Interface For Use in Bacnet Commissioning Manual: Model Name: Dms502B51
Interface For Use in Bacnet Commissioning Manual: Model Name: Dms502B51
Contents Page
[BACnet Object System Diagram of Interface for use in BACnet] -----------------------5
[Specifications of Interface for use in BACnet] ---------------------------------------------6, 7
[Q & A] ---------------------------------------------------------------------------------------------54-59
Ex. 1: Connect to the central control panel via BACnet and send the accumulated power data.
Necessary software: SetupBACnet, English.dll, Necessary manual: CB06A069
Necessary software: SetupPPD, Necessary manual: CB06A070
Ex. 2: Update to the software which supports BTL and connect to central monitoring panel with BACnet.
Necessary software: SetupBACnet, English.dll; Necessary manual: CB06A069
Necessary software: bipsFtpSend.exe, EnglishFtpSend.dll, exe.bin.gz, ftpsend.bat; Necessary
manual: CB07A031
10/100BASE-T
Straight cable DIII -NET1
100BASE-TX Up to 64 indoor unit groups
HUB (1-00 - 4-15)
RS232C-1
DIII –NET2
Up to 64 indoor unit groups
(1-00 - 4-15)
DIII –NET3
(You can connect the trial operation PC in one of the two ways. You can use either method.): Refer to P.23 for the details.
* 1: The following conditions must be satisfied when using the 100BASE-TX straight cable:
● The 100BASE-TX straight cable (LAN straight cable) should be used. (This type of cable is sold at a common electrical store.)
● One free port should be reserved with the hub (procured locally) shown above. Also, an IP address which can be temporarily used
at the on-site test operation should be provided (ask the sales division or site).
● When only configuring the Interface for use in BACnet, you can connect the 100BASE-TX cross cable (LAN cross cable) directly to
the Interface for use in BACnet, rather than connecting the straight cable to the hub.
● You should be able to change the IP address of the trial operation PC and return to the original address after the test (refer to
P.25 for the procedure).
*: Using the 100BASE-TX straight cable for the trial operation ensures faster communication than using RS232C and allows quicker
settings.
*2: When connecting the trial operation PC to the Interface for use in BACnet using the RS232C cross cable, you must configure
the dial-up adapter and modem in advance. Refer to P.12 through P.21 for the procedure.
1-2. Communication cable specifications required for trial operation(communication cable to connect the Interface for use in
BACnet and trial operation PC) RS232C communication cable : Cross cable with 9 pin (female) - 9 pin (female)
1-3. Checking the version of the trial operation program installed on the PC
The trial operation program version 6.3.4.0 or higher is required for trial operation of the Interface for use in BACnet
(DMS502B51).
Check the version of the trial operation program installed on the PC before visiting the site in the following procedure.
(How to check the trial operation program version)
Right-click the trial operation program of Interface for use in BACnet [1] (program name: SetupBACnet),
and choose "Property (R)".
Click the "Version" tab [2] and confirm that the version number shown in the "File Version" field [3]
is 6.3.4.0 or higher.
Any trial operation programs with lower version than the version shown above cannot configure
Interface for use in BACnet which is in conformity with BTL. Obtain Version 6.3.4.0 or higher and install
it on the PC before the trial operation.
2
You must initialize the Interface for use in BACnet before the trial operation. Therefore, you need to gather
the object information listed below ([1] - [6]) before visiting the site. Obtain this information from the sales
person of Daikin or distributor for the object.
(Fill in the information proprietary to the object in the blank space of [1] - [6].)
[1] Confirmation of communication method between the Interface for use in BACnet and the central control panel
Communication method between the Interface for use in BACnet and the central control panel
No. Communication method Communication method for the object (circle one of them)
1 BACnet/IP communication
[5] Items monitored/controlled from the central control panel for air conditioners
Monitor/control
Member from the central
number Object type (for control panel for
Monitor/control item
(for BACnet) e ac h air
BACnet) c o n dit io n e r
(yes/no)
1 ON/OFF (setting) BO
2 ON/OFF (status) BI
3 Alarm Sign BI
4 Error Code MI
5 Operation M ode (setting) MO
6 Operation M ode (status) MI
7 Airflow Rate (setting) MO
8 Airflow Rate (status) MI
9 M easured Room Temperature AI
10 Set Room Temperature AV
11 Filter Limit Sign BI
12 Filter Limit Sign Reset BV
13 Remote Control Operation (ON/OFF) BV
14 Remote Control Operation (Operation M ode) BV
16 Remote Control Operation (Set Temperature) BV
(*1)17 Remote Control Operation (Sub Group Address Control Rejection) BV
(*2)18 Accumulated gas Accumulator
19 Accumulated power Accumulator
20 Communication Status BI
(*1)21 System Forced OFF BV
22 Air Direction (setting) AV
23 Air Direction (status) AI
24 Forced Thermostat OFF (setting) BO
25 Forced Thermostat OFF (status) BI
26 Energy Efficiency Command (setting) BO
27 Energy Efficiency Command (status) BI
28 Thermostat Status BI
29 Compressor Status BI
30 Indoor Fan Status BI
31 Heater Operation Status BI
32 Ventilation mode(setting) MO
33 Ventilation mode (status) MI
(*3)34 Ventilation amount (setting) MO
(*3)35 Ventilation amount (status) MI
*1: Instructed per D III-NET communication port.
