Albatros2

Operator units / Room units /


Auxiliary devices
Technical Manual

CE1U2358en_04 Building Technologies


2014-09-26
Content

1 Overview .........................................................................................................5
2 Mounting and installation...............................................................................9
2.1 Wired components............................................................................................9
2.1.1 Room unit QAA55… ........................................................................ 10
2.1.2 Room unit QAA75… ........................................................................ 12
2.1.3 Operator unit AVS37.29x ................................................................. 14
2.1.4 Operator unit AVS37.394 ................................................................. 15
2.1.5 Operator unit AVS37.390... .............................................................. 16
2.2 RF components .............................................................................................. 17
2.2.1 Room unit QAA58… ........................................................................ 18
2.2.2 Room unit QAA78... ......................................................................... 21
2.2.3 RF module AVS71.390 ....................................................................25
2.2.4 RF module BSB AVS71.393 ............................................................ 27
2.2.5 RF repeater AVS14.390 ................................................................... 29
2.2.6 RF outside sensor AVS13.399 ......................................................... 32
2.2.7 Checking the RF components .......................................................... 36
3 Handling ........................................................................................................ 37
3.1 QAA55... / QAA58........................................................................................... 37
3.1.1 Operation......................................................................................... 37
3.1.2 Programming ................................................................................... 41
3.2 QAA75... / QAA78… / AVS37… ...................................................................... 42
3.2.1 Operation......................................................................................... 42
3.2.2 Programming ................................................................................... 53
3.2.3 User levels ....................................................................................... 56
3.2.4 Room unit, operator unit settings...................................................... 58
3.2.5 Settings in detail .............................................................................. 60
3.3 AVS37.390... .................................................................................................. 68
3.3.1 Operation......................................................................................... 68
3.3.2 Programming ................................................................................... 73
3.3.3 User levels ....................................................................................... 75
3.3.4 Overview of the settings ................................................................... 76
4 Technical data............................................................................................... 78
4.1 Operator unit and room units QAA5x... / QAA7x... / AVS37... .......................... 78
4.2 RF module AVS71.390 ................................................................................... 80
4.3 RF module BSB AVS71.393 ........................................................................... 81
4.4 RF repeater AVS14.390.................................................................................. 82
4.5 RF outside sensor AVS13.399 ........................................................................ 83
Index ....................................................................................................................... 84

3
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
4
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1

1 Overview
This document The room and operator units described in this document operate in an optimum
manner BMUs for floor-standing or wall-mounted boiler controllers. The room and
operator units are suitable for plants that do not require cooling.

List of described devices

Room unit QAA5x.110/101.

Room unit QAA7x.61x/101, room unit QAA7x.61x/501

5
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1

Operator unit AVS37.294/109, operator unit AVS37.294/509

Operator unit AVS37.296/109

Operator unit AVS37.394/109

Operator unit AVS37.390/209

6
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1

RF module AVS71.390

RF module BSB AVS71.393

7
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Overview
1

RF repeater AVS14.390

RF outside sensor AVS13.399

8
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2

2 Mounting and installation

2.1 Wired components


Devices in general

Do not expose devices to dripping water.

Room units Install room units in the main occupancy rooms.


The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the
floor)

Powered by base The base provides the power for QAA55 and QAA75. When the units are removed
from the base, power is cut off (i.e. the units are out of operation).

9
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components

2.1.1 Room unit QAA55…


Installation

Connections

1 CL+ BSB data


2 CL- BSB ground

10
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2

Dimensions and drilling


plan

11
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components

2.1.2 Room unit QAA75…


Installation

There must be sufficient clearance above the unit to install and remove it as
needed.

12
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2

Connections
Terminal Designation QAA75.610 QAA75.611
1 CL+ BSB data BSB data
2 CL- BSB ground BSB ground
3 G+ Reserved Power supply DC 12 V

Dimensions and drilling


plan

13
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components

2.1.3 Operator unit AVS37.29x


Installation
Installation Removal

Connections The AVS37.294 operator unit must be connected to terminal X30 of the basic unit
using the AVS82.491/109 connecting cable. The connectors are coded.

Dimensions

Panel cutout

14
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
Wired components
2

2.1.4 Operator unit AVS37.394


Dimensions

Siemens supplies operator unit AVS37.394 without a housing.

Connections The AVS37.394 operator unit must be connected to terminal X30 on the basic unit
using the AVS82.491/109 connecting cable. The connectors are coded.

15
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 Wired components

2.1.5 Operator unit AVS37.390...


Connections The AVS37.390 operator unit must be connected to terminal X30 of the basic unit
using the AVS82.491/109 connecting cable. The connectors are coded.

Dimensions

VA Visual area
AA Active area
A Control panel, front

The AVS37.390 operator unit is a PCB version without casing, supplied by


Siemens.

16
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

2.2 RF components
RF devices in general The wireless components should be located such that transmission is as
interference-free as possible. For installation, the following points must be
observed:
l Not in the vicinity of electrical cables, strong magnetic fields or equipment such
as PCs, TVs, microwave ovens, etc.
l Not near larger metal structures or constructional elements with fine metal
meshes, such as special glass or concrete.
l The distance to the transmitter should not exceed 30 meters or 2 floors

Do not expose devices to dripping water.

Room units Install room units in the main occupancy rooms.


The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the
floor)

17
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

2.2.1 Room unit QAA58…


Installation

Dimensions and drilling


plan

18
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

RF connection

NOTICE

● Establish RF connection while unmounted and near the RF module (BSB).


● The base unit powers the RF module (BSB).
● The devices battery supply must be activated (remove the battery protective
strip).

Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the occupancy button for at least 3 seconds.
a The room unit switches to the service level (Display "ru 1").
3. Depending on the heating circuit, turn knob to "ru 2", "ru 3".
4. Press occupancy button 3 times, until "P3" appears.
5. Press operating mode button.
a The process of opening the connection is started.
a The connection is complete as soon as the LED RF module (AVS71.390) turns
off and the room unit re-starts.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
a The room unit displays the room temperature.

Refer to Section Operation [➙ 37] for button labels.

19
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

Testing

NOTICE

● The test is made to check the quality of the radio link.


● Testing takes place at the final installation location.

1. Press the occupancy button for at least 3 seconds.


a The room unit switches to the service level (Display "ru..").
2. Press occupancy button 4 times, until "P4" appears.
3. Press operating mode button.
a Test mode begins. 24 telegrams are sent.

The test can be stopped by pressing the operating mode or occupancy buttons.

Example of a display during the test:

The test results are displayed on the display:


l The digits on the left show telegrams that have been sent, the digits on the
right telegrams that have been received.
l The test will be ended after 24 telegrams. The test is considered successful
when at least 50% of the telegrams sent have been received.
l If the test was not successful, some other mounting location should be chosen,
or the AVS14.390 RF repeater should be used.

20
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

2.2.2 Room unit QAA78...


Mounting with base.

In the case of mounting with base, there must be sufficient clearance above the
unit, enabling it to be fitted and removed

21
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

Mounting without base.

Connections / power Power is supplied via three 1.5 V alcaline batteries of type AA (LR06).
supply

Dimensions and drilling


plan

22
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

RF connection

NOTICE

● Establish RF connection while unmounted and near the RF module (BSB).


● The base unit powers the RF module (BSB).
● The devices battery supply must be activated (remove the battery protective
strip).

Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the OK button on the room unit.
a The room unit switches to the programming level.
3. Press the Info button for at least 3 seconds.
4. Using the knob, select "Commissioning" operating level and press the OK
button.
5. Using the knob, select "Operator unit" operating page and press the OK button.
6. Select operating line 40 "Used as" and make the proper settings.
7. Press the OK button to confirm.
8. Using the knob, select "RF" operating page and press the OK button.
9. Select operating line 120 "Binding" and press the OK button.
10. Use the setting knob to set to "Yes".
11. Press the OK button to confirm.
a The process of opening the connection is started.
a The display shows the progress of opening the connection in %. This process
can take 2...300 seconds.
a The connection is established when "Device ready" appears and the LED on
the RF module (AVS71.390) turns off.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").

Refer to Section Operation [➙ 42] for button labels.

23
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

Testing

NOTICE

● The test is made to check the quality of the radio link.


● Testing takes place at the final installation location.

1. On unit (as described above), select operating page "RF".


2. Select operating line 121 "Test mode" and press the OK button.
3. Use the setting knob to set to "On".
4. Press the OK button to confirm.
a Test mode begins. 24 telegrams are sent.

The test can be stopped by pressing the ESC button

Example of a display during the test:

The test results are displayed on the display:


l The digits on the left show telegrams that have been sent, the digits on the
right telegrams that have been received.
l The test will be ended after 24 telegrams. The test is considered successful
when at least 50% of the telegrams sent have been received.
l If the test was not successful, some other mounting location should be chosen,
or the AVS14.390 RF repeater should be used.

24
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

2.2.3 RF module AVS71.390


The RF module extends the product range by introducing wireless communication.
The RF modules allow system components, such as room units, to transmit data
without laying cables.

RF module (AVS71.390) and RF module BSB (AVS71.393) cannot be used


concurrently.

Engineering Do not install the unit inside metal casings (e.g. inside the boiler).

Installation

A: LED
B: Button

Terminals The cable of the RF module has a plug to connect to the controller (connection
X60).

Disconnect all power prior to connecting the basic unit!

25
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

Dimensions and drilling


plan

RF connection via RF The RF link is establishing using the RF module as described in the corresponding
module section on RF components.

26
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

2.2.4 RF module BSB AVS71.393


The RF module BSB extends the product range by introducing wireless
communication. The RF module BSB allows system components, such as room
units, to transmit data without laying cables.
In contrast to the RF module AVS71.390 communication occurs between RF
module BSB and basic unit (controller) via BSB. As a result, the RF module BSB
can be placed farther away from the basic unit (controller) (see Technical data).

RF module (AVS71.390) and RF module BSB (AVS71.393) cannot be used


concurrently.

Engineering l Do not install the unit inside a metal housing.


l Use the device only inside a building.

Installation

Connections
1 CL+ BSB data
2 CL- BSB ground
3 G+ DC 12 V

Troubleshooting

This pattern means: "No communication BSB" or "No communication BSB-RF".

27
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

Dimensions and drilling


plan

RF connection via RF l The RF link is establishing using the RF module BSB as described in the
module BSB corresponding section on RF components.
l LED on: Device is ready for operation.

28
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

2.2.5 RF repeater AVS14.390

NOTICE

● The radio repeater must be installed inside the building


● A power supply near the RF module (BSB) is required for the RF repeater to
set up the RF connection (see below).

Installation

Connections Power is supplied via the enclosed power pack. The wires are interchangeable.

Dimensions and drilling


plan

29
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

RF connection

NOTICE

● Establish RF connection while unmounted and near the RF module (BSB).


● The base unit powers the RF module (BSB).
● Power to the RF repeater must be properly installed.

1 2

1 Button 2 LED

Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the button on the installed RF repeater until the LED starts flashing
quickly.
a The connection is established when the LED on the RF module (AVS71.390)
extinguishes.
a The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").

30
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

Testing

NOTICE

● The test is made to check the quality of the radio link.


● Testing takes place at the final installation location.

1. Press the button on the RF repeater from 3 to (at most) 8 seconds.


a The LED blinks slowly.
- When radio communications are operating correctly, the LED on the RF
module (AVS71.390) flashes briefly at 10-second intervals.
- With RF module BSB (AVS71.393), the LEDs go off every 10 seconds.
2. After the test, press the button on the RF repeater again briefly until the LED
extinguishes.

The test can be cancelled by pressing the ESC button.

Operating principle The RF repeater forwards the RF signals between RF module (BSB) and base unit.
No further binding between the RF repeater and room unit required.

31
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

2.2.6 RF outside sensor AVS13.399

NOTICE

● The RF transmitter must be installed inside the building


● Place the RF transmitter to be able to exchange batteries.

Mounting type
RF transmitter Outside sensor

32
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

1 Remove the battery transit tab.

2 Battery

Connections l Connect the outside sensor to the RF transmitter via 2-core-line; the
connections can be interchanged.
l Power is supplied via three 1.5 V alcaline batteries of type AAA (LR03).

Dimensions and drilling


plan

33
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

RF connection

NOTICE

● Establish RF connection while unmounted and near the RF module (BSB).


● The base unit powers the RF module (BSB).
● The devices battery supply must be activated (remove the battery protective
strip).

1 2

1 Button

2 LED

Establishment 1. Press the button on the RF module (BSB) for at least 8 seconds.
a The LED on the RF module (BSB) blinks rapidly.
2. Press the button on the transmitter of the RF outside sensor for at least 8
seconds.
a This LED also blinks rapidly.
- The connection is established when the LED on the RF module
(AVS71.390) extinguishes.
- The LED of the RF module BSB (AVS71.393) lights again after 5 seconds
(operating state "On").
3. Press the button on the RF outside sensor again briefly until the LED
extinguishes.

34
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
RF components
2

Testing

NOTICE

● The test is made to check the quality of the radio link.


● Testing takes place at the final installation location.

1. Press the button on the transmitter of the RF outside sensor between 3 and
max 8 seconds.
a The LED blinks slowly.
- When radio communications are operating correctly, the LED on the RF
module (AVS71.390) flashes briefly at 10-second intervals.
- With RF module BSB (AVS71.393), the LEDs go off every 10 seconds.
2. After checking, press again briefly the button on the transmitter of the RF
outside sensor until the LED extinguishes.

The test can be cancelled by pressing the ESC button.

35
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Mounting and installation
2 RF components

2.2.7 Checking the RF components


To check required RF components, go to the "RF" operating page, operating lines
130 to 132 and 134 to 137.
Via the operating level "Commissioning".
In the aforementioned operating lines, you can see whether the desired room units,
operator units and RF repeaters (as applicable) are operations or not (or no
reception).

The final check of the RF components is conducted using an operator or room


unit featuring operating line display (not QAA5x).

36
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3

3 Handling

3.1 QAA55... / QAA58...

3.1.1 Operation
Operating elements
1

1 Select heating mode

2 See room comfort setpoint. Other settings.

3 Occupancy button. navigation

37
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA55... / QAA58...

Display Displays all segments:

Example of basic display:

Explanation The display has the following meaning:

Heating to Comfort setpoint Error messages

Heating to the Reduced set point Burner in operation (oil/gas


burner).

Selecting pace heating


mode

This button is used to switch between the different operating modes.


The selection is displayed by a bar below the heating mode symbol.

Automatic operation
In automatic mode the room temperate is controlled as per the scheduler.
Characteristics of automatic mode:
l Heating mode according to the time program

l Room setpoints per the heating program "Comfort setpoint" or "Reduced

setpoint"
l Protective functions active.
l Automatic summer / winter changeover and automatic 24-hour heating limit
active (ECO functions)

38
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3

Continuous operation or
Under continuous operation, the room temperature is maintained at a constant to
the selected operating level.

