Interface For Use in Bacnet Commissioning Manual: Model Name: Dms502B51

1. This document provides instructions for commissioning the DMS502B51 Interface for use in BACnet. 2. It describes the object system diagram and specifications of the Interface, and provides a work procedure for setting up and testing the Interface including connecting it to a trial operation PC, selecting communication protocols and settings values, and checking that management point types are registered correctly. 3. The document also includes reference information for items that do not need changed from factory settings, and questions and answers regarding commissioning the Interface.

Uploaded by

Lucio Jr Ruiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
544 views59 pages

Interface For Use in Bacnet Commissioning Manual: Model Name: Dms502B51

1. This document provides instructions for commissioning the DMS502B51 Interface for use in BACnet. 2. It describes the object system diagram and specifications of the Interface, and provides a work procedure for setting up and testing the Interface including connecting it to a trial operation PC, selecting communication protocols and settings values, and checking that management point types are registered correctly. 3. The document also includes reference information for items that do not need changed from factory settings, and questions and answers regarding commissioning the Interface.

Uploaded by

Lucio Jr Ruiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 59

CB06A069E 1/59

Interface for use in BACnet


Commissioning Manual
Model name : DMS502B51

Daikin Industries, Ltd. CB06A069E


CB06A069E 2/59

Version Date Revision Histroy Section Approved by Checked by Prepared by

Device K. M atsuura K.Wada S. Hasuike


First 12/26/2006 Newly compiled Engineerin
g Group
K. M atsuura K.Wada S. Hasuike
Device
A 05/11/2007 For BTL Engineerin
g Group

Change product name K. M atsuura K.Wada S. Hasuike


Making of air conditioning unit's control item
Device
high performance.Addition of regarding
B 02/20/2009 Engineerin
"Warning" as "Error", automatic recognition of 3
g Group
levels Air flow rate, and "Dry" setting in
operation mode.
・P.8 Applied OS of service PC is changed
Solution
・P.8 Change of Commissioning tool version
C 06/29/2011
・P.11 Addition of menber object number 18
Product K. M atsuura T.I i T.Okada
Group
(It is for Japanese market only.)
・P.8 The version number of the trial operation
program is changed to "Ver6.3.3.0".
・P.45,P46 The note about the value and unit of
       temperature.
Solution
・P.47 The description about the value and unit of
D 12/27/2011 Product K. M atsuura T.I I R.Okada
temperature in BACnet/IP communication
Group
is added.
・P.58 The description about the value and unit of
temperature displayed in BACnet history is
added.
・P8 The version number of the trial operation
program is changed to "" Ver6.3.4.0".
・P10 Addition of menber object
number 32,33,34,35
Solution
・P36,P37,P44,P45,P46
E 01/16/2013 Product K. M atsuura T.I I R.Okada
The description about Register M anagement
Group
Point types is added.

・P11,P34 Setting temperature unit(Celsius/Fahrenheit)

Daikin Industries, Ltd. CB06A069E


CB06A069E 3/59

Contents Page
[BACnet Object System Diagram of Interface for use in BACnet] -----------------------5
[Specifications of Interface for use in BACnet] ---------------------------------------------6, 7

[Before Visiting the Site]


1. Check the specifications of the PC and communication
cable used for the trial operation as well as the version
of the trial operation program. --------------------------------------------------------8
2. Obtaining Object Information --------------------------------------------------9-11
3. Setting the Trial Operation PC Modem ---------------------------------------12-21
(When connecting the Interface for use in BACnet and the trial operation PC
using RS232Ccommunication)

[Work Procedure for the Interface for use in BACnet]


