Panel: Lp1 Location: Server Room

The document contains details of three electrical panels - LP1, PP2, and PP3 located in a server room. Panel LP1 has a total connected load of 8400VA serving UPS systems and lighting. Panel PP2 has a total connected load of 6063VA serving air conditioners. Panel PP3 has a total connected load of 8160VA serving small power loads and lighting. All three panels require 40A, 2-pole breakers and wiring of 8.0mm2 and 5.5mm2 in existing 32mm PVC conduits.

Uploaded by

John Bundang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views1 page

Panel: Lp1 Location: Server Room

The document contains details of three electrical panels - LP1, PP2, and PP3 located in a server room. Panel LP1 has a total connected load of 8400VA serving UPS systems and lighting. Panel PP2 has a total connected load of 6063VA serving air conditioners. Panel PP3 has a total connected load of 8160VA serving small power loads and lighting. All three panels require 40A, 2-pole breakers and wiring of 8.0mm2 and 5.5mm2 in existing 32mm PVC conduits.

Uploaded by

John Bundang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

PANEL : LP1

LOCATION : SERVER ROOM


Circuit BREAKER RATING WIRE CONDUIT
Description of Loads Volts VA A
Number
P AT AF (THHN) + GRD (THHN) Dia-mm
1 UPS 3000VA 230 3000 13.04 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
2 UPS 3000VA 230 3000 13.04 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
3 Lighting 230 600 2.61 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
4 Spare 230 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
5 Small Power 230 1800 7.83 2 20 50 2-3.5 + 1-3.5 20mm dia PVC

TOTAL CONNECTED LOAD 8400 36.52

IT 29.22
Use 40Amps, 2P,6o Hz, 240V, N1 enclosure
Use 8.0 mm2 + 5.5mm2 in 32mm dia PVC conduit ( Existing)

PANEL : PP2
LOCATION : SERVER ROOM
Circuit
Description of Loads Volts VA A
Number BREAKER RATING WIRE CONDUIT
P AT AF (THHN) + GRD (THHN) Dia-mm
1 2HP ACCU 230 1865 8.11 2 30 50 2-5.5 + 1-3.5 25mm dia PVC
2 2HP ACCU 230 1865 8.11 2 30 50 2-5.5 + 1-3.5 25mm dia PVC
3 3/4 HP ACCU 230 700 3.04 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
4 3/4 HP ACCU 230 700 3.04 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
5 1 HP ACCU 230 933 4.06 2 20 50 2-3.5 + 1-3.5 20mm dia PVC

TOTAL CONNECTED LOAD 6063 26.36

IT 25.75
Use 40Amps, 2P,60 Hz, 240V, N1 enclosure
Use 8.0 mm2 + 5.5mm2 in 32mm dia PVC conduit ( Existing)

PANEL : PP3
LOCATION : SERVER ROOM
Circuit
Description of Loads Volts VA A
Number BREAKER RATING WIRE CONDUIT
P AT AF (THHN) + GRD (THHN) Dia-mm
1 Small Power 230 1440 6.26 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
2 Small Power 230 3240 14.09 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
3 Lighting 230 600 2.61 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
4 Small Power 230 2880 12.52 2 20 50 2-3.5 + 1-3.5 20mm dia PVC
5 Spare 230 2 20 50 2-3.5 + 1-3.5 20mm dia PVC

TOTAL CONNECTED LOAD 8160 35.48

IT 28.38
Use 40Amps, 2P,60 Hz, 240V, N1 enclosure
Use 8.0 mm2 + 5.5mm2 in 32mm dia PVC conduit ( Existing)