Heating to the Comfort setpoint

Heating to the Reduced set point

Characteristics of continuous operation:


l Heating mode with no time program.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit inactive in the case of continuous operation with Comfort setpoint

Protection
When using Protection, the heating system is off. But it remains protected against
frost (frost protection temperature) provided there is no power failure.
Characteristics of Protection:
l Heating OFF.
l Temperature according to frost protection.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit active

39
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA55... / QAA58...

Adjusting the room


temperature setpoint

Turn the setting knob to increase or decrease the Comfort setpoint heating .

NOTICE

● Direct settings using the knob have no effect if the plant is in an operating
state other than Comfort heating .
● Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.

Presence button

If you do not use the rooms for short periods of time, you can press the presence
button to temporarily reduce heating.
Heating operation changes from Comfort setpoint heating to reduced setpoint
heating.
Press the occupancy button again as soon as the rooms are occupied.

NOTICE

● The occupancy button is only active in automatic mode.


● The current selection is active until the next switching action as per the
switching program.

40
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA55... / QAA58...
3

3.1.2 Programming
Setting principle 1. Press the occupancy button (> 3 seconds).
a The room unit switches to the service level.
The first parameter is selected; the present value blinks.
2. Use the setting knob to set the parameter.
3. Briefly press the occupancy button.
a The next parameter is selected for setting.
4. Exit service level:
- After 8 seconds without activity, the room unit exists the service level.
- Briefly press the operating mode button.

Settings

Parameter Display Function

Used as ru = 1 The room unit is addressed as RU1 (default setting).


ru = 2 The room unit is addressed as RU2.
ru = 3 The room unit is addressed as RU3.
Direct adjustment P1 = 1 Automatic storage: (default setting)
A setpoint readjustment with the knob is adopted either by pressing the operating mode
button or without any further confirmation (timeout).
P1 = 2 Save with confirmation:
A setpoint readjustment with the knob is adopted only after pressing the operating
mode button.
Programming lock P2 = 0 OFF: All operating elements released (default setting).
P2 = 1 ON: Following operating elements are locked:
- Operating mode changeover heating circuit.
- Readjustment of Comfort setpoint.
- Changeover of operating level (occupancy button).
RF connection* P3 Start connection with operating mode button.
Test mode* P4 Start test of RF connection with operating mode button.

* QAA58… only.

NOTICE

● If operation lock is active and one of the locked buttons is pressed, "OFF" is
displayed for 3 seconds.
● The operation lock does not prevent the service level from being accessed.

41
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

3.2 QAA75... / QAA78… / AVS37…

3.2.1 Operation
Operating elements
Room units

QAA75... / QAA78… 1

4
5

1 Selecting pace heating mode 5 Navigation and setting

2 Selecting DHW heating 6 Presence button

3 Quitting the setting 7 Display information

4 Adopting the setting

42
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Operator unit 1 2
AVS37…

4 5 6 7 8 9 10

1 Selecting DHW heating 6 Quitting the setting

2 Selecting pace heating mode 7 Navigation and setting

3 Display information 8 Adopting the setting

4 Service socket (BSB) 9 Manual operation

5 Unlock (only AVS37.296) 10 Chimney sweep function

43
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Display Displays all segments:

Explanation The display has the following meaning:

Heating to the Comfort setpoint Holiday function active

Heating to the Reduced set point Reference to heating circuit.

Heating to the frost protection setpoint Service / special functions

Cooling to cooling setpoint. Error messages

Process running – please wait Info level activated

Change battery Programming activated


Burner operating (only oil/gas boiler); Heating temporarily switched off
active burner stage. ECO function active
Compressor operating (HP only).

44
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Selecting pace heating


mode

This button is used to switch between the different operating modes.


The selection is displayed by a bar below the heating mode symbol.

Automatic operation
In automatic mode the room temperate is controlled as per the scheduler.

Characteristics of automatic mode:


l Heating mode according to the time program

l Room setpoints per the heating program "Comfort setpoint" or "Reduced

setpoint"
l Protective functions active.

l Automatic summer / winter changeover (ECO functions)

Continuous operation or
Under continuous operation, the room temperature is maintained at a constant to
the selected operating level.

Heating to the Comfort setpoint

Heating to the Reduced set


point

Characteristics of continuous operation:


l Heating mode with no time program.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit inactive in the case of continuous operation with Comfort setpoint

45
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Protection
When using Protection, the heating system is off. But it remains protected against
frost (frost protection temperature) provided there is no power failure.

Characteristics of Protection:
l Heating OFF.
l Temperature according to frost protection.
l Protective functions active.
l Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit active

Controller stop function The controller stop function is triggered by pressing the operating mode buttons for
an extended period (> 3 seconds).

The controller stop function can be used to manual control the burner.
The operator's output specifications override the control algorithm for the LMS14...

Exception The 2-point controller places the burner out of service, if the flow temperature
achieves the maximum boiler temperature (OL 2212: Setpoint).

46
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Selecting DHW heating

The button is used to set DHW heating mode.


The following functions are available, depending on whether it is a DHW storage
tank or instantaneous DHW heater:

Plant type Operating Press button Display


mode

DHW storage On. 1x 1. bar to the left (under DHW symbol).


tank
Off 2x No bar.
Instantaneous On. 1x 1. + 2. Bar left
heater.
ON ECO 2x 1. bar to the left (under DHW symbol).
Off 3x No bar.

DHW mode
On: The DHW is treated according to the selected switching program. Keep hot
function is generally released.
On Eco: Same as operating mode "On", but: Keep hot function is off.
Off: No DHW heating, but the protective function is active.

The keep hot function maintains the temperature of the instantaneous DHW
heater so that warm water is quickly available the next time the facet is turned on.

DHW push
The DHW push function is only available for the DFW storage tank.

The DHW push is triggered by pressing the DHW mode button for an extended
period (> 3 seconds).
DHW push initiates a single DHW charging cycle to the nominal setpoint. The push
is active until the nominal DHW setpoint is reached.
DHW push can also be started when:
l DHW mode is "off".
l Operating mode changeover is effected via H1 or centrally (LPB)
l All heating circuits use the holiday function

NOTICE

Once triggered, the DHW push cannot be cancelled via the operator unit.

47
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Adjusting the room


temperature setpoint

Turn the setting knob to increase or decrease the Comfort setpoint heating .

NOTICE

● Direct settings using the knob have no effect if the plant is in an operating
state other than Comfort heating .
● For reduced setpoint, press OK, select operating page “Heating circuit“ and
adjust the “Reduced setpoint”.
● Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.

Presence button

If you do not use the rooms for short periods of time, you can press the presence
button to temporarily reduce heating.
Heating operation changes from Comfort setpoint heating to reduced setpoint
heating.
Press the occupancy button again as soon as the rooms are occupied.

NOTICE

● The occupancy button is only active in automatic mode.


● The current selection is active until the next switching action as per the
switching program.

48
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Displaying information

Various data can be displayed by pressing the info button.

Displays The following information is displayed:


l Error message (error code list).
l Maintenance messages (maintenance code list).
l Special mode messages (special mode code list).
l Info lines.

NOTICE

● The code lists are documents in the corresponding controller user's guides.
● The info line texts are self explanatory.

