Temperature Controller: Instruction Manual
Temperature Controller: Instruction Manual
T
MILACRON MODEL
TEMPERATURE CONTROLLER
TEMPERATURE CONTROLLER
INSTRUCTION MANUAL
MFC with
T Series Instrument
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TABLE OF CONTENTS
1.0 GENERAL 7
1.1 Receiving Instructions 8
1.2 Introduction 8
1.3 Safety 8
1.4 Efficiency 9
1.5 Water Treatment 9
1.6 Components 10
2.0 INSTALLATION 13
2.1 General 14
2.2 To and from process connections 14
2.3 Water supply connection 15
2.4 Drain connection 15
2.5 Electrical connection 17
4.0 TROUBLESHOOTING 49
4.1 Unit will not start (Display is not Illuminated) 50
4.2 Unit will not start (Display is Illuminated) 50
4.3 Unit Stops 50
4.4 Unit Overheats 51
4.5 Unit Underheats 52
4.6 Pressure Relief Valve Leaks 53
4.7 Cooling Valve Fault 54
5.0 MAINTENANCE 55
5.1 Pump Seal Replacement 56
5.2 Heater Replacement 59
5.3 Cooling Valve Service 61
5.4 Voltage Change 67
5.5 Sensor Probe Service 68
5.6 Pressure Switch Service 68
5.7 Electronic Instrument Repair Policy And Procedure 69
5.8 Temperature Probe Calibration 70
5.9 Heater Contactor & Pump Motor Starter 71
6.0 COMPONENTS 73
6.1 Mechanical system 74
6.2 Electrical system 76
Page: 6
Temperature Control Unit : MFC with T Series Instrument
1.0 GENERAL
1.1 Receiving Instructions
1.2 Introduction
1.3 Safety
1.4 Water Treatment
1.5 Components
A. Temperature control units are generally shipped skid mounted, boxed and wrapped in
plastic prior to shipment.
B. Unbox the unit before accepting delivery. Check for visible damage and document any
evident damage on the delivery receipt or refuse the shipment. Shipping damage is the
responsibility of the carrier.
C. In order to expedite payment for damages, should they occur, follow proper procedures
and keep detailed records. Take photographs of any suspected damage.
1.2 INTRODUCTION
A. This manual covers temperature control units from 10 to 34 kW of heating capacity using
the T Series microprocessor control instrument. The standard fluid operating temperature
range for this temperature control unit is 32°F to 250°F for units. Consult the factory if you
have questions about the operating range of your temperature control unit.
B. The intent of this manual is to serve as a guide in the installation, operation and
maintenance of your temperature control unit. Improper installation can lead to equipment
damage and poor performance. Failure to follow the installation, operation and
maintenance instructions may result in damage to the unit that is not covered under the
limited warranty. This manual is for standard products. The information contained in this
manual is intended to be general in nature. The information is typical only and may not
represent the actual unit purchased.
C. When calling for assistance from the Manufacturer’s Service Department, it is important
to know the model and serial number of the particular unit. The model number includes
critical unit information which is helpful when troubleshooting operating difficulties. The
serial number allows the service team to locate manufacturing and testing records which
can have additional information relating to a particular unit.
WARNING: This equipment contains hazardous voltages that can cause severe injury or
death. Disconnect and lock out incoming power before installing or servicing the equipment.
1.3 SAFETY
A. It is important to become thoroughly familiar with this manual and the operating
characteristics of the unit.
C. Observe all warning and safety placards applied to the unit. Failure to observe all
warnings can result in serious injury or death to the operator and severe mechanical
damage to the unit.
D. Observe all safety precautions during installation, startup and service of this equipment
due to the presence of high voltage. Only qualified personnel should install, startup and
service this equipment.
E. When working on this equipment, observe precautions in literature and on tags, stickers
and labels located on the equipment. Wear work gloves and safety glasses.
F. Before installing and operating the unit, be aware of and follow any local laws and codes
that apply to the installation.
WARNING
J5318-BF
3. Alerts the user to a hot surface danger due to high operating temperatures.
CAUTION
A. The fluid used in your temperature control unit will greatly effect its short and long-
term operation. Lack of as well as improper water treatment can damage the
temperature control unit by causing scale build-up, excessive corrosion and/or bacterial
contamination. It is the equipment owner’s responsibility to prevent damage caused by
poor water quality. The services of a water treatment professional is recommended.
B. The use of untreated or improperly treated water in a temperature control unit may result
in scaling, erosion, corrosion, algae, bacteria or slime. The manufacturer recommends
filtering the process water to prevent solids from plugging critical parts.
D. The Manufacture assumes no responsibility for equipment failures which result from
untreated or improperly treated water.
E. Do not use deionized water in this unit. Some customized units may be compatible with
deionized water. Consult the factory before using deionized water.
1.5 COMPONENTS
Electrical Panel
Lift-Off Cover
Panel
Instrument
(Not visible in this photograph.)
Pressure Gauges
Heater
Thermoformed Cover
Panel
Electrical Panel
(Inside stainless steel cabinet.)
Pump Motor
Pump
Vented Stainless
Steel Cabinet
Caster
2.0 INSTALLATION
2.1 General
2.2 To and From Process Connections
2.3 Water Supply Connection
2.4 Drain Connection
2.5 Electrical Connection
2.1 GENERAL
A. Care should be taken to use materials (hose, rigid piping, valves or filters) rated for
the temperature and pressure duty of your unit. Most units have a maximum operating
temperature of 300°F or less and a maximum pressure of 150 PSI. The unit is most
efficient when full size plumbing is run from the unit connections to and from the process.
If necessary, reduce the plumbing size at your process, not at the unit.
B. Be certain all process piping materials have the equivalent or larger diameter of the
particular process connection.
To Process
*Drain
From Process
**Water Supply
Drain*
B. Connect the unit’s From Process port to the Water Out port on the process manifold.
C. Please note: Process water piping circuitry should be designed to avoid an excessive
use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid
tight twists or curls and excessive lengths.
D. Valves and filters may be installed in the process water piping circuitry to facilitate service
and maintenance, provided that such devices maintain the full inside diameter of the
process connection. If installed, all such devices must be open and clean during unit
operation.
WARNING: Check local codes to determine proper use of back flow prevention device in
water supply line.
A. Connect the unit’s Water Supply port to the plant’s city water, well water, tower water or
chilled water supply.
B. Water supply pressure requirements vary with operating temperatures. The chart below
shows the required operating water supply pressures for various operating process
temperatures. The required water supply pressure retains process water in a liquid state
at temperatures over 180°F. Failure to maintain the required water supply pressure will
cause premature failure of and increase maintenance in susceptible areas such as the
shaft seal and heater.
OPERATING TEMPERATURE
180°F 190°F 200°F 210°F 220°F 230°F 240°F 250°F
20 PSI 25 PSI 30 PSI 35 PSI 40 PSI 45 PSI 50 PSI 55 PSI
WATER SUPPLY PRESSURE
D. Static water supply pressure can be determined at the unit’s location by reading the unit’s
0-160 PSI pressure gauges when the unit’s pump motor is OFF.
A. Connect the unit’s DRAIN port to one of the following, Typical pressure reducing
valve installation (shown on
determined by the water supply source: S-925 model).
B. The factory recommends a minimum of 10 psi pressure differential between the water
supply and drain line for proper cooling.
2. Consult factory when selecting the correct cooling valve for your application.
WARNING: Never operation the Temperature Control Unit with a closed drain.
A. STANDARD MODELS
1. Electrical power supply requirements for standard units are identified on the
equipment data tag. Verify that available voltage supply is the same as the unit’s
voltage requirements.
Use of incorrect voltage will void the unit’s warranty and cause a significant
hazard that may result in serious personal injury and/or unit damage.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage
requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s
warranty and cause a significant hazard that may result in serious personal injury and unit
damage.
WARNING: Electric Shock Hazard. High Voltage is present in the electrical cabinet.
Disconnect power before servicing. Follow all facility lock-out tag-out procedures.
3. For units with 24 and 34 KW heaters, the operator must provide a four conductor
power cable and the fused disconnect.
4. The owner supplied fused disconnect must be sized and installed according to
the unit’s power supply requirements and local electrical codes.
