0% found this document useful (0 votes)
101 views

Wireless Sensor Access Point

The document is a technical data sheet for the Easergy TH110 wireless thermal sensor. It provides details about the sensor's applications, performance, specifications, and certifications. The sensor allows for continuous thermal monitoring of critical electrical connections and measures temperature from -25°C to 115°C. It is self-powered by network current and uses Zigbee wireless communication to transmit sensor readings to an access point.

Uploaded by

Miguel
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views

Wireless Sensor Access Point

The document is a technical data sheet for the Easergy TH110 wireless thermal sensor. It provides details about the sensor's applications, performance, specifications, and certifications. The sensor allows for continuous thermal monitoring of critical electrical connections and measures temperature from -25°C to 115°C. It is self-powered by network current and uses Zigbee wireless communication to transmit sensor readings to an access point.

Uploaded by

Miguel
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

[ TECHNICAL DATA SHEET ] Page 01

Easergy TH110
Wireless Thermal Sensor
MASKED PRODUCT
ODUCT IMAGE
Easergy TH110 Wireless Thermal sensor
Applications
The Easegy TH110 is a battery free wireless smart sensor enabling to
perform the continuous thermal monitoring of all the critical
connections made on field like:
• Cable connections
• Bus bar connections
• Withdrawable CB connections
It allows also the monitoring of any power connections of indoor
installation like MV Transformers connections or LV Switchgears.

High performances
Easergy TH110 can perform
erform accurate thermal monitoring because
b it
is in direct contact with the measured point guaranteeing an accuracy
of ±1°C.
Wide measurable temperature range from -25°C up to 115°C (max
150°C).

Self powered
Easergy TH110 is battery free self powered by the
t network current.
The minimum activation current is 5A for average power conductor
dimensions.

Wireless
Byy using Zigbee Green Power wireless communication protocol
IEEE802.15.4 at 2,4GHz Easergy TH110 ensure a reliable and robust
communication
It must be paired with an access point having the function to
concentrate the signal coming from different sensors.

Easy installation
TH110 allows the thermal monitoring of every possible critical points
thanks to its very compact footprint (31x31x14mm) and its only
on 15g
weight.
This sensor can be installed directly on the conductive metal part or
on the shielded insulated part.

Reference and packaging

EMS59440 Easergy TH110 set of 3 pieces


EMS59441 Ferromagnetic ribbon for energy harvesting

The TH110 is supplied


ed in a package with a min quantity of 3 sensors.
sensors
[ TECHNICAL DATA SHEET ] Page 02

