Assele Bus STN EL

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 33

GRAND SUMMARY

BILL Nº 1 DEMOLISHING WORK . . . . . . . . . . . . . . . . . . . . . . BIRR

BILL Nº 2 PASSENGER TERMINAL BUILDING (G+4) ….............BIRR


BILL Nº 3 GUARD HOUSE . . . . . . . . . . . . . . . . . . . . . . . BIRR
BILL Nº 4 MAINTENANCE GARAGE (G+0) BIRR
BILL Nº 5 DRY LATRINE . . . . . . . . . . . . . . . . . . . . . . BIRR
BILL Nº 6 SITE WORK. . . . . . . . . . . . . . . . . . . . . . . BIRR
SERVICE SUM. . . . . . . . . . . . . . . . . . BIRR
15% VAT . . . . . . . . . . . . . . . . . . . . . . . BIRR
PROJECT AMOUNT. . . . . . . . . . . . . . BIRR
10% CONTINGENCY. . . . . . . . . . . . . BIRR
ITEM DESCRIPTION UNIT QTY RATE AMOUNT

15. ELECTRICAL WORKS

SUPPLY , INSTALL,TEST AND COMMISSIONING OF ALL


ELEECTRICAL SYSTEMS
GENERAL NOTE
Shop drawings and as built drawings for all systems. All Materials shall be 3
rd party certified with minimum of 2years of waranty.
All electrical systems shall be installed,tasted and commissioned by certified
professionals.
All boards electrical systems shall be wired and tested as relevant national
and international hospital standards .
All wiring shall conform to the National Electrical Code.
All distribution boards need to be type tested assembly.

Unlimited break Capacity of the circuit breaker (Icu):-


Icu for 1ph MCB`s is 6KA, and 3ph 10KA for breakers less than 63A/3ph
From 80A-160AIcu=15kA-20kA
From 200A-400AIcu=25kA-35kA
From 500A-800AIcu=35kA-60kA

Use MCB breakers for ratings from10A - 80A(3ph)


Use MCCB breakers for ratings from100A - 630A
Use ACB breakers for ratings from 800A and above of adjustable fixed
breakers