WARNING: DO NOT connect the unit to a voltage supply source not equal
to the unit’s voltage requirements as specified on the unit’s data plate. Use
of incorrect voltage will void the unit’s warranty and cause a significant
hazard that may result in damage to the unit or serious personal injury.
2. Appropriate conduit and fittings should be selected which will maintain the
integrity of the cabinet.
WARNING: Check that all electrical connections are tight before starting.
Disconnect power before servicing. Follow all facility lock-out tag-out procedures.
D. GENERAL
1. Make certain all ground connections to the unit are properly affixed. A proper
connection to earth ground is required. A conduit ground is not a reliable
conductor!
2. Make certain the power conductor, disconnecting means, and fusing are properly
sized according to the unit’s power supply requirements.
3. Make certain all electrical connections are tightly affixed. Any loose wiring
connections must be tighten before engaging the power supply.
Page: 20
Temperature Control Unit : MFC with T Series Instrument
3.0 OPERATIONS
3.1 General
3.2 Machine Start Up and Operation
3.3 Instrument Operation : Basic Use
3.4 Instrument Operation : Basic Setup
3.5 Instrument Operation : Remote Setup
3.6 Instrument Operation : Features Setup
3.7 Instrument Operation : Machine Setup
3.8 Instrument Operation : Tools and Status
3.9 Shut Down Sequence
3.1 GENERAL
A. Failure to follow the factory required operation procedures may adversely affect the unit’s
ability to adequately control process temperature and may create a hazardous operating
condition which may result in unit damage or serious operator injury.
3.2 Machine start-up/operations procedure - follow this segment to start the unit
after the initial installation or to restart the unit after reinstallation to the same or
different process. This section includes information on system fill, electric motor
phasing (pump rotation) and process flow adjustments.
3.3 Instrument Operation - follow this segment to start up and operate the
instrument. This section includes information on automatic and manual venting,
setpoint selection and adjustment, and feature explanations.
3.4 Shut down procedure - follow this segment to shut down the unit. This segment
includes information on system cool down, shut down, electrical power supply
precautions, and disconnection from the system.
A. System Fill
1. Engage the water supply source by opening the water supply valve (customer
installed) at the unit’s location. If a valve is not installed, engage the water supply
source at the plant’s water supply central control point.
2. Once the water supply source is open, the unit will fill automatically. Allow a
few moments for the unit to completely fill. The operator can determine the unit
is properly filled when the To Process pressure gauge and the From Process
pressure gauge stabilize at equal or closely similar pressure.
3. The operator must check for any water leakage in the unit’s mechanical system,
the process, and throughout the plant’s water supply system. If a water leak
is observed, the operator must disengage the water supply system, relieve all
pressure, and repair the leak. The operator must verify the leak is repaired by
refilling the system as outlined in this procedure.
4. During system fill, air is often trapped in the water system. Air is purged
automatically via the AVTTM valve during initial pump start-up. All air must be
purged before the unit is engaged for process temperature control. The automatic
stat-up vent parameters are adjustable. See Section 3.5.F for more information.
Entrained air in the system will adversely affect the unit’s ability to control
process temperature and can cause heater failure when the heating elements
are exposed to this air.
1. The operator must determine the electric motor is phased correctly. Incorrect
phasing means the pump is rotating backwards and results in poor operation and
eventual damage. There are two ways to determine correct phase.
2. Instrument. When power is supplied to the unit and if the phase is incorrect
the instrument will display a yellow Alert icon. Press the Tools & Status icon to
advance to the Tools & Status screen. Press AC Phase to advance to the AC
Phase screen to determine the recommended action to correct the phase issue
or continue to Section B4.
200
main disconnect.
°F
Manual Vent << Back << Back
3. Pump. This is done by visually inspecting the rotation of the motor shaft.
b. Remove the thermoformed cover panel and open the hinged electrical
cabinet panel cover. Note that the electrical power is engaged at this
point and caution must be observed while the electrical supply is
engaged and the cabinet panel is open.
WARNING: Electrical power is engaged and caution should be employed while the cabinet is
open.
e. Observe the motor shaft as it slows to Remove shaft cover to view the
a stop to identify the rotation. Correct motor shaft.
rotation is “clockwise”, when viewed
from the rear of the motor. Incorrect
rotation is “counter-clockwise” when
viewed from the rear of the motor. If
the shaft does not rotate when the unit
is started, the operator must identify
the cause as outlined in this manual’s
troubleshooting and repair section.
a. Disengage the electrical power supply to the unit at the unit’s disconnect
switch. Follow proper lockout procedures before proceeding.
WARNING: To correct phase ... switch power leads at the disconnect switch only.
1. The operator must determine and set proper water flow rate for the most efficient
and trouble free operation.
a. Water flow rate through the process is determined by the pressure losses
in the process loop. Generally, higher flow rates result in turbulent flow
achieving maximum temperature control.
b. If the flow rate exceeds the motor horsepower capacity, the electric motor
will draw excessive amps. This is a result of the process loop’s ability to
flow water at a greater rate than can be provided by the pump. This will
eventually result in tripping the thermal motor overload relay (overload
relays open) and the unit will shut down
c. The yellow Alert : Motor Overloads icon will display on the instrument.
Press the Tools & Status icon to advance to the Tools & Status screen.
Press Motor Overloads to advance to the informational screen for
required action.
200
procedures. Reduce the fluid
°F flow rate.
Manual Vent << Back << Back
2. If an excessive flow situation is encountered and the motor overload circuit has
tripped, the operator must manually reset the overload relay before operations
can continue. This is done by opening the electrical panel cover, identifying
the reset lever on the overload relay and pushing the reset lever “in” until the
overloads are reset (evidenced by a “clicking” sound as the overloads reset).
3. If a motor overload situation persists, the operator must adjust the flow rate to
match the system pressure loss (reduce flow rate) to prevent continual tripping of
the overload relay. This procedure is outlined here:
a. Open electrical cabinet panel door. The panel cover is hinged and held
open by a support cable. Note that the electrical power is engaged at
this point and caution must be observed while the cabinet panel is
open.
b. Identify the motor starter block. This block consists of the motor starter
contactor and the overload relay.
WARNING: Electrical power is engaged and caution should be employed while the cabinet is
open.
f. The amp meter will display the motor Pump Motor Controller
amps. Compare the actual motor amps
as displayed on the amp meter to the
full load amp rating as listed on the motor name plate.
This unit features a touch screen interface panel. Press gently on the screen to navigate.
Do not press the screen with tools or other foreign objects when navigating. A physically
damaged screen voids the unit warranty.
Touch Screen
1. When the correct electrical power and adequate water supply pressure are
supplied, the unit can be started.
Standby
Setup
Ready
Setpoint
2. Ready. When the electrical power supply is engaged the display will illuminate.
The Standby Screen is displayed and shows the last selected Setpoint
temperature. The Ready Indicator is shown if the unit is ready for operations. The
Setup, Tools & Status and Power buttons are also displayed.
3. Alert. An Alert Indicator will display if there is an error or mechanical issue with
the unit. Alerts are explained in detail elsewhere in this manual.
These Alerts prevent the unit from starting or operating and must be corrected
immediately.
• Water Pressure
• Motor Overload
• High Temperature
• Cooling Valve
• Sensor (To)
• Sensor (From)
• AC 3-Phase
Alert
Water Pressure
Standby
Setup Alert
Cooling Valve
Ready Alert
Sensor Probe
Alert
Alert
Setpoint
AC 3-Phase
High Temperature
When the unit is powered up, the instrument checks the status of the water supply,
process temperature and motor overloads. The unit will not start if one of the following
conditions is present.
Standby
Setup
Ready Alert
Water Pressure
Alert
Alert
Setpoint
Water Pressure
High Temperature
Shows the Alert Icons that do
prevent the unit from starting
that can be displayed in the 200 °F Alert
Motor Overloads
2. Motor overload switch opened. The Alert - Motor Overload icon is displayed.
The pump motor is protected from excessive flow by a set of thermal overload
relays which open (trip) with excessive amperage. If the overload relay is open,
the overload relay must be reset before operations can continue. An excessive
flow condition must be corrected immediately.
3. High temperature limit switch open. The Alert - High Temperature icon is
displayed. The unit is prevented from operating with process temperatures
exceeding 256°F by the high temperature limit switch. This switch is installed
in the To Process temperature sensor. If a high temperature condition exists,
the unit must first cool down before the high temperature limit switch can
automatically reset.
