Albatros2 Operator Units / Room Units / Auxiliary Devices: Technical Manual
Albatros2 Operator Units / Room Units / Auxiliary Devices: Technical Manual
1 Overview .........................................................................................................5
2 Mounting and installation...............................................................................9
2.1 Wired components............................................................................................9
2.1.1 Room unit QAA55… ........................................................................ 10
2.1.2 Room unit QAA75… ........................................................................ 12
2.1.3 Operator unit AVS37.29x ................................................................. 14
2.1.4 Operator unit AVS37.394 ................................................................. 15
2.1.5 Operator unit AVS37.390... .............................................................. 16
2.2 RF components .............................................................................................. 17
2.2.1 Room unit QAA58… ........................................................................ 18
2.2.2 Room unit QAA78... ......................................................................... 21
2.2.3 RF module AVS71.390 ....................................................................25
2.2.4 RF module BSB AVS71.393 ............................................................ 27
2.2.5 RF repeater AVS14.390 ................................................................... 29
2.2.6 RF outside sensor AVS13.399 ......................................................... 32
2.2.7 Checking the RF components .......................................................... 36
3 Handling ........................................................................................................ 37
3.1 QAA55... / QAA58........................................................................................... 37
3.1.1 Operation......................................................................................... 37
3.1.2 Programming ................................................................................... 41
3.2 QAA75... / QAA78… / AVS37… ...................................................................... 42
3.2.1 Operation......................................................................................... 42
3.2.2 Programming ................................................................................... 53
3.2.3 User levels ....................................................................................... 56
3.2.4 Room unit, operator unit settings...................................................... 58
3.2.5 Settings in detail .............................................................................. 60
3.3 AVS37.390... .................................................................................................. 68
3.3.1 Operation......................................................................................... 68
3.3.2 Programming ................................................................................... 73
3.3.3 User levels ....................................................................................... 75
3.3.4 Overview of the settings ................................................................... 76
4 Technical data............................................................................................... 78
4.1 Operator unit and room units QAA5x... / QAA7x... / AVS37... .......................... 78
4.2 RF module AVS71.390 ................................................................................... 80
4.3 RF module BSB AVS71.393 ........................................................................... 81
4.4 RF repeater AVS14.390.................................................................................. 82
4.5 RF outside sensor AVS13.399 ........................................................................ 83
Index ....................................................................................................................... 84
3
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
4
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1
1 Overview
This document The room and operator units described in this document operate in an optimum
manner BMUs for floor-standing or wall-mounted boiler controllers. The room and
operator units are suitable for plants that do not require cooling.
5
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1
6
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1
RF module AVS71.390
7
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1
RF repeater AVS14.390
8
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2
Powered by base The base provides the power for QAA55 and QAA75. When the units are removed
from the base, power is cut off (i.e. the units are out of operation).
9
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components
Connections
10
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2
11
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components
There must be sufficient clearance above the unit to install and remove it as
needed.
12
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2
Connections
Terminal Designation QAA75.610 QAA75.611
1 CL+ BSB data BSB data
2 CL- BSB ground BSB ground
3 G+ Reserved Power supply DC 12 V
13
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components
Connections The AVS37.294 operator unit must be connected to terminal X30 of the basic unit
using the AVS82.491/109 connecting cable. The connectors are coded.
Dimensions
Panel cutout
14
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2
Connections The AVS37.394 operator unit must be connected to terminal X30 on the basic unit
using the AVS82.491/109 connecting cable. The connectors are coded.
15
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components
Dimensions
VA Visual area
AA Active area
A Control panel, front
16
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
2.2 RF components
RF devices in general The wireless components should be located such that transmission is as
interference-free as possible. For installation, the following points must be
observed:
l Not in the vicinity of electrical cables, strong magnetic fields or equipment such
as PCs, TVs, microwave ovens, etc.
l Not near larger metal structures or constructional elements with fine metal
meshes, such as special glass or concrete.
l The distance to the transmitter should not exceed 30 meters or 2 floors
17
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
18
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
RF connection
NOTICE
Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the occupancy button for at least 3 seconds.
a The room unit switches to the service level (Display "ru 1").
