0% found this document useful (0 votes)
114 views9 pages

Ceiling Concealed Fan Coil Unit: CEILING Installation, Operating & Maintenance

This document provides installation, operation, and maintenance instructions for ceiling concealed fan coil units. Key points include: - The units are designed for concealed ceiling installation and include hanging holes for mounting. Proper clearance and insulation is required. - Pipe and electrical connections should be installed according to local codes. Water pipes must be insulated to prevent freezing. - Detailed diagrams show the unit dimensions and clearances needed above and around the unit. Drain piping must have a minimum slope of 1:50. - Air ducts must be sized properly to match the unit's external static pressure and be made of fire-proof materials per local codes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views9 pages

Ceiling Concealed Fan Coil Unit: CEILING Installation, Operating & Maintenance

This document provides installation, operation, and maintenance instructions for ceiling concealed fan coil units. Key points include: - The units are designed for concealed ceiling installation and include hanging holes for mounting. Proper clearance and insulation is required. - Pipe and electrical connections should be installed according to local codes. Water pipes must be insulated to prevent freezing. - Detailed diagrams show the unit dimensions and clearances needed above and around the unit. Drain piping must have a minimum slope of 1:50. - Air ducts must be sized properly to match the unit's external static pressure and be made of fire-proof materials per local codes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

CEILING Installation, Operating & Maintenanceance Manual

Ceiling Concealed Fan Coil Unit


Model: FWMH2/3/4/6/8/10/12A(N)0(Z)V1

FWMH2/3/4/6/8/10/12A(N)3(Z)V1

FWMH2/3/4/6/8/10/12A(N)6(Z)V1

FWMH2/3/4/6/8/10/12A(N)8(Z)V1
M08019017541
FWMH1005-A2
Contents
Safety precaution ----------------------------------------------------------------------------------1
Installation--------------------------------------------------------------------------------------------2
Service and Maintenance------------------------------------------------------------------------4
Trouble shooting -----------------------------------------------------------------------------------5
Outlines and Dimensions -----------------------------------------------------------------------6
SAFETY PRECAUTION

WARNING CAUTION
z Installation and maintenance should be performed Please take note of the following important points when
by qualified persons who are familiar with local installing.
code and regulation, and experienced with this type
of appliance. z Ensure that the drainage piping is connected
z All field wiring must be installed in accordance with properly.
the national wiring regulation. If the drainage piping is not connected properly, it may
z Ensure that the rated voltage of the unit cause water leakage which will dampen the furniture.
corresponds to that of the name plate before z Sharp edges and coil surfaces are potential locations
commencing wiring work according to the wiring which may cause injury hazards. Avoid from being in
diagram.
contact with these places.
z The unit must be GROUNDED to prevent possible
z Tightening torque should not be too high when connecting
hazard due to insulation failure.
water pipes, in order to avoid brass deformation or
z All electrical wiring must not touch the water piping
water-leakage by torsion split.
or any moving parts of the fan motors.
z Confirm that the unit has been switched OFF before z Water coil not used during winter season shall be drained,
installing or servicing the unit. or anti-freezing solution shall be added to the water circuit
z Risk of electric shock, can cause injury or death. to avoid freezing.
Disconnect all remain electric power supplies z Before turning off the power supply set the remote
before servicing. controller’s ON/OFF switch to the “OFF” position to
z DO NOT pull out the power cord when the power is prevent the nuisance tripping of the unit. If this is not
ON. This may cause serious electrical shocks which done, the unit’s fans will start turning automatically when
may result in the fire hazards.
power resumes, posing a hazard to service personnel or
z Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1m from TVs and the user.
radios, to prevent distorted pictures and static. z Ensure the color of wires of the outdoor unit and the
{Depending on the type and source of the electrical terminal markings are same to the indoors
waves, static may be heard even when more than respectively.
1m away}. z IMPORTANT: DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.

NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products
shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the
refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local
and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use,
recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential
negative consequences for the environment and human health. Please contact the installer or local
authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with
relevant local and national legislation.

1
INSTALLATION

RECEIVING
All units leaving the factory have been inspected to ensure the shipment of high quality products and
reasonable means are utilized to properly pack the fan coil units to protect them in transit.
Carefully inspect all shipments immediately upon delivery. When damage is visible, note this fact on the
carrier’s freight bill and request that the carrier send a representative to inspect the damage. This may be
done by telephone or in person, but should always be confirmed in writing.
The shipment should be unpacked in the presence of the agent so that the damage or loss can be
determined. The carrier’s agent will make an inspection report and a copy will be given to the consignee for
forwarding to the carrier with a formal claim.
LOCATION
Before installation, please check the following:
1. There must be enough space for unit installation and maintenance. Please refer to the outline and
dimensions and fig.1 for the minimum distance between the unit and obstacle.
2. In case of installation in free blow, the unit must be installed at a minimum height of 2.5m to avoid contact
with the appliance.
3. Please ensure enough space for piping connection and electrical wiring.
4. Please make sure that the hanging rods can support weight of the unit.
INSTALLATION
1. The unit is designed for concealed ceiling installation.
2. There are holes on the top of the unit for hanging. Please refer to Fig.1. Fig.2 and Fig.3.
3. Make sure that the top of the unit is level.
INSULATION
1. The insulation design and materials should be complying with local and national codes and regulations.
2. Chilled water pipes and all parts on the pipes should be insulated.
3. It is also necessary to insulate the air duct.

