The LMS1x and this Data Sheet are intended for use by OEMs which integrate the
BMUs in their products.
Notes
Please note!
All the safety, warning, and technical notes given in the user manual for the
LMS1x (U7471/U7472) also apply to this document in full. Failure to observe
this information poses a risk of damaging the safety functions and the risk of
electric shock.
LMS1x are digital boiler management units (BMUs) for use with gas-fired
appliances equipped with premix burners. They are used for startup, control and
supervision of premix burners with capacities from <10 kW to 1 MW in intermittent
operation with direct ignition of the main flame. The OEM must make certain that
the LMS1x are suited for the application in question.
The LMS1x provide all supervisory and control functions required for burner
operation, space heating and DHW heating. They also offer modular system
extensions in the form of integrated communication interfaces. Output modulation
is performed via a PWM-controlled fan with pneumatic/electrical gas-air ratio
control.
With the LMS14, load modulation is performed via a PWM-controlled fan with
pneumatic gas-air ratio control.
2/30
Documentation
LMS14
LMS15
Type (ASN) Description
no.
CC1E7471 *)
LMS14 Boiler Management Unit CC1Q7471
CC1U7471
CC1E7471 *)
Boiler Management Unit CC1Q7471
LMS15
Sitherm Pro CC1U7471
CC1U7472
3/30
LMS15
Type (ASN) Description
no.
4/30
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic burner control systems for burners and DIN EN 298
appliances burning gaseous or liquid fuels
Only LMS15: EN 12067-2
Gas/air ratio controls for gas burners and gas burning
appliances
Part 2: Electronic types
Safety and control devices for gas burners and gas DIN EN 13611
burning appliances - General requirements
Control functions in electronic systems for gas burners DIN EN 14459
and gas burning appliances
Methods for classification and assessment;
Automatic electrical controls for household and similar use DIN EN 60730-2-5
Part 2-5:
Particular requirements for automatic electrical burner
control systems
The relevant valid edition of the standards can be found in the declaration of
conformity!
ISO 9001:2015
ISO 14001:2015
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
LMS14
LMS15 ---
Disposal notes
The LMS1x contains electrical and electronic components and must not be disposed of
together with domestic waste. Local and currently valid legislation must be complied
with.
5/30
The LMS1x has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, corresponds to approx. 10 years of
service (starting from the date of manufacture on the type label).
This is based on the endurance tests specified in the standard EN 298. A summary of
the conditions has been published by the European Control Manufacturers Association
(www.afecor.org).
The designed lifetime is based on use of the LMS1x according to the manufacturer’s
Data Sheet and User Manual. After reaching the designed lifetime in terms of the
number of burner startup cycles, or the respective time of usage, the LMS1x is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery.
Type summary
LMS14
Printed circuit board design
Without combustion optimization
LMS15
Printed circuit board design
With combustion optimization
Note
Details on the accessories and required system components can found in the LMS1x
product range overview Q7471.
6/30
Basic unit
General Mains voltage (rated voltage)
LMS14.815B109 only AC 120 V +10%/-15%
All other LMS14 types AC 230 V +10%/-15%
Mains frequency
LMS14.815B109 only 60 Hz to EN 298
All other LMS14 types 50 Hz to EN 298
Power consumption
Operation Max. 14 W
Power pack Max. 14 W
Rated surge voltage category III (EN 60664-1:2008)
Degree of protection IP00
IP40 according to EN 60529:1991 +
A1:2000 + A2:2013 (to be ensured when
fitted inside the boiler)
Safety class LMS14 designed for use in equipment of
protection class I according to
EN 60730-1:2017
Degree of pollution 2
Software classes As per EN 60730-2:2015 + A1:2019
Controller part Class A
LMS14 Class C
Dimensions (L x W x D) 230 x 150 x 30 mm
Weight Approx. 0.254 kg
Unit fuse 2 x T6.3H250 internal
Caution!
Risk of damage to the fuel valve switching contacts!
If the internal mains fuse (FB01/FB02) is blown due to overload or short-circuit at
the fuel valve connections, the LMS14 must be replaced.
Caution!
When making 100% inspections as per EN 60335-1:2012 + A1:2019 + A2:2019 +
A11:2014 + A13:2017 + A14:2019 Addendum A, only AC voltage may be applied.
If DC voltage tests are conducted, the LMS14 can get damaged.
7/30
Environmental
conditions Warning!
Condensation, formation of ice and ingress of water are not permitted!
Failure to observe this information poses a risk of damaging the safety
functions and a risk of electric shock.
8/30
Attention!
Fuse protection!
The following connecting terminals are protected by the unit fuse as per the
chapter titled Technical data - General data.
The cross sections of the connection lines must be designed according to the unit
fuses.
Please note!
Interchangeability of L/N conductors!
L-conductors and N-conductors are not interchangeable across all LMS14
variants!