Trial operation flow -------------------------------------------------------------------------22
1. Connect the trial operation PC and Interface for use in BACnet via
the RS232C cross cable or the hub using the 100BASE-
TX straight cable. -----------------------------------------------------------------------23, 24
2. Start the trial operation program. -----------------------------------------------25, 26
3-1. Select Protocol -------------------------------------------------------------------------27
3-2. Set Port Number -------------------------------------------------------------------------28
3-3. Instance Number -------------------------------------------------------------------------29
3-4. COV Output Yes/No --------------------------------------------------------------------30, 31
3-5. Set IP address --------------------------------------------------------------------32, 33
3-6. Set Locale -------------------------------------------------------------------------34
3-7. Set Current Time -------------------------------------------------------------------------35
3-8. Register Management Point Types ------------------------------------------------36, 37
4. Reset the Interface for use in BACnet. -----------------------------------------------38-40
5. Start the trial operation program. ----------------------------------------------41, 42
6. Select the Operation Status menu and check
the following: ---------------------------------------------------------------------------------43
7. Check the registration of management point types ---------------------------------44
8. Check the all points from the central control panel. -----------------------45, 46

[Reference: Items which do not need to be changed from


the factory settings] ------------------------------------------------------------------------------47-53

[Q & A] ---------------------------------------------------------------------------------------------54-59

Daikin Industries, Ltd. CB06A069E


CB06A069E 4/59

[Software and Manuals Used for Trial Operation]

Function of Interface for use


Necessary software Necessary manual Note
in BACnet
Monitoring/controlling air
conditioners from central SetupBACnet, English.dll CB06A069
control panel
Fetching accumulated power
SetupPPD, defaultLangPPD.dll CB06A070
(fee management from central
control panel)
SetupBACnet, English.dll CB06A069

Updating the software for SetupBACnet, English.dll


CB06A069
Interface for use in BACnet main bipsFtpSend.exe, EnglishFtpSend.dll
unit
CB07A031
exe.bin.gz, ftpsend.bat

Ex. 1: Connect to the central control panel via BACnet and send the accumulated power data.
 Necessary software: SetupBACnet, English.dll, Necessary manual: CB06A069
Necessary software: SetupPPD, Necessary manual: CB06A070
Ex. 2: Update to the software which supports BTL and connect to central monitoring panel with BACnet.
 Necessary software: SetupBACnet, English.dll; Necessary manual: CB06A069
Necessary software: bipsFtpSend.exe, EnglishFtpSend.dll, exe.bin.gz, ftpsend.bat; Necessary
manual: CB07A031

Download software and manual from Daikin distributors' page if necessary.

Daikin Industries, Ltd. CB06A069E


CB06A069E 5/59
[BACnet Object System Diagram of Interface for use in BACnet]

[Function Overview of Interface for use in BACnet]


● Communication interface between the central control panel and air conditioners.
Central control
 You can connect the central control panel and air conditioners via BACnet (Note 1)
panel which is an open network.
 You can send operation status from each air conditioner to the central control panel
and start/stop each air conditioner from the central control panel.
Note 1: A communication protocol supported by the IPv4 standard.
: BACnet/IP

BACnet / Ethernet IPv4

Forcibly stops air conditioner


with contact input.

Security Reception Disaster


Lighting
subsystem /transformation preventing subsystem
subsystem
subsystem
Outdoor unit Outdoor unit

10/100BASE-T
Straight cable DIII -NET1
100BASE-TX Up to 64 indoor unit groups
HUB (1-00 - 4-15)
RS232C-1

Connected via Connected via


100BASE-TX RS232C cross
VRV Heat Reclaim Ventilator
straight cable (* 1) cable (* 2)
(indoor unit)

Outdoor unit Outdoor unit

DIII –NET2
Up to 64 indoor unit groups
(1-00 - 4-15)

VRV Heat Reclaim Ventilator


Trial operation PC (indoor unit)
(with trial operation program installed)

DIII –NET3

DIII –NET4 When using optional D III board (DAM411B51)