Easergy TH110
Wireless Thermal Sensor
MASKED PRODUCT IMAGE
Rated supply Starting current: for energy harvesting 0.4A / cm of the peripheral AC live part (Battery free)
Voltage limit of the active part 52kV
Current limit of the active part 5000A
Wireless communication protocol Zigbee green power at 2.4 GHz according to IEEE 802.15.4
Transmission period 60s
Mounting support Direct on active part or shielded insulation part by fixing tape
Height 14 mm
Depth 31 mm
Width 31 mm
Product weight 0.015 kg
Product certifications CB IECEE ID: FR682889
cBVus ID: CABA
FCC ID: 2AHP8-097742
IC : 21245-097742
LV Directive 2014/35/EU
EMC Directive 2004/108/EC
RE Directive 2014/53/EU (R&TTE directive 1999/5/EC)
Main Standards EN / IEC 61010 2010
UL 61010 -1 2012
ETSI EN 300238 2012 V1.9.1 (§ 3.2 R&TTE Directive)
IEEE 802.15.4 2013
Power emission EIRP= +5dBm
Resistance to electrostatic discharge 2-4-8-15kV (Direct & Indirect contact) according to EN/IEC 61000-4-2
2-4-8-15kV (in air) according to EN/IEC 61000-4-2
Resistance to electromagnetic fields 30V/m (80MHz...5.7 GHz) according to EN/IEC 61000-4-3
20 V/m (80MHz....5.9 GHz) according to EN/IEC 61000-4-3
Resistance to conducted disturbances, induced by 20 V (0.15...80 MHz) according to EN/IEC 61000-4-6
radio frequency fields
Power frequency magnetic field immunity 1000A/m Pulse EN/IEC 61000-4-8
300A/m Continue EN/IEC 61000-4-8
Pulse magnetic field immunity 1000A/m Pulls EN/IEC 61000-4-9
Damped oscillatory magnetic field immunity 30A/m (0.1 & 1 MHz) EN/IEC 61000-4-10
Electrical fast transient/burst immunity 4kV impulse EN/IEC 61000-4-4
2kV 5min (Marine) EN/IEC 61000-4-4
Damped oscillatory wave immunity 3kV (CM - 100kHz & 1MHz) EN/IEC 61000-4-18
2.5kV (CM - 3MHz, 10MHz, 30MHz) EN/IEC 61000-4-18
Surge immunity 0.5-1-2-4kV (Common mode) EN/IEC 61000-4-5
0.5-1-2-4kV (Differential mode) EN/IEC 61000-4-5
Immunity to common mode conducted disturbances 30V Continuous (0 – 150kHz) EN/IEC 61000-4-16
300V Short duration (0 – 150kHz) EN/IEC 61000-4-16
Ambient air temperature for operation -25...80°C Any live and measured parts shall be lower than IEC limits (115°C Max)
Accuracy within ambient air temperature for operation +/-1°C between -25°C...80°C and +/-2°C outside the range.
Measured temperature for operation -25...115°C for 80°C at maximum ambient temperature
-25...125°C for 40°C at maximum ambient temperature
150°C max (limited time)
Ambient air temperature for storage -40...70°C
Relative humidity 10...95 % over a period of 24h condensation may occasionally occur in operation
10...90% over a period of one month condensation may occasionally occur in operation
IP degree of protection IP54 IEC 60529
Mechanical impact IK07 IEC 62262 (Exposed side vs Measuring side)
Pollution degree 2 IEC 61010-1
Operating altitude 0...2000 m
Storage altitude 0...3000 m
Vibrations sinusoidal during transport 5-8Hz Ampl 7.5mm, 8-200Hz 2g, 200-500Hz 4g 20 cycles Test Fc
according to IEC 60068-2-6 (2M3 according to IEC 60721-3-2)
Vibrations random during transport 10-2000Hz 0,1g/Hz 30 min/axe according to IEC 60068-2-64
Shocks 3 shocks 2 directions 3 axes 40g 6ms (Ea) according to IEC 60068-2-27 (2M3)
1000 shocks 2 directions 3 axes 20g 16ms (Ea) according to IEC 60068-2-27
Free falls 2m 2 free falls according to IEC 60068-2-31
Vibrations sinusoidal in operation (Installed on bar) 5-500Hz 1g 1cycle (10min) 3mm Test Fc according to IEC 60068-2-6 (3M5 according to IEC 60721-3-3)
Shocks in operation (Installed on bar) 3 shocks 3 directions 10g 11ms (Ea)according to IEC 60068-2-27 (3M5 according to IEC 60721-3-3)
Glow-wire flammability withstand 650°C
Maximum distance between sensor and the access point 100m in free field unobstructed
25m when the components are separated by one layer of metal
10m when the components are separated by two layers of metal
CL110(EMS59443)
Indoor thermal and humidity sensor
H×D×W: 20mm×40mm×40mm
Product datasheet ZBRN32
Characteristics access point - 2 RJ45-24..240V AC/DC-4 displays-5
LEDs

Main
Range of product Harmony
Product or component type Wireless access point
Device short name ZBRN2
Product specific application Interface to PLC
Function of module Monostable

Complementary
[Us] rated supply voltage 24...240 V AC/DC at 50/60 Hz (- 10...10 %)

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Immunity to microbreaks 10 ms
Response time < 30 ms after transmitter clicks
Channels utilisation <= 60
Power consumption in W <= 4 W AC/DC
Breaking capacity 15 W
Breaking capacity 750 VA

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Control circuit frequency 50...60 Hz +/- 10 %

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Short-circuit protection 16 A by GB2 circuit breaker
Rated short-duration power frequency withstand voltage 1.5 kV at 50 Hz conforming to EN/IEC 60947-5-1
[Uimp] rated impulse withstand voltage 4 kV
Surge withstand 1 kV (differential mode) conforming to IEC 61000-4-5
2 kV (common mode) conforming to IEC 61000-4-5
Width 122 mm
Height 90 mm
Depth 60 mm
Product weight 0.27 kg
Marking CE

Environment
product certifications CCC
CE
CSA
C-Tick
GOST
UL
directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
1999/5/EC - R&TTE directive
standards EN/IEC 60950-1
EN/IEC 61131-2
UL 508
EN 62311
CSA C22.2 No 14
ETSI EN 300 440-2
ETSI EN 300 328
ambient air temperature for storage -40...70 °C
vibration resistance +/- 3.5 mm (f= 5...14 Hz) conforming to IEC 60068-2-6
1 gn (f= 5...150 Hz) on panel mounting conforming to IEC 60068-2-6
2 gn (f= 8...150 Hz) on DIN rail conforming to IEC 60068-2-6
IP degree of protection IP20 (terminals)

1/2
IP20 (casing) conforming to IEC 60529

2/2
Ribbon for TH110(EMS59441)
Diam: 150mm
Weight: 1㎏