When the unit is powered up, the instrument also checks the status of the cooling valve,
phase and sensor probes. Although the unit will start if one of these Alerts is present, it
is in the best interest of machine efficiency and safety to correct these issue as soon as
possible.
Standby
Alert
Setup AC - 3 Phase
Ready Alert
Cooling Valve
Alert Alert
Alert
Setpoint
AC - 3 Phase Sensor
Sensor(From)
(To)
Shows the Alert Icons that
do not prevent the unit from
starting that can be displayed 200 °F Alert
Sensor (From)
1. Sensor Probes: Two Alerts are possible concerning sensor probes. The Alert
- Sensor (To) icon is displayed when the To Process sensor probe has issues.
The Alert - Sensor (From) is displayed when the From Process sensor probe has
issues. A possible cause of a probe issues is the probe service connection is wet.
Locate the 2 pin (white plug) service connection, open and dry with compressed
air. If this does not remove the error indication, inspect the probe wiring, which
could be incorrect or damaged. Probe connections are at the instrument panel.
Correct wiring is (from top to bottom) ‘white’ - ‘black’ - ‘white’ - ‘black’ - ‘red’ - ‘red’.
If probe connections are correct and the error condition remains, the probe may
be faulty and should be replaced.
2. Cooling Valve: Indicates the instrument cannot verify valve position. Refer to
section 5.3 for service.
3. Phase: Follow the procedure outlined in section 3.2. paragraph B ‘Electric Motor
Phasing’ to correct a phase error. If a phase error can not be cleared even
though the pump motor is rotating correctly, the three phase monitor is defective
and should be replaced. Disconnect the unit until a replacement is obtained.
The unit can be started by pressing the Green Power Icon. Please note the unit will not
start if Alerts are displayed for Water Supply, Motor Overload or Hight Temperature.
Standby
Setup
Ready
Setpoint
200
Shows the two Power Icons
that can be displayed in the °F
Power Icon space.
1. Green. The green Power icon shows when the unit is ready to start. Simply press
the green power icon and the unit will start. This power icon will not show if the
unit can not start due to an certain types of Alerts.
2. Red. The red Power Icon shows when the unit can be stopped. Simply press the
red Power icon and the unit will stop operations.
3. Note : If the Pump Seal Cooling feature is enabled the unit will continue to
operate in the cooling mode even if the red Power icon is pressed. The Pump
Seal Cooling feature is explained elsewhere in this manual.
To Process Setup
85 °F Ready
Setpoint
200 °F
The Home Screen
1. The Home Screen is the screen that appears once the unit has started. It offers
To Process temperature, Setpoint temperature, Setup button, the Tools and
Status button and various machine and alert icons.
2. Icons with a gold outline are buttons. Press the button to advance to different
screens.
3. Icons with a white outline are indicator icons and offer information only and are
not buttons.
F. VENTING
Venting is important to remove entrained air from the process system. Venting is done
by opening the cooling valve and discharging water and air to drain. As the water is
discharged entrained air is expelled to drain. Entrained air in the system is evident by a
“rattling” sound in the unit and fluctuating pressure gauges.
1. The unit is programmed to Auto Vent when the unit is started and the To Process
temperature is under 100°F. This parameter can be adjusted via the Setup menu.
2. If the To Process temperature is above 100°F, the unit will bypass the auto
venting mode.
3. Manual Venting. Forced (manual) venting can be done by pressing the Tools
and Status button to advanced to the Tools and Status screen. Press the Manual
Vent button to advance to the Manual Vent screen. Press the Start button to
initiate the manual vent. Press the Stop button to stop the manual vent. When the
Stop button is pressed the instrument returns to the Home screen.
To Process Probe
In Progress
200 °F
Manual Vent << Back
1. Use the Up and Down Arrows on the Home screen to select the Setpoint as
displayed in the Setpoint window. Release the Arrow Key once the Setpoint is
reached. The controller will save the Setpoint.
2. Press the Setpoint window. The gold outline around the window indicates the
window can be pressed to advance to another screen.
To Process Setup
78 °F Heating
100%
Setpoint
5 Water
Supply 6 Pressure
Setpoint
Cooling Valve
To Process Probe
In Progress
78 °F Heating
100%
200 °F Cooling
8%
Setpoint Setpoint
200 °F 200 °F
1. The Heating Icon displays when the unit switches to the heating mode. The Red
Heating Icon will display the amount of heat input from 1 - 100%.
2. The Cooling Icon displays when the unit calls for cooling. The amount of cooling
is indicated by 0 - 100% blue Cooling icon.
125 °F Heating
100%
200 °F 192 °F 200 °F 192 °F
1. Press the To Process temperature button to advance to the From Process and
Flow Display screen. The To Process temperature icon has a yellow outline
indicating it is a button.
125 °F Heating
100% 0 GPM Low Flow Alarm
• Machine
Start/Stop Cooling Alarm Cooling Cooling
Enable
Remote
Setpoint Autovent Flow
Autovent Valve Size
Autovent
125 °F Heating
100% 10
0 °F
GPM High Devivation
Low Flow Alarm
More
10 °F << Back
Setpoint 10 °F Low
HighDevivation
Deviation
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation
B. Low Flow Alarm. Press the yellow outline box next to Low Flow Alarm to select the
value. Press OK to save the value and return to the Setup screen.
C. High and Low Deviation. Press the yellow outline boxes next to High Deviation or Low
Deviation to select the respective value. A minimum temperature deviation of 5°F is
recommended. An alert is provided when the current value is outside the specified range
for approximately 1 minute. The High and Low temperature alert is set by entering a
deviation from current setpoint and is not an absolute value. The deviation value follows
any setpoint change. No need to reset the deviation values with the setpoint is changed.
A. The Remote Setup allows the user to customize the unit parameters for Second Setpoint,
Remote Start/Stop, Remote Setpoint and Communications.
B. Pressing either the Home button returns the user to the Home screen. Pressing the
Features or Machine buttons on the Remote Setup Screen will advance the user to the
Features or Machine Setup screens. Use the Basic button to return to the Basic Setup
screen.
10 °F << Back
Setpoint 10 °F Low
HighDevivation
Deviation Remote
Communicatons Auto Vent
<< Back
Start/Stop
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Remote
Setpoint
Setpoint
Interface
C. Second Setpoint. This screen allows the user to configure a second setpoint. A Second
setpoint is a temperature the unit will control to for other purposes.
125 °F Heating
100% 10
0 °F
GPM High Devivation
Low Flow Alarm
More Second
SecondSetpoint
Setpoint
Pump Seal
Communication
Cooling
More
10 °F << Back
°F Low
HighDevivation
<< Back
Setpoint 10 Deviation Remote
Communicatons Auto Vent
Start/Stop
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Remote
Setpoint
Setpoint
Interface
0 sec Delay
c 0 Cancel OK Cancel OK
Cancel OK
<<
c 0 <<
3. Delay. Press to advance to the Second Setpoint Delay screen to select the delay
in seconds.
D. Remote Start/Stop This screen allows the user to configure the Remote Start/Stop
1. Special hardware is required for remote start and stop including a cable and box,
which must be installed prior to selecting this parameter.
2. Select Yes or No. The selection donut will indicate the selection. Press OK to
save the selection. Press Cancel to cancel the selection.
125 °F Heating
100% 10
0 °F
GPM High Devivation
Low Flow Alarm
More Second
SecondSetpoint
Setpoint Pump Seal
Communication
Cooling
More
10 °F << Back
°F Low
HighDevivation
<< Back
Setpoint 10 Deviation Remote
Communicatons Auto Vent
Start/Stop
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Remote
Setpoint
Setpoint
Interface
Machine SetProtocol
Communication Up
Showing the advance to Remote 66
Start/Stop
Euromap
the Remote Start/Stop
Yes
Setup screen.
No
Cancel
Cancel OK
OK
E. Remote Setpoint. This screen allows the user to configure the remote setpoint.
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Remote
Setpoint
Setpoint
Interface
Basic Setup
Showing the screen
Remote Setpoint Enable
advance to the Remote
No
Setpoint Enable screen.
Yes
Cancel OK
1. Special hardware is required for remote setpoint including a cable and box, which
must be installed prior to selecting this parameter.