3. Depending on the heating circuit, turn knob to "ru 2", "ru 3".
4. Press occupancy button 3 times, until "P3" appears.
5. Press operating mode button.
a The process of opening the connection is started.
a The connection is complete as soon as the LED RF module (AVS71.390) turns
off and the room unit re-starts.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
a The room unit displays the room temperature.
19
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
Testing
NOTICE
The test can be stopped by pressing the operating mode or occupancy buttons.
20
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
In the case of mounting with base, there must be sufficient clearance above the
unit, enabling it to be fitted and removed
21
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
Connections / power Power is supplied via three 1.5 V alcaline batteries of type AA (LR06).
supply
22
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
RF connection
NOTICE
Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the OK button on the room unit.
a The room unit switches to the programming level.
3. Press the Info button for at least 3 seconds.
4. Using the knob, select "Commissioning" operating level and press the OK
button.
5. Using the knob, select "Operator unit" operating page and press the OK button.
6. Select operating line 40 "Used as" and make the proper settings.
7. Press the OK button to confirm.
8. Using the knob, select "RF" operating page and press the OK button.
9. Select operating line 120 "Binding" and press the OK button.
10. Use the setting knob to set to "Yes".
11. Press the OK button to confirm.
a The process of opening the connection is started.
a The display shows the progress of opening the connection in %. This process
can take 2...300 seconds.
a The connection is established when "Device ready" appears and the LED on
the RF module (AVS71.390) turns off.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
23
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
Testing
NOTICE
24
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
Engineering Do not install the unit inside metal casings (e.g. inside the boiler).
Installation
A: LED
B: Button
Terminals The cable of the RF module has a plug to connect to the controller (connection
X60).
25
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
RF connection via RF The RF link is establishing using the RF module as described in the corresponding
module section on RF components.
26
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
Installation
Connections
1 CL+ BSB data
2 CL- BSB ground
3 G+ DC 12 V
Troubleshooting
27
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
RF connection via RF l The RF link is establishing using the RF module BSB as described in the
module BSB corresponding section on RF components.
l LED on: Device is ready for operation.
28
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
NOTICE
Installation
Connections Power is supplied via the enclosed power pack. The wires are interchangeable.
29
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
RF connection
NOTICE
1 2
1 Button 2 LED
Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the button on the installed RF repeater until the LED starts flashing
quickly.
a The connection is established when the LED on the RF module (AVS71.390)
extinguishes.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
30
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
Testing
NOTICE
Operating principle The RF repeater forwards the RF signals between RF module (BSB) and base unit.
No further binding between the RF repeater and room unit required.
31
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
NOTICE
Mounting type
RF transmitter Outside sensor
32
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
2 Battery
Connections l Connect the outside sensor to the RF transmitter via 2-core-line; the
connections can be interchanged.
l Power is supplied via three 1.5 V alcaline batteries of type AAA (LR03).
33
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
RF connection
NOTICE
1 2
1 Button
2 LED
Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the button on the transmitter of the RF outside sensor for at least 8
seconds.
a This LED also blinks rapidly.
- The connection is established when the LED on the RF module
(AVS71.390) extinguishes.
- The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
3. Press the button on the RF outside sensor again briefly until the LED
extinguishes.
34
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2
Testing
NOTICE
1. Press the button on the transmitter of the RF outside sensor between 3 and
max 8 seconds.
a The LED blinks slowly.
- When radio communications are operating correctly, the LED on the RF
module (AVS71.390) flashes briefly at 10-second intervals.
- With RF module BSB (AVS71.393), the LEDs go off every 10 seconds.
2. After checking, press again briefly the button on the transmitter of the RF
outside sensor until the LED extinguishes.
35
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components
36
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3
3 Handling
3.1.1 Operation
Operating elements
1
37
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA55... / QAA58...
Automatic operation
In automatic mode the room temperate is controlled as per the scheduler.