1. ELECTRICAL INSTALLATION

DISTRIBUTION BOARDS
3rd party certified.
All boards shall be wired and tested as relevant IEC standards.
Ratings of terminal blocks shall be appropriate and according to IEC
standards.
1 Flush mounted sub distribution board, MDB-MAIN(from Bus-Bar), IP54,
made of steel with lockable door including earthing lead, front cover all fixing
and connection accessories, complete and consisting of:-
1pc main MCCB of 800A, 3ph, Icu= 50KA
7Pcs of MCCB of 125A, 1ph, Icu= 20KA
4Pcs of MCCB of 100A, 1ph, Icu= 20KA
3Pcs of MCCB of 80A, 1ph, Icu=16KA
2Pcs of MCB of 25A, 1ph, Icu=10KA
use DIN rail mounted terminal blocks with end brackets and marking tags for
all outgoings.
1pc factory made drawing pocket, Himel PP-A4 or equivalent.
All complete with phase-bar system of 1000A and 10% reserve spaces 11 Nº 1 1,250,000.00 1,250,000.00
. -
2 Flush mounted sub distribution board, SDB-GFMR IP54, made of steel with -
lockable door including earthing lead, front cover all fixing and connection -
accessories, complete and consisting of:- -
1pc main MCCB of 125A, 3ph, Icu= 10KA -
2Pcs of MCB of 40A, 3ph, Icu= 10KA -
2Pcs of MCB of 32A, 3ph, Icu= 10KA -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 10% reserve spaces Nº 1 185,000.00 185,000.00
3 Flush mounted sub distribution board, SDB-FFMR,4FMR- IP54, made of -
steel with lockable door including earthing lead, front cover all fixing and -
connection accessories, complete and consisting of:- -
1pc main MCCB of 125A, 3ph, Icu= 10KA -
2Pcs of MCB of 50A, 3ph, -
2Pcs of MCB of 40A, 3ph, -
2Pcs of MCB of 32A, 3ph, -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 10% reserve spaces Nº 2 195,000.00 390,000.00
4 Flush mounted sub distribution board, SDB-FFML2FML,3FML,4FML- IP54, -
made of steel with lockable door including earthing lead, front cover all fixing -
and connection accessories, complete and consisting of:- -
1pc main MCCB of 100A, 3ph, Icu= 10KA -
2Pcs of MCB of 50A, 3ph, Icu= 10KA -
2Pcs of MCB of 32A, 3ph, Icu= 10KA -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 10% reserve spaces Nº 4 165,000.00 660,000.00
5 Flush mounted sub distribution board, SDB-2FMR,3FMR- IP54, made of -
steel with lockable door including earthing lead, front cover all fixing and -
connection accessories, complete and consisting of:- -
1pc main MCCB of 125A, 3ph, Icu= 10KA -
2Pcs of MCB of 50A, 3ph, Icu= 10KA -
2Pcs of MCB of 32A, 3ph, Icu= 10KA -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 10% reserve spaces Nº 2 187,000.00 374,000.00
6 Flush mounted sub distribution board, SDB-GFL(from Bus-Bar), ,IP54, made -
of steel with lockable door including earthing lead, front cover all fixing and -
connection accessories, complete and consisting of:- -
1pc main MCB of 25A, 3ph, Icu= 10KA -
4Pcs of MCB of 16A, 1ph, -
6Pcs of MCB of 10A, 1ph, -
2Pcs of MCB of 16A, 1ph, -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 1 65,000.00 65,000.00
7 Flush mounted sub distribution board, MDB-UPS(from Bus-Bar), ,IP54, -
made of steel with lockable door including earthing lead, front cover all fixing -
and connection accessories, complete and consisting of:- -
1pc main MCB of 125A, 3ph, Icu= 25KA -
12Pcs of MCB of 25A,3ph,Icu=10KA -
use DIN rail mounted terminal blocks with end brackets and marking tags for -
all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 250A and 20% reserve spaces Nº 1 158,000.00 158,000.00
8 Flush mounted sub distribution board, SDB-GFR1,FFL,4FR1(from Bus-Bar ) -
,IP54, made of steel with lockable door including earthing lead, front cover -
all fixing and connection accessories, complete and consisting of:- -
1pc main MCB of 40A, 3ph, Icu= 10KA -
7 Pcs of MCB of 10A, 1ph, -
8Pcs of MCB of 16A, 1ph, -
2Pcs of MCB of 16A, 1ph, -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 3 85,000.00 255,000.00
9 Flush mounted sub distribution board, SDB-FF,2,3CAFE (from Bus- -
Bar),IP54, made of steel with lockable door including earthing lead, front -
cover all fixing and connection accessories, complete and consisting of:- -
1pc main MCB of 50A, 3ph, Icu= 10KA -
2Pcs of MCB of 10A, 1ph, Icu= 6KA -
11Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 20A, 3ph, Icu= 10KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with bus bar system of 80A and 10% reserve spaces Nº 3 125,000.00 375,000.00
10 Flush mounted sub distribution board, SDB-4CAFE (from Bus-Bar),IP54, -
made of steel with lockable door including earthing lead, front cover all fixing -
and connection accessories, complete and consisting of:- -
1pc main MCB of 50A, 3ph, Icu= 10KA -
7Pcs of MCB of 10A, 1ph, Icu= 6KA -
12Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 20A, 3ph, Icu= 10KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with bus bar system of 80A and 10% reserve spaces Nº 1 85,000.00 85,000.00
11 Flush mounted sub distribution board, SDB-FFR CAFE (from Bus-Bar),IP54, -
made of steel with lockable door including earthing lead, front cover all fixing -
and connection accessories, complete and consisting of:- -
1pc main MCB of 50A, 3ph, Icu= 10KA -
2Pcs of MCB of 10A, 1ph, Icu= 6KA -
11Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 20A, 3ph, Icu= 10KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with bus bar system of 80A and 10% reserve spaces Nº 1 122,000.00 122,000.00
12 Flush mounted sub distribution board, SDB-FFR1(from Bus-Bar ) ,IP54, -
made of steel with lockable door including earthing lead, front cover all fixing -
and connection accessories, complete and consisting of:- -
1pc main MCB of 40A, 3ph, Icu= 10KA -
7 Pcs of MCB of 10A, 1ph, -
8Pcs of MCB of 16A, 1ph, -
2Pcs of MCB of 16A, 1ph, -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 1 88,000.00 88,000.00
13 Flush mounted sub distribution board, SDB-2F,3FL,4FL(from Bus-Bar ) -
,IP54, made of steel with lockable door including earthing lead, front cover all -
fixing and connection accessories, complete and consisting of:- -
1pc main MCB of 40A, 3ph, Icu= 10KA -
9Pcs of MCB of 10A, 1ph, Icu= 6KA -
11Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 3 120,000.00 360,000.00
14 Flush mounted sub distribution board, SDB-UPS -
GFL,2FR1,3FR1,4FL,4FR1(from Bus-Bar ) ,IP54, made of steel with -
lockable door including earthing lead, front cover all fixing and connection -
accessories, complete and consisting of:- -
1pc main MCB of 25A, 3ph, Icu= 10KA -
5Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 5 75,000.00 375,000.00
15 Flush mounted sub distribution board, SDB-UPS 2,3FL,GFR1(from Bus-Bar -
) ,IP54, made of steel with lockable door including earthing lead, front cover -
all fixing and connection accessories, complete and consisting of:- -
1pc main MCB of 25A, 3ph, Icu= 10KA -
13Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 3 82,538.00 247,614.00
16 Flush mounted sub distribution board, SDB-UPS FFL,GFR2(from Bus-Bar ) -
,IP54, made of steel with lockable door including earthing lead, front cover all -
fixing and connection accessories, complete and consisting of:- -
1pc main MCB of 25A, 3ph, Icu= 10KA -
8Pcs of MCB of 16A, 1ph, Icu= 6KA -
2Pcs of MCB of 16A, 1ph, Icu= 6KA(RESERVE) -
Use DIN rail mounted terminal blocks with end brackets and marking tags -
for all outgoings. -
1pc factory made drawing pocket, Himel PP-A4 or equivalent. -
All complete with phase-bar system of 50A and 20% reserve spaces Nº 2 73,865.00 147,730.00
LIGHT POINT -
-
17 Light points in medium duty rigid thermoplastic spring bendable conduit of -
16mm fed by PVC insulated copper cable of 3x2.5sq.mm. Nº 1644 2,535.00 4,167,540.00
-
SWITCHES -
3rd party certified -
18 IP 54 10A/1ph flush mounted with appropriate cover plate, frame and box. -
Note: use appropriate modular back box for concrete &masonry wall for -
light or gypsum wall. -
a 1-way Nº 45 585.00 26,325.00
b Two -way Nº 62 650.00 40,300.00
c Double Nº 185 700.00 129,500.00
d Intermediate Nº 19 750.00 14,250.00
e Triple Nº 41 800.00 32,800.00
f 6pcs of single phase 16A tumbler switch with 20units metallic box with Nº 1 12,500.00 12,500.00
accessories -
g 10pcs of single phase 16A tumbler switch with 24units metallic box with Nº 1 20,560.00 20,560.00
accessories -
19 TYPE OF LIGHT FITTINGS WITH LAMPS -
19 -
Note: all light fittings should have appropriate electric drivers, lamps, -
mounting and other necessary accessories. -
TYpe 1(Parking & kitchen) -
a Mounting - ceiling Surface -
Lamp type- T8 LED,6500K/lumen-6400 -
Lamp wattage-40 watts/30000hr -
Connection Push-in connector (PI) or with pull relief (PIP) -
Ingress protection-66 -
Housing 14 mm in height: 60 mm including the driver,length 1268mm -
,width 128 mm -
Frame: plastic,Back cover: steel -
Optic cover; light guide and diffuser: plastic, -
Driver box: plastic Driver :-Built-in,Mains voltage 100-240V /50-60 Hz Nº 74 6,500.00 481,000.00
Type 2(Corridor & cafe) -
b Mounting - ceiling recessed/surface,downlight -
Lamp type- LED,6500K,lumen-1800 -
Lamp wattage-18 watts/30000hr -
Connection Push-in connector (PI) or with pull relief (PIP) -
Ingress protection-44 -
Size (Not exact)-Dia 383mm and height 30mm -
Frame: plastic,Back cover: steel -
Optic cover; light guide and diffuser: plastic, -
Driver box: plastic Driver :-Built-in,Mains voltage 100-240V /50-60 Hz Nº 511 3,500.00 1,788,500.00
type 3(toilet) -
c Mounting - ceiling recessed/surface,downlight -
Lamp type- LED,6500K,lumen-1800 -
Lamp wattage-18 watts/30000hr -
Connection Push-in connector (PI) or with pull relief (PIP) -
Ingress protection-66 -
Size (Not exact)-Dia 383mm and height 30mm -
Frame: plastic,Back cover: steel -
Optic cover; light guide and diffuser: plastic, -
Driver box: plastic Driver :-Built-in,Mains voltage 100-240V /50-60 Hz Nº 213 3,500.00 745,500.00
Type 5(WALL Mirror ) -
d Mounting -Wall surface -
Lamp type-LED -
Number of Lamps -- -
Lamp holder- poly carbonate with contacts in phosphor -
bronze(Prismatic) -
Lamp wattage-12watts -
Luminary material-cylindrical made of sheet stainless Steel -
Ingress protection-40 Nº 97 2,985.00 289,545.00
Size -dia.198mm and height 65mm -
control gear-220V/50HZ, -
Type 6(Office & shop) -
e Mounting -Ceiling surface/reccesed -
Lamp type-LED -
Number of Lamps -- -
Lamp holder- poly carbonate with contacts in phosphor -
bronze(Prismatic) -
Lamp wattage-27watts -
Luminary material-cylindrical made of sheet stainless Steel -
Ingress protection-40 -
Size -length 595mm,width-595mmand height 65mm -
control gear-220V/50HZ, Nº 516 4,685.00 2,417,460.00
type 7(stair) -
f Mounting - ceiling surface -
Lamp type- LED -
Lamp holder- poly carbonate with contacts in phosphor -
bronze,prismatic -
Lamp wattage-40 watts -
Luminary material-cylindrical made of sheet stainless Steel -
Ingress protection-40 -
Size -DIA.301mm and height 105mm -
control gear-220V/50HZ,Electronic ballast Nº 44 6,500.00 286,000.00
type 8(entrance) -
g Mounting - ceiling surface -
Lamp type- LED -
Lamp holder- poly carbonate with contacts in phosphor -
bronze,prismatic -
Lamp wattage-40 watts -
Luminary material-cylindrical made of sheet stainless Steel -
Ingress protection-54 -
Size -DIA.301mm and height 105mm -
control gear-220V/50HZ,Electronic ballast Nº 6 6,500.00 39,000.00
type 10(Conference ) -
h Mounting - ceiling reccessed -
Lamp type- LED -
Lamp holder- poly carbonate with contacts in phosphor -
bronze,prismatic -
Lamp wattage-40 watts -
Luminary material-cylindrical made of sheet stainless Steel -
Ingress protection-40 -
Size -DIA.250mm and height 105mm -
control gear-220V/50HZ,Driver Nº 56 6,500.00 364,000.00
Mounting - Wall surface Emeregency/Sinage -
i Lamp type- LED -
Number of Lamps - -
Lamp wattage-Equivalent to 5watts/3hr,25000hrs -
Luminare material-polycarbonate -