2. Select Yes or No. The selection donut will indicate the selection. Press OK to
save the selection. Press Cancel to cancel the selection.
3. The factory default for Remote Setpoint is No.
F. Communications. This screen allows the user to configure the communications protocol.
Select Communications Protocol, Communications Data Rate and Communications
Address.
1. Communications Protocol: This is the data format for communication between
the unit and the host computer. Available values are :
ModbusTM TCP is the common transport protocol of the Internet and ModbusTM
125 °F Heating
100% 0 GPM Low Flow Alarm
More Second
SecondSetpoint
Setpoint
Pump Seal
Communication
Cooling
More
200 °F 10
10
°F
°F
Low Deviation
Low Devivation
Remote
Remote
Setpoint
Setpoint
Interface
1 Address
ModbusTM TCP register definitions are located in the Appendix of this manual.
4. The communication port is typically located near the top of the unit.
A. This is the Features screen allows the operator to program settings for Interface, Pump
Seal Cooling, Autovent, Screen Locking and Pump Stopped Alarm.
B. Pressing the Home button returns the user to Home. Pressing the Remote or Machine
buttons will return the user to the Remote Setup screen or advance to the Machine Setup
screen. Use the Basic button to return to the Basic Setup screen.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Interface Screen Locking
C. Interface. This screen allows the user to select language and units.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Interface Screen Locking
Pump Stopped
Setpoint 10 °F High Deviation Pump Seal
Cooling Alarm
1. Select English or Spanish. The selection icon appears next to the selection. The
default is English. Press Cancel to keep the selection as is and to close.
2. Press Units to advance to the Units screen. Select Imperial or Metric. The
selection icon appears next to the selection. The default is Imperial. Press OK to
save the selection. The default is English. Press Cancel to keep the selection.
D. Pump Seal Cooling. This screen allows the user to configure the pump seal cooling
parameter.
1. Pump seal cooling is a feature to automatically cool the unit before shut down,
after the user has pressed the red Shut Down button.
2. For example, if the unit is operating at a high temperature and the user presses
the red Shut Down button, the unit will continue to operate in the cooling mode
until the Pump Seal Cooling Temperature is reached or the Pump Seal Cooling
Time has elapsed.
3. Pump Seal Cooling Enabled. Select Yes or No. The selection donut will indicate
the selection. Press OK to save the selection. Press Cancel to cancel the
selection. The factory default is Yes.
125 °F Heating
100% 10
0 °F
GPM High Devivation
Low Flow Alarm
More Interface
Second
Second Setpoint
Setpoint Pump Seal
Screen Locking
Communication
Cooling
More
10 °F << Back
°F Low
HighDevivation Pump Seal << Back
Setpoint 10 Deviation Remote
Communicatons
Cooling
Pump
Auto Stopped
Vent
Alarm
Start/Stop
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Remote
Autovent
Setpoint
Setpoint
Interface
4. Pump Seal Cooling Temp. Select the temperature the unit will cool to when
Pump Seal Cooling is enabled.
5. Pump Seal Cooling Time. Select the amount of time the unit will engage the
Pump Seal Cooling feature.
6. Note. The Pump Seal Cooling will cool down to the selected temperature or the
programed time, whichever occurs first.
E. Auto Vent. This screen allows the user to select the autovent temperature and duration.
100 °F Temperature
<< Back
30 sec Time
Machine Machine
1 2 3 Configuration 1 2 3 Configuration
Autovent Temperature Autovent Time
4 5 6 4 5 6
0 °F 0 sec
7 8 9 7 8 9
c 0 Cancel OK
<<
c 0 << Cancel OK
1. As the factory default, when the unit is started and if the process temperature is
under 100°F the unit will autovent for 30 seconds.
2. The user can configure this screen to set the temperature at which autovent can
occur and the duration of the autovent.
A. The Machine Setup screen allows the operator to program settings for Max Setpoint,
Alarm Output, Flow, Heat Only Mode, Mold Purge Enable, Valve Size and System
Information.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Max Setpoint
Interface Heat Only Mode
System
Information
B. Pressing the Home button returns the user to Home. Pressing the Remote or Feature
buttons on the Machine Setup Screen will return the user to the Remote Setup screen or
the Features Setup screen. Use the Basic button to return to the Basic Setup screen.
C. Max Setpoint. Press the Max Setpoint button to advance to the Maximum Setpoint
screen. This screen allows the user to select the maximum setpoint for the unit.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm
Max Setpoint
Interface Heat Only Mode
System
Information
c 0 << Cancel OK
1. This feature is useful in some application where the setpoint must never be
changed above a certain temperature. The Maximum Setpoint can never exceed
250°F in the Temptender unit. The factory default value is 250°F.
2. Use the keypad or the arrow keys to input the value and then press OK to save
and return to the Machine Setup screen. Press Cancel to not save the new value
and to return to the Machine Setup screen.
D. Alarm Output. Press the Alarm Output button to advance to the Alarm Output screen.
This screen allows the user to select the manner of alarm signal.
125 °F Heating
100% 10
0 °F
GPM High Devivation
Low Flow Alarm
More Max
Second Setpoint
Setpoint
Interface Pump
Heat Seal
Only
Cooling
Mode
System
More
Information
10 °F << Back
Setpoint 10 °F Low
HighDevivation
Deviation Pump Seal
Communicatons
Alarm Output
Pump
Auto Seal
Mold Vent
Puge << Back
Cooling Cooling
Enable
200 °F 10
10 GPM
°F Low
Low Flow Alarm
Deviation Remote
Flow
Autovent
Setpoint
Interface
Valve Size
Autovent
Note: this selection requires additional hardware. See factory for details.
E. Flow. Press the Flow button to advance to the Flow screens. This screen allows the user
to select parameters regarding the flow display.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Interface
Second
Max Setpoint
Setpoint
Interface Communication
Heat Only Mode
System
Information
Pump Seal
Setpoint 10 °F High Deviation Pump Seal
Remote
Alarm Output
Cooling
Pump Seal
Mold Puge
Cooling
Start/Stop Cooling
Enable
2. Flow Calibration. Press the Flow Calibration button to advance to the Flow
Calibration screen.
a. Using a reliable and accurate external flow meter the user can input the
value in this screen to match the unit’s displayed flow to the external flow
meter.
b Use the keypad or the arrow keys to input the value and then press OK
to save and return to the Machine Setup screen. Press Cancel to return
to the Machine Setup screen without saving the new value.
c. The factory default is 3000 for 5 & 7½ horsepower units. The default for
¾ - 3 horsepower units is 770.
3. Flow Offset. Press the Flow Offset button to advance to the Flow Offset screen.
a. This screen allows the user to select the flow offset according to the
pump horsepower.
b. The factory default for this value is -3 for ½ - 3 horsepower pump. The
default is 0 for 5 and 7½ horsepower pumps.
c. Enter the value using the keypad or the arrow keys. Press Ok to save the
value and return to the Machine Setup screen. Press Cancel to return to
the Machine Setup screen without saving the new value.
F. Heat Only Mode. Press the Heat Only Mode button to advance to the Heat Only Mode
screen.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm
Max Setpoint
Interface Heat Only Mode
System
Information
Cancel OK
1. This screen allows the user to select the heat only mode. In this mode, the unit
will only use the heater. The cooling valve will be disabled in this mode.
2. Press Yes or No to select the heat only mode. The selection donut indication
displays next to the selection. Press Cancel to return to the Machine Setup
screen without saving the new value.
G. Mold Purge Enabled. Press the Mold Purge Enabled button to advance to the Mold
Purge Enabled screen. This screen allows the user to enable the mold purge system.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Max Setpoint
Interface Heat Only Mode
System
Information
Cancel OK
1. Select Yes to enable the Mold Purge system. Then press OK to save the
selection and return to the Machine Setup screen. Press Cancel to return to the
Machine Setup screen without saving the new value.
3. The mold purge option is typically factory installed and this value is preselected
from the factory. If the mold purge option is field installed, it is necessary to
change the selection from No to Yes.
H. Valve Size. Press the Valve Size button to advance to the Valve Screen screen.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Max Setpoint
Interface Heat Only Mode
System
Information
Machine Setup
Showing the screen Valve Size
advance to the Valve 500:1
Size screen.