*2 : Member number 18 is for Japanese market only.
*3 :The fresh up (Auto) may not be available for monitor/control operation depending on
the specifications of the central monitoring panel.
● Setting BACnet Broadcast
[Note]
BACnet allows two types of broadcasts; global broadcast and local broadcast (Note that they are different from
UDP/IP's broadcast). With global broadcast, messages broadcasted are sent beyond the BACnet router to other
BACnet networks. With local broadcast, messages broadcasted are not sent beyond the BACnet router but only reach
nodes within the same BACnet network. (Details of the global broadcast and local broadcast are described in Section
6.3.2 of the ANSI/ASHRAE Standard 135-2004.)
If a slow BACnet network (e.g., BACnet connected via RS232C) is connected via the BACnet router to the BACnet/IP
network where the station exists, and unregistered COVs which are sent from the station each time an air conditioner
changes its status are also propagated over the slower network, these COVs will occupy the communication line of the
slower network. Therefore, COVs need to be locally broadcasted in such a network configuration.
Note that the Who-Is/I-Am services are globally broadcasted even for BACnet/IP.
Daikin Industries, Ltd. CB06A069E
CB06A069E 11/59
IP address Ex.192.168.0.2
Subnet mask Ex.255.255.255.0
Default gateway address Ex.192.168.0.100
One of the following invalid addresses is used as the default gateway address:
An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
A loop-back address (127.0.0.0 - 127.255.255.255)
An invalid address is used for the subnet mask (outside the range 128.0.0.0 - 255.255.255.255, hexadecimal "1" portion
contain non-sequential value or blank).
[Example]
255.255.255.244 -> NG (hexadecimal "1" portion contain non-sequential value.)
1-4. Click the Add button [1]. The display changes to the dialog shown at the below right.
Check the "Don’t detect my modem ; I Will select it from a list." option [2] and click the Next button [3].
1 3
1-5. Click the Have Disk… button [4]. The display changes to the dialog shown on the next page.
1-10. Choose the COM port [10] to connect the RS232C cable to, and click the Next > button [11].
10
11
12
13
1-13. "Generic NULL Modem v2" is added to [14] and modem set up completes.
Next, follow the instructions on the following pages to set up the dial-up adapter.
14
2-7. Enter a name to identify this connection [5]. This example uses "Interface for use in BACnet".
5
Interface for use in BACnet
2-10. When the dialog shown below opens, click the Properties button [9].
2-11. If multiple choices are shown in [10], select "Generic NULL Modem v2".
Then click the Configure button [11].
10
11
12
13
Since the IP
address of Interface
Start the trial operation program. for use in BACnet
[5] (On the trial operation PC, double-click SetupBACnet.) has been changed as
P41, 42 Enter the IP address. required at the site in
[3]-5, the trial
operation PC's IP
address should also
Select the Operation Status menu and check the following:
Operation status of all the air conditioners with the D III-NET concentrated addresses can be
be changed to the IP
address temporarily
[6] properly monitored.
All the D III-NET concentrated devices used with the Interface for use in BACnet can be used for the trial
P43 properly monitored. service operation
([6]-2 on P.11).
(*) You cannot
connect to the
[7] Register Management Point types .
Interface for use in
P44 Check that the management point types have been registered correctly. BACnet unless the IP
address is changed.
*2 RS232C
Ethernet -1
100BASE-TX
Cross cable 100BASE-TX
Ethernet
100BASE-TX HUB (*Procured locally)
*1
Ethernet
100BASE-TX
Ethernet 100BASE-TX straight cable
*: Check the port on the hub to connect
the cable at the site.
* If the hub is faulty or cannot be procured Ethernet
locally, use the Ethernet 100BASE-TX 100BASE-TX
cross cable to directly connect the trial straight cable
operation PC and 100BASE-TX port of (procured
Interface for use in BACnet. locally)
(You can connect the trial operation PC in one of the three ways. You can use any method.):
* 1: Use the 100BASE-TX straight cable. The following conditions must be satisfied when using the 100BASE-TX
straight cable:
● The 100BASE-TX straight cable (LAN straight cable) should be used. (This type of cable is sold at a common
electricalstore.) Also prepare the 100BASE-TX cross cable (LAN cross cable) which can be used when the hub is
faulty.
● One free port should be reserved with the hub (procured locally) shown above. Also, an IP address which can be
temporarily used at the on-site test should be provided (ask the sales division or site).
● You should be able to change the IP address of the trial operation PC and return to the original address after the test
(refer to the next for the procedure).