(You can connect the trial operation PC in one of the two ways. You can use either method.): Refer to P.23 for the details.
* 1: The following conditions must be satisfied when using the 100BASE-TX straight cable:
● The 100BASE-TX straight cable (LAN straight cable) should be used. (This type of cable is sold at a common electrical store.)
● One free port should be reserved with the hub (procured locally) shown above. Also, an IP address which can be temporarily used
at the on-site test operation should be provided (ask the sales division or site).
● When only configuring the Interface for use in BACnet, you can connect the 100BASE-TX cross cable (LAN cross cable) directly to
the Interface for use in BACnet, rather than connecting the straight cable to the hub.
● You should be able to change the IP address of the trial operation PC and return to the original address after the test (refer to
P.25 for the procedure).
*: Using the 100BASE-TX straight cable for the trial operation ensures faster communication than using RS232C and allows quicker
settings.

*2: When connecting the trial operation PC to the Interface for use in BACnet using the RS232C cross cable, you must configure
the dial-up adapter and modem in advance. Refer to P.12 through P.21 for the procedure.

Daikin Industries, Ltd. CB06A069E


CB06A069E 6/59

[Specifications of Interface for use in BACnet(1)]

Daikin Industries, Ltd. CB06A069E


CB06A069E 7/59

[Specifications of Interface for use in BACnet(2)]

1) Electrical rating 6) Contact I/O


(1) Rated voltage: Single-phase 100 - 240 VAC Do-1: ON when Interface for use in BACnet is
50/60 Hz malfunctioning
(2) Power consumption: Max. 20 W Do-2: ON when the connected air conditioner is
2) Environmental conditions malfunctioning
(1) Power supply voltage variation: ± 10% of Di-1 - 4: Air conditioner forced stop contact input for
the rated value each D III-NET communication port
(2) Operating temperature: -10 - 50 C OPDi-1 - 12: Power pulse input for proportional power
(3) Operating humidity: 0 - 90 % (no dewing) distribution among air conditioners
(4) Storage temperature: -20 - 60 C OPDi-13 - 16: Not used
3) Performance - Insulation resistance: 50 MΩ or
higher at DC500 V mega
4) Weight: 3.0 kg
5) Surface: Stainless hairline finish

Daikin Industries, Ltd. CB06A069E


CB06A069E 8/59

[Before Visiting the Site]


1. Check the specifications of the PC and communication cable used for the trial operation as well as the version
of the trial operation program.
1-1. PC specifications
OS : Windows XP SP3
Communication port necessary on PC : PC's RS232C communication port: 1 port
(Since the trial operation may not be performed properly if you convert
a USB port into the RS232C communication port, be sure to prepare
a PC with an RS232C communication port.)
: Ethernet (for LAN communication): 1 port

1-2. Communication cable specifications required for trial operation(communication cable to connect the Interface for use in
BACnet and trial operation PC) RS232C communication cable : Cross cable with 9 pin (female) - 9 pin (female)

Ethernet (100BASE-TX) cable: LAN cable (straight cable)


Ethernet (100BASE-TX) cable: LAN cable (cross cable)
(Used when there is no hub at the site or the hub is faulty.)

1-3. Checking the version of the trial operation program installed on the PC

The trial operation program version 6.3.4.0 or higher is required for trial operation of the Interface for use in BACnet
(DMS502B51).
Check the version of the trial operation program installed on the PC before visiting the site in the following procedure.
(How to check the trial operation program version)
Right-click the trial operation program of Interface for use in BACnet [1] (program name: SetupBACnet),
and choose "Property (R)".
Click the "Version" tab [2] and confirm that the version number shown in the "File Version" field [3]
is 6.3.4.0 or higher.
Any trial operation programs with lower version than the version shown above cannot configure
Interface for use in BACnet which is in conformity with BTL. Obtain Version 6.3.4.0 or higher and install
it on the PC before the trial operation.
2

Daikin Industries, Ltd. CB06A069E


CB06A069E 9/59

2. Obtaining Object Information (1/3)

You must initialize the Interface for use in BACnet before the trial operation. Therefore, you need to gather
the object information listed below ([1] - [6]) before visiting the site. Obtain this information from the sales
person of Daikin or distributor for the object.
(Fill in the information proprietary to the object in the blank space of [1] - [6].)