49
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Error / maintenance In exceptional cases, the basic display shows one of the following symbols:

Error message. Maintenance or special mode.


If this symbol appears, an error in the plant If this symbol appears, a maintenance
has occurred. message is delivered or the plant has
changed to special operation.

Press the info button and read further Press the info button and read further
information. information.

The LPB number on the display indicates the device in the LPB system from which
the error or maintenance message, or special operation, was triggered. The first 2
digits give the segment address, the 2 digits after the dot the device address.
Hence, 02.01 denotes segment 2, device 1.

Reset function The reset function for meters and the resettable parameters appears on the bottom
line of the display, provided a reset is permitted on the current operating line (end
user / commissioning / heating engineer).

After activation with the OK button, the display will show a flashing “Yes”.

After confirmation with the OK button, the relevant parameter or meter is reset.

50
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Manual operation

A short press (< 3 seconds) of the manual operation button enable the manual
operating mode.
When manual operation is active, the relays are no longer switched according to
the control state, but are set to a predefined manual operation state depending on
their function.
The burner relay switched on in manual control can be switched off by the
electronic temperature controller (TR).

Setpoint adjustment in The device switches to the basic display after enabling manual operation.
manual control
The (maintenance) special mode symbol is displayed.

1. Press the INFO button.


a Device switches to the Info display for manual operation.
2. Use the knob to set the setpoint.

Chimney sweep function

A short press (< 3 seconds) of the chimney sweep function enables the manual
operating mode.
It produces the operating state required for making measuring emissions (flue gas).

Set burner output The device switches to the basic display after enabling chimney sweep function.
The (maintenance) special mode symbol is displayed.

1. Press the INFO button.


a Device switches to the Info display for the chimney sweep function.
2. Depending on the device: Use the knob to set the burner output.

51
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Bleed function

A long press ( > 3 seconds) of the manual operation button enables the bleeding
function.
The bleeding function bleeds any air in the heating/hot water system using an
automatic bleeder installed above the boiler. The system pumps are switched on in
a specified sequence.

Unlocking function

Some errors result in a lock of LMS14/15...


These errors cannot be reset via standard menu ("Reset?").

Locking error features:


l Remain saved also after mains off.
l Unlocking is required even after the fault no longer is present.
l If error still persists, remove first the error.

Operation of unlocking button:


l 0.4...10 seconds: LMS14/15... is unlocked.
l > 10 seconds: LMS14/15... is locked.
Note: Unlock by unlocking button (0.4...10 seconds).

The unlocking button executes the same function as switching of LMS input
"Reset" (X4/X4a).

52
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

3.2.2 Programming
Setting principle Settings that cannot be made directly with the help of operating elements are made
through programming. For this purpose, the individual settings are structured in the
form of menus and operating lines, thus creating practical groups of settings.
The following example shows how to set the time of day and the date.

Example "Setting the


time of day"

NOTICE

● When pressing the ESC button, you go one step back; adjusted values will
not be adopted
● If no setting is made for 8 minutes, the display returns automatically to the
basic display
● Operating lines may be hidden, depending on the type of controller, the
configuration made and the user level

Operation Display example Description

1 Basic display.
If the basic display is not shown, press the ESC
button to go back.

Press OK.

2 The bottom section of the display shows various


menus.
Turn the setting knob until operating page Time
of day and date appears.

Press the OK button to confirm.

53
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Operation Display example Description

3 In the bottom section of the display, the first


operating line of operating page Time of day
and date appears.
Turn the setting knob until operating line Hours /
minutes appears.

Press the OK button to confirm.

4 The display shows the hours blinking.


Turn the setting knob until the hours of the time
of day are correct.

Press the OK button to confirm.

5 The display shows the minutes blinking.


Turn the setting knob until the minutes of the
time of day are correct.

Press the OK button to confirm.

54
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Operation Display example Description

6 The settings are saved and the displays stops


blinking.
Now, you can make further settings or
press the operating mode button to return to the
basic display.

7 Unit now returns to basic display.

Example of menu
structure

55
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

3.2.3 User levels

The user levels only allow authorized user groups to make settings. To reach the
required user level, proceed as follows:

Operation Display example Description

1 Basic display.
If the basic display is not shown, press the
ESC button to go back.

Press OK.

2 You are on user level Enduser.

Long press of the INFO button (> 3 Seconds).

3 You are now given a choice of user levels.


Turn the setting knob until the required user
level is reached.

Press OK.

56
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Operation Display example Description

You are now at the required user level.

To reach the OEM level, the relevant code must be entered.

Setting structure "End The example given here shows that certain user levels do not allow certain
user" settings. The example shows them highlighted. On the unit, they are hidden.

Setting structure
"Heating engineer"

57
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

3.2.4 Room unit, operator unit settings


The table displays settings relevant to room and operator units.
Key
E End-user F heating engineer
I Commissioning O OEM

Operating line
User level
Function [value range] Standard Min max Unit
Time of day and date
1 E Hours/minutes - 00:00 23:59 hh:mm
2 E Day / month - 01.01 31.12 dd.mm
3 E Year - 2004 2099 yyyy
5 F Start of summertime 25.03 01.01 31.12 dd.mm
6 F End of summertime 25.10 01.01 31.12 dd.mm
Operator section
20 E Language German -
German ¦ English ¦ French ¦ Italian ¦ etc.
21 O Display of special operation On: QAA7x.6xx/101,201,501; AVS37.x9x/109,509
Off ¦ On Off: QAA7x.6xx/301,701; AVS37.x9x/209,309,709
22 F Info Temporarily -
Temporarily ¦ Permanently
24*** O Lighting Temporary -
Off ¦ Temporarily ¦ Permanently
26 F Operation lock Off -
Off ¦ On
27 F Programming lock Off -
Off ¦ On
28 I Direct adjustment Storage with confirmation -
Automatic storage ¦ Storage with confirmation
29 E Units °C, bar -
°C, bar ¦ °F, PSI
30 O Save basic settings No -
No ¦ Yes
31 O Activate basic settings No -
No ¦ Yes
32 O Basic settings Incompatible -
Compatible ¦ Compatibility restricted ¦ Incompatible ¦
Incompatible operator unit
39 O Commissioning menu On. -
Off ¦ On
40* I Used as Room unit 1 -
Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1 ¦
Operator unit 2 ¦ Operator unit 3 ¦ Service unit
42* I Assignment device 1 Heating circuit 1 -
Heating circuit 1 ¦ Heating circuits 1 and 2 ¦ Heating circuits 1
and 3 ¦ All heating circuits
44 I Operation HC2 Jointly with HC1 -
Jointly with HC1 ¦ Independently
46 I Operation HC3 Jointly with HC1 -
Jointly with HC1 ¦ Independently

58
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

47* I Room temperature device 1 For all assigned HCs -


None Heating circuit 1 only ¦ For all assigned HCs
48* I Occupancy button device 1 For all assigned HCs -
None ¦ Heating circuit 1 only ¦ For all assigned HCs
54* F Readjustment room sensor 0.0 -3 99.9 -

70 F Software version -

Wireles
s
120** I Binding No
No ¦ Yes
121** I Test mode Off
Off ¦ On
130 I Room unit 1 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
131 I Room unit 2 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
132 I Room unit 3 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
133 I Outside sensor - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
134 I RF repeaters - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
135 I Operator unit 1 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
136 I Operator unit 2 -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
137 I Operator unit 3 - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
138 I Service unit - -
Missing ¦ In operation ¦ No recept'n ¦ Change batt
140 I Delete all devices No -
No ¦ Yes

* QAA7x only
** QAA78 only
*** Not QAA78

59
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

3.2.5 Settings in detail

Operating page "Time of day and date"


The controller has a yearly clock with time of day, weekday and date.