(Note) If you are executing trial operations for multiple Interface for use in BACnet using the same object, be
sure to keep the Interface for use in BACnet powered off or the 100BASE-TX cable disconnected until the
whole procedure of [4] in this manual has been completed.
(All Interface for use in BACnet have the identical IP address set at the factory. Therefore, if you connect them
to the trial operation PC via the hub using 100BASE-TX, the trial operation may not be executed properly
since their default addresses are the same.)
*: Using the 100BASE-TX straight cable for the trial operation ensures faster communication than using RS232C and
allows quicker settings.
*: If the IP address of Interface for use in BACnet has been changed from the trial operation PC and the new
address is unknown, you can only connect the Interface for use in BACnet and PC using the RS232C cross
cable (method *3).
In this case, be sure to set up the trial operation PC's modem as instructed in "3. Setting the Trial Operation
PC Modem" of [Before Visiting the Site]. (You can change connection to the 100BASE-TX cable once you find
the IP address of Interface for use in BACnet with RS232C cable connection.)
Dialog box 1. Local Area Connection Properties Dialog box 2. Internet Protocol (TCP/IP) Properties
3
4
1 5
2
Do not
change
these fields.
7 6
[Table 1: Trial Operation PC's Current Address]
[3] IP address Ex.150.35.20.60
2-1. Enter the information above in "IP address" [3], "subnet mask" [4], and "default gateway" [5] in the dialog box 2
of Step 1-3, and press the OK button [6]. The dialog box 1 reappears. Click the OK or Cancel button [7].
3. Return the IP address to the original address after the trial operation.
(Be sure to return the trial operation PC's IP address to the original address.)
3-1. Return the trial operation PC's IP address to the original address recorded in Step 1-3, as instructed in Steps
2-1 and 2-2.
[When connecting the trial operation PC and Interface for use in BACnet via 100BASE-TX]
1. Before starting the trial operation program, check if the local time zone is correctly selected with the PC's "Date and
Time Property". If it is not, the correct time cannot be set.
On the dialog box 1, double-click the trial operation program (SetupBACnet) [1].
The dialog box 2 opens to enter the IP address.
2. Enter the IP address as instructed below in the IP Address field [2].
● When the IP address of Interface for use in BACnet has not been changed from the factory setting
→ Enter "192.168.0.1".
* In this case, change the trial operation PC's IP address to "192.168.0.2" (refer to P.24 for the procedure).
● When the IP address of Interface for use in BACnet has been changed from the factory setting at the site
→ Enter the IP address as instructed in [6]-1 on P.11.
* In this case, change the trial operation PC's IP address to the IP address given in [6] on P.11 (refer to P.24 for
the procedure).
3. Click the OK button [3]. The dialog box 3 at the bottom of this page opens.
2 3
HUB
When connecting the Interface for use in BACnet and the trial operation
PC via Ethernet, they cannot communicate with each other unless the
following IP address settings are used.
IP address of Interface for IP address set for the IP address temporarily used
use in BACnet has been Interface for use in for the trial service
changed at the site BACnet in [6]-1 on P.11. operation in [6]-2 on P.11.
[When connecting the trial operation PC and Interface for use in BACnet via RS232C]
1. Set up the modem as instructed in "3. Setting the Trial Operation PC Modem" in [Before Visiting the Site].
2. Connect the trial operation PC and RS232C-1 port of Interface for use in BACnet with the RS232C cross cable
(9-pin-9-pin).
4. When the dialog box below opens, click the Dial button [1]. The icon shown below right will appear on the task bar
(bottom right of the screen).
5. Before starting the trial operation program, check if the local time zone is correctly selected with the PC's "Date and
Time Property". If it is not, the correct time cannot be set.
On the dialog box 1, double-click the trial operation program (SetupBACnet) [2]. The IP address entering dialog box
opens.
6. Change the IP address to "192.168.3.1" and click the OK button [3].
The dialog box shown at the bottom of this page opens.
2
Dialog box 3. Malfunction History 3
7
5
6
Daikin Industries, Ltd. CB06A069E
CB06A069E 28/59
3
4
Dialog box 2. BACnet Port No. Setting Dialog box 3. Reset Request
5 7
4
Dialog box 2. BACnet Device Setting Dialog box 3. Reset Request
7
5
6
Daikin Industries, Ltd. CB06A069E
CB06A069E 30/59
4. Set the COV output. (When using the BACnet/IP protocol, this setting is not required because the central control
panel communicates with each air conditioner for this setting.)
4-1. Click the BACnet button [1].
4-2. Click the COV button [2].
4-3. Select the COV for each air conditioner or COV for each air conditioner block in [3]. (Block setting may not be
necessary for some cases.)
4-4. The current COV output setting of Interface for use in BACnet is shown in [4]. Use the scroll bar [5] to see the entire list.
4-5. If the current COV output setting of Interface for use in BACnet needs to be changed, click the Modify button [6].
(If modification is not required, proceed to the next page.)
4-6. The dialog box 2 "BACnet COV Setting" opens. Check the box [7] of each item to output COV.