[1] Confirmation of communication method between the Interface for use in BACnet and the central control panel

Communication method between the Interface for use in BACnet and the central control panel
No. Communication method Communication method for the object (circle one of them)

1 BACnet/IP communication

[2] BACnet communication port number


*: The factory setting is 47808. The available setting range is 1 - 65535.
BACnet communication port
number

[3] Instance number for the Interface for use in BACnet


*: The available setting range is 0 - 4194302 and the factory setting is 0.
Device instance number
of Interface for use in
BACnet

[4] Working drawings


● Cable routing diagram (which provides the following information)
 The number and locations of the Interface for use in BACnet
 The number and locations of the optional D III boards
 The number and locations of the optional Di boards
 Material (e.g., drawing) which shows the number of air conditioners and mapping between the
addresses and locations of air conditioners

Daikin Industries, Ltd. CB06A069E


CB06A069E 10/59
2. Obtaining Object Information (2/3)

[5] Items monitored/controlled from the central control panel for air conditioners

Monitor/control
Member from the central
number Object type (for control panel for
Monitor/control item
(for BACnet) e ac h air
BACnet) c o n dit io n e r
(yes/no)
1 ON/OFF (setting) BO
2 ON/OFF (status) BI
3 Alarm Sign BI
4 Error Code MI
5 Operation M ode (setting) MO
6 Operation M ode (status) MI
7 Airflow Rate (setting) MO
8 Airflow Rate (status) MI
9 M easured Room Temperature AI
10 Set Room Temperature AV
11 Filter Limit Sign BI
12 Filter Limit Sign Reset BV
13 Remote Control Operation (ON/OFF) BV
14 Remote Control Operation (Operation M ode) BV
16 Remote Control Operation (Set Temperature) BV
(*1)17 Remote Control Operation (Sub Group Address Control Rejection) BV
(*2)18 Accumulated gas Accumulator
19 Accumulated power Accumulator
20 Communication Status BI
(*1)21 System Forced OFF BV
22 Air Direction (setting) AV
23 Air Direction (status) AI
24 Forced Thermostat OFF (setting) BO
25 Forced Thermostat OFF (status) BI
26 Energy Efficiency Command (setting) BO
27 Energy Efficiency Command (status) BI
28 Thermostat Status BI
29 Compressor Status BI
30 Indoor Fan Status BI
31 Heater Operation Status BI
32 Ventilation mode(setting) MO
33 Ventilation mode (status) MI
(*3)34 Ventilation amount (setting) MO
(*3)35 Ventilation amount (status) MI
*1: Instructed per D III-NET communication port.
*2 : Member number 18 is for Japanese market only.
*3 :The fresh up (Auto) may not be available for monitor/control operation depending on
the specifications of the central monitoring panel.
● Setting BACnet Broadcast

BACnet Broadcast Local or Global (circle one of them)

[Note]
 BACnet allows two types of broadcasts; global broadcast and local broadcast (Note that they are different from
UDP/IP's broadcast). With global broadcast, messages broadcasted are sent beyond the BACnet router to other
BACnet networks. With local broadcast, messages broadcasted are not sent beyond the BACnet router but only reach
nodes within the same BACnet network. (Details of the global broadcast and local broadcast are described in Section
6.3.2 of the ANSI/ASHRAE Standard 135-2004.)
 If a slow BACnet network (e.g., BACnet connected via RS232C) is connected via the BACnet router to the BACnet/IP
network where the station exists, and unregistered COVs which are sent from the station each time an air conditioner
changes its status are also propagated over the slower network, these COVs will occupy the communication line of the
slower network. Therefore, COVs need to be locally broadcasted in such a network configuration.
Note that the Who-Is/I-Am services are globally broadcasted even for BACnet/IP.
Daikin Industries, Ltd. CB06A069E
CB06A069E 11/59

2. Obtaining Object Information (3/3)

[6] IPv4 address (IP address)


Use a private address as the IP address.
You can set the address and subnet mask to arbitrary values from the PC.
Default: Address = 192.168. 0.1, subnet mask = 255.255.255.0
(Also write another IP address which can be temporarily used for the trial service operation, which will not be
used after the trial operation.)