Characteristics of automatic mode:
l Heating mode according to the time program
setpoint"
l Protective functions active.
l Automatic summer / winter changeover and automatic 24-hour heating limit
active (ECO functions)
38
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3
Continuous operation or
Under continuous operation, the room temperature is maintained at a constant to
the selected operating level.
Protection
When using Protection, the heating system is off. But it remains protected against
frost (frost protection temperature) provided there is no power failure.
Characteristics of Protection:
l Heating OFF.
l Temperature according to frost protection.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit active
39
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA55... / QAA58...
Turn the setting knob to increase or decrease the Comfort setpoint heating .
NOTICE
● Direct settings using the knob have no effect if the plant is in an operating
state other than Comfort heating .
● Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.
Presence button
If you do not use the rooms for short periods of time, you can press the presence
button to temporarily reduce heating.
Heating operation changes from Comfort setpoint heating to reduced setpoint
heating.
Press the occupancy button again as soon as the rooms are occupied.
NOTICE
40
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3
3.1.2 Programming
Setting principle 1. Press the occupancy button (> 3 seconds).
a The room unit switches to the service level.
The first parameter is selected; the present value blinks.
2. Use the setting knob to set the parameter.
3. Briefly press the occupancy button.
a The next parameter is selected for setting.
4. Exit service level:
- After 8 seconds without activity, the room unit exists the service level.
- Briefly press the operating mode button.
Settings
* QAA58… only.
NOTICE
● If operation lock is active and one of the locked buttons is pressed, "OFF" is
displayed for 3 seconds.
● The operation lock does not prevent the service level from being accessed.
41
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
3.2.1 Operation
Operating elements
Room units
QAA75... / QAA78… 1
4
5
42
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Operator unit 1 2
AVS37…
4 5 6 7 8 9 10
43
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
44
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Automatic operation
In automatic mode the room temperate is controlled as per the scheduler.
setpoint"
l Protective functions active.
Continuous operation or
Under continuous operation, the room temperature is maintained at a constant to
the selected operating level.
45
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Protection
When using Protection, the heating system is off. But it remains protected against
frost (frost protection temperature) provided there is no power failure.
Characteristics of Protection:
l Heating OFF.
l Temperature according to frost protection.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit active
Controller stop function The controller stop function is triggered by pressing the operating mode buttons for
an extended period (> 3 seconds).
The controller stop function can be used to manual control the burner.
The operator's output specifications override the control algorithm for the LMS14...
Exception The 2-point controller places the burner out of service, if the flow temperature
achieves the maximum boiler temperature (OL 2212: Setpoint).
46
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
DHW mode
On: The DHW is treated according to the selected switching program. Keep hot
function is generally released.
On Eco: Same as operating mode "On", but: Keep hot function is off.
Off: No DHW heating, but the protective function is active.
The keep hot function maintains the temperature of the instantaneous DHW
heater so that warm water is quickly available the next time the facet is turned on.
DHW push
The DHW push function is only available for the DFW storage tank.
The DHW push is triggered by pressing the DHW mode button for an extended
period (> 3 seconds).
DHW push initiates a single DHW charging cycle to the nominal setpoint. The push
is active until the nominal DHW setpoint is reached.
DHW push can also be started when:
l DHW mode is "off".
l Operating mode changeover is effected via H1 or centrally (LPB)
l All heating circuits use the holiday function
NOTICE
Once triggered, the DHW push cannot be cancelled via the operator unit.
47
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Turn the setting knob to increase or decrease the Comfort setpoint heating .
NOTICE
● Direct settings using the knob have no effect if the plant is in an operating
state other than Comfort heating .
● For reduced setpoint, press OK, select operating page “Heating circuit“ and
adjust the “Reduced setpoint”.
● Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.
Presence button
If you do not use the rooms for short periods of time, you can press the presence
button to temporarily reduce heating.
Heating operation changes from Comfort setpoint heating to reduced setpoint
heating.
Press the occupancy button again as soon as the rooms are occupied.