Ingress protection-67 -
Size -length 460mm,width 80mm and 200mm height -
control gear-220/50hz Nº 137 3,850.00 527,450.00
-
SOCKET OUTLETS POWER POINTS AND FLOOR BOX -
3rd party certified -
Flush mounted with appropriate cover plate, frame and box. -
Note: use modular approprate back box for concrete ,masonry wall and for -
light or gypsum wall. -
20 Socket outlet points approve type flush mounted fed by PVC insulated -
copper cable of 3x2.5mm2 in medium duty rigid thermoplastic conduit of -
diameter 16mm. Nº 743 2,535.00 1,883,505.00
21 Socket outlet Twin points approve type flush mounted fed by PVC insulated -
copper cable of 3x2.5mm2 in medium duty rigid thermoplastic conduit of -
diameter 16mm. Nº 162 3,200.00 518,400.00
22 Socket outlet points approve type flush mounted fed by PVC insulated -
copper cable of 3x2.5mm2 in medium duty rigid thermoplastic conduit of -
diameter 25mm.(for AHD,BOILER,FCU) Nº 13 2,850.00 37,050.00
23 Ditto but for wireless access points (height=2.2meter) Nº 20 2,950.00 59,000.00
24 Socket outlet points approve type flush mounted fed by PVC insulated -
copper cable of 3x6mm2 in medium duty rigid thermoplastic conduit of -
diameter 25mm. Nº 33 3,850.00 127,050.00
-
25 Socket out lets with detachable frames & corresponding box 3rd party certified -
a 16A,1ph Nº 663 850.00 563,550.00
b 16A, 1ph with interlocked on/off switch and indicator lamp Nº 13 2,500.00 32,500.00
c Twin 16A, 1ph Nº 162 1,200.00 194,400.00
d 25A, 3ph with interlocked on/off switch and indicator lamp Nº 10 1,850.00 18,500.00
Automatic Hand Dryer -
26 Supply and install 220V/50HZ automatic hand dryer -
with heating temperature of 40-60degree Celsius -
with dynamical balanced centrifugal fan of multiple -
metalic vanes, fire retardant,high gloss finsh plastic -
cover and mounting base,infrared sensors complete with -
all the accessories . No 20 125,000.00 2,500,000.00
27 POWER CABLES -
-
All power cables shall be of copper with standard cores -
With all IEC and IEEE standards related to power cables. -
Copper conductors of solid,flexible,stranded conductors -
with single/multi-core assembed cables. -
Insulation of an extruded layer XLPE applied of the conductors -
Sheath of an extruded layer PVC applied to the outside of -
conductors. -
All power distribution cables shall rated at 0.6/1KV. -
-
POWER CABLE -
NYY 0.6/1KV -
28 3x50/25+1x25sq.mm ml 70 3,062.00 214,340.00
29 3x35/16+1x16sq.mm ml 100 2,165.00 216,500.00
30 3x25/16+1x16sq.mm ml 80 1,655.00 132,400.00
31 5x10sq.mm ml 100 1,200.00 120,000.00
32 5x6sq.mm ml 200 850.00 170,000.00
33 Additional PVC Pipes for tele ,power and data distribution -
a. Diameter 32mm(of tentative measurment) ml 340 85.00 28,900.00
b. Diameter 50mm(of tentative measurment) ml 240 95.00 22,800.00
c. Diameter 110mm(of tentative measurment) ml 400 225.00 90,000.00
d. Diameter 160mm(of tentative measurment) ml 400 455.00 182,000.00
-
UPS -
with 3 years Warranty -
34 Approved type Standalone type 60KVA UPS , 3x380V+/-5%, -
50Hz, with 10-min, hot swappable sealed -
lead-acid battery 10 years ,on-line double conversion technology, integrated -
automatic By-pass, manual maintenance -
By-pass,automatic battery test, power factor 0.95, efficiency -
95% or greater, surge protector audio visual display -
of load, battery and UPS status, input harmonic filter, -
maintenance by-pass switch, all complete including -
cabling.Including 1pc front mount digital data logger -
for all electrical parameters with RS485 Port and -
non volatile memory for network connection. -
(the installation/connection of the three UPS -
will be given to the contractor as per the client request -
and it shall be approved by the consultant) No 1 3,853,680.00 3,853,680.00
-
CABLE SUPPORT SYSTEMS -
I GALVANIZED ENCLOSED CABLE TRAY -
Note: all installation including support distance should be in accordance with -
manufacturer's instructions and / or as shown on the drawings. -
All cable tray shall run neatly and fixed in contact with the horizontal and -
vertical corner of the wall/Colon with the necessary drops and riser. -
The cable tray must consisting of accessories like clamp kit, coupling plate -
,cable mounting bracket , grounding cable drop out plate ,elbows and T-joints -
for horizontal, bracket, mounting box support, suspension and top cover -
bracketed cap, cable retainer, hinge connector for vertical change in direction, -
wall /pendent bracket for ceiling support ,box for cable junctions for all the -
necessary accessories -
The quantity is tentative ,it should be determined in the site. -
a 100mmx400mm/1mm two compartment for tele/data and power systems -
enclosed perforated cable tray . m 700 2,500.00 1,750,000.00
35 PASSANGER LIFT -
I. Supply install passenger lifts as per the following specifications custom -
made for made for shaft indicated on the drawing -
Passenger Lift -
Technical Specifications -
Standards -
ISO 7465:2001,EN-81,BS ,ANSI,JIS,ISO 9001, -
ES 3158:2006,ES 3159:2006 , latest editions of BS/EN -
or ES and others quality certificate for design, manufacturing installation and -
commissioning lifts and quality certificate for design, -
manfucturing,commissioning lifts parts. -
-Electromagnetic compatibility -
- Electromagnetic immunity -
-Electrical Safety -
- Electronic equipment for use in power facilities: -
- Standards for lift installation in market places -
Mechanical property and Finishing Material -
Function :-Passenger Lift -
Rated load : - 1360kg, 17person variable with the shaft -
Rated speed :- 1.5m/sec -
Number of stops:-5in one line -
Floor -G+4 -
Cabin door type:- Automatic single door center opening two panel -
Landing door type:- Automatic single door center opening two panel -
No entrance :- one(1) @ 0 degree -
Floor - Vinyl composition tile/wear resistant rubber -
Wall - Stainless steel and one side -
Interior face of doors - Stainless steel -
Ceilings - Stainless steel panels/diffuser gird -
Handrail -stainless steel, two sides -
Mirror -Silver color, rear panel -
Frame- Stainless steel -
Exterior face of door - Stainless steel -
Drive system and Elevator operation -
- Machine room less bottom drive -
-collective Selective control -
-Electric traction type belt type -
-VVVF with encoder -
Digital data logger unit for all lift and electrical parameters with RS485 Port -
and non volatile memory for network connection -
Special operation and facilities -
- Smoke Detectors integrated with building fire alarm system -
- Alarm buzzer -
- Chime gong to sound present audio able indication -
control -
- Toggle switch -
- call registered light -
- Inter phone to communicate with machine room -
- Over load indicator both audible and visual indicators -
Car and Landing operation panel -
- Car display for position and direction -
- Digital car position and direction control -
-Digital landing position & direction indicator on -
all floors -
- lift movement control -
-Vandal proof Wait/stop push button -
-Car display for position and direction -
Control and safety features -
-Dynamic braking for traction machine in event of power -
failure -
Power supply -
- 380volts AC 50Hz 3phase -
Disable -
- Add Braille tactile to all emergency buttons -
Lighting Supply -
- 220v, 50Hz, 1ph -
- Indirect light in diffuser grid -
Ventilation -
-Car ventilation with fan built in the ceiling -
-Temperature control Thermostat -
Rescue device(UPS) -
-Automatic rescue device/ back up(UPS) when power fails -
All power outputs are electronically protected -
against short circuit -
Earth leak detection for traction machine during emergency operation(short -
circuit, overload, loss of connection of a phase to the motor, phase -
imbalance,thermal protection, over speeding, turning blockage) Performs -
analysis of optimum motor turning direction (minimum battery consumption -
during emergency operation) Conforms to EN81 regulation -
CCTV / IP-Surveillance for Lift -
Provide passenger lifts appropriate type of camera with its mounting -
accessories complete wiring and integrated with the building security /CCTV -
system as per local and international standards. -
Shaft Information -
Shall take and consider appropriate manufacturers' standards for the shaft and -
machine room size before manufacturing and prepare working drawing -
referring to the arctectrural and structural for submission with the technical -
specification. -
Coordinate with architectural and structural drawings during constriction -
with appropriate changes with notice to comply with the standards Submit for -
approval complete up to date lift specification of the above items including -
guide rails,suspension counter weight terminal stopping and final limit -
switches, guarding car frames, safety gear and over speed governor overload -
device and full load device, controller automatic control system, -
reinforcement bar buffer, duty ,rewiring ,conducting/trucking and other -
required and necessary specification with working drawing referring to -
architectural and structural from at lift suppliers with 3years grantee period -
in lift manufacturing ,design, installation and maintenance. No 2 6,805,000.00 13,610,000.00
II Supply install passenger lifts as per the following specifications custom -
made for made for shaft indicated on the drawing -
Passenger Lift -
Technical Specifications -
Standards -
ISO 7465:2001,EN-81,BS ,ANSI,JIS,ISO 9001, -
ES 3158:2006,ES 3159:2006 , latest editions of BS/EN -
or ES and others quality certificate for design, manufacturing installation and -
commissioning lifts and quality certificate for design, -
manfucturing,commissioning lifts parts. -
-Electromagnetic compatibility -
- Electromagnetic immunity -
-Electrical Safety -
- Electronic equipment for use in power facilities: -
- Standards for lift installation in market places -
Mechanical property and Finishing Material -
Function :-Passenger Lift -
Rated load : - 800kg,10person variable with the shaft -
Rated speed :- 1.5m/sec -
Number of stops:-5 in one line -
Floor -G+4 -
Cabin door type:- Automatic single door center opening two panel -
Landing door type:- Automatic single door center opening two panel -
No entrance :- one(1) @ 0 degree -
Floor - Vinyl composition tile/wear resistant rubber -
Wall - Stainless steel and one side -
Interior face of doors - Stainless steel -
Ceilings - Stainless steel panels/diffuser gird -
Handrail -stainless steel, two sides -
Mirror -Silver color, rear panel -
Frame- Stainless steel -
Exterior face of door - Stainless steel -
Drive system and Elevator operation -
-Machine room less bottom drive -
-collective Selective control -
-Electric traction type belt type -
-VVVF with encoder -
Digital data logger unit for all lift and electrical parameters with RS485 Port -
and non volatile memory for network connection -
Special operation and facilities -
- Smoke Detectors integrated with building fire alarm system -
- Alarm buzzer -
- Chime gong to sound present audio able indication -
control -
- Toggle switch -
- call registered light -
- Inter phone to communicate with machine room -
- Over load indicator both audible and visual indicators -
Car and Landing operation panel -
- Car display for position and direction -
- Digital car position and direction control -
-Digital landing position & direction indicator on -
all floors -
- lift movement control -
-Vandal proof Wait/stop push button -
-Car display for position and direction -
Control and safety features -
-Dynamic braking for traction machine in event of power -
failure -
Power supply -
- 380volts AC 50Hz 3phase -
Disable -
- Add Braille tactile to all emergency buttons -
Lighting Supply -
- 220v, 50Hz, 1ph -
- Indirect light in diffuser grid -