Use the scroll bar [8] to set (or confirm) all the items, click the Set button [9].
4-7. To save the COV output setting data in the trial operation PC, click the Text Save button [10] (this step is optional).
The dialog box "Save As" opens. Enter a unique name to identify the setting data.
6 4
10
Dialog box 2. BACnet COV Setting
7
9
Daikin Industries, Ltd. CB06A069E
CB06A069E 31/59
12
11
13
14
Select the BACnet menu and configure One of the following invalid addresses is used as the IP address:
the following: An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
A loop-back address (127.0.0.0 - 127.255.255.255)
1. Select Protocol An address of which the host portion (hexadecimal "0" portion of subnet mask) contains all "0"s or
2. Set Port Number "1"s
3. Instance Number An address of which the network portion (hexadecimal "1" portion of subnet mask) contains all "0"s
or "1"s
4. COV Output Yes/No
[3] Under Special Setting menu …
[Example]
244.1.1.1 -> NG (outside the range of Class A - C addresses)
127.0.0.1 -> NG (Loop-back address)
5. Set IP address IP: 198.168.1.0/Subnet: 255.255.255.0 -> NG (host portion contains all "0"s.)
6. Set Locale IP: 192.168.0.1/Subnet: 192.0.0.0 -> NG (network portion contains all "1"s.)
7. Set Current Time
One of the following invalid addresses is used as the default gateway address:
8. Register Management Point types An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
A loop-back address (127.0.0.0 - 127.255.255.255)
An invalid address is used for the subnet mask (outside the range 128.0.0.0 - 255.255.255.255,
hexadecimal "1" portion contain non-sequential value or blank).
[Example]
255.255.255.244 -> NG (hexadecimal "1" portion contain non-sequential value.)
5. Set the IP address of Interface for use in BACnet, subnet mask, and default gateway address.
Refer to [6] "IPv4 address" in "2. Obtaining Object Information" of this manual.
This section shows the steps to set this IP address data to the Interface for use in BACnet.
5-1. Click the Special Setting button [1].
5-2. Click the IP Address button [2].
5-3. The current IP address of Interface for use in BACnet, subnet mask, and default gateway address are shown in [3].
5-4. If the current IP address of Interface for use in BACnet, subnet mask, and default gateway address are different from the desired
settings, click the Modify button [4].
(If modification is not required, proceed to the next page.)
5-5. The dialog box 2 "IP Address Setting" opens. Enter desired values from the PC's keyboard into [5], then click the Set button [6].
5-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.
3
4
5 7
6
Daikin Industries, Ltd. CB06A069E
CB06A069E 33/59
Acceptable IPv6 address is as follows:
Select the BACnet menu and configure [Address]
the following: XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:XXXX
1. Select Protocol XXXX::XXXX
2. Set Port Number XXXX::
3. Instance Number ::ddd.ddd.ddd.ddd
4. COV Output Yes/No XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:ddd.ddd.ddd.ddd
[3] Under Special Setting menu … XXXX::XXXX:ddd.ddd.ddd.ddd
5. Set IP address XXXX::ddd.ddd.ddd.ddd
6. Set Locale ::XXXX:ddd.ddd.ddd.ddd
7. Set Current Time ::XXXX
8. Register Management Point types * X: Hexadecimal
d: Decimal
* Allowed characters: 0 - 9, A - F (a - f),
colon (:), and period (.)
5. Set the IPv6 self IP address of Interface for use in BACnet and multicast address.
If there is no device performing IPv6 communication on the same network, this
setting is not required.
5-7. Click the Special Setting button [1].
5-8. Click the IP Address button [2].
5-9. The current IPv6 self address of Interface for use in BACnet, multicast address are shown in [3].
5-10. If the current IPv6 self address and multicast address are different from the desired settings, click the Modify button [4].
(If modification is not required, proceed to the next page.)
5-11. The dialog box 2 "IPv6 Address Setting" opens. Enter desired values from the PC's keyboard into [5], then click the Set
button [6].
5-12. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK
button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.
Dialog box 1. Special Setting 1
3
4
5 7
6
Daikin Industries, Ltd. CB06A069E
CB06A069E 34/59
5
Dialog box 2. Locale
Dialog box 3. Reset Request
6
7
9
8
Daikin Industries, Ltd. CB06A069E
CB06A069E 35/59
4
Dialog box 2. Clock Setting
5 5
8. Update the management point type for each equipment connected to the Interface for use in BACnet.
* It takes a while for the Interface for use in BACnet to detect connected equipments.
After connecting a equipments, wait for a few minutes, and then click the Refresh button.
* Immediately after installing the Interface for use in BACnet (at factory default), a connected device will be
listed in the dialog box if it is "VENTIAIRE(Heat Reclaim Ventilator)," but it will not be listed in the dialog box
for other device types (VRV System, SkyAir, etc.)
* When an equipment is replaced with the same type of equipment, in such cases as "Indoor" to "Indoor" or
"VENTIAIRE (Heat Reclaim Ventilator) " to "VENTIAIRE (Heat Reclaim Ventilator)," the substituted equipment
will not be listed in the dialog box.