NOTICE
48
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Displaying information
NOTICE
● The code lists are documents in the corresponding controller user's guides.
● The info line texts are self explanatory.
49
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Error / maintenance In exceptional cases, the basic display shows one of the following symbols:
Press the info button and read further Press the info button and read further
information. information.
The LPB number on the display indicates the device in the LPB system from which
the error or maintenance message, or special operation, was triggered. The first 2
digits give the segment address, the 2 digits after the dot the device address.
Hence, 02.01 denotes segment 2, device 1.
Reset function The reset function for meters and the resettable parameters appears on the bottom
line of the display, provided a reset is permitted on the current operating line (end
user / commissioning / heating engineer).
After activation with the OK button, the display will show a flashing “Yes”.
After confirmation with the OK button, the relevant parameter or meter is reset.
50
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Manual operation
A short press (< 3 seconds) of the manual operation button enable the manual
operating mode.
When manual operation is active, the relays are no longer switched according to
the control state, but are set to a predefined manual operation state depending on
their function.
The burner relay switched on in manual control can be switched off by the
electronic temperature controller (TR).
Setpoint adjustment in The device switches to the basic display after enabling manual operation.
manual control
The (maintenance) special mode symbol is displayed.
A short press (< 3 seconds) of the chimney sweep function enables the manual
operating mode.
It produces the operating state required for making measuring emissions (flue gas).
Set burner output The device switches to the basic display after enabling chimney sweep function.
The (maintenance) special mode symbol is displayed.
51
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Bleed function
A long press ( > 3 seconds) of the manual operation button enables the bleeding
function.
The bleeding function bleeds any air in the heating/hot water system using an
automatic bleeder installed above the boiler. The system pumps are switched on in
a specified sequence.
Unlocking function
The unlocking button executes the same function as switching of LMS input
"Reset" (X4/X4a).
52
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
3.2.2 Programming
Setting principle Settings that cannot be made directly with the help of operating elements are made
through programming. For this purpose, the individual settings are structured in the
form of menus and operating lines, thus creating practical groups of settings.
The following example shows how to set the time of day and the date.
NOTICE
● When pressing the ESC button, you go one step back; adjusted values will
not be adopted
● If no setting is made for 8 minutes, the display returns automatically to the
basic display
● Operating lines may be hidden, depending on the type of controller, the
configuration made and the user level
1 Basic display.
If the basic display is not shown, press the ESC
button to go back.
Press OK.
53
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
54
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Example of menu
structure
55
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
The user levels only allow authorized user groups to make settings. To reach the
required user level, proceed as follows:
1 Basic display.
If the basic display is not shown, press the
ESC button to go back.
Press OK.
Press OK.
56
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Setting structure "End The example given here shows that certain user levels do not allow certain
user" settings. The example shows them highlighted. On the unit, they are hidden.
Setting structure
"Heating engineer"
57
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Operating line
User level
Function [value range] Standard Min max Unit
Time of day and date
1 E Hours/minutes - 00:00 23:59 hh:mm
2 E Day / month - 01.01 31.12 dd.mm
3 E Year - 2004 2099 yyyy
5 F Start of summertime 25.03 01.01 31.12 dd.mm
6 F End of summertime 25.10 01.01 31.12 dd.mm
Operator section
20 E Language German -
German ¦ English ¦ French ¦ Italian ¦ etc.