Time of day and date must be set for the time switch automatic.

No. Operating line Settings

1 Hours/minutes
2 Day / month
3 Year
5 Start of summertime
6 End of summertime

Daylight saving The dates set for the changeover from wintertime to summertime, and vice versa,
time/standard time ensure that on the first Sunday after the set date the time of day will change from
changeover 02:00 (wintertime) to 03:00 (summertime) and from 03:00 (summertime) to 02:00
(wintertime).

Operating page "Operator unit"


Operation and display
No. Operating line Settings

20 Language German ¦ English ¦ French ¦ Italian ¦ etc.


21 Display of special operation Off ¦ On
22 Info Temporarily ¦ Permanently
24 Lighting Off ¦ Temporarily ¦ Permanently
26 Operation lock Off ¦ On
27 Programming lock Off ¦ On
28 Direct adjustment Automatic storage ¦ Storage with confirmation
29 Units °C, bar ¦ °F, PSI
30 Save basic settings No ¦ Yes
31 Activate basic settings No ¦ Yes
32 Basic settings Compatible ¦ Compatibility restricted ¦ Incompatible ¦
Incompatible operator unit
39 Commissioning menu Off ¦ On

60
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Languages Available languages vary depending on country and version.


Display of special l Off
operation Special operation is not displayed on the basic display. Display of special operation
is available on the info level only.
l On.
The "Tool" symbol is displays and special operations are displayed directly in the
basic display. Switching to the info level not required.
Special operation includes, for example, manual operation, emergency more,
outside temperature simulation, Eco mode and output test.
Info l Temporary
After pressing the info button, a change to the “predefined” basic display is made
after a maximum of 8 minutes or by pressing the operating mode button (with the
QAA78… only 2 minutes) .
l Permanently
After pressing the info button, a change back to the "new" basic display is made
after a maximum of 8 minutes. The info value selected last will be adopted by the
new basic display.
This setting cannot be made for QAA78…
Lighting l Off
No lighting.
l Temporary
Operator intervention (press of a button, turn of a knob) switches on lighting and
then switches it off 8 minutes after the last action.
l Permanently
Continuous lighting
Operation lock All operating elements are locked when operation lock is switched on that would
allow intervention in plant operations (heating circuit operating mode, hot water
operating mode, etc.).
Programming lock Parameter values can still be displayed, but not changed if the programming lock is
enabled.
l Temporary cancellation of programming
On the programming level, locked programming can temporarily be deactivated. To
do this, press the OK and ESC buttons simultaneously for 3 seconds. Temporary
deactivation of the programming lock is maintained until programming is quit.
l Continuous cancellation of programming
First run a temporary cancellation, then operating line 27 "Programming lock" to
cancel the programming lock.
Direct adjustment l Automatic storage:
A setpoint readjustment made with the knob is adopted either by pressing the OK
button or without any further confirmation (timeout).
l Storage with confirmation
A setpoint readjustment made with the knob is adopted only after pressing the OK
button.
Units l Temperature/Pressure values in °C, bar.
l Temperature/Pressure values in °F, PSI.
Save basic setting With the exception of the data listed below, the setting data are transferred from
the memory of the controller to the connected operator unit.

61
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Enable basic setting With the exception of the data listed below, the setting data of all operating levels
are transferred from the memory of the operator unit to the connected controller.
Former setting data in the controller will be overwritten.
The following data will not be overwritten:

line number Operating line

130 Room unit 1


131 Room unit 2
132 Room unit 3
133 Outside sensor
134 RF repeaters
135 Operator unit 1
138 Service unit
140 Delete all devices
516 Default values
536 Default values
556 Default values
576 Default values
6222 Device hours run
6600 Device address
6601 Segment address
6650 Outside temp source

The following data will not be overwritten either:


RF list, hours run / start counter, yield meter, maintenance meter, slave pointer,
and error history.

RF connection must be restored following "Enable basic setting".

"Enable basic setting" is only shown under certain circumstances. Refer to


following associations under "Basic setting" (operating line 32).

Basic setting "Basic setting" displays the compatibility of device versions and data sets on the
controller and operator unit. The following applies:

Compatibility check Output Operating line 31 / Write


data set

Device versions/revisions are Compatible BZ 31 shown/data set


the same; data is the same. writable.
Device versions/revisions are Compatibility restricted BZ 31 shown/data set
not the same; data is the writable after query.
same.
All other cases. 'Incompatible' BZ 31 hidden/download to
controller not possible.

62
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Commissioning menu. The commissioning menu is automatically displayed upon PowerUp and must be
processed. The user must enter the language settings and time. Once completed,
the basic display is displayed and the menu no longer appears at PowerUp. It can,
however, be enabled again using the parameter "Commissioning menu" and then
is displayed again the next time power is interrupted.
Addition: The process can be bypassed by pressing the ESC button on the
commissioning menu. The basic display is immediately displayed and the
commissioning menu returns at the next PowerUp (since it has not yet been
processed).
Used as
No. Operating line Settings

40* Used as Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1
¦ Operator unit 2 ¦ Operator unit 3 ¦ Service unit
* QAA7x only

Basic principle: the number (1, 2, or 3) after the room unit or operator unit indicates
the heating circuit (1, 2, or 3) controlled by the operator unit.
Additional assignments are available for room unit/operator unit 1 on heating
circuits 1 to 3 (heating circuit assignment: Operating lines 42 to 48).

Heating circuit
assignment No. Operating line Settings

42* Assignment device 1 Heating circuit 1 ¦ Heating circuits 1 and 2 ¦ Heating


circuits 1 and 3 ¦ All heating circuits
44 Operation HC2 Jointly with HC1 ¦ Independently
46 Operation HC3 Jointly with HC1 ¦ Independently
47* Room temperature None ¦ Heating circuit 1 only ¦ For all assigned HCs
device 1
48* Occupancy button device None ¦ Heating circuit 1 only ¦ For all assigned HCs
1
* QAA7x only

The following example illustrates applications available using the settings "Used
as" (operating line 40) together with "Heating circuit assignment" (operating lines
42 to 48).
Examples Existing heating circuits 1 and 2 should be controlled centrally from room unit 1 for
logistical reasons. The room temperature on room unit 1 is relevant to only heating
circuit 1 since climatic conditions for the heating circuit 2 (e.g. winter garden) may
differ from heating circuit 1. A room unit 2 allows for separate temperature
measurements and individually setting of heating circuit 2. Conversely, operating
unit 1 operates the occupancy button.
Settings for the example:

QAA7x, unit 1
Operating line 40 Room unit 1
Operating line 42 Heating circuits 1 and 2
Operating line 47 For heating circuit 1 only
Operating line 48 For all assigned heating circuits

QAA7x, unit 2
Operating line 40 Room unit 2

63
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

"Used as" in detail Definition of the operator unit (QAA7x only) as room unit, operator unit or service
(operating line 40). unit. Assignment to a heating circuit (can be extended for room unit/operator unit
1).

Room unit/operator unit controls heating circuit 1; can be extended using settings in
1. operator line 42; provided the heating circuit is activated on the
basic unit.
Room unit/operator unit controls heating circuit 2; provided the heating circuit is
2. activated on the basic unit.
Room unit/operator unit controls heating circuit 3; provided the heating circuit is
3. activated on the basic unit.
Operator unit 1 control the heating circuits activated on the basic unit.