8-5. After the list in the dialog box displays, click the Update button [5].
8-6. The dialog box 2 "Check" opens. Click the Yes button [6].
8-7. The dialog box 3 "SetupBACnet" opens. Click the OK button [7].
Perform power resetting upon completion of the above setting procedure.
* Note that the updated setting is enabled only after power resetting is performed.
6
Dialog box 3. SetupBACnet
3
5
4 7
When Situation Change in equipment connected to Interface for use in BACnet Update required or Management point
not types
You can reset the Interface for use in BACnet in two methods as described in this page and next page. You
can use either method.
1-1. To make the new settings effective, reset the Interface for use in BACnet from the trial operation PC.
1-1-1. Click the Special Setting button [1].
1-1-2. Click the Reboot button [2].
1-1-3. Click the Reboot button [3] at the bottom right of the screen. The dialog box 2 "Warning" opens.
1-1-4. Click the OK button [4]. The dialog box 3 "Warning" opens.
1-1-5. Click the OK button [5]. The dialog box 4 "Reboot" opens.
1-1-6. The Interface for use in BACnet will reboot and the dialog box 5 opens to indicate termination of the trial
operation program.
1-1-7. Click the OK button [6] to terminate the trial operation program.
1
2
4
Dialog box 3. Warning
5
3
Dialog box 4. Reboot Dialog box 5. Exiting from Program
You can reset the Interface for use in BACnet in two methods as described in the previous page and this page. You can use
either method.
1-2. To make the new settings effective, reset the Interface for use in BACnet by powering it Off then On.
1-2-1. Terminate the trial operation program. Click the Exit button [1]. The dialog box 2 opens to confirm the termination.
1-2-2. Click the OK button [2] to terminate the trial operation program.
1-2-3. When you are connecting the PC and the Interface for use in BACnet via RS232C, double-click the icon at
the bottom right of the PC screen (i.e., on the task bar).
1-2-4. Power Off then On the Interface for use in BACnet to reset it. The Power switch is located at [4] of the Photo 1 below. Turn
this switch
Off, then turn it On again after one second.
Dialog box 1. Trial operation program Dialog box 2. Termination confirmation
Dialog box 3. Interface for use in BACnet Status Photo 1. Outer view of Master Station III
4
3
3. When using the 100BASE-TX cable to connect the Interface for use in BACnet and trial operation
PC, change the PC's IP address.
*: This procedure is not necessary when connecting them via RS232C.
(The screens shown below are Windows XP's examples, and the actual screens differ depending on the OS used.)
3-1. Double-click the Network Connections icon on the Control Panel. Click the Local Area Connection and right-click
to choose "Properties". The dialog box 1 below opens.
3-2. Select "Internet Protocol (TCP/IP)" [1] and click the Properties button [2]. The dialog box 2 opens. This dialog
box shows the trial operation PC's current IP address [3], subnet mask [4], and default gateway address [5].
3-3. Refer to the table in "[6]-2. IP address temporarily used for the trial service operation" of “2. Obtaining
Object Information”, and enter the information above in "IP address" [3], "subnet mask" [4], and
"default gateway" [5], then click the OK button [6].
The dialog box 1 reappears. Click the OK button [7].
3-4. Reboot the PC as required by the PC.
(Reboot may not be necessary depending on the Windows version. Reboot the PC only when requested.)
Dialog box 1. Local Area Connection Properties Dialog box 2. Internet Protocol (TCP/IP) Properties
3
4
1 5
2
Do not change
these fields.
7 6
(Note) Be sure to return the IP address to the original address after the trial operation.
Return the trial operation PC's address to the original address recorded in Table 1 on P.24, as
directed in Steps 3-1 through 3-4 above.
[When connecting the trial operation PC and Interface for use in BACnet via 100BASE-TX]
1. Double-click the trial operation program (SetupBACnet) icon [1] on the dialog box 1. Dialog box 2 to enter the IP
address opens.
2. Enter the IP address in [2] according to the information in [6]-1 “IP address for Interface for use in BACnet" of "2.
Obtaining
Object Information".
* The IP address of the trial operation PC needs to be changed to the address shown in [6]-2 of "2. Obtaining
Object Information".
3. Click the OK button [3]. The dialog box 3 at the bottom of this page opens.
2 3
HUB
When connecting the Interface for use in BACnet and the trial operation
PC via Ethernet, they cannot communicate with each other unless the
following IP address settings are used.
IP address of Interface for IP address set for the IP address temporarily used
use in BACnet has been Interface for use in for the trial service
changed at the site BACnet in [6]-1 on P.11. operation in [6]-2 on P.11.
[When connecting the trial operation PC and Interface for use in BACnet via RS232C]
1. Set up the modem as instructed in "3. Setting the Trial Operation PC Modem" in [Before Visiting the Site].
2. Connect the trial operation PC and RS232C-1 port of Interface for use in BACnet with the RS232C cross cable
(9-pin-9-pin).