21 O Display of special operation On: QAA7x.6xx/101,201,501; AVS37.x9x/109,509
Off ¦ On Off: QAA7x.6xx/301,701; AVS37.x9x/209,309,709
22 F Info Temporarily -
Temporarily ¦ Permanently
24*** O Lighting Temporary -
Off ¦ Temporarily ¦ Permanently
26 F Operation lock Off -
Off ¦ On
27 F Programming lock Off -
Off ¦ On
28 I Direct adjustment Storage with confirmation -
Automatic storage ¦ Storage with confirmation
29 E Units °C, bar -
°C, bar ¦ °F, PSI
30 O Save basic settings No -
No ¦ Yes
31 O Activate basic settings No -
No ¦ Yes
32 O Basic settings Incompatible -
Compatible ¦ Compatibility restricted ¦ Incompatible ¦
Incompatible operator unit
39 O Commissioning menu On. -
Off ¦ On
40* I Used as Room unit 1 -
Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1 ¦
Operator unit 2 ¦ Operator unit 3 ¦ Service unit
42* I Assignment device 1 Heating circuit 1 -
Heating circuit 1 ¦ Heating circuits 1 and 2 ¦ Heating circuits 1
and 3 ¦ All heating circuits
44 I Operation HC2 Jointly with HC1 -
Jointly with HC1 ¦ Independently
46 I Operation HC3 Jointly with HC1 -
Jointly with HC1 ¦ Independently
58
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
70 F Software version -
Wireles
s
120** I Binding No
No ¦ Yes
121** I Test mode Off
Off ¦ On
130 I Room unit 1 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
131 I Room unit 2 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
132 I Room unit 3 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
133 I Outside sensor - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
134 I RF repeaters - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
135 I Operator unit 1 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
136 I Operator unit 2 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
137 I Operator unit 3 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
138 I Service unit - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
140 I Delete all devices No -
No ¦ Yes
* QAA7x only
** QAA78 only
*** Not QAA78
59
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Time of day and date must be set for the time switch automatic.
1 Hours/minutes
2 Day / month
3 Year
5 Start of summertime
6 End of summertime
Daylight saving The dates set for the changeover from wintertime to summertime, and vice versa,
time/standard time ensure that on the first Sunday after the set date the time of day will change from
changeover 02:00 (wintertime) to 03:00 (summertime) and from 03:00 (summertime) to 02:00
(wintertime).
60
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
61
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Enable basic setting With the exception of the data listed below, the setting data of all operating levels
are transferred from the memory of the operator unit to the connected controller.
Former setting data in the controller will be overwritten.
The following data will not be overwritten:
Basic setting "Basic setting" displays the compatibility of device versions and data sets on the
controller and operator unit. The following applies:
62
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Commissioning menu. The commissioning menu is automatically displayed upon PowerUp and must be
processed. The user must enter the language settings and time. Once completed,
the basic display is displayed and the menu no longer appears at PowerUp. It can,
however, be enabled again using the parameter "Commissioning menu" and then
is displayed again the next time power is interrupted.
Addition: The process can be bypassed by pressing the ESC button on the
commissioning menu. The basic display is immediately displayed and the
commissioning menu returns at the next PowerUp (since it has not yet been
processed).
Used as
No. Operating line Settings
40* Used as Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1
¦ Operator unit 2 ¦ Operator unit 3 ¦ Service unit
* QAA7x only
Basic principle: the number (1, 2, or 3) after the room unit or operator unit indicates
the heating circuit (1, 2, or 3) controlled by the operator unit.
Additional assignments are available for room unit/operator unit 1 on heating
circuits 1 to 3 (heating circuit assignment: Operating lines 42 to 48).
Heating circuit
assignment No. Operating line Settings
The following example illustrates applications available using the settings "Used
as" (operating line 40) together with "Heating circuit assignment" (operating lines
42 to 48).
Examples Existing heating circuits 1 and 2 should be controlled centrally from room unit 1 for
logistical reasons. The room temperature on room unit 1 is relevant to only heating
circuit 1 since climatic conditions for the heating circuit 2 (e.g. winter garden) may
differ from heating circuit 1. A room unit 2 allows for separate temperature
measurements and individually setting of heating circuit 2. Conversely, operating
unit 1 operates the occupancy button.
Settings for the example:
QAA7x, unit 1
Operating line 40 Room unit 1
Operating line 42 Heating circuits 1 and 2
Operating line 47 For heating circuit 1 only
Operating line 48 For all assigned heating circuits
QAA7x, unit 2
Operating line 40 Room unit 2
63
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
"Used as" in detail Definition of the operator unit (QAA7x only) as room unit, operator unit or service
(operating line 40). unit. Assignment to a heating circuit (can be extended for room unit/operator unit
1).