NOTICE

● One user ("Used as") can be assigned to exactly one operator unit.
● The operator unit neither records nor sends room temperature if QAA7x is
defined as the operator or service unit.

Heating circuit
assignment in detail.

Assignment device 1 Extended assignment of heating circuits 1 to 3 for room unit/operator unit 1.
(operating line 42)
Heating circuit 1 controls heating circuit 1.
Heating circuits 1 and 2 controls heating circuits 1 and 2.
Heating circuits 1 and 3 controls heating circuits 1 and 3.
All heating circuits controls heating circuits 1, 2, and 3.

Operation of HC2 Defines the effect of operation (operating mode button, knob) on the room
(operating line 44). unit/operating unit 1 for heating circuit 2 or on the service unit.

Commonly with HC1 Operation acts commonly on heating circuits 1 and 2.


Independently The action of operation is queried on the display as soon as the
operating mode button is pressed or the setting knob is
operated.

Operation of HC3 See "Operation of HC2" (operating line 44).


(operating line 46).

64
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Room temperature The room temperature value for room unit 1 can be assigned to the relevant
device 1 (operating line heating circuits. If only 1 heating circuit is assigned, the room temperature value is
47) always assigned to it.

None Heating circuit 1 has no room temperature value; room


temperature values from heating circuits 2 and 4 do not come
from room unit 1.
For heating circuit 1 Heating circuits 2 and 3 do not receive their room temperature
only values from room unit 1; except for heating circuit 1.
For all assigned Heating circuits 2 and 3 receive their room temperature values
heating circuits from room unit 1; heating circuit 1 as well.

Occupancy button device The action of the occupancy button on room unit/operator unit 1 can be assigned to
1 (operating line 48). the relevant heating circuits. If only heating circuit 1 is assigned, the occupancy
button always acts on that heating circuit.

None Heating circuit 1 has no occupancy function; the occupancy


functions for heating circuits 2 and 3 and not operated on room
unit/operator unit 1.
For heating circuit 1 Occupancy functions for heating circuits 2 and 3 are not operated
only on room unit/operator unit 1; exclusively those for heating circuit
1.
For all assigned Occupancy functions for heating circuits 2 and 3 are operated on
heating circuits room unit/operator unit 1; as well as those for heating circuit 1.

Overview of Settings for QAA7x


dependencies Depending on the selected "Used as" of the unit (operating line 40), the following
settings (marked with X) can be made when assigning the heating circuit.

Operating line
40 42 44 46 47 48
Room unit 1 Heating circuit 1
Heating circuits 1 and 2 x x x
Heating circuits 1 and 3 x x x
All heating circuits x x x x
Room unit 2
Room unit 3
Operator unit 1 Heating circuit 1
Heating circuits 1 and 2 x x
Heating circuits 1 and 3 x x
All heating circuits x x x
Operator unit 2
Operator unit 3
Operator unit 1 X X (x)

65
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 QAA75... / QAA78… / AVS37…

Settings for AVS37.294


Operating unit AVS37.294 is factory set as "Operating unit1" (see operating line
40) acting on "All heating circuits " (see operating line 42). Operating lines 44 and
46 can be set.

Operating line
40 42 44 46 47 48
Operator unit 1 All heating circuits x x

Room sensor
No. Operating line Settings

54* Readjustment room sensor


* QAA7x only, configured as room unit.

The temperature display can be readjusted.


Device data
No. Operating line Settings

70 Software version

The information represents the latest version of the room unit.

66
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
QAA75... / QAA78… / AVS37…
3

Operating page "RF"


Binding
No. Operating line Settings

120** Binding No ¦ Yes


121** Test mode Off ¦ On
* QAA78 only

For more detailed information, refer to the descriptions in Section "Wireless


components" [➙ 17].
Binding When commissioning the system, the wireless peripheral devices (room units) are
assigned to the basic unit.
Test mode The test mode is used for checking the radio link. The test should be made when
the installation is entirely completed.
RF device list
No. Operating line Settings

130 Room unit 1 Missing ¦ In operation ¦ No recept'n ¦ Change batt


131 Room unit 2 Missing ¦ In operation ¦ No recept'n ¦ Change batt
132 Room unit 3 Missing ¦ In operation ¦ No recept'n ¦ Change batt
133 Outside sensor Missing ¦ In operation ¦ No recept'n ¦ Change batt
134 RF repeaters Missing ¦ In operation ¦ No recept'n ¦ Change batt
135 Operator unit 1 Missing ¦ In operation ¦ No recept'n ¦ Change batt
136 Operator unit 2 Missing ¦ In operation ¦ No recept'n ¦ Change batt
137 Operator unit 3 Missing ¦ In operation ¦ No recept'n ¦ Change batt
138 Service unit Missing ¦ In operation ¦ No recept'n ¦ Change batt
140 Delete all devices No ¦ Yes

Delete all devices The radio link to all devices will be cancelled. If radio communication is required
again, a new binding must be established.

67
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...

3.3 AVS37.390...

3.3.1 Operation
Operating elements

4 5

1 Selecting the operating mode 4 Adjusting the nominal DHW setpoint

2 Display information 4 Navigation and settings

3 Chimney sweep function 5 Set room comfort setpoint.

5 Navigation and settings

The above illustration shows an example of the front of an operator unit (not
supplied as standard).

68
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3

Display Displays all segments:

Explanation The display has the following meaning:

Heating to the Comfort setpoint Burner in operation; active burner


stage.
Heating to the Reduced set point Error messages

Boiler operation active Service / special operation

Boiler operation DHW heating


active

Selecting the operating


mode

Press the button to switch from heating mode on / off to DHW heating, and vice
versa.
The selection made is indicated by a bar which appears below the respective
symbol.

Controller stop function The controller stop function is triggered by pressing the operating mode buttons for
an extended period (> 3 seconds).

The controller stop function can be used to manual control the burner.
The operator's output specifications override the control algorithm for the LMS14...

Exception The 2-point controller places the burner out of service, if the flow temperature
achieves the maximum boiler temperature (OL 2212: Setpoint).

69
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...

Adjusting the room


temperature setpoint

Press the +/- buttons to directly lower or increase the Comfort setpoint .

For the Reduced setpoint


l Press OK.
l Select the operating line for the “Reduced setpoint”.

Each time you make a readjustment, wait at least 2 hours, allowing the room
temperature to adapt.

Set nominal DHW


setpoint

Press the + / - buttons to increase or decrease the nominal DHW setpoint.

70
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3

Displaying information

Various data can be displayed by pressing the info button.


The display alternates, showing the value and the info no.

No. 1 Boiler temp No. 12 State DHW


No. 2 Return temperature No. 13 State of boiler
No. 3 Outside temperature No. 14 State solar
No. 4 DHW temp 1 No.15 flue gas temperature
No. 5 DHW temp 2 No.16 Indication of operation FA
No.6 Collector temp No.17 Ionization flow
No. 10 State heating circuit 1 No.18 SW diagnostic code
No. 11 State heating circuit 2

71
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...

Error / maintenance In exceptional cases, the basic display shows one of the following symbols:

Error messages Maintenance or special mode.


If this symbol appears, an error in the plant If this symbol appears, a maintenance
has occurred. message is delivered or the plant has
changed to special operation.

The display shows letter “c”, followed by the


error no. The display shows letter “c”, followed by the
error no.