Ventilation -
-Car ventilation with fan built in the ceiling -
-Temperature control Thermostat -
Rescue device(UPS) -
-Automatic rescue device/ back up(UPS) when power fails -
- All power outputs are electronically protected -
against short circuit -
Earth leak detection for traction machine during emergency operation(short -
circuit, overload, loss of connection of a phase to the motor, phase -
imbalance,thermal protection, over speeding, turning blockage) Performs -
analysis of optimum motor turning direction (minimum battery consumption -
during emergency operation) Conforms to EN81 regulation -
CCTV / IP-Surveillance for Lift -
Provide passenger lifts appropriate type of camera with its mounting -
accessories complete wiring and integrated with the building security /CCTV -
system as per local and international standards. -
Shaft Information -
Shall take and consider appropriate manufacturers' standards for the shaft and -
machine room size before manufacturing and prepare working drawing -
referring to the arctectrural and structural for submission with the technical -
specification. -
Coordinate with architectural and structural drawings during constriction -
with appropriate changes with notice to comply with the standards Submit for -
approval complete up to date lift specification of the above items including -
guide rails,suspension counter weight terminal stopping and final limit -
switches, guarding car frames, safety gear and over speed governor overload -
device and full load device, controller automatic control system, -
reinforcement bar buffer, duty ,rewiring ,conducting/trucking and other -
required and necessary specification with working drawing referring to -
architectural and structural from at lift suppliers with 3years grantee period -
in lift manufacturing ,design, installation and maintenance. No 1 5,650,000.00 5,650,000.00
36 Air termination network -
Shall include all metallic structures in the network with appropriate welding -
(ventpipes,ducts ,GIS roof & structures) -
The network shall be secure fixed to the roof with brass plate and phosphorus -
screws every 2m air terminals shall be copper round end -
With proper mast and base ,adaptor, mast clamp, guy kit, cable tie and other -
necessary accessories. -
39 Air terminals -
a. Interceptor with radius of protection(Rp)>=55m with protection level of -
99% Nº 1 125,000.00 125,000.00
Horizontal conductor -
b.25x3mm copper tape welded and connected at every 2m with the Ega roof -
and each other ml 200 3,685.00 737,000.00
Down conductor -
c.25x 3mm copper tape with vertical supporting every 2m to the wall clipped ml 350 3,685.00 1,289,750.00
properly. -
d.1x95mm2 bare copper conductor -
ml 100 650.00 65,000.00
e.Diameter 20mm & 2400mm long copper rod with 60x60x70 Double brick -
manhole described as EL of detailed drawings Nº 4 1,500.00 6,000.00
II SECTION TWO:NETWORK SYSTEM -
-
ALL DATA AND TELEPHONE SYSTEMS SHOULD -
COMPLY WITH THE FOLLOWING CHARACTERS -
All data systems cables and equipments shall conform with -
ANS/TIA-942/ISO/IEC IS 11801/IEEE or equivalent. -
Use all cablings of UTP CAT6a/class Ea/10Gbit/sec/100m/ -
23AWG/500MHz/RJ-45/10GB BAZE-T. -
Use proper horizontal/vertical cable managers in the rack. -
Use proper size of patch pannels(24/48port) of CAT6a RJ-45 -
wall and floor box outlets. -
Data and Telephone system shall have 3rd party -
certificates with as built and shop drawings. -
All horizontal cabling shall be of pure copper UTP type. -
Back bone cables shall be of Multi-mode mode 8 cores with -
50/125microns for the data systems and standard UTPcables -
and termination boxes for 20/30/120/200 pairs for the -
telephone systems. -
Data and Telephone system -
3rd party certified -
Horizontal cabling of pure full copper type. -
1 CAT6a RJ45 8 contact data/tele socket out let points for -
flush mounting in thermoplastic conduit of 25mm/duct -
with appropriate type junction box fed by standard -
(2x CAT6a UTP cable) for 10G BASE-T internet data -
transfer rate of min.10Gbit/s and the necessary accessories to make -
the system complete(One data and one tele outlet) Nº 420 3,895.00 1,635,900.00
-
Extra over Data/telephone socket out lets -
with detachable frames & corresponding -
box 3rd party certified -
2 Twin modular type of CAT6a (2xRJ45) 8contact of Data -
socket out lets ( one data and one tele outlet) Nº 162 1,650.00 267,300.00
PATCH PANEL -
Fiber optics patch pannel(optical Patch pannel) -
3 48 port optical patch pannel with corresponding -
power supply unit with power plug and pivoting cabinet -
with rack for wall mounting , knock-out holes for -
cable entrance and conduit connection, ventilation -
ports ,patch cords and 25% reserve space for hubs and -
switches,with fiber to copper converters, all the necessary -
accessories to make the system complete No 10 62,500.00 625,000.00
4 Patch pannels with size of 72ports/3U of CAT6a RJ45 8contact 4 pairs -
for data with rack of 18U pivoting cabinet swing 19" steel enclosure with -
transparent and lockable door, with corresponding power -
supply unit of 8pcs scuko type socket out lets and plug -
and standard pivoting cabinet with rack for wall mounting , -
knock-out holes for cable entrance and conduit connection, -
ventilation ports , standard prefabrecated patchcords (1meter) , -
8port fiber Patch panel & termination box with sleeve/pigtails -
and connectors and 25% reserve space for access switches -
, including screen lable holder , complete connection and -
all the necessary accessories.. Nº 4 85,000.00 340,000.00
5 Patch pannels with size of 48ports/2U of CAT6a RJ45 8contact 4 pairs -
for data with rack of 18U pivoting cabinet swing 19" steel enclosure with -
transparent and lockable door, with corresponding power -
supply unit of 8pcs scuko type socket out lets and plug -
and standard pivoting cabinet with rack for wall mounting , -
knock-out holes for cable entrance and conduit connection, -
ventilation ports , standard prefabrecated patchcords (1meter) , -
8port fiber Patch panel & termination box with -
sleeve/pigtails and connectorsand 25% reserve space -
for access switches , including screen lable holder , complete -
connection and all the necessary accessories.. Nº 3 65,000.00 195,000.00
Back bone cabling -
6 Back bone cabling for flush mounting in thermoplastic -
conduit of 25mm diam.with appropriate type junction -
fed by standard graded index, -
indoor,Single mode 9.5/125 micrometer OS2 -
8cores Fiber optics data cable for 10Gbit/s -
base ethernet with standard connector plug to be fixed -
on patch pannel/switch /hub data transfer rate of -
2000MHz and the necessary fiber optic accessories to -
make the system complete. ml 200 6,500.00 1,300,000.00
Floor box -
- Floor box shall be fixed neatly in contact with the -
horizontal surface of the floor with the necessary fixers -
or connectors with IP 54 enclousures -
- Floor box ,data,socket and telephone out lets -
shall be the product of the same manfacture. -
7 Approved type dual service Slim modular round -
Non-Metallic Concrete Floor Box with complete -
conduit accessories consisting of 4pcs RJ45/8 -
contact data socket outlet,4pcs pre-wired twin schuko -
RED 220V receptacles over floor covers and frames . -
Supplied with reusable concrete cap, conduit hub -
plugs and reducers.with two hubs for low voltage -
and two hubs for power. Reducers to provide reduction -
of PVC conduit.Markings inside the boxUniversal cover -
and sub-plate Nº 70 12,000.00 840,000.00
JUNCTION BOXES -
8 Approved type 20x20x10cm data -
pull& termination box Nº 20 2,500.00 50,000.00
Screed-covered trunking system for floor box data -
and power outlets(in accordance with DIN EN 10327) -
Galvanised sheet metal made of zinc-plated steel plate with -
trunking width 240/340 mm and height of 28mm with -
minimum thickness of 1mm both upper and lower parts -
with two/three compartiments accessories consists of:- -
Clamp, Bracket, End bracket, Vertical elbow, Pipe inlet, -
Universal junction box with foil casing at each 3m -
Universal junction box with steel plate casing at each floor -
box entry with pipe inlet and Fitting frame -
9 Install approved type under floor wiring duct system -
with the system requirement with their minimum -
standard satisfied -
a. 240x28mm/1mm with two compartiments separete data and -
power cables path or standard equivalent m 560 5,385.00 3,015,600.00
CCTV SYSTEM -
10 IP based POE type Closed circuit television equipment, -
equipment supplied, installed,connected, tested and -
commissioned including cables, complete all -
as specified (or equivalent) with shop drawings. -
a. Surveillance Cameras: -
General feature that must be included: -
□ Full HD Image Resolution. -
□ Face Recognition. -
□ Noise Reduction. -
□ Color Day/ B&W Night. -
□ POE (Power Over Ethernet). -
□ Motion Detection. -
□ Snapshot ability -
Approved type POE Indoor color autodome fixed day and -
night IR(15m) RJ45 camera with the following minimum requirments :- -
* IR of 15meter LED illiminator, compression format of MPEG-4,H-264 -
* Power over Ethernet is mandatory -
*Lens with varifocal auto Iris 3.7-12mm lens -
*Image sensor 1/3"CCD, with 3 MP/Full HD 1080p -
With mounting brackets including other necessary accessories -
to make the system functional. Nº 44 22,500.00 990,000.00
b. Central Management Software (CMS): -
The System should: -
□ Support 50 IP Cameras real-time live viewing and recording. -
□ Support the following Recording Modes: -
□ Continuous, Scheduling, Event Triggered -
□ Support Triplex mode (monitoring /playback /recording). -
□ Support H.264/MPEG-4/MJPEG formats -
□ Supports alarm and events. -
□ Supports playback. -
□ Support recording audio. -
□ Supports the motion Detection -
C.Licenced softwares for IP camera and switch(NVR)with complete -
instruction preloded to camera,test and commissioning servers and -
switch all according to the requirment of manfactures all complete Nº 1 65,000.00 65,000.00
D. Server & Storage: -
□ The server specifications must be enough to connect -
simultaneous 50 IP Cameras and storage for continuous 24 -
recording for all cameras with a good performance and -
without any reduction in quality. -
□ Capacity of external storage must be enough to store all -
cameras with 24 hour continues recording for at least 30 days -
with best resolution and with capacity not less than 40 Terabytes. -
□The server must support extending the storage capacity in -
future without replacing working storage -
11 Processor: 2 x Quad-Core Intel Xeon Processor (12MB L3,3.xGhz) -
Memory: 32GB (4 x8 GB DDR3-1333 MHz -
Raid Controller Hardware RAID Controller supports RAID 0,1,5. -
Optical Drive: 16X DVD+/-RW Drive. -
Network adapter : Integrated 2 x Intel Gigabit Ethernet Ports -
Inputs: Keyboard &Mouse: USB. -
Power: Hot swap redundant Power & Fan -
O.S: Windows Server 2008 and higher -
Capacity: at least 40 Terabytes (TB) and extendable in feature Nº 1 250,000.00 250,000.00
12 d. PC Workstations: -
Detailed specifications are as following: -
Processor: Intel CPU -Dual-core - Core i5 3.x GHz, 8M Cache. -
Memory: 8 GB DDR3 SDRAM Speed 1333 MHz , -
Hard Drive: 500GB -SATA Graphics Card: 2GB dedicated -
graphic card,(HDMI , DVI ) with 19" screen -
Network adapter : Gigabit Ethernet Card -
Keyboard &Mouse: USB with wooden working table Nº 1 125,000.00 125,000.00
LED color 48" monitor with pixel pitch of 1280x1024, HDMI -
VGA/AV,USB ports and connectors,control consule , keyboard, -
mouse and remote controller on standard wooden table and -
drawer including other necessary accessories Nº 2 85,000.00 170,000.00
e. PoE Switches: -
□ All switches to be supplied from the type of POE for all Ports. -