1000:1
Cancel OK
1. This screen allows the user to select the correct valve size for the unit. This
parameter is preset at the factory for the valve that is installed in the unit from
the factory. However, if the valve is replaced with a larger or smaller valve, this
parameter must be set to correlate with the replacement valve.
2. Press 500:1 for 1/2” modulating cooling valve or 1000:1 for the 3/4” modulating
cooling valve. The selection icon indicates the selected value. Press OK to save
the value and return to the Machine Setup screen. Press Cancel to return to the
Machine Setup screen without saving the new value.
I. System Information.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm
Max Setpoint
Interface Heat Only Mode System
Information
System Information
Showing the screen
advance to the System
Software Version
fbed448395c9b2b2642843eb6
Information screen. << Back
A. Press the Tools and Status Button from the Home screen to advance to the Tools and
Status screen. This screen gives the user insights into the operation and status of the
unit.
125
AC Phase indicates that
°F Showing the screen advance
is turning in theto
AC Phase Cooling Valve
Heating the pump
100% wrong direction.
the Tools and Status screen.
Supply Water Pressure To Process Probe
200
main disconnect.
°F
Manual Vent << Back << Back
2. A Red light indicates the item is in a stop or error condition. Refer to the
troubleshooting section for more information on items that have caused a stop or
error condition.
B. Manual Vent. Press the Manual Vent button to advance to the Manual Vent screen.
To Process Probe
In Progress
200 °F
Manual Vent << Back
Press Start button to initiate the venting process. Press the Stop button to stop the
manual vent cycle.
C. AC Phase. If the AC Phase light is red the unit is not correctly phase. Press AC Phase
to advance to the AC Phase screen to determine the recommended action to correct the
phase issue.
200
main disconnect.
°F
Manual Vent << Back << Back
1. A phase issue is usually detected at first start up. In the Standby screen an
yellow AC 3-Phase icon will display. The unit will operate if the green Power
button is pressed. However, the unit’s pump will operate backwards and there will
be minimal flow to process.
D. Supply Water Pressure. If the Supply Water Pressure light is red there is not enough
water supply pressure to allow the unit to run. Press Supply Water Pressure to advance
to the Supply Water Pressure screen to determine the recommended action to correct the
issue.
200
valves are open. Increase
°F water supply
Manual Vent << Back pressure. << Back
1. The unit will not operate without adequate water supply pressure. Sufficient water
supply pressure must be present to close the water pressure switch. See Section
2.3 for additional information.
2. At first start up this Alert will display and the unit will not start. If water supply
pressure fails during operations, the Alert will show with an Error display on the
Home scree.
3. Once adequate water supply pressure is established, the alert will clear
automatically.
E. Pump Overload. If the Pump Overload light is red the pump overload is tripped. The
unit will not run if the motor overload is tripped. Press Pump Overload to advance to the
Pump Overload informational screen for recommended actions.
Standby
Setup To Process
125
Pump Overload error indicates
AC Phase
°F Cooling Valve
Heating the pump is drawing more
Ready 100% Probe current than it is rated for.
Supply Water Pressure To Process
200 200
procedures. Reduce the fluid
°F °F flow rate.
Manual Vent << Back << Back
1. The Home screen will display the yellow Alert for Motor Overloads. The unit will
not run with a Motor Overload alert.
This error is triggered by excessive flow causing the pump to draw more amps
then it is rated for. A throttling valve should be placed in the from process line to
control flow.
2. At first start up this Alert will display and the unit will not start. If the motor
overloads fail during operations, the Alert will show with an Error display on the
Home scree.
3. Follow all safety precautions and plant lock out tag out policies to access the
electrical panel. Reset the overload by pressing the reset lever.
F. High Temperature Limit. If the High Temperature Limit light is red the high temperature
limit switch is tripped. The unit will not run if the high temperature limit is tripped. Press
High Temperature Limit to advance to the High Temperature Limit informational screen for
recommended actions.
Standby
Setup To Process
125
A high temperature limit error
AC Phase
°F Cooling Valve
Heating indicates the Hi Temp Limit
Ready 100% Probe has tripped because the
Supply Water Pressure To Process
fluid temperature limit exceeds
Alert switch setting.
Pump Overlaod From Process Probe
Setpoint
High Temperature
Setpoint Action : check for cause and
High Temperature Limit
200 200
allow the unit to cool before
°F °F attempt to
Manual Vent << Back restart. << Back
1. The Home screen displays the yellow Alert for High Temp Limit. The unit will not
run with a high temperature alert.
3. The high temperature limit switch will automatically reset as the unit cools.
G. Cooling Valve. If the Cooling Valve light is red the modulating cooling valve is
experiencing problems. Press Cooling Valve to advance to the Cooling Valve
informational screen for recommended actions.
Standby
Setup To Process
125
A Cooling Valve error indicates
AC Phase
°F Cooling Valve
Heating valve did not move to the closed
Ready 100% Probe position when expected.
Supply Water Pressure To Process
Alert Pump Overlaod From Process Probe Action : Check the home position
switch for obstructions or damage.
Setpoint
Cooling Valve
Setpoint Replace valve if indicated.
High Temperature Limit
200 °F 200 °F
Manual Vent << Back << Back
1. The Cooling Valve fault is caused when the valve can not find the ‘home’ position.
Many times debris or other obstructions can cause this. If not, the valve could be
defective and should be replaced.
2. The unit will continue to run even when a Cooling Valve Alert is present.
H. To Process Probe & From Process Probe. If the To Process or From Process Sensor
Probe lights are red the probe is experiencing problems.
Standby
Setup To Process
125
A Probe error indicates that a
AC Phase
°F Cooling Valve
Heating
temperature probe is reporting
Ready 100% Probe faulty information. The System
Supply Water Pressure To Process
will coast with no heating or
cooling
Alert Pump Overlaod From Process Probe
Setpoint
Sensor (To)
Setpoint Action : make sure connector is
High Temperature Limit
200 200
dry. Replace with a known
°F °F good probe.
Manual Vent << Back << Back
3. The unit will continue to run even when a Sensor Alert is present.
A. PRECAUTIONS/WARNINGS
1. The operator must precisely follow all shut down procedures outlined in this
manual. If the operator fails to do so, an unsafe condition can develop resulting in
damage to the unit or injury and/or death to operating personnel.
2. When disconnecting the unit from the process system, the operator must
determine the unit’s process temperature is at ambient or below 85°F and all
system pressure is relieved and the unit’s pressure gauges read “0”. Injury or
death to operating personnel and damage to the unit could result if a hot and
pressurized unit is disconnected from the system.
b. This feature opens the cooling valve and cools the unit to a pre-set
temperature or time which is programmed in the setup menu. This
feature cools the unit down so that it is at a temperature where it can be
safely removed from service.
c. Verify that the feature has cooled the unit to below 85°F before going to
step 2 below.
If the temperature is still above 85°F to and follow the procedure listed in
step 1.b before following steps 2 - 5 below.
If the temperature is below 85°F follow steps 2 - 5 below to override the
automatic feature and stop the unit immediately. The red Shut Off button
must be pressed twice to override the feature.
3. Disengage the water supply to the unit by closing the water supply valve (if
installed) or by turning off the water supply source at the central control point. If
any residual pressure is evident open the pressure relief valve to dissipate.
4. Disengage the power at the fused disconnect. The display will go dark at this
time.
5. Before disconnecting and removing the process circuitry, be certain all system
pressure is vented and the pressure gauges read “0”.
When the process circuitry is disconnected and removed from the unit, a small
amount of water will be discharged from the unit.
Please note that this water should not be warm or pressurized if all shut down
and disconnecting procedures were followed. Remaining process water can be
discharged by removing the pump casing drain plug.
4.0 TROUBLESHOOTING
4.1 Unit will not start (Display is not Illuminated)
4.2 Unit will not start (Display Illuminated)
4.3 Unit Stops
4.4 Unit Overheats
4.5 Unit Underheats
4.6 Pressure Relief Valve Leaks
4.7 Cooling Valve Fault
A. One or more fuses at the main disconnect device are open (blown). Determine continuity
at each fuse. If continuity is not determined, replace the fuse. Then determine cause of
blown fuse.
B. Control circuit transformer fuse is open (blown). Determine continuity at the control circuit
transformer fuse. If continuity is not determined, replace the fuse.
