SFP-2402(E)
2-Zone Fire Alarm Control Panel
General
The Notifier SFP-2402 and SFP-2402E Fire Alarm Control Pan-
els (FACPs) bring the latest in microprocessor technology to
conventional fire controls. The SFP-2402 is compatible with the
i³™ smoke detectors from System Sensor with drift compensa-
tion, maintenance alert, and freeze warning. Automatic synchro-
nization of audio/visual devices with three selections for
manufacturer protocol. The Notification Appliance Circuit (NAC)
protocol can silence audible devices while strobes continue to
flash, using a single pair of wires.
The SFP-2402 is compatible with conventional input devices
such as two- and four-wire smoke detectors, pull stations, water-
flow devices, tamper switches and other normally-open contact
devices. Refer to the Notifier Device Compatibility Document PN
15378 for a complete list of compatible devices.
Note: Unless indicated otherwise, the term “SFP-2402” refers to
both SFP-2402 and SFP-2402E models.
Features
• Two Style B (Class B) Initiating Device Circuits (IDCs).
6876cov.jpg
• One Style Y (Class B) NAC.
• 24 VDC.
• i³™ Technology features:
– Drift compensation automatically adjusts detector sensitiv-
ity and increases resistance to false alarms caused by dust
– Temporal or Steady signal
accumulation. – Silenceable or Nonsilenceable
– Maintenance Alert LEDs (per zone) warn of excessive dirt • Silent or audible Walk Test operation mode commanded from
accumulation, preventing false alarms (meets NFPA 72 the front keypad, with automatic return-to-normal after one
requirements). hour of inactivity.
– Detector sensitivity is automatically measured by the • Each zone may be programmed for supervisory or fire; each
detector, which automatically adjusts its sensitivity back to zone has separate red and yellow LEDs.
the factory settings when it becomes more sensitive due to • Disable switches provided for each zone.
contaminants settling in the chamber. • Form-C Alarm and Trouble relays.
– Wireless handheld sensitivity meter eliminates the need for • 3.0 amps total usable current.
voltmeters, magnets, and a physical connection to the
detector. The reader displays sensitivity in terms of percent • Piezo sounder for alarm, trouble, supervisory and mainte-
per foot obscuration and provides text status indication. nance.
– Supervisory LED (per zone) provides warning if a detector • Control buttons:
senses temperature approaching freezing. – ACK (Acknowledge)
– Special test protocol and LED indication allows quick test of – Alarm Silence
all detectors without need for a ladder. – Reset
• NAC synchronization features:
– Walk Test
– Synchronization of standard ANSI audible signals as
– Zone Enable/Disable (one per zone)
required by NFPA 72.
• LED indicators:
– Synchronization of ADA compliant strobes per NFPA 72.
– Selectable for System Sensor, Wheelock, and Gentex – Fire Alarm (one per zone)
protocols. – Supervisory (one per zone)
– Selective Silence for manual silence of horns while – Trouble (one per zone)
strobes continue to flash on the same NAC. – Maintenance (one per zone)
– Alarm verification selectable for each zone. – AC Power
– Disable switches provided per zone. – NAC Disable
• NAC programmable for: – Zone Disable
– Silence Inhibit – NAC Fault
– Auto Silence – System Trouble
– Strobe Synchronization – Power Trouble
– Selective Silence (horn-strobe mute) – Walk Test