13 □ Switches must be supplied from a company specializing in the -
field of networking ( Cisco, Dlink,..) with standard warranty -
not less than 2 years. -
□ The through put supported be switches must be enough to -
transport all continuous cameras recording with 24 hours working -
a.POE Switch 24 Port 10/100/1000TX +2 Port 1000base SFP Nº 1 105,000.00 105,000.00
b.POE Switch 24 Port 1000TX +4 Port 1000base GBIC(SFP) Nº 5 100,000.00 500,000.00
-
14 Approved type 24 channels Network Video Recorder(NVR) -
with the following minimum requirments :- -
* CPU of 500MHz, with memory of RAM of 1GB -
*Hard Disk capacity of 10TB -
* Manage upto 24 network cameras -
* Compression format of MPEG-4/MJPEG/H-246 -
* Connectors with USB/RS-485/RS-232/DI/DO connectors/RJ45 -
*Power supply of 12V DC with adaptor -
including other necessary accessories to make the system -
functional. Nº 1 165,000.00 165,000.00
15 POE type IP CCTV points fed by cable of category 2x UTP CAT6a -
4 pair data cable inside medium duty PVC conduit -
of 25mm diam. Price to include CAT 6a RJ45 -
termination on switch and all necessary accessories. Nº 44 8,500.00 374,000.00
19" 24U equipment rack with glass door, removable side panel, -
vent panels with ventilation equipments including fan and -
thermostat, heavy duty, castor wheels and all necessary -
accessories type Legrand or approved equivalent. No 1 65,000.00 65,000.00
All other accesories and items, cables requirements not -
covered by the above items and required to complete -
the specified works with manuals necssary softwares,trainings Ls 1 215,000.00 215,000.00
-
VOICE EVACUATION SYSTEM -
voice evacuation equipment, supplied, installed, connected, tested and -
commissioned including control speaker cables, conduits and all -
necessary accessories, complete as manufactured and/or -
shown on drawings. -
16 voice alarm controller -
-30 zone system controller -
- expandable up to 60 zones -
- built in 240W booster amplifier -
- digital pre-recorded messages -
- emergency microphone input on the front panel -
- 16 priority levels including emergency -
-Individual BGM volume control for each zone -
-Standard and emergency control input and outputs No. 1 350,000.00 350,000.00
b.Voice alarm 180W booster No. 1 35,000.00 35,000.00
c.Voice alarm call stations No. 1 15,000.00 15,000.00
d.Voice Alarm Remote Control Panel No. 1 165,000.00 165,000.00
e.Voice Alarm BGM(back ground music source) No. 1 18,500.00 18,500.00
f.Voice Alarm digital Message Manager No. 1 25,000.00 25,000.00
-
17 Configuration/diagnostic & logging software No. 1 50,000.00 50,000.00
18 6W ceiling mounted speaker with fixing accessories -
and surface mounting box No. 147 15,600.00 2,293,200.00
19 Softwares, documentation, instruction of -
owner's staff, power supplies. LS 1 65,000.00 65,000.00
20 Floor standing 19" rack 585(W)x2000(H)x585(D)mm -
with glass door. No. 1 95,200.00 95,200.00
21 Voice evacuation system points fed through audio cable of -
PVC-insulated, A1-screened, twisted pair, 1sq.mm -
stranded tinned copper wire, type Belden or approved -
equivalent and in medium duty rigid thermospastic -
conduit of minimum diameter of 16mm including -
junction box and all other fixing accessories. No. 147 1,850.00 271,950.00
22 Licenced soft wares for IP projector ,screen and switch management -
with complete instruction preloded to projector, -
servers and switch all according to the requirment -
of manfactures all complete Ls 1 250,000.00 250,000.00
23 Cable PVC sheathed PVC insulated cable of rating 0.6/1KV -
in pvc conduit of 25mm diam. approved equivalent and of 3x2.5mm2. -
with 16A/1ph mounted on the ceiling with all accessories. m 250 65.00 16,250.00
24 15U wall mounted metalic rack with accessories No 1 185,000.00 185,000.00
-
FIRE ALARM SYSTEM -
Intelligent fire alarm equipment, supplied, installed, -
connected, tested and commissioned including fire -
rated cables, conduits and all necessary accessories, -
as shown on drawings. -
-To be done by specilized sub-contractor -
25 Intelligent addressable fire control ,voice evacuation and indicating -
panel, including Notification Appliance Circuit Modules, -
Control Relay Module , auxiliary contact and under -
mentioned specification -
-Input power 220VAC, 50 Hz -
-Capable of networked connection RS485 -
-Programmable internal hard ware and output circuits -
-Programmable soft ware zones -
-Accessories for out put connection for telephone circuit -
-Sealed battery capable of supply to all equipments for -
at least 72Hr -
-Intelligent signaling line circuit -
-voice alarm system interface -
-Trouble acknowledge and alarm silence switch -
-Visual and audible trouble alarm by zone -
-Manual acknowledge function -
-Minimum of 40 zones digital -
-LCD display (80 characters) -
-Program keypad -
-LED indicators -
-13 relay outputs -
-4 loops -
-Compatible devices -
-Compatible intelligent devices -
with all necessary accessories as BS EN 54 -
standards to make the system complete and functional No. 1 425,000.00 425,000.00
26 Loop powered Addressable Alphanumeric liquid -
crystal display (LCD) type repeater pannel c/w all -
necessary mounting accessories, for surface/ flush. No. 12 78,550.00 942,600.00
(to be located in the stairs and corridors) -
27 Intelligent ionization multi sensors all necessary mounting -
accessories for surface / flush No. 204 8,500.00 1,734,000.00
Digital Manual call (non breakable and resettable glass) -
28 Addressable manual pull switch station type all -
necessary mounting accessories, for surface mounting No. 23 12,500.00 287,500.00
29 Loop powered Addressable Sounders -
indicators /speaker / strobe (Red) c/w all necessary -
mounting accessories, for surface mounting No. 23 8,500.00 195,500.00
FIRE ALARM POINTS -
30 Smoke / heat and sounder points fed through fire -
resistant cable of 2-core 1.5sq.mm inside PVC -
conduit of 20mm diameter including all accessories. No. 239 2,050.00 489,950.00
31 Manual call points fed through fire resistant cable -
of 2-core1.5sq.mm inside PVC conduit of 16mm -
diameter including all accessories. No. 23 1,985.00 45,655.00
Note: Voice evacuation and the Fire-alarm system should be integrated. -
SOUND SYSTEM FOR MULTI PURPOSE HALL -
32 Sound system points fed through audio cable of -
PVC-insulated, A1-screened, twisted pair, 1sq.mm -
stranded tinned copper wire, type Belden or approved -
equivalent and in medium duty rigid thermospastic -
conduit of minimum diameter of 16mm including -
junction box and all other fixing accessories. No. 32 1,850.00 59,200.00
33 6W ceiling mounted speaker with fixing accessories -
and surface mounting box No. 32 15,600.00 499,200.00
34 160W amplifier No. 1 28,968.00 28,968.00
35 Table mounted microphone No. 2 -
SOUND SYSTEM FOR MULTI PURPOSE HALL2 -
36 Sound system points fed through audio cable of -
PVC-insulated, A1-screened, twisted pair, 1sq.mm -
stranded tinned copper wire, type Belden or approved -
equivalent and in medium duty rigid thermospastic -
conduit of minimum diameter of 16mm including -
junction box and all other fixing accessories. No. 8 1,850.00 14,800.00
37 6W ceiling mounted speaker with fixing accessories -
and surface mounting box No. 8 15,600.00 124,800.00
38 40W amplifier No. 2 9,350.00 18,700.00
39 Table mounted microphone No. 2 3,500.00 7,000.00
SOUND SYSTEM FOR OUTDOOR -
40 Sound system points fed through audio cable of -
PVC-insulated, A1-screened, twisted pair, 2.5sq.mm -
stranded tinned copper wire, type Belden or approved -
equivalent and in medium duty rigid thermospastic -
conduit of minimum diameter of 16mm No. 10 2,150.00 21,500.00
41 20W pole mounted horn speaker(IP-66) with fixing accessories -
and surface mounting box No. 10 18,500.00 185,000.00
42 -
240W amplifier No. 1 48,500.00 48,500.00
TOTAL IN BIRR 70,972,672.00
-
MECHANICAL HVAC WORKS -
1 AIR CONDITIONING SYSTEM -
1.1 OUTDOOR & INDOOR UNITS -
1.1.1 AIR HANDLING UNIT FOR ASSEMBLY HALL -
Supply,install,train and commision dual flow air handling unit -
(AHU-1) for assembly hall of the bus terminal station building as -
shown on the drawing and as per the following design condition and -
specification. -
Design Condition (The equipment shall be at maximum -
eficiency at design condition) -
Assembly hall design temperature[°C]=18-20 -
Assembly hall design Relative humidity(rh)[%]=40-60 -
Between fluctuations of about ±1% rh with ±1K(kelvin) and -
±2% rh with ±2K(kelvin) -
Environment condition(Maximum) -
Outside temperature[°C]=29 -
Outside Relative humidity(rh)[%]=80 -
The equipment main components -
Mixing Box -
Primary (prefilter), Adsorbent/chemisorbent section and Final -
particulate filter section boxes -
Cooling box -
Heating box -
Heat recovery box -
Return fan -
Supply fan -
Temperature,pressure humidity and air flow sensors -
Sound attenuator -
Control panel -
Airhandling unit shall satisfy EN 1886 - 1998 for “Air handling -
units – Mechanical performance” and EN 13053 - 2001 for -
"Air handling units – Ratings and performance for"units, -
components and sections used for museum -
FILTERS -
Primary filters (Pre-filtration) shall achieve a MERV 8 or above, as -
tested in accordance with ASHRAE Standard 52.2-2012 at system -
rated air flow. -
Adsorbent/chemisorbent section:shall consist of a media bed(s) -
that is capable of reducing contaminants of concern to the levels -
listed below. Air flow through the molecular filter bed may vary -
Contaminants Recommended Limits parts per million -
Sulfurdioxide 2.7micrograms per m2 2.6 pbb -
Ozone 4micrograms per m2 2.6 pbb -
Nitrogen dioxide 5 micrograms per m 2 2.6 pbb -
Formaldehyde 5micrograms per m2 2.6 pbb -
with filter type, for proper reduction of molecular contaminants -
donot exceed manufaccturer's maximum rated air flow. This -
media bed would consist of an activated carbon media and a -
media capable of removing sulfur dioxide and formaldehyde. -
This can be accomplished in various ways,but most commonly -
with a potassium permanganate impregnated media or a -
specialty-treated carbon media. -
Fine particulate filters shall achieve a MERV 15 OR HIGHER, as -
tested in accordance with ASHRAE Standard 52.2-2012. -
Pressure difference shall be monitored for the filter proper -
operational management and centrally controlled. -
Heating/Cooling section -
Cooling and heating coil is based on heat pump heat recovery -
refrigrant piping. -
Supply/Return Fan -
Back ward driven fan type and the flow rate as per the specification -
Sensors/Control panel -
Temperature/pressure/flow rate and humidity sensors shall be fixed -
at the supply and return section of the AHU. These sensors shall -
be connected and work together with the main control panel fixed -
in assembly hall and AHU built in controller to achieve the demanded -
designed/setted room condition. -
The control panel recieves the sensors input signal and intrepretes -
with respect to the setted/designed room temperature and control -
the flow rate by working with the variable motorized volume -
control damper,and as well heat pump refrigrant flow. -
Mixing box -
This section shall have three opening: One for fresh air, the other -
for return air and the third for exhaust air which volume flow rate -
depends on the mixing box motorized damper actuated by the -
main controller and AHU built in controllers working together. -
The damper proportion ration shall be from 0-100% -
The AHU will be equipped with DAD and respective comfort control -
panel conectivity components(motors,fixtures,etc) and sensors. -
Sound attenuator -
The sound level shall be according to the ASHRAE standard for -
museums and if the sound level beyond the standard the AHU -