1. IP address for the Interface for use in BACnet


IP address Ex.192.168.0.1
Subnet mask Ex.255.255.255.0
Default gateway address Ex.192.168.0.100
2. IP address temporarily used for the trial service operation (which will not be used after the trial operation)

IP address Ex.192.168.0.2
Subnet mask Ex.255.255.255.0
Default gateway address Ex.192.168.0.100

Restriction on IPv4 address (The following addresses cannot be used.)


One of the following invalid addresses is used as the IP address:
 An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
 A loop-back address (127.0.0.0 - 127.255.255.255)
 An address of which the host portion (hexadecimal "0" portion of subnet mask) contains all "0"s or "1"s
 An address of which the network portion (hexadecimal "1" portion of subnet mask) contains all "0"s or "1"s
[Example]
 244.1.1.1 -> NG (outside the range of Class A - C addresses)
 127.0.0.1 -> NG (Loop-back address)
 IP: 198.168.1.0/Subnet: 255.255.255.0 -> NG (host portion contains all "0"s.)
 IP: 192.168.0.1/Subnet: 192.0.0.0 -> NG (network portion contains all "1"s.)

One of the following invalid addresses is used as the default gateway address:
 An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
 A loop-back address (127.0.0.0 - 127.255.255.255)

An invalid address is used for the subnet mask (outside the range 128.0.0.0 - 255.255.255.255, hexadecimal "1" portion
contain non-sequential value or blank).
[Example]
 255.255.255.244 -> NG (hexadecimal "1" portion contain non-sequential value.)

[7] Celsius/Fahrenheit setting


Set the unit for the temperature sent/received to/from the central monitoring panel in BACnet communications
to either "Celsius" or "Fahrenheit.“
"Celsius" is set as factory default.

Temperature unit Select Celsius or Fahrenheit.


in BACnet communication (put a ring around either of them.)

Daikin Industries, Ltd. CB06A069E


CB06A069E 12/59

3. Setting the Trial Operation PC Modem


(When connecting the Interface for use in BACnet and the trial operation PC using
RS232C communication)
1. Set up the modem.
1-1. Open the Control Panel on the PC.

1-2. Double-click "Phone and Modem Options".

Daikin Industries, Ltd. CB06A069E


CB06A069E 13/59
1-3. When the dialogs is shown at the below left, enter values as shown and click the OK button. The
display changes to the dialog shown at the below right. Click the OK button, and continue to Step 1-4.

1-4. Click the Add button [1]. The display changes to the dialog shown at the below right.
Check the "Don’t detect my modem ; I Will select it from a list." option [2] and click the Next button [3].

1 3

1-5. Click the Have Disk… button [4]. The display changes to the dialog shown on the next page.

Daikin Industries, Ltd. CB06A069E


CB06A069E 14/59
1-6. Click the Browse… button [5] to open the dialog shown in Step 1-7, and specify the GenericNULL
modem ver 2.0 folder already copied on the desktop.

1-7. Select "mdmcisc2" and click the Open button[6].

1-8. Click the OK button [7].

Daikin Industries, Ltd. CB06A069E


CB06A069E 15/59
1-9. Choose "Generic NULL Modem v2" [8] and click the Next > button [9].

1-10. Choose the COM port [10] to connect the RS232C cable to, and click the Next > button [11].

10

11

Daikin Industries, Ltd. CB06A069E


CB06A069E 16/59
1-11. Click the Continue Anyway button [12] because this program will cause no problem.

12

1-12. Click the Finish button [13].