A. Power supply is ON. The operator can determine that electrical power supply to the unit
is “on” when the instrument display is illuminated. Even with the main power supply on,
the unit is prevented from operating by one of the following conditions:
A. The operator should determine the main power supply to the unit is ON by an illuminated
display. With the main power supply “on”, the unit will be prevented from starting by the
following conditions:
1. Water supply pressure inadequate. The display shows a red Alarm Shutdown
icon and a yellow Alter : Water Pressure icon. The unit is prevented from
200 °F
3. High temperature limit switch open. The
display shows a red Alarm Shutdown icon and Error Screen showoing Yellow Motor
a yellow Alter : High Temperature icon. The unit Overload Alert Icon
is prevented from operations at temperatures
exceeding 256°F by a “high temperature
limit switch”. This switch is installed in the To
Error
Setup
Alert
unit cannot be started and must “cool down” Setpoint
High Temperature
1. Inadequate water supply pressure. The unit must be supplied with adequate
water flow to provide cooling when required. The minimum pressure differential
between the water supply and drain to achieve full cooling capacity is 10 PSI.
The minimum water supply pressure is 20 PSI. A drop in water supply pressure
operation will cause the pump to stop and a safety fault to be displayed.
2. AVTTM modulating cooling valve defective. The instrument opens and closes
the AVTTM cooling valve in incremental steps between 0 to 100% as prescribed by
the current process load. A continual discharge stream of process water to drain
is present under most operating conditions (except at full heat-up). This allows
the unit to maintain virtual straight-line control of process water temperature.
If the AVTTM valve becomes clogged with process water debris or scaled with
mineral deposits, its operation is hindered or fully prevented and adequate
process water discharge to drain is prevented. The operator must remove the
AVTTM valve and remove any loose debris. Massive debris or scale deposits may
necessitate replacement of the AVTTM valve. The procedure for servicing the
AVTTM valve is outlined in Section 5.3 of this manual. Note: a defective cooling
valve may not trigger a yellow Alert : Cooling Valve icon in all cases. The
Alert is triggered when the motor movement is not aligned with the home
switch.
3. Drain line obstruction. The operator must determine if the drain line is obstructed by the
following conditions. Section 2.4 outlines the parameters of correct drain line installation.
a. Closed drain line valve. An installed but partially or fully closed valve in the
drain line prevents full discharge to drain and contributes to an overheating
condition. The operator should determine the drain line is open.
b. High drain back pressure. Pressurized plant drain lines will prevent flow to
drain if the differential between the water supply pressure and the drain line
pressure is inadequate. The factory recommended minimum differential is 20 psi.
If the differential is less than the factory recommendation, plant service personnel
should take measures to reduce drain line pressure.
1. Process water leakage. When the instrument engages the heater to elevate
process temperature, the input of heat into the process can be offset by a
defective AVTTM valve. If the AVTTM valve is defective, it may pass a larger than
required stream to drain, thus providing unwanted cooling. A defective AVTTM
valve should be repaired immediately.
2. Heater element failure. A failed heater element will not input adequate heat
into the process to elevate the process water temperature. The operator must
check the amps at the heater contactor with the contactor energized. Zero amps
at the contactor indicate a failed heater or burnt wire connections. The operator
should remove the failed heater and replace with a new heater according to the
procedure outlined in section 5.2.
3. Unit capacity too low. This occurs when the process requires more heat than
the unit is capable of producing. The only option in such cases is to install a unit
with an adequate heater kW rating for the load.
A. The unit has a 150 psi pressure relief valve mounted in the cooling cylinder. If the valve is
found to be leaking, the operator should check the following:
1. Water supply pressure exceeds 75 psi. The unit is designed to operate with
water supply NOT exceeding 75 psi. See section 2.3 paragraph B for specific
water supply pressure requirements at corresponding setpoint temperatures.
If the plant water supply pressure exceeds 75 psi, the pressure relief valve
may leak. Static water supply pressure can be determined at the unit’s location
by reading the unit’s 0-160 PSI pressure gauges when the unit’s motor pump
is off. If the water supply pressure at the unit’s location exceeds 75 PSI, a
pressure reducing valve must be installed in the water supply line. The factory
recommended ‘regulated pressure out’ is 55 PSI. Refer to section 7.3 for
regulator installation drawing.
2. Back flow prevention device in water supply line. If a back flow prevention
device (check valve, pressure regulator, closed valve) is installed in the water
supply line, increased pressures from thermal expansion are unable to move
into the water supply line. This will increase the unit’s internal pressure causing
the pressure relief valve to leak. Refer to section 7.3 for regulator installation
drawing.
3. Valve contamination. The pressure relief valve may become contaminated with
water debris causing the valve not to close properly. If this is the case, flushing
the valve for a moment will cleanse the seat and allow it to work properly. If
flushing the valve does not remedy the leaking, the valve must be replaced.
A. AVTTM FAULT. When power is applied, the AVTTM valve begins a ‘homing process’. The
valve is turned forward and backward across a limit switch to establish the valve position.
If valve position cannot be established, a fault will be displayed.
C. Refer to section 5.3 for AVTTM service and repair Cooling Valve
<< Back
Page: 54
Temperature Control Unit : MFC with T Series Instrument
5.0 SERVICE/MAINTENANCE
5.1 Pump Seal Replacement
5.2 Heater Replacement
5.3 Cooling Valve Service
5.4 Voltage Change
5.5 Sensor Probe Service
5.6 Pressure Switch Service
5.7 Electronic Instrument Repair Policy & Procedure
5.8 Temperature Probe Calibration
5.9 Heater Contactor & Pump Motor Starter
C. Generally, heaters fail due to low water flow, low water Heater Figure 5.2A
pressure, air in the system or defective heating elements.
11. Replace the 4 heater mounting bolts. Alternate to the opposite bolt while
tightening.
12. Reconnect the power cable to the heater terminals. Be certain to tighten the
power cord junction box connector. Replace the junction box cover and the lift-off
cover panel.
A. The AVTTM cooling valve is a two component assembly, consisting of the motor/gearbox
and valve assembly, mated with a machined aluminum coupling. The AVTTM valve
assembly is sheltered by an thermoformed drip cover (figure 5.3A). The drip cover is
secured by two nuts and can be removed. When removed, the AVTTM valve components
can be viewed (figure 5.3B).
B. The conditions that require servicing of the AVTTM modulating valve are as follows:
Mounting flange
Figure 5.3A
Coupling
Valve
Home switch
Motor / Gearbox
Figure 5.3B
2. Valve assembly defective. The valve assembly may become fouled with
process debris or the internal components may be defective.
C. The components of the AVTTM valve can be serviced separately. To begin the AVTTM valve
service procedure, proceed with steps 1 - 5:
1. Disengage process operations and verify all system pressure is relieved and the
unit’s pressure gauges read “0”.
2. Disengage main power supply and verify the Power light on the display is “off”.
NOTE: It will also be necessary to remove the 2 screws that secure the micro
switch to completely remove the motor since they are hard wired together.
7. Remove the 2 mounting screws. The motor and gearbox will now be loose.
Carefully separate the motor/gearbox from the attached coupling from the valve
assembly.
9. Align the motor/gearbox assembly mounting holes to the holes in the cooling
cylinder. Replace the 2 mounting screws and loosely install the microswitch
screws.
10. Reconnect the wiring harness. Home base is the reference point from which the
controller is able to open the valve incrementally. If the unit is not able to find
home, a valve fault “ULU” will appear in the Temperature display window. Adjust
the home switch to clear the fault.
11. Adjusting the home switch. Apply power. The coupling should begin to turn.
When the lobe on the coupling is directly under the roller for the microswitch,
turn off the power. Adjust the microswitch so that the roller fully depresses the
microswitch. Turn on the power and the valve should turn forward and backwards
a few times and then stop at the home position.
NOTE: Important... The valve stem should be in this position (as indicated
in the diagram) and the valve should be CLOSED. If the valve is open,
manually turn the square stem 90° so that the valve is closed.
12. Be certain the unit is totally depressurized with the unit’s pressure gauges
MTG Screws
Switch
Lobe
Coupling
13. The valve assembly is a ball valve specially designed only to work with the AVTTM
motor. The valve assembly is secured to the cooling cylinder by a top plate and
4 mounting screws. The drain connection originates at the valve top plate with
a brass elbow and close nipple fitting. The connection can be maintained when
servicing the valve.