shall have a sound attenuator to attain the standard sound level -
for public gathering in the assembly hall. -
- AHU shall be acaustically lined -
BODY -
Aluminium structure with thermal break and with double skin -
panels of RAL7039 with pre-coated steel exterior and galvanized -
steel interior and with insulation of 50 mm thickness mineral -
wool 35kg/m3 . -
The AHUs will be connected to the aeraulic networks by means of -
class M0 flexible sleeves to prevent any transfer of vibration. -
Sound traps should also be provided according to the project's -
acoustic instructions. -
At the end of the work, the contractor shall replace all the filters -
in the facility. -
The contractor of this work package will ensure the construction -
of the condensate evacuation network from the cooling coils -
to the nearest waste water evacuation networks. The condensates -
will be evacuated by gravity. The condensate network will be made -
of PVC or cast iron according to its DN and will also provide the -
supply of anti-vibration mounts preventing any solid-state -
transmission. -
The contractors shall link the building management system using -
bus links put on standby by the AHU work package. -
AHU -1 -
supply air quantity [m 3 /Hr]= 14,291 No 1 2,160,000.00 2,160,000.00
AHU shall be manufactured as per recognized codes & standards -
and shall be approved by submitting catalogues and product certificate. -
Price shall also include all necessary main control system in assembly -
hall & electric wiring/where not specified in the electrical design/ and -
all necessary accessories for the proper functioning of the system. -
The contractor shall verify the final required AHU total performance -
based on the selected/purchased filters, sound dampers, grills, actual -
duct layouts cooling & heating load of rooms & etc. -
1.1.2 VRF HEAT RECOVERY HEAT PUMP SET -
1.1.2.1 HEAT RECOVERY OUTDOOR UNIT FOR ASSEMBLY HALL -
Supply, install, training and commission three pipe (liquid, gas & discharge) -
air cooled heat recovery of Variable Refrigerant Volume (VRV) for AHU -
conditioning the assemby hall of the building and as per the drawing lay out. -
VRF heat recovery HVAC system shall be a controllable variable capacity. The -
outdoor -
unit shall be Suitable for the production of liquid and gas refrigrant for cooling and -
heating of the room as per the diferent time demand. -
The units shall be equipped with high efficiency scroll compressors, -
external copper coils with aluminium louvers, plate heat exchangers -
The base, the structure and the panels shall be made of galvanised -
steel treated with rustproof polyester paint. -
The unit shall includes units with 6 compressors divided into two -
independent circuits.There should be an electronic thermostatic valve -
to bring energy efficiency benefits during the heat recovery outdoor unit is -
working at partial loads and integrated hydronic kit that encloses the main -
hydraulic components; shall be in configurations with two variable flow -
drive pumps with appropriate static pressures for the system & storage tank. -
The units shall be equipped with plug-fans and inverter motors -
coupled directly with the fan, with the electronic condensation control -
as standard, which adjusts the air flow according to the actual -
system requirements. -
The unit shall have an integrated system controls and communication -
network. AHU shall be controlled individually with the oytdoor unit performance. -
Additionally,heat recovery systems shall be capable of simultaneous heating and -
cooling of as per each AHU units. They must all also have Variable Refrigerant -
Temperature (VRT)Controls. -
Accessories -
The accessories necessary to connect the system include copper -
piping, wired remote controllers, LCD Touch Screen monitor. -
The system must also be provided with web access, weekly schedule -
with optimum start and Timed Override -
VFHR-1 -
Reference: DAIKIN MODEL REYQ384TTJU/REQ384TYDN or equivalent -
Nominal cooling capacity[kw]=105 -
Nominal heating capacity[kw]=99 set 1 2,790,000.00 2,790,000.00
power[kw] ≤ 40 @ 50 Hz,380v -
Refrigrant : R410a -
The unit price shall also include all works including power and -
control wiring (high voltage and low voltage ) for the AHU -
shall be approved by the engineer prior to shipment to site and must satisfy eurovent -
& UL standards and recommendation for matching ASHRAE standards. -
The VRV out door unit should equiped with all auxilary system which -
enable the specific room which the AHU delivered conditioned air -
controlled as per setted value. -
1.1.2.2 Supply, install & commision EXV control set compatible with the AHU. The -
expansion -
valve set used for refrigrant flow and pressure control in DX coil shall equipped with -
wiring and thermistors for effective & efficient management of the heat recovery -
system. set 1 87,500.00 87,500.00
The unit price shall include all analogue and digital temperature,mpressure and flow -
measurement devices and switches used for efficient management of the AHU -
system. -
The item shall be approved by the engineer prior to shipment to site and must satisfy -
eurovent & UL standards and recommendation for matching ASHRAE standards. -
1.1.2.3 -
Supply, install & commision control box compatible to the AHU which control the -
expansion valve set & outdoor units capacity.The controller shall equipped with -
communication & power wiringfor effective & efficient management of the heat -
recovery -
and AHU system. -
The item shall be approved by the engineer prior to shipment to site and must satisfy set 1 87,500.00 87,500.00
eurovent & UL standards and recommendation for matching ASHRAE standards. -
1.1.2.4 -
Supply, install & commision central remote controller compatible to the AHU which -
display the status of the system total status. -
The controller shall equipped with communication & power wiringfor effective & -
efficient management of the heat recovery and AHU system. -
The item shall be approved by the engineer prior to shipment to site and must satisfy -
eurovent & UL standards and recommendation for matching ASHRAE standards. -
1.1.2.5 Supply,fill and commision additional refrigrant R410A Kg 48 11,500.00 552,000.00
1.1.2.6 HEAT RECOVERY OUTDOOR UNIT FOR MEETING ROOMS -
Supply, install, training and commission three pipe (liquid, gas & discharge) air -
cooled -
heat recovery of Variable Refrigerant Volume (VRV) for VRV indoor units -
designed -
for conditioning of meeting & descussion rooms of the building as per the drawing. -
VRF heat recovery HVAC system shall be a controllable variable capacity. The -
outdoor -
unit shall be Suitable for the production of liquid and gas refrigrant for cooling -
and -
heating of the rooms as per the diferent time demand. -
The units shall be equipped with high efficiency scroll compressors,external copper -
coils -
with aluminium louvers, plate heat exchangers -
The base, the structure and the panels shall be made of galvanised -
steel treated with rustproof polyester paint. -
The unit shall includes units with 4 compressors divided into two -
independent circuits.There should be an electronic thermostatic valve -
to bring energy efficiency benefits during the heat recovery outdoor unit is -
working at partial loads and integrated hydronic kit that encloses the main -
hydraulic components; shall be in configurations with two variable flow -
drive pumps with appropriate static pressures for the system & storage tank. -
The units shall be equipped with plug-fans and inverter motors -
coupled directly with the fan, with the electronic condensation control -
as standard, which adjusts the air flow according to the actual -
system requirements. -
The unit shall have an integrated system controls and communication -
network. Each AHU and VRV indoor units shall be controlled individually -
and as a group.Additionally,heat recovery systems shall be capable of -
simultaneous heating and cooling of individual as per each AHU & indoor -
units demand. They must all also have Variable Refrigerant Temperature -
(VRT)Controls. -
Accessories -
The accessories necessary to connect the system include copper -
piping, wired remote controllers, LCD Touch Screen monitor. -
The system must also be provided with web access, weekly schedule -
with optimum start and Timed Override -
VFHR-2 -
Reference: DAIKIN MODEL REYQ168TTJU/REQ168TYDN or equivalent -
Nominal cooling capacity[kw]=42 set 1 2,790,000.00 2,790,000.00
Nominal heating capacity[kw]=40 -
power[kw] ≤ 40 @ 50 Hz,380v -
Refrigrant : R410a -
The unit price shall also include all works including power and -
control wiring (high voltage and low voltage ) for the indoor and -
VRF outdoor units and shall be approved by the designer prior to shipment to site -
and -
must satisfy eurovent standards and recommendation for matching with ASHRAE -
and UL -
standards and recommendation for matching with indoor smooth operation of air -
conditioning systems.The VRF out door unit should equiped with all auxilary system -
which enable the specific rooms indoor units delivered conditioned air -
controlled as per setted value. -
1.1.2.7 Supply, install & commision control box compatible to the VRV indoor and out door -
system which control the whole system of outdoor indoo units capacity variability. -
The controller shall equipped with communication & power wiring for effective & set 1 250,000.00 250,000.00
efficient management of the heat recovery and AHU system. -
The item shall be approved by the engineer prior to shipment to site and must satisfy -
eurovent & UL standards and recommendation for matching ASHRAE standards. -
1.1.2.8 HEAT PUMP INDOOR UNIT -
Supply, install and commision a modular round flow sensing casset type ceiling -
mounted indoor units as shown on drawing complete with the following features: -
i. True 360° Airflow and three room sensors enables optimized occupant -
comfort and efficiency -
ii. Energy efficient with DC fan motor and auto-logic that adjusts fan speed -
based on space load -
iii. Optional self-cleaning air filter of a mold resistance net panel to further increase -
efficiency and reduce maintenance costs, when used in VRV IV systems -
iv. Very flexible with different possible airflow patterns, ensuring ideal air distribution -
to maximize comfort and efficiency -
v. Compact design to allow for installation in small ceiling voids -
vi. Sound pressure levels as low as 27 db(A) -
vii. Enhanced indoor air quality and LEED ready with MERV 13 filter options -
viii. Low power consumption dc motor drain pump. -
ix. Compatible control box which display the performance of the indoor unit and the -
room environmental condition. -
xii. Fresh intake shall be possible. -
The built-in occupancy sensor used for saving energy and optimize occupancy comfort -
In order to save energy,the function of the occupancy sensor can be used to -
automatically set back the air temperature and also lower the fan speed if no -
people are present in the room. Additionally,Together with the occupancy sensors -
(which included in this scope to be supplied,installed and commisioned) -
the air-temperature sensor and the built-in surface temperature sensor are used to -
maintain an even and comfortable temperature distribution from floor to -
ceiling in the room. This is done by automatically adjusting the supplied airflow rate -
and the individual position of each of the four supply air louvers in the unit,thus -
maintaining the required comfortable space environment comfortable space -
environment. -
Dust is deposited into a collection box during the self-cleaning process.When indicated -