4. When the dialog box below opens, click the Dial button [1]. The icon shown below right will appear on the task bar
(bottom right of the screen).
2
Dialog box 3. Malfunction History 3
Check that the D III-NET communication cabling and address assignment for the air conditioners are correctly done.
1. Check that the operation status of the air conditioners and other concentrated devices connected can be properly
monitored.
1-1. Click the Operating State button [1]. Select the D III NET communication port of the Interface for use in BACnet to check
communication in
[2]. The dialog box 1 "Operating State" opens.
1-2. Operation status of the air conditioners and concentrated devices connected to the port selected in Step 1-2 is shown in [3].
Check if other connected concentrated devices can be monitored in this dialog box.
1-3. Start and stop each air conditioner to check if the cabling and address assignment for it are correctly done.
This step needs two persons. One person operates the trial operation PC, while the other person checks each indoor unit to
check cabling and address assignment. Start and stop each indoor unit to check whether or not it is correctly instructed and/or
monitored.
You can use one of the following two methods:
1. Use the remote controller to start/stop the indoor unit and check if the status is reflected on the trial operation PC.
Check [4] in the screen below while operating the indoor unit to start/stop with the remote controller.
2. If the remote controller is not provided, start/stop the indoor unit from the trial operation PC and check if the air conditioner
actually starts/stops by checking the fan rotation of the indoor unit.
Select the indoor unit to check in [5] and click the Aircon Control button [6]. The dialog box 2 "Air Conditioner Control" opens.
Select "ON" or "OFF" in [7] and select "No Change" in [8]. Finally, click the Set button [9].
Check if the indoor unit actually starts or stops.
1-4. Repeat Steps 1-1 through 1-3 to check all the air conditioners.
Dialog box 1. Operating State
5
4
Check that the Management point type registered correctly for each connected device.
*Refer to the page 36,37 for necessary cases of when to register the Management point type for connected equipments.
1-2. The operating state of each air conditioner connected to the port selected in 1-1 is shown in [4].
Check [5] Management point types to make sure that the management point types are registered
correctly for each connected air conditioner.
Check if each air conditioner operates as instructed from the central control panel.
1. Check if the air conditioner can be properly controlled from the central control panel.
1-1. Check the items which are designated by the manufacturer to be monitored/controlled from the central control panel in the table of
[5] Items monitored/controlled from the central control panel for air conditioners in "2. Obtaining Object Information". Be sure to
keep records of the items checked, so that which items were checked (for the reference in case if a trouble
occurs after delivery).
● Check if the air conditioner operates as instructed from the central control panel in one of the following methods:
1. Check with the trial operation PC of Interface for use in BACnet (see below for the procedure).
2. Check with the air conditioner's remote controller.
3. Check with another concentrated device (e.g., central remote controller) (when other concentrated devices are used together)
The procedure to check the operation status of the air conditioner using the trial operation PC of Interface for use in BACnet is
described below.
Access to the Operating State dialog box for the air conditioners as instructed on the previous page.
You can toggle the display between the simple and detailed formats by clicking the Simple button [1] or Detail button [2].
Each format lists the following items.
Check if operation status of the air conditioner can be properly monitored from the central control panel.
1. Check if operation status of the air conditioner can be properly monitored from the central control panel.
1-1. Check the items which are designated by the manufacturer to be monitored/controlled from the central control panel in the table of
[5] Items monitored/controlled from the central control panel for air conditioners in "2. Obtaining Object Information". Be sure to
keep records of the items checked, so that which items were checked (for the reference in case if a trouble
occurs after delivery).
● You need to change the operation status of the air conditioner for this check. Change the operation status of the air conditioner
in one of the following methods:
1. Change with the trial operation PC of Interface for use in BACnet (see below for the procedure).
2. Change with the air conditioner's remote controller.
3. Change with another concentrated device (e.g., central remote controller) (when other concentrated devices are used
together)
4. The only way to check failure notification is to make an air conditioner failure to actually happen. Therefore, you need to do
some work such as removing the sensor from the outdoor unit.
*: Be sure to restore the air conditioner to the original status. Note that you cannot check the filter and element signs.
The following shows how to change operation status of the air conditioner from the trial operation PC of Interface for use in BACnet.
1-1-1. Select the indoor unit to check in [1] and click the Aircon Control button [2]. The dialog box 2 "Air Conditioner Control" opens.
1-1-2. Select items to change in [3] and click the Set button [5].
(Select "No Change" for items you do not want to change in [3]. You can select multiple items at the same time.)
To apply the same change to multiple air conditioners, check them in [4]. The items shown right below can be changed from the
trial operation PC.
3
5
F.Dev box
[To open this dialog box]
BACnet→F.Dev
[The factory setting]
・Registration as a Foreign:Disabled
[About Foreign Device]
If there is no BBMD(BACnet/IP Broadcast Management
Device) on the same subnet as Interface for use in BACnet,
it cannot receive broadcast messages from other subnets.