14. Remove the 4 mounting screws. The top plate, mounting bolts, valve assembly
and the mounting plate with the attached micro-switch will now be loose.
Carefully separate the valve from the motor/gearbox.
15. At this step, the valve can be rebuilt or replaced. To rebuild the valve, order
PN 8764939, and install new stem packing O-ring, seal rings, and seats (see
diagram below). Once the value is back together, continue with step 17:
16. Aligned the valve assembly coupling to the motor/gearbox and place on the
cooling cylinder. A gasket or seal is not required.
17. Replace the top plate, the micro switch mounting plate and the 4 mounting bolts.
Tighten the 4 mounting bolts alternating to the opposite bolts.
18. Once power is reapplied, the instrument will align the AVTTM modulating valve to
“home base”. Home base is the reference point from which the controller is able
to open the valve incrementally. Process operations can resume. If the unit is
not able to find home, a valve fault ULU will appear in the temperature display.
Readjust the home switch to clear the fault. Adjust the home switch as needed
(as outlined in Step 11).
A. Some units can undergo a field voltage conversion by qualified technicians. Consult with
the Service Department to determine if your unit can be converted. Have your Serial
Number ready at the time of the call.
1. 240/3/60 to 480/3/60
2. 480/3/60 to 240/3/60
3. 480/3/60 to 208/3/60
B. For a field voltage changeover, the following items will require replacement or rewiring:
Motor Starter and Overload Block
1. Heater (rewiring)
2. Motor (rewiring)
3. Transformer (rewiring)
4. Motor starter and overload block (replace)
5. Replace unit data tag with tag stating new
voltage and amp rating.
7. Rewire the transformer to the proper voltages as shown by the schematic on the
transformer.
8. Replace the motor starter and overload block. Adjust the overload block
settings for the current draw at the new voltage.
Wiring schematics for 240 and 480 volt heaters Revised 4/11 Figure 5.5B
208/240 460/480
4 4
6 7
5
1
L1
8
7
6
2
L2
9
8
Transformer Figure 5.5E
3 1 L1
L3 2 L2
9 3 L3
Wiring schematics for 240 and 480 volt pump motors Figure 5.5C
Figure 5.5F
replacement. 200 °F
b. Determine that all process pressure is relieved and the unit’s pressure
gauges read “0” pressure.
c. Drain the unit by removing the pump casing drain plug. The unit can be
drained below the sensor probe mount if preferred.
e. Using a crescent wrench, remove the sensor probe from the cylinder. To
install a new sensor probe continue as follows:
f. The new sensor probe threads should be lined with teflon tape and
coated with leak preventative sealant. Using a crescent wrench, thread
the new sensor into the machined boss of the cylinder.
B. The switch will close and consent the control circuit when
sufficient water supply pressure is presented. The switch
is factory set to 20 psi.
D. In cases where sufficient water supply pressure is present as indicated by the unit’s
pressure gauges and the pump is “off”, and if the pressure switch fails to close, the
pressure switch may be defective. To replace the pressure switch, follow the steps
outlined:
1. Shut down unit operations according to section 3.4 in this manual. Be certain
proper lock-out procedures are followed. Also, be certain system pressure is
eliminated and the unit’s pressure gauges read “0” pressure.
3. A capillary runs from the cooling cylinder to the pressure switch. Remove the
capillary connection.
6. The pressure switch is mounted onto the electrical cabinet with two 1/2” nuts in
series. Remove the nuts to remove the pressure switch. A new pressure switch
from the factory should be installed by continuing with step 7.
7. Thread one 1/2” nut onto the pressure switch and then place the pressure switch
through the panel in the original mounting hole. Thread the second 1/2” nut from
the bottom of the pressure switch. Tighten to lock the pressure switch in place.
8. Install the brass elbow fitting. Teflon tape and leak preventative paste should be
used to prevent water leakage. Install the capillary tube and resume operations.
A. The control instrument used in this temperature control unit is covered by the
Manufacturer’s warranty.
3. Return the defective instrument freight pre-paid for full credit. If the defective
instrument is not returned you will need to pay for it.
b. Send your instrument back for repair, freight prepaid. For a nominal fee,
your instrument will be repaired and returned.
c. Purchase a new instrument and repair the old one as a back up.
3. If you are sending your instrument back for repair, call the Service Department
for more information. Do not disassemble the instrument.
D. Other Information:
A. Equipment Needed:
1. Potentiometer adjustment tool / flat-blade screw driver (tip width of 0.050” or less
works best
3. 1/2” plug
4. Digital thermometer
B. Setup:
1. Disengage process operations according to the procedure outlined in the unit
manual. The operator must be certain all system pressure is relieved and unit
pressure gauges read “0”.
3. Remove the “to process” temperature probe and insert a ½” plug in its place.
4. Prepare an ice bath (a cup of water with lots of ice). You should place a digital
thermometer in the ice bath to read the temperature of the bath. Place the probe
in the ice bath.
C. Procedure:
1. Restart the instrument according to the procedures outlined in the unit manual.
3. The “to process” temperature on the display should equal the temperature of the
ice bath as indicated by the digital thermometer. If not, change the calibration.
4. The calibration potentiometer is located on the top of the CPU board. To access
it, open the electrical cabinet panel door. Caution must be employed when the
electrical panel door is open since power is applied to unit.
WARNING: Electrical power is engaged and caution should be employed while the cabinet is
open.
5. Locate the “to process” calibration potentiometer using Figure 1 as a guide. Use
the small screwdriver to turn the potentiometer.
6. Adjust the potentiometer until the “to process” temperature on the display equals
the temperature of the ice bath.
7. When the two temperatures are equal, the calibration procedure is complete.
NOTE: The “from process” probe has its own calibration potentiometer. If
calibration of this probe is required, repeat the setup and calibration procedure
with the “from process” probe.
8. Stop the unit following the shutdown procedure described in the manual
and place all process probes back in the unit to return to normal operation.
To Process
Calibration
Potentiometer
From Process
Calibration
Potentiometer
From Process
Calibration
Potentiometer
To Process
Calibration
Potentiometer
A. The “standard” mechanical contactor for the heater will cycle proportionally to the amount
of heat input required for the process and may cycle frequently.
B. This is a “wear” item that must be routinely inspected and replaced when the contacts
begin to indicate wear/pitting.
C. Failure to maintain the contactor may result in overheating of the components and
catastrophic electrical failure.
D. The “standard” mechanical pump motor starter must also be routinely inspected and
replaced when the contacts begin to indicate wear/pitting.
6.0 COMPONENTS
6.1 Mechanical System
6.2 Electrical System
4. Impeller. The impeller is custom designed for the unit and creates the higher flow
(gpm) from standard HP ratings (figure 6.1B).
command by the instrument. The electric motor is protected from excessive amperage
by a set of thermal overload relays, which open when excessive amperage “heats” the
overloads and the relay opens (figure 6.2B).
E. PRESSURE SWITCH. The electric panel mounted pressure switch will close when
sufficient pressure is supplied to the unit (20 psi). A closed pressure switch will consent
the control circuit to the instrument controller to allow process operations (figure 6.2B).
F. SENSOR PROBES. The unit uses two sensor probes. The “to process” temperature
sensor and the “high temperature limit” safety switch” are housed in the same assembly
and mounted in the heater/pump discharge tank (figure 6.2C). The “from process” probe
is mounted in the suction tank.
G. POWER CORD. On standard models with 10kW and 16kW heaters and 1 - 3 HP pumps
are supplied with a 3 conductor with 1 ground wire sized for the unit and 10’ in length.
Standard models with 24kW and 34kW heaters are not supplied with a power cord and
the customer must provide a 3 conductor with 1 ground wire sized for the unit.
7.1 PHYSICAL
To Process
Instrument
Drain
Pressure Gauges
From Process
26 5/8
Water Supply
HEATER
TO PROCESS
PRESSURE GAUGE
TO PROCESS
CONNECTION
TO PROCESS SENSOR
HI TEMP SAFETY
DRAIN CONNECTION
FROM PROCESS
CONNECTION
DISCHARGE TANK
WATER SUPPLY
CONNECTION FROM PROCESS
PRESSURE GAUGE
SUCTION TANK
PUMP
DRAIN
TO PROCESS
FROM PROCESS
DRAIN
SENTRA '1"
DRAIN CONNECTION
SENTRA '2"
FROM PROCESS
CONNECTION
DRAIN CONNECTION
TO PROCESS
CONNECTION
TO PROCESS CONNECTION
A. Molders often need to run different temperatures on each mold half to produce the best
quality part.