Room unit/operator unit controls heating circuit 1; can be extended using settings in
1. operator line 42; provided the heating circuit is activated on the
basic unit.
Room unit/operator unit controls heating circuit 2; provided the heating circuit is
2. activated on the basic unit.
Room unit/operator unit controls heating circuit 3; provided the heating circuit is
3. activated on the basic unit.
Operator unit 1 control the heating circuits activated on the basic unit.
NOTICE
● One user ("Used as") can be assigned to exactly one operator unit.
● The operator unit neither records nor sends room temperature if QAA7x is
defined as the operator or service unit.
Heating circuit
assignment in detail.
Assignment device 1 Extended assignment of heating circuits 1 to 3 for room unit/operator unit 1.
(operating line 42)
Heating circuit 1 controls heating circuit 1.
Heating circuits 1 and 2 controls heating circuits 1 and 2.
Heating circuits 1 and 3 controls heating circuits 1 and 3.
All heating circuits controls heating circuits 1, 2, and 3.
Operation of HC2 Defines the effect of operation (operating mode button, knob) on the room
(operating line 44). unit/operating unit 1 for heating circuit 2 or on the service unit.
64
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Room temperature The room temperature value for room unit 1 can be assigned to the relevant
device 1 (operating line heating circuits. If only 1 heating circuit is assigned, the room temperature value is
47) always assigned to it.
Occupancy button device The action of the occupancy button on room unit/operator unit 1 can be assigned to
1 (operating line 48). the relevant heating circuits. If only heating circuit 1 is assigned, the occupancy
button always acts on that heating circuit.
Operating line
40 42 44 46 47 48
Room unit 1 Heating circuit 1
Heating circuits 1 and 2 x x x
Heating circuits 1 and 3 x x x
All heating circuits x x x x
Room unit 2
Room unit 3
Operator unit 1 Heating circuit 1
Heating circuits 1 and 2 x x
Heating circuits 1 and 3 x x
All heating circuits x x x
Operator unit 2
Operator unit 3
Operator unit 1 X X (x)
65
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…
Operating line
40 42 44 46 47 48
Operator unit 1 All heating circuits x x
Room sensor
No. Operating line Settings
70 Software version
66
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3
Delete all devices The radio link to all devices will be cancelled. If radio communication is required
again, a new binding must be established.
67
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...
3.3 AVS37.390...
3.3.1 Operation
Operating elements
4 5
The above illustration shows an example of the front of an operator unit (not
supplied as standard).
68
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3
Press the button to switch from heating mode on / off to DHW heating, and vice
versa.
The selection made is indicated by a bar which appears below the respective
symbol.
Controller stop function The controller stop function is triggered by pressing the operating mode buttons for
an extended period (> 3 seconds).
The controller stop function can be used to manual control the burner.
The operator's output specifications override the control algorithm for the LMS14...
Exception The 2-point controller places the burner out of service, if the flow temperature
achieves the maximum boiler temperature (OL 2212: Setpoint).
69
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...
Press the +/- buttons to directly lower or increase the Comfort setpoint .
Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.
70
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3
Displaying information
71
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...
Error / maintenance In exceptional cases, the basic display shows one of the following symbols:
72
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3
3.3.2 Programming
Setting principle Settings that cannot be made directly with the help of operating elements are made
through programming. For that, the respective setting buttons are used as follows:
NOTICE
● When pressing the ESC button, you go one step back; adjusted values will
not be adopted
● If no setting is made for 8 minutes, the display returns automatically to the
basic display
● Operating lines may be hidden, depending on the type of controller, the
configuration made and the user level
Press OK.
73
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...
74
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3
75
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...