with light on the unit and on the controller display, the dust collection box in the unit -
can easily and quickly be emptied with a standard vacuum cleaner. -
The unit shall also equiped with electronic expansion valve for refrigrant control and -
a protection means using devices of fuse/breaker & fan motor thermal protection. -
The item external finish shall be a galvanized steel plate. -
Accessories -
hangers,support ,false ceiling covering to aestetic -
HRIU-1 -
Duty-Cooling/Heating Capacity [KW]: 5.3/5.2 No 8 2,535,000.00 20,280,000.00
Reference:DAIKIN,FXFQ18TVJU -
1.1.2.9 Supply and install copper pipe,branch pieces, R410a refrigerantcharge -
elbow, tees, yees for VRV air conditioning system as shownon the -
drawing. Price shall include hangers,valves, flexible conn-ection,oil balancing pipe -
gages, insulation,collective drainage system to make the system functional. -
Insulation -
Type- closed cell rubber tube insulation + vapor barrier -
For concealed piping -
- 10 mm x 48 kg/m3 insulation, vapour barrier and adhesive -
adhesive tape covering -
For exposed piping -
- 20mm x 48kg/m3 insulation , vapour barrier and 0.4mm -
aluminum cladding. -
pipe size (mm) -
Diameter in mm -
9.5 lm 62 450.00 27,900.00
12.7 lm 10 685.00 6,850.00
15.9 lm 25 850.00 21,250.00
19.1 lm 22 1,150.00 25,300.00
22.2 lm 10 1,358.00 13,580.00
28.6 lm 18 1,625.00 29,250.00
34.9 lm 15 2,150.00 32,250.00
41.28 lm 15 2,850.00 42,750.00
1.1.2.10 Supply and install condensate hard pvc pipes with all -
acessories the price shall include insulation. -
VP25 (OD 32,ID 25) lm 200 250.00 50,000.00
1.1.2.11 supply and fix yee joint in suction and gas side -
branches as shown on drawing. No 14 350.00 4,900.00
1.1.8 design supply and install integrated managenent -
system for indoor and outdoor units complete -
with control cable system fire protection. ls 1 285,000.00 285,000.00
1.2 AIRCONDITIONING DUCTS & DIFFUSERS -
1.2.1 AIRCONDITIOING DUCTS -
Supply, fix, test and commission galvanized steel air distribution ducts as -
where shown on the drawing. All duct construction,duct thickness and -
installation shall follow the technical specification of this project, -
standards and recommendations given on SMACNA(Sheet Metal and Air -
Conditioning Contractors National Association, INC) and EBCS 11 -
Price shall include all the necessary duct fittings, reinforcement, hot dipped -
galvanized steel support roads, brackets,fixing clamps angle,iron walls, -
vanes, etc and all the necessary fittings and .civil assistance works. -
Insulation -
For concealed duct -
- 25mm x 48kg/m3 k = 0.033 w/mk fiber glass insulation, -
vapour barrier and adehesive tape covering. -
For exposed duct -
- 50mm x 48kg/m3 k = 0.033 w/mk fiber glass insulation, -
vapour barrier and 0.4mm aluminum cladding -
Duct -
Supply and install galvanized steel sheet for supply and return duct system -
as shown on the drawing complete with insulated flexible duct,transition -
duct, hangers & supports, silencer vibration isolator, damper, turning & -
splitter vanes at each fitting, stiffener, flanges.etc to make the system -
complete. -
Up to 600 mm Duct longer size : Duct thickness 0.8mm -
1000 to 1200 mm Duct longer size: Duct thickness 1mm -
SUPPLY DUCT SIZE [mm X mm] -
300 X 375 lm 5 12,050.00 60,250.00
300 X 675 lm 7 13,500.00 94,500.00
300 X 950 lm 7 17,585.00 123,095.00
350 X 950 lm 7 17,950.00 125,650.00
450 X 950 lm 7 18,500.00 129,500.00
450 X 1000 lm 7 19,000.00 133,000.00
500 X 1000 lm 7 19,650.00 137,550.00
500 X 1200 lm 8 19,850.00 158,800.00
525 X 1200 lm 16 20,000.00 320,000.00
850 X 1200 lm 10 23,000.00 230,000.00
900 X 1200 lm 13 23,500.00 305,500.00
925 X 1200 lm 6 23,850.00 143,100.00
925 X 1275 lm 4 24,500.00 98,000.00
950 X 1275 lm 3 24,850.00 74,550.00
950 X 1300 lm 16 25,000.00 400,000.00
RETURN DUCT SIZE [mm X mm] -
300 X 350 lm 4 7,500.00 30,000.00
300 X 625 lm 6 13,500.00 81,000.00
400 X 625 lm 7 14,500.00 101,500.00
400 X 800 lm 7 16,250.00 113,750.00
400 X 950 lm 7 17,500.00 122,500.00
450 X 950 lm 7 18,250.00 127,750.00
500 X 950 lm 8 18,750.00 150,000.00
500 X 1100 lm 7 19,500.00 136,500.00
500 X 1200 lm 10 19,850.00 198,500.00
550 X 1200 lm 7 20,000.00 140,000.00
600 X 1200 lm 6 20,850.00 125,100.00
900 X 1200 lm 17 23,500.00 399,500.00
-
1.2.2 SUPPLY & RETURN DIFFUSERS -
All supply and exhaust air diffusers & others shall be -
approved quality and located to ensure the correct air -
distribution pattern without stagnant regions or draughts -
occurring in the room that they are serving. Price shall -
include dampers, sealing gaskets & all necessary accessories -
& connecting pieces for the proper functioning of the -
systems. -
Supply, fix, test & commission exhaust air intake grilles. The frame and -
blades shall be made from high quality extruded aluminum profile -
advantages of corrosion resistance & rigidity. Price shall include foam -
gasket seal around the back of the frame & flexible duct connectors -
as required. -
i). RAD-1(RETURN AIR REGISTER) -
i). Capacity =605 LPS -
Size :500 X 500mmxmm -
Colour : As per the Architect's preference Nº 21 225,000.00 4,725,000.00
Reference : Airmaster ,ARR-V With fixed horizontal blades at 45 0 -
ii). SAD-1(SUPPLY AIR REGISTER) -
i). Capacity = 661LPS -
Size :600 X 400mmxmm -
Colour : As per the Architect's preference Nº 27 235,000.00 6,345,000.00
Reference : Airmaster ,ASR-H With fixed horizontal blades at 45 0 -
2 TOILET VENTILATION SYSTEM -
2.1 EXHAUST FANS -
2.1.1 INLINE TYPE EXHAUST FANS -
Supply and install inline type centrifugal s-proof exaust air -
extruction fan as shown on the drawing complete with multi- -
speed switch, back draught shutter, spigot,Weather proof -
protection cover. sound attenuator & all fixing accessories -
including support base. price shall include all accessories -
to make the system complete. -
Purpose- exhausting air from toilet -
Type: Inline type centrifugal fan -
The unit price for all the fan listed below shall include a fitting -
structure ( like seating structure and making better look with respect -
to aestatic) to for the fans ,electricale cabling ,demolishing & -
reconstruction of building parts. -
ITEF-3 -
i). Flow capacity [m 3 /Hr] = 408 @ 200Pa -
Power[KW] < 0.15 Sound[dB]< 33 -
Reference : Dynair ,MINIBOX 200 Or Equivalent Nº 8 25,500.00 204,000.00
The unit price shall include shutter,duct clamp & standard flexible -
duct speed regulator with on/off switch installed on the common wall -
of the toilet which will be accessible to facility attendants. -
ii) Supply & install noise attenuator of approved quality -
before exaust air fan as per manufacturers instruction. Nº 8 20,000.00 160,000.00
The total sound level shall become 20dB from 33dB of the fan level. -
The unit price shall include two standard flexible ducts. -
Reference : Dynair ,1S122600 Or Equivalent -
iii) Supply and install exhaust air louver, including -
connecting pieces & necessary accessories all as per the manufacturer -
recomendation. Color shall be as the curtain wall color -
or shall be approved by the architects. -
Size:Compatible with the selected fan outlet size. Nº 8 16,500.00 132,000.00
Reference : Dynair ,2SR2000 Or Equivalent -
ITEF-4 -
i). Flow capacity [m 3 /Hr] = 205 @ 120Pa -
Power[W] < 50 Sound[dB]< 35 -
Reference : Dynair ,AXC/LINE METAL 125B Or Equivalent Nº 6 17,500.00 105,000.00
The unit price shall include shutter,duct clamp & standard flexible -
duct speed regulator with on/off switch installed on the common wall -
of the toilet which will be accessible to facility attendants. -
ii) Supply & install noise attenuator of approved quality -
before exaust air fan as per manufacturers instruction. Nº 1 15,000.00 15,000.00
The total sound level shall become 20dB from 43dB of the fan level. -
Reference : Dynair ,1SI2242 Or Equivalent -
The unit price shall include two standard flexible ducts. -
iii) Supply and install exhaust air louver, including -
connecting pieces & necessary accessories all as per the manufacturer -
recomendation. Color shall be as the curtain wall color -
or shall be approved by the architects. -
Size: Compatible with the selected fan outlet size. Nº 1 14,500.00 14,500.00
Reference : Dynair ,2SR1250 Or Equivalent -
ITEF-5 -
i). Flow capacity [m 3 /Hr] = 510 @ 160Pa -
Power[W] < 50 Sound[dB]< 38 -
Reference : Dynair ,AXC/LINE METAL 160B Or Equivalent Nº 1 27,850.00 27,850.00
The unit price shall include shutter,duct clamp & standard flexible -
duct speed regulator with on/off switch installed on the common wall -
of the toilet which will be accessible to facility attendants. -
ii) Supply & install noise attenuator of approved quality -
before exaust air fan as per manufacturers instruction. Nº 1 21,500.00 21,500.00
The total sound level shall become 20dB from 43dB of the fan level. -
Reference : Dynair ,1SI2242 Or Equivalent -
The unit price shall include two standard flexible ducts. -
iii) Supply and install exhaust air louver, including -
connecting pieces & necessary accessories all as per the manufacturer -
recomendation. Color shall be as the curtain wall color -
or shall be approved by the architects. -
Size: Compatible with the selected fan outlet size. Nº 1 18,500.00 18,500.00
Reference : Dynair ,2SR1600 Or Equivalent -
2.1.2 BOX TYPE EXHAUST FAN -
Supply , install & commission box type exhaust fan for toilets ventilation -
system as shown in the drawing which is made of double wall skill -
corrosion-resistance stainless-steel sheet with internal plenum lining of -
self-extinguishing technopolymer material , non-abrading, noise and -
non-flammable heat insulation material confirming class A of DIN -
standard.The item shall be provided vibration isolator base with -
appropriate damping coefficient and sternness coefficient well designed -
aluminum sheet shelter with supportive structure which must be -
approved before installation,supportive structure, flexible duct connection -
(rectangular aluminum sheet with extruded aluminum coil type), control -
board which have electrical and mechanical fault indicator and also it -
must have speed regulator mounted inside the building as per approved -
location. -
The unit price shall include all the necessary accessory items ( like colar -
with duct clamping, flexible duct, etc) and related works (like power -
cabling from thereby power supply point, construction & de-construction -
of civil work,etc) which make the system complete in functioning and -
aesthetic. -
BTEF-1 -
Air flow rate [m3/Hr] = 4600 @ 500Pa -
Power input [ 380 V/50HZ/3N] [kw] < 1.0 Nº 1 385,000.00 385,000.00
Accessories -
- provide ON/OFF indicator (light type) and surface mounted speed -
controller. -
- Resilient mounting kit -
- Flexible connection duct -
- Air operated louver shatter -
- Fire damper -
- support structures -
The unit price shall also include for all the necessary accessory items -
and tasks which make the system functionally and aesthetically complet. -
REFERENCE -
BRAND: DYNAIR or EQUIVALENT -
MODEL UNIT : BOX T 12/12 -
WITH FLEXIBLE JOINTS AND CONTROL PANEL. -
2.2 TOILET VENTILATION DUCT -
Supply, fix, test and commission galvanized steel air distribution ducts as -
where shown on the drawing. All duct construction,duct thickness and -
installation shall follow the technical specification of this project, -
standards and recommendations given on SMACNA(Sheet Metal and Air -
Conditioning Contractors National Association, INC) and EBCS 11 -
Price shall include all the necessary duct fittings, reinforcement, hot dipped -
galvanized steel support roads, brackets,fixing clamps angle,iron walls, -
vanes, etc and all the necessary fittings and .civil assistance works. -
Duct longer size Sheet metal -
(mm) thickness (mm) -
Up to 350 mm 0.6 mm -
400 to 660 mm 0.7 mm -
670 to 910 mm 0.9 mm -
920 to 1270 mm 1.0 mm -
1280 to 1520 mm 1.3 mm -
1530 to 2130 mm 1.5 mm -
GROUND FLOOR -
100 X 150 lm 12 -
100 X 175 lm 18 -
100 X 250 lm 19 -
125 X 250 lm 25 -
150 X 250 lm 8 -
175 X 250 lm 6 -
200 X 250 lm 8 -
225 X 250 lm 3 -
225 X 300 lm 9 -
200 X 150 lm 4 -
200 X 275 lm 4 -
-
FIRST FLOOR -
100 X 150 lm 9 -
100 X 175 lm 9 -
100 X 250 lm 13 -
125 X 250 lm 18 -
150 X 250 lm 11 -
175 X 250 lm 3 -
200 X 250 lm 8 -
225 X 250 lm 8 -
200 X 150 lm 3 -
200 X 500 lm 4 -
-
SECOND & THIRD FLOOR -
100 X 150 lm 12 -
100 X 175 lm 10 -
100 X 250 lm 14 -
125 X 250 lm 44 -
150 X 250 lm 12 -
175 X 250 lm 4 -
250 X 500 lm 4 -
325 X 500 lm 4 -
-
FOURTH FLOOR -
100 X 150 lm 6 -
100 X 175 lm 5 -
100 X 250 lm 6 -
125 X 250 lm 8 -
150 X 250 lm 2 -
375 X 500 lm 4 -
-
2.3 EXHAUST AIR INTAKE GRILLES & ACCESSORIES -
All supply and exhaust air diffusers & others shall be -
approved quality and located to ensure the correct air -
distribution pattern without stagnant regions or draughts -
occurring in the room that they are serving. Price shall -
include dampers, sealing gaskets & all necessary accessories -
& connecting pieces for the proper functioning of the -
systems. -
Supply, fix, test & commission exhaust air intake grilles. The frame and -
blades shall be made from high quality extruded aluminum profile -
advantages of corrosion resistance & rigidity. Price shall include foam -
gasket seal around the back of the frame & flexible duct connectors -
as required. -
i). EAG-1 -
i). Capacity =28.3l/s -
Size :150 X 150mmxmm -
Colour : As per the Architect's preference Nº 110 7,500.00 825,000.00
Reference : Airmaster ,ARG-H With fixed horizontal blades at 45 0 -
ii). EAG-2 -
i). Capacity =51l/s -
Size :200 X 150mmxmm -
Colour : As per the Architect's preference Nº 4 4,500.00 18,000.00
Reference : Airmaster ,ARG-H With fixed horizontal blades at 45 0 -
2.4 DAMPERS AND ACCESSORIES : -
All dampers and accessories shall be manufactured as per -
recognized codes, standards & full fill the requirments -
specified in the specification. -
Volume Dampers -
Supply ,install,test and commission volume dampers of -
approved quality as where shown on the drawings. -
Price shall include all the necessary accessories and -
connecting pieces. -
I - On extract duct -
For duct Size: 200 X 150 mmxmm/ VCD-1 Nº 2 16,800.00 33,600.00
150 X 250 mmxmm/ VCD-5 Nº 5 18,000.00 90,000.00
125 X 250 mmxmm/ VCD-6 Nº 9 17,500.00 157,500.00
3 KITCHEN VENTILATION -
3.1 KITCHEN VENTILATION FAN -
Supply,install and commission backward curved blades centrifugal fans for -
smoke of 300 ºC temperature. The fan shall be a corrosion resistant type -
manufactured of casing and impeller in stainless steel .The fan shall be -
provided with appropriate and approved the steel structure for seat with -
foundation in the ground. The fan shall equiped with control board which -
have electrical and mechanical fault indicator and also it must have speed -
regulator mounted inside the building as per approved. The fan motor shall -
be a type of suitable for speed regulation. -
KEF-1 -
Air flow rate [LPS] = 28,728 @ 200Pa -
Power input [ 380 V/50HZ/3N] [kw] < 7.5 -
ACCESSORIES Nº 8 -
Condensate drain hole -
Inspection door -
Inlet & outlet counter flange -
Inlet & outlet protection guard -
Antivibration mount -
REFERENCE -
BRAND: DYNAIR or EQUIVALENT -
MODEL UNIT : PR-L ATX 806 -
WITH FLEXIBLE JOINTS AND CONTROL PANEL. -
3.2 KITCHEN HOOD -
Supply and install kitchen hood of island type which made of -
stainless steel sheet metal of 1.0 mm thick with fire proof paint, -
all fittings plus an adapter and back drawght shutter,flexible duct, -
volume control damper, washable & replicable grease filter, lighting, -
condensation trap system, special paint finish and fixing structures. -
Size (L x W x H) [mm] -
5500 x 4000 x 6000 Nº 8 -
The unit should satisfy EBCS, ASHRAE & SMANCA standards -
The unite price shall include all the necessary accessory items & tasks -
to complete the system functionally, & aesthetically. -
4 BMS controller -
Design, Supply, install and commision BMS control -
system for heat pump, fans air handling units and fan coil units (indoor LS 1 -
units) complete with all acessories including energy management module. -
TOTAL TO SUMMARY……………………. BIRR 47,073,075.00
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
15. ELECTRICAL WORKS
Guard House
SUPPLY AND INSTALL
Distribution boards for UPS
All boards shall be wired and tested as relevant
IEC standards
1 Flsuh mounted………………..SDB-WT NO 1 8,500.00 8,500.00
2 Flsuh mounted………………..SDB-FF NO 1 7,850.00 7,850.00
LIGHT POINTS -
3 NO 18
Light points in medium duty rigid conduit of 16mm fed by 2,500.00 45,000.00
SWITCHES IP54 -
4 1-way NO 4 585.00 2,340.00
5 Two-gang 1-way NO 5 700.00 3,500.00
6 2-way NO 6 650.00 3,900.00
SOCKET OUTLETS POINTS -
Socket outlet -
7 16A for flush mounting -
Socket 2p+e out let ……………………………. NO 5 2,500.00 12,500.00
8 Ditu as above but for twin outlet NO 1 2,650.00 2,650.00
Extra Over Socket Outlet -
9 16A, 1ph NO 5 850.00 4,250.00
10 16A, 1ph, twin outlet NO 1 1,200.00 1,200.00
TYPE OF LIGHT FITTINGS WITH LAMPS -
11 Type 1 NO 4 6,500.00 26,000.00
12 Type 2 NO 10 3,500.00 35,000.00
13 Type 3 NO 2 3,500.00 7,000.00
14 Type 4 NO 2 2,985.00 5,970.00
POWER CABLES AND PVC PIPE -
15 5X4 MM2 from SDB-WT to SDB-FF inf pvc pipe dia. m 10 785.00 7,850.00
16 m 50
4x6 mm2 from the mearest source to SDB-WT in pvc pipe 625.00 31,250.00
-
Concrete pipe -
17 Concrete pipe dia. 10cm m 15 8,500.00 127,500.00
VOICE/DATA SYSTEM -
18 RJ11+RJ45 twin outlets ………………. NO 2 1,150.00 2,300.00
19 Twin Tele/data points fed by cable………………………. NO 2 1,250.00 2,500.00
Double brick Man hole -
20 40 x 40 x 50 cm NO 2 5,600.00 11,200.00
Grounding -
21 50 x 50 x 50 cm single brick …………………….. NO 1 7,580.00 7,580.00
22 1 x 6 sq.mm bare copper wire ml 10 185.00 1,850.00
23 Dia. 16mm and 2400mm long copper rod…………… NO 1 1,500.00 1,500.00
-
Total TO summery…………………………. 359,190.00
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Dry Latrin
9.Electrical Installation Works
9.1 Distribution Boards
Flush mounting distribution board SDB-Dp
with lockable accessories consisting of
1 pc mainMCB of 20A,1PhIcu=6kv
all complete with phase bar of 25A & ample
reserve
space,color coded & labeled NO 1
- 2,500.00 2,500.00
9.2 Light Points -
Flush mounted light points fed through PVC -
insulated conductors of 2x2.5 mm² inside PVC -
conduits of 16 mm diameter, including -
junction boxes with covers NO 10 2,050.00 20,500.00
9.3 Switches -
Single pole switch recessed NO 2 585.00 1,170.00
Ligheting fixtures -
9.4 Mounting ceiling surface no of lamp 1, -
compact flourescent NO 10 4,500.00 45,000.00
Light Fittings and Lamps -
9.5 (Specified Type or Equivalent) -
Fluorescent fitting type MODUS -
TU 136K + 1XT8 36W/840 lamp. NO 10 4,500.00 45,000.00
TOTAL TO -
SUMMARY…………………. BIRR 114,170.00
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SITE WORK
2 ELECTRICAL SITE WORK
Utility connection
ALL ELECTRICAL ITEMS NEED
TO BE 3rd PARTY CERTIFIED
02. ELECTRICAL SITE WORK
All electrical material need to 3rd party certified
Utility connection
5 years of guarantee
1 Supply and install premanufactured Distubution
system (compact sub station ) with oil colled
transformer of 800KVA ,air insulated RMU 3+1 with
digital data logger unit for all electrical parameters
with RS485 Port and non volatile memory for network
connection with medium voltage CT and VT,
internal breaker ,CT and VT for KWH,KVAR
lockable door and separate lockable portion to
accommodate all EEPCO active and
reactive power meters installed , low voltage side
switch gears and all medium, low and high-tension
cable connection accessories and all the necessary
accessories as per EEPCO regulation and the low
voltage side consisting of type tested low voltag switch
gear, LVSG, with hard drawn high conductivity copper
bus bars of 2000A rating, 200KA for 1 sec.including all
controlling and other necessary accessaries with 40%
reserve space, all tested and wired to relevant IEC
standard and consisting of :-
1Pc Main ACB of 1600A, 3ph Icu=160kA
withdrawable type
1pc MCCB of 800A,3ph
1pc MCCB of125A,3ph
2pc MCCB of100A,3ph
2pc MCCB of80A,3ph
2pc MCCB of 25A,3ph
2Pc MCCB of 25A,1ph
2Pc contactor 25A,3ph
2Pc MCB 6A,1ph Icu=6KA
2pc programable timer swich/light sensitive switch
1 pc 4 pole ,40kA class 1 SPD
1 pc fused load break switch for SPD of 80A/3p
1pc surge arrestor 40KA
3Pcs current transformers: 1600/5A