B. The Factory can provide a dual zone dolly that holds two standard single zone
temperature control units to meet this need.
C. The dual zone dolly provides the convenience of a dual zone configuration while
providing the economic first cost and ease of maintenance associated with independent
single zone units.
D. Options:
8.0 APPENDIX
8.1 Model # Coding
8.2 Interpretation of Process Pressure Gauges
8.3 Operation of Mold Purge
8.4 SPI Commands
8.5 Communication Cable
8.6 Optional Alarm Operation
8.7 AVTTM Valve Troubleshooting and Components
8.8 AS5 Pump Parts List - 1/2 hp to 1 hp
8.9 AS5 Pump Parts List - 1.5 hp to 3 hp
The data tag on your Sentra Temperature Control Unit provides general information about the unit. Compare the information
below with your data tag for more information about your unit. Some data tags may have other or different information. If you
need specific information about the configuration of your unit contact the factory with the serial number from your unit.
Model
S K - 10 45 - T
Nominal Heater Kilowatts
6 = 6 KW
10 = 10 KW
16 = 16 KW
24 = 24 KW
34 = 34 KW
GPM by HP
20 = 20 GPM @ 1/2 Horsepower
35 = 35 GPM @ 3/4 Horsepower
45 = 45 GPM @ 1 Horsepower
65 = 65 GPM @ 1 1/2 Horsepower
75 = 75 GPM @ 2 Horsepower
80 = 80 GPM @ 3 Horsepower
90 = 90 GPM @ 5 Horsepower
100 = 100 GPM @ 7 1/2 Horsepower
Control Instrument
T = T series instrument
G = G series instrument
VE = VE series instrument
T300 = T300 instrument
G300 = G300 instrument
D. PUMP MOTOR OVERLOAD CONDITION. If the ∆ P is low with the pump rotating
correctly, then the flow rate is high, which probably will result in a motor overload. Refer
to the representative pump curve below.
A. The mold purge system is a mixture valves and piping that when activated and supplied with
compressed air will expel process water from the mold or process to the central water return line or
drain.
B. Mold Purge is an optional feature and not included on all units. The function of the Mold Purge
requires the purchase on the option.
C. The Mold Purge parameter must be enabled to operate the mold purge. Press Setup to
advance to the Setup screen, then press More to advance to the Advance Setup screen and finally
press More to advance to the Machine Setup screen. Press the Mold Purge Enable button to
advance to the Mold Purge Enable screen. Select Yes to enable the Mold purge system. Press OK
to save the selection.
To Process Setup Basic Remote Features Machine Basic Remote Features Machine
125 °F Heating
100% 0 GPM Low Flow Alarm Max Setpoint
Interface Heat Only Mode
System
Information
Machine Setup
Mold Purge Enable
No
Yes
Cancel OK
LINE TO DRAIN
CHECK VALVE
Prevents compressed air from purging unit
200
High Temperature Limit
°F
Mold Purge Manual Vent << Back
<< Back
5. Press the Stop button to disengage the purge cycle. Use the Back back to return
to the Tools & Status screen.
ALERT: The Purge cycle must be started and stopped. If not stopped, the Purge cycle will
continue and will consume compressed air until stopped.
6. When water is purged disconnect air supply. The unit can be disconnected at this
time as most of the process fluid should be out of the process lines.
WARNING: Use caution when disconnecting process lines because residual pressure will
remain in the lines. The remaining pressure will be equal to the compressed air pressure
used for the purge process. Use caution because disconnecting process lines under pressure
incorrectly may cause injury.
Note in the above example that different device types may have the same address. This
is because the SPI Protocol uses the device type as part of its internal address.
1. Verify that each piece of equipment is properly grounded to its power source.
2. Inspect cables inside and outside the electrical cabinet. Repair or replace
as necessary. The cable scheme used by most manufacturers allows the
communication signals to ‘pass through’ each piece of equipment. Therefore,
when a piece of equipment is disconnected from the middle of the network, all
the equipment ‘after’ that one will be disconnected, too. If a piece of equipment
is being permanently removed, the device cables should be rearranged at the
molding machine to reconnect the other equipment.
3. Check the Data Transfer Rate and Address of each piece of equipment. For
example, if both Temperature Controllers have the same address, they will both
try to ‘talk’ at the same time and garble each other’s data.
5. Attach each device, singly, to the molding machine and see if it ‘talks’. Add
additional devices until a problem is seen.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 ALARM - PHASE
PROCESSING
ALARM - SYSTEM POLL SELECT
ALARM - PROCESS C1 C2 C1 C2 COMMAND DESCRIPTION
ALARM - MACHINE
20 44 Status Machine 2
ALARM - HIGH TEMPERATURE
ALARM - LOW TEMPERATURE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ALARM - LOW FLOW* PROCESSING
ALARM - SYSTEM
ALARM - PROCESS
ALARM - MACHINE
ALARM - SENSOR
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 48 20 49 Machine
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ALARM - ACKNOWLEDGE
ALARM - ON/OFF
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 4A 20 4B Protected mode - machine
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
MACHINE - ON/OFF
ON/OFF ALLOWED
ALARM - ACKNOWLEDGE
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 70 Temperature to process
20 72 Temperature from process*
20 78 Flow rate from unit GPM*
20 E0 Blanket Poll
Returns: 20 30 Setpoint
20 32 High alarm deviation
20 34 Low alarm deviation
20 40 Status process
20 70 To process temperature
A. The unit is standard with a 110 volt AC alarm output. The alarm output can be connected
to customer provided alarm annunciation, plant-wide monitoring system or optional
annunciation.
B. A beacon alarm is used when both visual and audible alarm annunciation is needed. The
beacon is an integral light and buzzer assembly to provide high visibility in a busy, noisy
shop. The beacon will signal until the alarm condition is acknowledged by the operator.
C. Audible Alarms provide a loud signal when an alarm condition is present. The audible
alarm is mounted on the front cover of the unit.
Gear Box
Temperature Control Unit : MFC with T Series Instrument
Home Switch
8.7 AVTTM COOLING VALVE COMPONENTS
www.milacron.com
Phone: 513-536-2584
Milacron Process Support Business
4165 Halfacre Road Batavia, Ohio 45103
5/16-18 x 2” 5/16 Lock #8-32 Valve #5/16-18 x 3-3/8”
Hex Head Screw Washer Lock Nut Body Threaded Rod
Page: 92
Temperature Control Unit : MFC with T Series Instrument
Temperature High Alarm 3 R/W 0-50 F SKT, SKG, SKHE Protocol RTU
SKT, SKG, SKHE Address 1
Temperature Low Alarm 4 R/W 0-50 F Deviation Value
SKT, SKG, SKHE Baud Rate 96
Flow Low Alarm 5 R/W 0-99 GPM Deviation Value
The following Modbus/TCP communication functions are supported.
0X Commands FC1 - Read Coils
1X Commands FC2 - Read Inputs
To Process Temperature 6 R 0-255 F 4X Commands FC3 - Read holidng registers
3X Commands FC4 - Read input registers
From Process Temperature 7 R 0-255 F 0X Commands FC5 - Write Coil
To Process Flow Rate 8 R 0-99 GPM 4X Commands FC5 - Write single register
4X Commands FC16 - Write multiple register
Process Status 9 1 - 16 R
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Lo Lo Hi Alarm Alarm Alarm Pump On
Flow Temp Temp. Machine Process
Machine Status 1 10 17 - 32 R
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Phase Heater Pump Lo Lo Lo HTL Alarm Alarm Alarm Pump On
Wrong Fail O/L Flow Press Temp Switch Machine Process
Machine Status 2 11 33 - 48 R
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Sensor Alarm Alarm Alarm Pump On
Fail Machine Process
Reserved 12 49 - 64 R
Reserved 13 65 - 80 R
Reserved 14 81 - 96 R
PART # DESCRIPTION
PART # DESCRIPTION
Page: 96
END
© 2018 Milacron.
RE 10042018