Chimney sweep function

The chimney sweep function is activated by a short press (maximum 3 seconds) of


the chimney sweep button. This function produces the operating state required to
make emission measurements (flue gas).

72
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3

3.3.2 Programming
Setting principle Settings that cannot be made directly with the help of operating elements are made
through programming. For that, the respective setting buttons are used as follows:

Example "Setting the


time of day"

NOTICE

● When pressing the ESC button, you go one step back; adjusted values will
not be adopted
● If no setting is made for 8 minutes, the display returns automatically to the
basic display
● Operating lines may be hidden, depending on the type of controller, the
configuration made and the user level

Operation Display example Description


1 Basic display.
If the basic display is not shown, press the ESC button
to return to it.

Press OK.

2 The display shows the first operating line, alternating


with the value.
Press the arrow button until you reach operating line
“Hours / minutes” (e.g. 50).

Press the OK button to confirm.

73
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...

3 The display shows the hours blinking.


Press the "+/-" button until the hours of the time of day
are correct.

Press the OK button to confirm.

4 The display shows the minutes blinking.


Press the "+/-" button until the minutes of the time of
day are correct.

Press the OK button to confirm.

5 The settings are saved and the displays stops blinking.


You can continue with other settings or press the
operating mode button to go to the basic display.

6 Unit now returns to basic display.

74
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3

3.3.3 User levels


The user levels only allow authorized target groups to make settings. To reach the
required user level, proceed as follows:

Operation Display example Description


1 You see the basic display.
Press the OK button for 3 seconds.

2 Now, you are on the user level “End user”.

Press the INFO button for 3 seconds.

3 You are on user level “Enduser”.


If the change to the “Heating engineer” level was successful,
the display shows “ON” as a confirmation.

75
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
3 AVS37.390...

3.3.4 Overview of the settings


The table displays all available settings.
Key
E End-user F heating engineer BZ Operating line

Operating line
Operating line clear-text units
User level
Function Default value Min max Unit
Time of day and date
50 1 E Hours/minutes 01:00 00:00 23:59 hh:mm
51 2 E Day / month 1.01 01.01 31.12 dd.mm
52 3 E Year 2004 2004 2099 yyyy
53 4 F Start of summertime 25.03 01.01 31.12 dd.mm
54 5 F End of summertime 25.10 01.01 31.12 dd.mm
59 6220 F software version - 0 99.9 -
Time prog heating circuit 1
60 500 E Preselection Mo - Su -
61 501 E 1. Phase on 6:00 00:00 24:00 hh:mm
62 502 E 1. phase off 22:00 00:00 24:00 hh:mm
63 503 E 2. Phase on --:-- 00:00 24:00 hh:mm
64 504 E 2. phase off --:-- 00:00 24:00 hh:mm
65 505 E 3. Phase on --:-- 00:00 24:00 hh:mm
66 506 E 3. phase off --:-- 00:00 24:00 hh:mm
Time prog heating circuit 2
67 520 E Preselection Mo - Su
68 521 E 1. Phase on 6:00 00:00 24:00 hh:mm
69 522 E 1. phase off 22:00 00:00 24:00 hh:mm
70 523 E 2. Phase on --:-- 00:00 24:00 hh:mm
71 524 E 2. phase off --:-- 00:00 24:00 hh:mm
72 525 E 3. Phase on --:-- 00:00 24:00 hh:mm
73 526 E 3. phase off --:-- 00:00 24:00 hh:mm
Time program for DHW
74 560 E Preselection Mo - Su
75 561 E 1. Phase on 6:00 00:00 24:00 hh:mm
76 562 E 1. phase off 22:00 00:00 24:00 hh:mm
77 563 E 2. Phase on --:-- 00:00 24:00 hh:mm
78 564 E 2. phase off --:-- 00:00 24:00 hh:mm
79 565 E 3. Phase on --:-- 00:00 24:00 hh:mm
80 566 E 3. phase off --:-- 00:00 24:00 hh:mm
Heating circuit 1
81 712 E Reduced setpoint HC1. 16 4 35 °C
82 720 E Heating curve slope HC1. 1.5 0.10 4.00 °C
83 721 F Heating curve displacement HC1. 0 -4.5 4.5 °C
84 730 E Summer/winter heating limit HC1. 18 ---/8 30 °C
85 741 F Flow temperature setpoint maximum HC1. 80 8 95 °C
Heating circuit 2

76
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Handling
AVS37.390...
3

86 1012 E Reduced setpoint HC2. 16 4 35 °C


87 1020 E Heating curve slope HC2. 1.5 0.10 4.00 °C
88 1021 F Heating curve displacement HC2. 0 -4.5 4.5 °C
89 1030 E Summer/winter heating limit HC2. 18 ---/8 30 °C
90 1041 F Flow temperature setpoint maximum HC2. 80 80 95 °C
Domestic hot water
91 1612 E reduced setpoint 40 8 80 °C
92 1620 F Release 1 0 4 -
Configuration
94 5701 F Hydraulic diagram. 3 2 85 -
95 5920 F Configuration output. 0 0 17 -
96 5950 F Function input H1 0 0 9 -
LPB system
97 6600 F Device address 1 0 16 -
Maintenance
99 7010 F Acknowledge message. - - - -

77
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 Operator unit and room units QAA5x... / QAA7x... / AVS37...

4 Technical data

4.1 Operator unit and room units QAA5x... / QAA7x... /


AVS37...

Power supply For devices without batteries (wired):


QAA55 Bus power BSB
QAA75.610 Bus power BSB, with optional G+
(BG lighting not possible)
QAA75.611 Bus power BSB (without BG lighting)
with G+ (with BG lighting).
AVS37.x9x, AVS37.390 G+ mandatory (always with BG lighting)
Notes BG lighting: Background lighting
G+ Voltage value: see basic unit.
For battery-powered devices:
Batteries QAA58: 2 pcs / QAA78: 3 pcs
Type of batteries 1.5 V alkaline size AA (LR06)
Battery life approx. 1.5 years
Room temperature Measuring range 0..0.50 °C
measurement
(only with QAA7x.../QAA55...) As per EN12098:
Range 15...25 °C within a tolerance of 0.8 K
Range 0...15 °C or 25...50 °C Within a tolerance of 1.0 K
Resolution 0.1 K.
Interfaces AVS37... / QAA75... / QAA55... BSB-W,
2-wire connection, not interchangeable.
Line length base unit/peripheral device
QAA75... / QAA55... Max. 200 m
AVS37... Max. 3 m
QAA58..., QAA78... BSB-RF
Frequency band 868 MHz
Degree of protection Protection class If correctly installed, low-voltage live parts meet
the requirements of safety class III according to
EN 60730-1
Protection degree of housing
QAA7x... / QAA5x... IP20 as per EN 60529
AVS37... IP40 as per EN 60529, when mounted
Degree of pollution 2 according to EN 60730-1
suitable for residential, commercial and
industrial environment

78
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
Operator unit and room units QAA5x... / QAA7x... / AVS37...
4

Directives and Standards Product standard EN 60730-1


Automatic electrical controls for household and
similar use
Electromagnetic compatibility For use in residential, commerce, light-industrial
(Applications) and industrial environments

