples:
bOUT := IN1 <= IN2; (* bOUT := TRUE, if IN1 is smaller than or equal to IN2 *)
bOUT := (IN1 <= IN2) & (IN2 <= IN3) & ... & (INn-1 <= INn);

> (GT)
Compares arguments on whether one is larger than another.
Examples:
bOUT := IN1 > IN2; (* bOUT := TRUE, if IN1 is larger than IN2 *)
bOUT := (IN1 > IN2) & (IN2 > IN3) & ... & (INn-1 > INn);

>= (GE)
Compares arguments on whether one is larger than or equal to another.
Example:
bOUT := IN1 >= IN2; (* bOUT := TRUE, if IN1 is larger than or equal to IN2 *)

= (EQ)
Compares arguments on whether they are equal.
Example:
bOUT := IN1 = IN2; (* bOUT := TRUE, if IN1 is equal to IN2 *)

<> (NE)
Compares arguments on whether they are unequal.
Example:
bOUT := IN1 <> IN2; (* bOUT := TRUE, if IN1 is unequal to IN2 *)

40
8 Functions
8.8 Date and time
These are specific functions that are not part of the DIN IEC 61131-3 standard.
For example, these functions can be used to query the input variable rtc.cdt, which returns the time since
the device was switched on (date and time start each time the device is switched on from 01.01.1970
00:00:00:00).

Admissible data types


Argument: DT (or DATE_AND_TIME)
Result: UINT

GET_YEAR
Returns the year (with century).
Examples:
iOUT := GET_YEAR(dt#2017-03-20-17:45:12); (* iOUT = 2017 *)

GET_MONTH
Returns the month.
Example:
iOUT := GET_MONTH(dt#2017-03-20-17:45:12); (* iOUT = 03 *)

GET_DAY
Returns the day.
Example:
iOUT := GET_DAY(dt#2017-03-20-17:45:12); (* iOUT = 20 *)

GET_HOUR
Returns the hour.
Example:
iOUT := GET_HOUR(dt#2017-03-20-17:45:12); (* iOUT = 17 *)

GET_MINUTE
Returns the minute.
Example:
iOUT := GET_MINUTE(dt#2017-03-20-17:45:12); (* iOUT = 45 *)

GET_SECOND
Returns the second.
Example:
iOUT := GET_SECOND(dt#2017-03-20-17:45:12); (* iOUT = 12 *)
iOUT := GET_SECOND(rtc_cdt); (* iOUT = 59, if rtc_cdt = 1970-01-01 00:00:59 *)

41
8 Functions
8.9 Other functions
These are specific functions that are not part of the DIN IEC 61131-3 standard.

IS_VALID
Checks the validity of a REAL number. The result is a Boolean value (valid = TRUE, invalid = FALSE).
Values ≥ 1.00E+37 (general error value) are considered as invalid, as are the values "Infinity" (INF) and
"No number" (NaN).
Examples:
bOUT := IS_VALID(1.2); (* bOUT = TRUE *)

SET_DEFAULT
Sets a REAL or a BOOL number to the default value.
Default value REAL: 5.0E+37 (math error value)
Default value BOOL: FALSE
Example:
SET_DEFAULT(bOUT); (* bOUT = FALSE *)
SET_DEFAULT(rOUT); (* rOUT = 5.0E+37 *)

42
9 Function modules

9 Function modules
Instance
A function module – called a function block in the ST editor – is a program organizational unit that returns
one or more values when executed (see also standard DIN IEC 61131-3). A function module can exist
in several instances (copies). Each of these instances has a corresponding identifier. The instances of
a function module are independent of each other.
If a function module called TON exists, for example in 4 instances, the individual instances are ad-
dressed with TON01, TON02, TON03, TON04.
The ST module includes the following function modules:

Identifier Instances Function


CTUD 4 Software up/down counter
TP 4 Impulse generator
TON 4 Switch-on delay
TOF 4 Switch-off delay
R_TRIG 4 Rising edge detection (0 -> 1)
F_TRIG 4 Falling edge detection (1 -> 0)
SR 4 Bistable function module (set priority)
RS 4 Bistable function module (reset priority)
SET_CP 1 Specify controller parameter

Parameters
One or more parameters (inputs) are passed to the function modules. The parameters follow in round
brackets after the specification of the instance. The sequence of the parameters is fixed. Like any in-
struction, the call for a function module is completed with a ";".
Example:
TON01(TRUE,5,1);

Inputs/outputs
The statuses of the inputs and outputs of all instances of the function modules remain constant until the
next call of the instance of the function module. The outputs can be queried and used in any operations.