Fig. 1 OBSTACLE OBSTACLE

B A
≥400mm ≥200mm

DRAIN PIPE
The suggested slope of the CEILLING
drain pipe is at least 1:50

Fig. 2 WITH AND WITHOUT PLENUM FORM:


NOTE:
Dimension M and N was
determined by air duct design, air
N A
duct should be fire-proof, refer to
concerned country national and
L
local regulations.
≥300mm
WATER OUTLET

Circulatory air pressure drop should


be approximately equal to the WATER INLET
M

External Static Pressure.


CEILING ACCESS PANEL
WITH AIR RETRUN
CEILLING

DISCHANGE AIR RETRUN AIR

2
Fig.3 DETAIL A:

EXPANSION SCREW

NUT
HANGING ROD

FAN COIL UNIT


FLAT WASHER

Detail A

AIR DUCT CONNECTION

1. Circulatory air pressure drop should be within External Static Pressure.


2. Galvanized steel air ducts are suitable.
3. Make sure there is no leak of air.
4. Air duct should be fire-proof, refer to concerned country national and local regulations.

PIPE CONNECTION

1. Using suitable fittings as water pipe connections with reference to the outline and dimensions.
2. The water inlet is on the bottom while outlet on top.
3. The connection must be concealed with rubberized fabric to avoid leakage.
4. Drain pipe can be PVC or steel.
5. Tightening torque should not be too high when connecting water pipes, in order to avoid brass
deformation or water-leakage by torsion split.
6. The suggested slope of the drain pipe is at least 1:50.

WIRING

1. Wiring connection must be done according to the wiring diagram on the unit.
2. The unit must be GROUNDED well.
3. An appropriate strain relief device must be used to attach the power wires to the terminal box.
4. A 7/8” hole is designed on the terminal box for field installation of the strain relief device.
5. Field wiring must be complied with the national security regulations.
6. A main switch or other means for disconnection, having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with the relevant local and national legislation.

3
SERVICE AND MAINTENANCE

For safety reasons, before carrying out any maintenance or cleaning operation, turn off the unit and cut the
voltage by turning the line switch to OFF.

Maintenance

The maintenance operations for the FWMH air conditioner and hot-air heating units are limited to the periodic
cleaning of the air filter and the heat exchanger, and the checking of the working efficiency of the condensate
discharge.
Only skilled personnel may perform the maintenance.
Pay utmost attention during the maintenance operations: accidentally coming into contact with some of the
metallic parts might cause injuries, therefore use safety work gloves.
Every time the units are started after a long idle period, make sure that air is NOT present in the heat
exchanger.
The motor is maintenance-free since it is equipped with self lubricating bearings.

Cleaning the air filter

Cut voltage to the unit by turning the line switch to OFF.


For cleaning the air filter proceed as follows:
Access the equipment through the inspection panel and remove the air filter by unscrewing the fixing knobs.
Wash the filter with lukewarm water or, for dry powders, with compressed air.
Reassemble the filter after having it dried up.

Cleaning the heat exchanger

It is advisable to check the condition of the heat exchanger before the start of the summer season. Also
check if the fins are not clogged by impurities.
To access the heat exchanger, remove the drain pan and the drain guide. Upon having accessed the heat
exchanger, clean with compressed air or low pressure steam, without damaging the fins of the heat
exchanger.
Before operating it in the summer, check the condensate discharges regularly.

4
TROUBLE SHOOTING

If the unit does not work properly, first check the points reported in the table below before requesting service.
If the problem cannot be solved, contact your dealer or service centre.

Symptom 1: The unit does not run at all

POSSIBLE CAUSES CORRECTIVE ACTION


Power failure Restore power
The automatic circuit breaker tripped Contact service centre
The switch is on Off position Turn On the unit, select On

Symptom 2: Poor cooling or heating performance

POSSIBLE CAUSES CORRECTIVE ACTION


Dirty or clogged air filter Clean the air filter
Obstacle near the air inlet or outlet Remove the obstacle
Air inside the heat exchanger Contact the installer
Doors and windows are open Close doors and windows
The unit is running at low speed Select medium or high fan speed

Symptom 3: The unit leaks

POSSIBLE CAUSES CORRECTIVE ACTION


The unit is not installed with the correct Contact the installer
inclination
The condensate discharge is clogged Contact the installer

5
OUTLINES AND DIMENSIONS

6
While utmost care is taken in ensuring that all details in the publication are correct at the time of
going to press, we are constantly striving for improvement and therefore reserve the right to alter
model specifications and equipment without notice. Details of specifications and equipment are
also subject to change to suit local conditions and requirements and not all models are available
in every market

You might also like