9/30
Note!
A fuel valve with rectifier may be connected to the fuel valve output only if
approved by Siemens!
In this case, additional protective measures inside the LMS14 must be taken
(optional components)
10/30
+5 V
Output voltage LMS14 DC 5 V ±5%
Short-circuit current (current Imax. 1 A
limitation)
+12 V
Output voltage LMS14 DC 12 V ±5%
Short-circuit current (current Imax. 0.8 A
limitation)
+15 V
Output voltage LMS14 DC 15 V ±5%
Short-circuit current (current Imax. 1.5 A
limitation)
+24 V
Output voltage LMS14 DC 24 V ±5%
Short-circuit current (current Imax. 1.1 A
limitation)
Note!
Sensor input BX4 has a fixed assignment to sensor B7. The reading of sensor B7 is
safety relevant.
11/30
12/30
13/30
PWM fan/Hall
connection facility
Warning!
Mandatory requirement: Observe separate Siemens specification
Spezifikation_LMU5x_TrafoGebläse_de_VX.Y.doc
10 V output
- Extra-low voltage
Output voltage at Iout = 0 DC 0..10.5 DC
Output current (short-circuit- Max. 15 mA
proof)
Calibration capability Characteristic curve coefficient
Current load 2.7 mA peak
Ripple <50 mV
Settling time 99% <500 ms
Zero point accuracy ±100 mV
Error for remaining range <0.1 V typical
<0.5 V max.
Can be calibrated by means of
parameters
- Cable length 10 m
14/30
15/30
Limitation of the BSB The LMS14 may only be subjected to a maximum load of 40 mA on the BSB ports
users (CL+/CL-) and a maximum load of 400 mA on the 12 V supply.
Danger!
These maximum currents must not be exceeded by the total number of bus
users combined. To avoid uncontrollable malfunctions on the LMS14, each
system must be checked accordingly.
16/30
Outputs for LED flame Outputs for connecting status LEDs (see drawing in the User Manual U7471, chapter
and LED fault (X30) Pin assignment for terminal X30)
Voltage DC 12 V
Current DC 2...10 mA (limit with Rv)
Cable length <3 m
17/30
Warning!
Only use the parameter stick during the parameter setting process on the
LMS14. It is not permitted to plug in the parameter stick during operation or to
use it in permanent operation!
Environmental
conditions
Warning!
Condensation, formation of ice and ingress of water are not permitted.
Failure to observe this information poses a risk of damaging the safety
functions and a risk of electric shock.
Warning!
The AGU2.56 may only be connected to the LMS14 or the OCI432 on the
designated plug-in space!
18/30
Note!
The data listed are only those deviating from the Technical Data of the LMS14
Warning!
When making 100% inspections as per DIN EN 60335-1, Addendum A, only AC
voltage may be applied. If DC voltage tests are conducted, the LMS15 can get
damaged.
Environmental
conditions
Warning!
Condensation, formation of ice and ingress of water are not permitted!
Failure to observe this information poses a risk of damaging the safety
functions and a risk of electric shock.
19/30
Electrical connections
Mains voltage Total current for all network components 5 A (at UMains = AC 230 V; Ta = 25 °C)
connections connected to the LMS15 and clip-ins
Attention!
Fuse protection!
The mains voltage connection terminals are protected by the unit fuse as per
the chapter Technical data - General data.
Note!
Conductors L- and N are interchangeable!
20/30
Functions
Note
The scope of functions depends on the LMS1x and its respective parameterization
(refer to LMS14 User Manual U7471 or LMS15 User Manual U7472).
21/30
The maximum functionality of the LMS14 system (120 V AC) is shown. The specific
scope of functions is to be determined according to the respective design /
configuration!
22/30
The maximum functionality of the LMS14 system (230 V AC) is shown. The specific
scope of functions is to be determined according to the respective design /
configuration!
23/30
The maximum functionality of the LMS15 system is shown. The specific scope of
functions is to be determined according to the respective design / configuration!
Ignition module
Reset Lockout reset button DC 24 V
PWM fan
Programmable analog / AC 230 V
H1 digital input
Programmable frequenzy /
H4 digital input Heating circuit pump QX2
P1
Programmable digital
RT / H5 input DHW pump 1
or diverting valve QX3
Gas pressure switch or
H6 programmable Unipolar / bipolar
digital input stepper motor Qx4
(diverting valve)
Air pressure switch or
H7 programmable Room unit S / 1 / 2 / 3
digital input
Extension module1 / 2 / 3
B2 Boiler flow sensor
Operating unit
B3 / B38 DHW sensor 1
Reset
B9 Outside sensor
LED interference
Multifunctional
BX1 sensor
LED flame
Multifunctional
BX2 sensor
Radio module
7471a45e/0918
24/30
25/30
26/30
LMS14 complete
(Deluxe)
27/30
28/30
29/30