Access to outputs
Outputs (structure elements) of function modules are accessed as usual in the programming language
Pascal.
Example:
Queries of the output ET of the function module TON with instance 01:
OUT := TON01.ET;

43
9 Function modules
9.1 Software up/down counter
The counter provides the following functions:
• Counting up
• Counting down
• Reset the counter to 0
• Set an upper counter value
• Query in case the upper counter value is exceeded
• Query of counter status 0
• Query counter value
The counter counts the positive edges at the inputs CU (counting upwards) and CD (counting down-
wards).

Call
CTUD<instance> (CU, CD, R, LD, PV);

Inputs
The parameters R, LD, CU and CD are sorted in descending order in the table according to their priority.

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
R BOOL TRUE = set counter status to 0
LD BOOL TRUE = set upper counter value
CU BOOL Positive edge = count up
CD BOOL Positive edge = count down
PV UINT Upper counter value

Outputs

Parameter Data type Query; (* description *)


CV UINT OUT := CTUD<instance>.CV;
(* OUT = counter status *)
QU BOOL OUT := CTUD<instance>.QU;
(* OUT = TRUE, if counter status > upper counter value *)
QD BOOL OUT := CTUD<instance>.QD;
(* OUT = TRUE, if counter status <= 0 *)

Comment
To set the upper counter value with LD, R must not be TRUE.
The values of the inputs/outputs are not retained via power off.

Examples
CTUD01 (IN, FALSE, FALSE, FALSE, 100); (* upwards counting of the positive edges of IN *)
CTUD01 (FALSE, IN, FALSE, FALSE, 100); (* downwards counting of the positive edges of IN *)
CTUD01 (IN, FALSE, TRUE, FALSE, 100); (* set counter status to 0 *)
CTUD01 (IN, FALSE, FALSE, TRUE, 100); (* set upper counter value: 100 *)

44
9 Function modules
9.2 Impulse generator
The following diagram illustrates the operating principle of the impulse generator:

Call
TP<instance> (IN, PT, TimeBase);

Inputs

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
IN BOOL Positive edge at IN sets Q for the time PT to TRUE
PT UINT Time (unit: TimeBase), for Q = TRUE, IN = TRUE
TimeBase UINT Unit of PT:
1 = ms
2=s
3 = min

Outputs

Parameter Data type Query; (* description *)


Q BOOL OUT := TP<instance>.Q;
(* OUT = TRUE for the time PT, if IN := 0 -> 1 *)
ET UINT OUT := TP<instance>.ET;
(* OUT = time passed since IN = TRUE until Q = FALSE (time
passed since the start of the active impulse phase) *)

Comment
The TimeBase parameter is an extension to DIN IEC 61131-3. This extension does not constitute a lim-
itation to the standard. According to the standard, the time limit is "implementation-dependent".
The values of the inputs/outputs are not retained when the power is turned off.

45
9 Function modules
The time resolution of the impulse length is 150 ms (device cycle time).

Example
TP01(IN, 5, 3);
(* Positive edge at IN sets TP01.Q for approx. 5 minutes to TRUE (note time resolution).
TP01.ET liefert die vergangene Zeit in Minuten seit Beginn der aktiven Pulsphase. *)

46
9 Function modules
9.3 Switch-on delay
The following diagram illustrates the operating principle of the switch-on delay:

Call
TON<instance> (IN, PT, TimeBase);

Inputs

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
IN BOOL IN = TRUE sets Q = TRUE, after the time PT is expired
PT UINT Delay time (unit: TimeBase)
TimeBase UINT Unit of PT:
1 = ms
2=s
3 = min

Outputs

Parameter Data type Query; (* description *)


Q BOOL OUT := TON<instance>.Q;
(* OUT = TRUE, if IN = TRUE and PT expired *)
ET UINT OUT := TON<instance>.ET;
(* OUT = time passed since IN = TRUE until Q = TRUE or until
IN = FALSE *)

Comment
The TimeBase parameter is an extension to DIN IEC 61131-3. This extension does not constitute a lim-
itation to the standard. According to the standard, the time limit is "implementation-dependent".
The values of the inputs/outputs are not retained when the power is turned off.