So the Interface for use in BACnet need to be set to behave
as a “Foreign Device (see BACnet Standards Annex-J ).”
By operating as a Foreign Device, it can receive broadcast
messages sent from other IP subnets via BBMD.
(a) Register to BBMD as a Foreign Device (at startup of Master Station, and thereafter at a regular interval)
Router IP Subnet1
BBMD Device
① Registration (Register-Foreign-Device)
IP Subnet2
Router
Foreign Device(Interface for use in BACnet)
Router IP Subnet1
BBMD Device
IP Subnet2
Router
Foreign Device(Interface for use in BACnet)
(c) Send its own broadcast messages to other devices on other subnets via BBMD
⑤ Broadcasting
Router IP Subnet1
In the case of Foreign Device, Distribute-Broadcast-To-Network is
sent to BBMD instead of Original-Broadcast-NPDU which is used
BBMD Device normally to send broadcast messages.
④ Broadcast message distribution request
(Distribute-Broadcast-To-Network)
IP Subnet2
Router
Foreign Device(Interface for use in BACnet)
Pulse Rate
[To open this dialog box]
Select Special Setting → Plus Rate.
[The factory setting]
The settings shown to the left.
[About pulse rate]
The Interface for use in BACnet can proportionally
distribute power to the air conditioners from the
central control panel, by performing proportional
power distribution in the trial operation.
This dialog box is used to change the pulse rate of
the power meter connected to each power pulse
input terminal of the Interface for use in BACnet.
*: Body Di: power pulse input of Interface for use in
BACnet
Extension Di: Power pulse input 1 - 12 of the
optional Di board
Malfunction Error画面
[To open this dialog box]
Select Special Setting → Malfunction Error
[The factory setting]
Error type of Notification:Error OR Warning
[About Malfunction Error]
This function is a setting up function of the
"Warning" signal send to the "Central Monitoring
Device " due to the change of the specification of
the handling of "Warning" of the air-conditioning
unit. It becomes possible to notify the " Central
Monitoring Device" of the crisis situation of the
system that ends to "Error" by setting this item to
"Error" +"Warning" beforehand.
Set it to "Error" when you exchange Interface for
use in BACnet in use.
[Q & A]
Question Answer
I cannot control or monitor air 1. Is the Interface for use in BACnet powered On?
2. Is the Ethernet cable connected to the Interface for use in BACnet and the central
conditioners from the central control control panel? (Refer to P.5.)
panel at all. What are the possible 3. Is the hub powered On?
causes? 4. Are the IP address, subnet mask, and default gateway address correct?
5. Is the device instance number of Interface for use in BACnet correct? (Refer to
P.29)
6. Is the air conditioner's concentrated address correct? (Refer to P.43)
7. Has the point list of air conditioners been supplied to the central control panel
manufacturer?
(If not, contact the sales person for the object.)
*: When using BACnet communication to connect to the central control panel,
this point list is used to configure the communication. This list should be
created by the sales division for each object and supplied to the central
control panel manufacturer.
I cannot control or monitor some 1. Has the central control panel manufacturer registered correct air conditioner
items of the air conditioner from the items (from the point list) which cannot be controlled or monitored from the
central control panel?
central control panel. What are the → Ask the central control panel manufacturer.
possible causes? 2. Has the Daikin's sales person listed correct air conditioner items (on the point
list) which cannot be controlled or monitored from the central control panel?
→ Ask the sales person for the object.
3. Are the items in question allowed to be controlled or monitored from the
central control panel?
→ Refer to the Engineering Data for the air conditioner, D-BACS
Engineering data, or other ones.
Status of the air conditioner is not The COV function selectively enables or disables each status items for report to
reported to the central control panel. the central control panel via the Interface for use in BACnet. Check with the
central control panel manufacturer for the current COV settings.
What are the possible causes?
[Q & A]
Question Answer
The Interface for use in BACnet and
trial operation PC cannot be
connected. What are the possible
causes?
1. When using the RS232C cross cable
Has the dial-up modem of the PC been properly set up? (Refer to P.12- 21 for details.)
Is the correct RS232C cable type used? Is it a cross cable?
Is the PC's RS232C communication port functioning?
1
2
[Q & A]
Question Answer
1. Create the point list for the new air conditioner and supply it to the central
control panel manufacturer (by sales division).
I must add an air conditioner after 2. Assign the address to the air conditioner at the site, and register the
management point types and check the connection to the air conditioner from
delivery. What should I do? the trial operation PC of Interface for use in BACnet.
(Refer to P.36, P.37 ,P.43, P44 for details.)
3. Check the connection between the new air conditioner and the central control
panel (Refer to P.45 and P.46 for details.)
4. Make the settings of PPD again.
Notice:Make it only after outputting the current charging data by the building
owner,because the integrated value becomes 0 when setting it again.
I must remove an air conditioner after 1. Inform the central control panel manufacturer of the air conditioner removed
delivery for movement. What should from the point list (by sales division).