EU Conformity (CE) AVS37: CE1T2357xx3


QAA7x: CE1T2357xx2
QAA55: CE1T2358x2
Environmental compatibility The product environmental declarations
CE1E2358en01, CE1E2358en04 (AVS37..),
CE1E2357en01 (QAA7x) and CE1E2358en03
(QAA55) contains data on environmentally
compatible product design and assessments
(RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
Climatic conditions For devices without batteries (wired):
Storage as per IEC721-3-1 Class 1K3, temp. -20….65 °C
Transport as per IEC721-3-2 Class 2K3, temp. -25….70 °C
Operation as per IEC721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
For battery-powered devices:
Storage as per IEC721-3-1 Class 1K3, temp. -20….30 °C
Transport as per IEC721-3-2 Class 2K3, temp. -25….70 °C
Operation as per IEC721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
Weight Excl. packaging AVS37.294: 160 g
AVS37.296: 161 g
AVS37.394: 112 g
AVS37.390: 45 g
QAA75.61x: 170 g
QAA78.610: 312 g
QAA55.11x: 115 g
QAA58.11x: 165 g

79
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 RF module AVS71.390

4.2 RF module AVS71.390

Power supply Powered via basic unit RVS… 5.5 V DC


Power consumption Max. 0.11 VA
Interfaces Connection to basic units RVS… 6-pole prefabricated
(power supply, communication) flat-ribbon cable, ready fitted,
Length 1.5 m
RF transmitter BSB-RF
Frequency band 868 MHz
Degree of protection Protection class If correctly installed, low-voltage live parts meet
the requirements of safety class III according to
EN 60730-1
Protection degree of housing IP40 according to EN 60529
Degree of pollution 2 according to EN 60730-1
suitable for residential, commercial and
industrial environment
Directives and Standards Product standard EN 60730-1
Automatic electrical controls for household and
similar use
Electromagnetic compatibility For use in residential, commerce, light-industrial
(Applications) and industrial environments

EU Conformity (CE) CE1T2357x8


Climatic conditions Storage to EN 60721-3-1 Class 1K3, temp. -20…65 °C
Transport to EN 60721-3-2 Class 2K3, temp. -25…70 °C
Operation to EN 60721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
Weight Excl. packaging 54 g

80
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
RF module BSB AVS71.393
4

4.3 RF module BSB AVS71.393

Power supply Powered via basic unit RVS… G+ (11.3...13.2 V)


Power consumption Max. 0.3 VA
Interfaces Connection to basic unit RVS… BSB-W,
(power supply, communication) 2-wire connection, not interchangeable
Length basic / peripheral unit Max. 200 m
RF transmitter BSB-RF
Frequency band 868 MHz
Degree of protection Protection class If correctly installed, low-voltage live parts meet
the requirements of safety class III according to
EN 60730-1
Protection degree of housing IP20 according to EN 60529
Degree of pollution 2 according to EN 60730-1
suitable for residential, commercial and
industrial environment
Directives and Standards Product standard EN 60730-1
Automatic electrical controls for household and
similar use
Electromagnetic compatibility For use in residential, commerce, light-industrial
(Applications) and industrial environments

EU Conformity (CE) CE1T2358xx04


Environmental compatibility The product environmental declaration
CE1E2358en03 contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
Climatic conditions Storage to EN 60721-3-1 Class 1K3, temp. -20….65 °C
Transport to EN 60721-3-2 Class 2K3, temp. -25….70 °C
Operation to EN 60721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
Weight Excl. packaging 115 g

81
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
4 RF repeater AVS14.390

4.4 RF repeater AVS14.390

Power supply Nominal voltage AC 230 V (+10% /-15%)


(primary side AC/AC adapter)
Nominal frequency 50 Hz ±6%
Power consumption max. 0.5 VA
Supply line protection Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
Interfaces RF transmitter BSB-RF
Frequency band 868 MHz
Degree of protection Protection class If correctly installed, low-voltage live parts meet
the requirements of safety class III according to
EN 60730-1
Protection degree of housing IP20 according to EN 60529
Degree of pollution 2 according to EN 60730-1
suitable for residential, commercial and
industrial environment
Directives and Standards Product standard EN 60730-1
Automatic electrical controls for household and
similar use
Electromagnetic compatibility For use in residential, commerce, light-industrial
(Applications) and industrial environments

EU Conformity (CE) CE1T2357x8


Environmental compatibility The product environmental declaration
CE1E2357en13 contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
Climatic conditions Storage as per IEC721-3-1 Class 1K3, temp. -20….65 °C
Transport as per IEC721-3-2 Class 2K3, temp. -25….70 °C
Operation as per IEC721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
Weight Excl. packaging RF repeater: 112 g
Power supply: 195 g

82
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Technical data
RF outside sensor AVS13.399
4

4.5 RF outside sensor AVS13.399

Power supply Batteries 2 pieces.


Type of batteries 1.5 V alkaline size AAA (LR03)
Battery life approx. 2 years
Interfaces RF transmitter BSB-RF
Frequency band 868 MHz
Degree of protection Protection class If correctly installed, low-voltage live parts meet
the requirements of safety class III according to
EN 60730-1
Protection degree of housing IP20 according to EN 60529
Degree of pollution 2 according to EN 60730-1
suitable for residential, commercial and
industrial environment
Directives and Standards Product standard EN 60730-1
Automatic electrical controls for household and
similar use
Electromagnetic compatibility For use in residential, commerce, light-industrial
(Applications) and industrial environments

EU Conformity (CE) CE1T2357x8


Environmental compatibility The product environmental declaration
CE1E2357en12 contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
Climatic conditions For devices without batteries:
Storage as per IEC721-3-1 Class 1K3, temp. -20….65 °C
Transport as per IEC721-3-2 Class 2K3, temp. -25….70 °C
Operation as per IEC721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
For battery-powered devices:
Storage as per IEC721-3-1 Class 1K3, temp. -20….30 °C
Transport as per IEC721-3-2 Class 2K3, temp. -25….70 °C
Operation as per IEC721-3-3 Class 3K5, temp. 0...50 °C (non-condensing)
Outside temperature Outside sensor QAC34/101
measurement
Measuring range -50..0.50 °C
Cable length Max. 5 m
Weight Excl. packaging RF transmitter: 160 g
Outside sensor QAC34: 73 g
Cable: 70 g

83
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Index

Index
A O
Automatic operation, 45 Outside sensor, 67
AVS13.399, 32
P
AVS14.390, 29
Protection, 46
AVS71.390, 25
Push, 47
AVS71.393, 27
R
B Repeater, 29, 67
Binding, 66
Reset, 50
Button
RF, 17
Drinking water, 47
Binding, 66
Heating mode, 45
Test mode, 66
Info, 49
RF outside sensor, 32
C RF repeater, 29
Chimney sweep function, 51, 72 Room sensor
Continuous operation, 45 Correction, 66
Correction Room unit, 67
Room sensor, 66
S
D Service unit, 67
Date, 60 Set time, 53, 73
Daylight saving time, 60 Settings, 60
Device list, 67 Software version, 66
Device version, 66 Standard time changeover, 60
DHW
T
Push, 47
Technical data
Display, 44, 44
AVS13.399, 83
Drinking water
AVS14.390, 82
Operation, 47
AVS37..., 78
E AVS71.390, 80
Error message, 50 AVS71.393, 81
QAA7x..., 78
H Test mode, 66
Heating mode, 45 Time of day, 60
HMI, 67
U
I User levels, 57
Info button, 49

L
Language, 61

M
Maintenance message, 50

84
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Index

85
Siemens Operator / Room / Auxiliary devices CE1U2358en_04
Building Technologies 2014-09-26
Issued by © 2012-2014 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.