1pc front mount digital data logger unit for all electrical 11
parameters with RS485 Port and non volatile
memory for network connection High performance
ventillation.
all the civil works as per the manufacturer
instruction and recommdtation No 1 1,500,000.00 1,500,000.00
Supply and install Genset with factory test report and -
2years factory fault guarentee -
Note: Before installation conform to the requirements of -
Generator set supplier. -
2
Supply and install out door with IP68 generator with foundation -
as per the manufacturer recommdation shock absorbing -
with access for the bus-way feeder at bottom/upper -
mounting rails and the following specifications:- -
Type water cooled turbo engine -
Altitude suitable for Site place -
Frequency 50Hz,pf=0.8 -
Stand by power 600KVA after de-rating -
Generator and Mains measurement of -
Phase to Phase volage -
Phase to neutral -
phase amperage,frequency,KVA,KW,KVAr,power factor -
Engine -

-coolant temprature,oil pressure,feul level,battery voltage,RPM -


Engine alarms:- -

High coolant tempreture,low coolant level,failure to stop,battery -


voltage failure,over/under speed,feul levels -
Alternator alarms:- -

High/low frequency,voltage,current,over load,incorrect phasing -


Connectivities:- -
Remote and local Monitoring(LAN,CANModem-GSM) -
Fuel transfer control,programmable alarms,synchronisation -
- with 1600 amp ATS -
- Molded case circuit breaker with -
access and bus way connection -
- Protection fuse -
-12-24V electric starting system including heavy duty -
dry charged battery pack -
-Sheet steel constructed frame -
-Ant vibration pad between engine /alternator and base -
frame and ground -
-Painting to high industrial standards -
-Operation and maintenance manuals ,spare parts -
for one year catalogs circuit diagram and test report -
-Sound/weatherproof Canopy with all the necessary Exhaust and
inlet -
ventilation system extended upto the area which doesn't -
affect the surrounding area with noise level of 75db@7meter -
(silencer/air inlet and out let sound attenuators and sound -
absorving wall lining) in consaltion with the engineer -
-Base mounted daily fuel tank complete with essential -
accessories comprising
lines dial type filiter,breather
content gauge feed accessories
and complete and return -
No 1 -
3 Custom designed Under ground fuel tank system -

capacity of 10000 liters with automatic pumps and accessories -

comprising filiter,breather feed and return lines,ultrasonic sensors -


dial type content gauge and complete accessories -
and connections with detail drawings submitted -
before installation in consulation with the engineer unit for fuel
tank -
to measuring all tank parameter with complete sensors -

and transducers , RS485 Port and non volatile memory for network -
connectionstandards
regulations all the civiland
works as per the
instruction andmanufacturer,
recommdtationlocal -
No 1 -
4 Generator sets control and switch gear system -
cabling and termination in accordance with manufacturer's -

instructions, supplied, installed, connected, color coded, tested -


and commissioned, complete, all as specified. Price should
necessary -
include multicore cables, connection box and other -
accessories. L.S 1 -
UPVC pipe -
5 a. Diameter 50mm m 300 95.00 28,500.00
b. Diameter 110mm m 2000 225.00 450,000.00
c. Diameter 80mm m 300 125.00 37,500.00
-
Man hole single brick wall With cast iron top -
cover inscribed with"EL MH" See the detail drawing -
6 a. 120x120x120 cm No 10 12,500.00 125,000.00
b. 50x50 x 60 cm No 12 7,850.00 94,200.00
Cables 0.6/1KV -
PVC sheathed XLPE insulated cable rating of 0.6/ 1KV, -
3rd party certified -
7 a. 3x300/150sq.mm m 600 13,565.22 8,139,130.43
b. 3x95/50sq.mm m 200 6,490.00 1,298,000.00
c. 5x6sq.mm m 120 850.00 102,000.00
c. 4x10sq.mm m 2400 1,200.00 2,880,000.00
-
Grounding -
8 a.50 x 50 x 50 cm single brick inspection pit with the -
cover top inscribed "Earthing" as per the detail -
drawing No 4 7,500.00 30,000.00
b. 1x150sq.mm bare copper wire m 50 1,200.00 60,000.00
c. 1x50sq.mm bare copper wire m 15 525.00 7,875.00
Diameter 16mm and 2400mm long copper rod -
Note:If the earth resistence is more than 5 ohms -
add additional electrode spaced at length of -
the electrode -
3rd party certified -
9 Type-1 Street lighting octagonal hot deep galvanized steel -
pole of 3mm thick and 8.0m height above ground -
level up to the fitting, with 1.5meter Double arm, -
free fixed door, including removable panel with -
clamps for power cables, and protective fuse holder -

with 1x6A fuse & 2x2.5sq.mm cable. Price to include foundation -


work and anchor bolts as indicated on detail -
drawing . No 16 35,000.00 560,000.00
10 Type-2 Street lighting octagonal hot deep galvanized steel -
pole of 3mm thick and 8.0m height above ground -
level up to the fitting, with 1.5meter Double arm, -
free fixed door, including removable panel with -
clamps for power cables, and protective fuse holder -

with 1x6A fuse & 2x2.5sq.mm cable. Price to include foundation -


work and anchor bolts as indicated on detail -
drawing . No 75 31,500.00 2,362,500.00
External light fixture -
3rd party certified -
11 Mounting - on arm of 8meter pole -
Lamp type-LED EQUIVALENT TO SON-T 250w Lumen -
Number of Lamps -1 -
Lamp wattage- -
Luminare material-fiber glass -reniforced &Polycarbonate -
Ingress protection-65 -
Size -length 510mm and width 300mm -
control gear-220V/50HZ No 107 18,500.00 1,979,500.00
Trench -
Including trench width 600mm and depth of -
1000mm filled with sand and warning tapes of -
100 mm wide plastic tape, coloured yellow with -
suitable warning legend describing buried -
electrical lines m 300 3,500.00 1,050,000.00
Concrete pipe -
12 Diameter 20cm m 200 2,850.00 570,000.00
Total TO summery…………………………. 21,274,205.43

You might also like