I do? 2. Power the Interface for use in BACnet Off then On again to reset it.
3. Make the settings of PPD again.
Notice:Make it only after outputting the current charging data by the building
owner,because the integrated value becomes 0 when setting it again.
[Q & A]
Question Answer
My customer told that an air 1. Is the remote controller used to stop the air conditioner?
conditioner automatically stops. 2. Is another connected concentrated device used to stop the air conditioner?
What are the possible causes? 3. Is the central control panel used to stop the air conditioner?
4. Did power failure occur at the air conditioner location?
→ Unless the indoor unit is configured to restart automatically after power
failure (using the remote controller in the on-site mode), the air
conditioner remains stopped after recovery from power failure.
My customer told that an air 1. Is the remote controller used to start the air conditioner?
conditioner automatically starts. 2. Is another connected concentrated device used to start the air conditioner?
What are the possible causes? 3. Is the central control panel used to start the air conditioner?
My customer told that an air 1. Are the central control panel and Interface for use in BACnet connected
conditioner cannot be controlled from correctly?
2. Is the central control panel functioning?
the central control panel. What are 3. Is the forced stop contact input of the Interface for use in BACnet
the possible causes? activated?
4. Are the air conditioner which cannot be controlled and Interface for use in
BACnet communicated correctly? (Is there any communication error?)
When I connect the previous trial A value and unit of Temperatures displayed on the trial operation(Ver. 6.3.2.0)
will be represented in Celsius.
operation(Ver. 6.3.2.0) to the
software for Interface for use in
(Note)
BACnet main unit in Fahrenheit
version (Ver. 6.33.00), what However, the value of temperatures displayed in "the BACnet history" may not
be shown correctly.
phenomenon happens?
Because the value recorded in Fahrenheit with the software for the main unit
(Ver. 6.33.00) is displayed in the trial operation (Ver. 6.3.2.0), the "value" in
Fahrenheit will be displayed with unit "°C".
For example, the History of changing the set temperature to "70°F" will be
displayed as "70°C".
[Q & A]
Question Answer
1. Investigate the objections thoroughly.
Objections were made that BACnet What phenomenon?
communication does not work. (Ex. Can the air conditioner be monitored or controlled? What is its address?
What should I check for? What model? Who is the central control panel manufacturer? What is
the central control panel model? etc.)
Determine when the communication error occurred.
(Ex. What year, hour, and minute?)
Determine the frequency of the error.
(Ex. Once a month)
Determine the object name and its delivery (test operation) date.
→ If you can troubleshoot the cause and determine the counter measure from
the objections, you need not proceed to the following steps.
2. Check if there was any problem in the trial operation with the check record.
(Refer to P.43 - 46.)
3. Check and save data related to BACnet stored in the Interface for use in
BACnet from the trial operation PC.
3-1. Save the BACnet history data in the trial operation PC.
3-1-1. Connect the trial operation PC and Interface for use in BACnet, and
start the trial operation program. Click the BACnet button [1] to open
the following dialog box.
3-1-2. Click the History button [2] and select 10000 [3], and click the Update
button [4].
3-1-3. Click the Text Save button [5] and enter a name which can easily
identify the data. (This data is used by the quality control ,design
dept ., etc. of the factory to analyze the failure when it cannot be
analyzed at the site.)
5
1
[Q & A]
Question Answer
Objections were made for the 1. Investigate the objections thoroughly.
Interface for use in BACnet from the What phenomenon?
(Ex. Can the air conditioner monitored or controlled? What is its address?
site after delivery. What information What model? Who is the central control panel manufacturer? What is the
or data should I correct? central control panel model? etc.)
Determine when the communication error occurred.
(Ex. What year, month, and day?)
Determine the frequency of the error.
(Ex. Once a month)
Determine the object name and its delivery date.
→ If you can troubleshoot the cause and determine the counter measure from
the objections, you need not proceed to the following steps.
2. Check and save data stored in the Interface for use in BACnet from the trial
operation PC.
2-1. Save the BACnet malfunction history data in the trial operation PC.
2-1-1. Connect the trial operation PC and Interface for use in BACnet, and
start the trial operation program. The following dialog box opens.
2-1-2. This dialog box displays history including air conditioner failures and
power ON/OFF status. Check the history and search for data related
to the objections.
2-1-3. Save the malfunction history data in the trial operation PC.
Click the Text Save button [1] and enter a name which can design
dept.,etc. easily identify the data. (This data is used by the quality
control division etc. of the factory to analyze the failure when it cannot
be analyzed at the site.)
The History Reset button [2] erases the malfunction history data stored
in the Interface for use in BACnet. However, because you usually
need not erase the history, do not click this button.
2-1-4. Check and save (if necessary) detailed malfunction history for each D3-
NET communication port in [3].
(Note 1): The malfunction history contains the latest 40 occurrences for
each category in [3] (main unit and ports 1 through 4).
(Note 2): To save the malfunction history, click the Text Save button [1]
for each category in [3] (main unit and ports 1 through 4).
3