Operating line
Operating line clear-text units
User level
Function Default value Min max Unit
Time of day and date
50 1 E Hours/minutes 01:00 00:00 23:59 hh:mm
51 2 E Day / month 1.01 01.01 31.12 dd.mm
52 3 E Year 2004 2004 2099 yyyy
53 4 F Start of summertime 25.03 01.01 31.12 dd.mm
54 5 F End of summertime 25.10 01.01 31.12 dd.mm
59 6220 F software version - 0 99.9 -
Time prog heating circuit 1
60 500 E Preselection Mo - Su -
61 501 E 1. Phase on 6:00 00:00 24:00 hh:mm
62 502 E 1. phase off 22:00 00:00 24:00 hh:mm
63 503 E 2. Phase on --:-- 00:00 24:00 hh:mm
64 504 E 2. phase off --:-- 00:00 24:00 hh:mm
65 505 E 3. Phase on --:-- 00:00 24:00 hh:mm
66 506 E 3. phase off --:-- 00:00 24:00 hh:mm
Time prog heating circuit 2
67 520 E Preselection Mo - Su
68 521 E 1. Phase on 6:00 00:00 24:00 hh:mm
69 522 E 1. phase off 22:00 00:00 24:00 hh:mm
70 523 E 2. Phase on --:-- 00:00 24:00 hh:mm
71 524 E 2. phase off --:-- 00:00 24:00 hh:mm
72 525 E 3. Phase on --:-- 00:00 24:00 hh:mm
73 526 E 3. phase off --:-- 00:00 24:00 hh:mm
Time program for DHW
74 560 E Preselection Mo - Su
75 561 E 1. Phase on 6:00 00:00 24:00 hh:mm
76 562 E 1. phase off 22:00 00:00 24:00 hh:mm
77 563 E 2. Phase on --:-- 00:00 24:00 hh:mm
78 564 E 2. phase off --:-- 00:00 24:00 hh:mm
79 565 E 3. Phase on --:-- 00:00 24:00 hh:mm
80 566 E 3. phase off --:-- 00:00 24:00 hh:mm
Heating circuit 1
81 712 E Reduced setpoint HC1. 16 4 35 °C
82 720 E Heating curve slope HC1. 1.5 0.10 4.00 °C
83 721 F Heating curve displacement HC1. 0 -4.5 4.5 °C
84 730 E Summer/winter heating limit HC1. 18 ---/8 30 °C
85 741 F Flow temperature setpoint maximum HC1. 80 8 95 °C
Heating circuit 2
76
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3
77
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 Operator unit and room units QAA5x... / QAA7x... / AVS37...
4 Technical data
78
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
Operator unit and room units QAA5x... / QAA7x... / AVS37...
4
79
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 RF module AVS71.390
80
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
RF module BSB AVS71.393
4
81
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 RF repeater AVS14.390
82
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
RF outside sensor AVS13.399
4
83
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Index
Index
A O
Automatic operation, 45 Outside sensor, 67
AVS13.399, 32
P
AVS14.390, 29
Protection, 46
AVS71.390, 25
Push, 47
AVS71.393, 27
R
B Repeater, 29, 67
Binding, 66
Reset, 50
Button
RF, 17
Drinking water, 47
Binding, 66
Heating mode, 45
Test mode, 66
Info, 49
RF outside sensor, 32
C RF repeater, 29
Chimney sweep function, 51, 72 Room sensor
Continuous operation, 45 Correction, 66
Correction Room unit, 67
Room sensor, 66
S
D Service unit, 67
Date, 60 Set time, 53, 73
Daylight saving time, 60 Settings, 60
Device list, 67 Software version, 66
Device version, 66 Standard time changeover, 60
DHW
T
Push, 47
Technical data
Display, 44, 44
AVS13.399, 83
Drinking water
AVS14.390, 82
Operation, 47
AVS37..., 78
E AVS71.390, 80
Error message, 50 AVS71.393, 81
QAA7x..., 78
H Test mode, 66
Heating mode, 45 Time of day, 60
HMI, 67
U
I User levels, 57
Info button, 49
L
Language, 61
M
Maintenance message, 50
84
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Index
85
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Issued by © 2012-2014 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
Document ID CE1U2358en_04
Edition 2014-09-26