47
9 Function modules
The time resolution of the delay time is 150 ms (device cycle time).

Example
TON01(IN, 6, 2);
(* IN = TRUE sets TON01.Q to TRUE after 6 seconds.
TON01.Q bleibt solange TRUE, wie IN = TRUE ist.
TON01.ET liefert die vergangene Zeit in Sekunden von IN = TRUE bis TON01.Q = TRUE (max. 6 Sekun-
den) oder bis IN = FALSE. *)

48
9 Function modules
9.4 Switch-off delay
The following diagram illustrates the operating principle of the switch-off delay:

Call
TOF<instance> (IN, PT, TimeBase);

Inputs

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
IN BOOL IN = TRUE sets Q = TRUE
IN = FALSE sets Q around the time PT delayed to FALSE
PT UINT Delay time (unit: TimeBase)
TimeBase UINT Unit of PT:
1 = ms
2=s
3 = min

Outputs

Parameter Data type Query; (* description *)


Q BOOL OUT := TOF<instance>.Q;
(* OUT = TRUE, if IN = TRUE or if IN = FALSE and PT has not
yet expired *)
ET UINT OUT := TOF<instance>.ET;
(* OUT = time passed since IN = FALSE until Q = FALSE
or until IN = TRUE *)

49
9 Function modules
Comment
The TimeBase parameter is an extension to DIN IEC 61131-3. This extension does not constitute a lim-
itation to the standard. According to the standard, the time limit is "implementation-dependent".
The values of the inputs/outputs are not retained when the power is turned off.
The time resolution of the delay time is 150 ms (device cycle time).

Example
TOF01(IN, 450, 1);
(* IN = TRUE sets TOF01.Q to TRUE.
After IN = FALSE, TOF01.Q remains TRUE until the time PT = 450 ms has expired.
TOF01.ET returns the time passed in milliseconds from IN = FALSE until TOF01.Q = FALSE (max. 450
ms) or until IN = TRUE. *)

50
9 Function modules
9.5 Rising edge detection
This function module detects a rising edge (transition 0 -> 1) .

Call
R_TRIG<instance> (CLK);

Input

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
CLK BOOL Due to a rising edge (0 -> 1) at CLK, Q = TRUE

Output

Parameter Data type Query


Q BOOL OUT := R_TRIG<instance>.Q;

Comment
The operating principle of the function module corresponds to the following program code:
VAR CLK : BOOL; END_VAR
VAR Q : BOOL; END_VAR
VAR M : BOOL := FALSE; END_VAR
Q := CLK AND NOT M;
M := CLK;
The Q output remains at its Boolean value from one call until the next. It follows the transition of the input
signal (CLK) from "0" to "1" and returns to "0" the next time it is called.

Example
IF reset_flag THEN
bool_out01 := FALSE;
END_IF;
R_TRIG01 (bool_in01); (* detection of a rising edge at input bool_in01 *)
bool_out01 := R_TRIG01.Q; (* short impulse at output bool_out01 for rising edge at input *)

51
9 Function modules
9.6 Falling edge detection
This function module detects a falling edge (transition 1 -> 0) .

Call
F_TRIG<instance> (CLK);

Input

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
CLK BOOL Due to a falling edge (1 -> 0) at CLK, Q = TRUE

Output

Parameter Data type Query


Q BOOL OUT := F_TRIG<instance>.Q;

Comment
The operating principle of the function module corresponds to the following program code:
VAR CLK : BOOL; END_VAR
VAR Q : BOOL; END_VAR
VAR M : BOOL := TRUE; END_VAR
Q := NOT CLK AND NOT M;
M := NOT CLK;
The Q output remains at its Boolean value from one call until the next. It follows the transition of the input
signal (CLK) from "1" to "0" and returns to "0" the next time it is called.

Example with R_TRIG and F_TRIG

bool_in01
t

bool_out01
t

bool_out02
t
IF reset_flag THEN
bool_out01 := FALSE;
bool_out02 := FALSE;
END IF;
R_TRIG01 (bool_in01); (* detection of a rising edge at input bool_in01 *)
bool_out01 := R_TRIG01.Q; (* short impulse at output bool_out01 for rising edge at input *)
F_TRIG01 (bool_in01); (* detection of a falling edge at input bool_in01 *)
bool_out02 := F_TRIG01.Q; (* short impulse at output bool_out02 for falling edge at input *)

52
9 Function modules
9.7 Bistable function SR
Bistable function (set priority) with lock

Call
SR<instance> (S1, R);

Inputs

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
S1 BOOL S1 = TRUE sets Q1 = TRUE
R BOOL R = TRUE sets Q1 = FALSE, if S1 = FALSE

Outputs

Parameter Data type Query


Q1 BOOL OUT := SR<instance>.Q1;

Comment
Output Q1 remains TRUE after being set by S1 until it is reset with R.
If S1 and R are set simultaneously (TRUE), output Q1 is also set (TRUE).

Logic function

Example
SR1 (bool_in01, bool_in02); (* set with input bool_in01, reset with input bool_in02 *)
bool_out01 := SR1.Q1; (* the status is output via output bool_out01. *)

53
9 Function modules
9.8 Bistable function RS
Bistable function (reset priority) with lock

Call
RS<instance> (S, R1);

Inputs

Parameter Data type Description


<Instance> 01 to 04 (specify instance with two digits)
R1 BOOL R1 = TRUE sets Q1 = FALSE
S BOOL S = TRUE sets Q1 = TRUE, if R1 = FALSE

Outputs

Parameter Data type Query


Q1 BOOL OUT := RS<instance>.Q1;

Comment
After resetting with R1, output Q1 remains FALSE until it is set with S.
If R1 and S are set simultaneously (TRUE), output Q1 is reset (FALSE).

Logic function

Example
RS1 (bool_in01, bool_in02); (* reset with input bool_in02, set with input bool_in01 *)
bool_out02 := RS1.Q1; (* the status is output via output bool_out02. *)

54
9 Function modules
9.9 Set controller parameter
The controller parameters of the second parameter set can be changed with this function module (spe-
cific function, not part of the standard DIN IEC 61131-3).

Call
Set_CP (Set, Key, Value);

Inputs

Parameter Data type Description


Controller UINT Controller no.: 0 = controller 1; 1 = controller 2; ...
Set = 0, if the device only has one controller (controller chan-
nel).
Parameter UINT Parameter:
0 = Xp1 (proportional band 1)
1 = Xp2 (proportional band 2)
2 = Tv1 (derivative time 1)
3 = Tv2 (derivative time 2)
4 = Tn1 (reset time 1)
5 = Tn2 (reset time 2)
6 = Cy1 (cycle time 1)
7 = Cy2 (cycle time 2)
8 = Y1 (max. output value limit)
9 = Y2 (min. output value limit)
Value REAL Value of the parameter concerned

Outputs
This function module has no outputs.

Comment
The values of the parameters are checked before being adopted in the controller. If the value is outside
the admissible range of values, the adoption is refused and an error value is returned in the variable ex-
t_error (can be evaluated in the ST code). If the value is valid, the new value is used from this point on.
The changed values are not stored in the controller configuration. After a reset (power on) the stored
values are used again as controller parameters.
To change several parameters, the function module must be called more than once (see example: two
calls).

55
9 Function modules
Example
VAR
controller : UINT; (* controller no. *)
para1 : UINT; (* Parameter 1 *)
value1 : REAL; (* value of parameter 1 *)
para2 : UINT; (* Parameter 2 *)
value2 : REAL; (* value of parameter 2 *)
END_VAR
SET_CP (controller, para1, value1);
SET_CP (controller, para2, value2);

56
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Street address: JUMO House 6733 Myers Road
Moritz-Juchheim-Straße 1 Temple Bank, Riverway East Syracuse, NY 13057, USA
36039 Fulda, Germany Harlow, Essex, CM20 2DY, UK
Delivery address: Phone: +44 1279 63 55 33 Phone: +1 315 437 5866
Mackenrodtstraße 14 Fax: +44 1279 62 50 29 Fax: +1 315 437 5860
36039 Fulda, Germany Email: [email protected] Email: [email protected]