13

1-13. "Generic NULL Modem v2" is added to [14] and modem set up completes.
Next, follow the instructions on the following pages to set up the dial-up adapter.

14

Daikin Industries, Ltd. CB06A069E


CB06A069E 17/59

2. Setting Up the Dial-Up Adapter.


2-1. Open the Control Panel on the PC.

2-2. Double-click the Network Connections icon.

Daikin Industries, Ltd. CB06A069E


CB06A069E 18/59
2-3. The dialog shown below opens. Click "Create a new connection" [1].

2-4. Click the Next button [2].

2-5. Click "Connect to the network at my workplace" [3].

Daikin Industries, Ltd. CB06A069E


CB06A069E 19/59
2-6. Click "Dial-up connection" [4].

2-7. Enter a name to identify this connection [5]. This example uses "Interface for use in BACnet".

5
Interface for use in BACnet

2-8. Enter "1" (one) in the Phone number field [6].

Daikin Industries, Ltd. CB06A069E


CB06A069E 20/59
2-9. Check the option [7] and click the Finish button [8].

2-10. When the dialog shown below opens, click the Properties button [9].

2-11. If multiple choices are shown in [10], select "Generic NULL Modem v2".
Then click the Configure button [11].

10
11

Daikin Industries, Ltd. CB06A069E


CB06A069E 21/59
2-12. Choose "38400" [12] and click the OK button [13]. This completes the setup procedure.

12

13

Daikin Industries, Ltd. CB06A069E


CB06A069E 22/59

[Work Procedure for the Interface for use in BACnet]


IP address set with the trial
operation PC when connecting
Trial operation flow the Interface for use in BACnet
Connect the trial operation PC and Interface for and the trial operation PC via
[1] use in BACnet via the RS232C cross cable or
the hub using the 100BASE-TX straight cable.
Ethernet.
IP address
P24
originally set
with the PC.
Start the trial operation program.
(On the trial operation PC, double-click SetupBACnet.)
[2] Enter the IP address.
P25-27 (When connecting the PC and Interface for use in BACnet via RS232C,
the IP address is fixed to "192.168.3. 1".)
If the IP address
of Interface for
use in BACnet
has not been
Select the BACnet menu and changed from
configure the following: the factory
1. Select Protocol
setting, change
2. Set Port Number
[3] 3. Instance Number the trial
P28-37 4. COV Output Yes/No operation PC's
Under Special Setting menu … IP address to
5. Set IP address
192.168.0.2.
6. Set Locale
7. Set Current Time (*) Factory-set
8. Register Management Point types IP address of
Interface for use
in BACnet is
192.168.0.1.
1. Reset the Interface for use in BACnet.
1-1. Reset from the trial operation program.
[4] 1-2. Reset by powering the device Off/On.
P38-40 2. When using the 100BASE-TX straight cable via the hub
to connect the Interface for use in BACnet and trial
operation PC, change the PC's IP address.

Since the IP
address of Interface
Start the trial operation program. for use in BACnet
[5] (On the trial operation PC, double-click SetupBACnet.) has been changed as
P41, 42 Enter the IP address. required at the site in
[3]-5, the trial
operation PC's IP
address should also
Select the Operation Status menu and check the following:
 Operation status of all the air conditioners with the D III-NET concentrated addresses can be
be changed to the IP
address temporarily
[6] properly monitored.
 All the D III-NET concentrated devices used with the Interface for use in BACnet can be used for the trial
P43 properly monitored. service operation
([6]-2 on P.11).
(*) You cannot
connect to the
[7] Register Management Point types .
Interface for use in
P44  Check that the management point types have been registered correctly. BACnet unless the IP
address is changed.

Check the all points from the central control panel.


[8]  Check whether or not all the air conditioners are properly
P45, 46 monitored/controlled from the central control panel.
Return the IP address
to the address
originally set with the
PC.

Daikin Industries, Ltd. CB06A069E


CB06A069E 23/59

Connect the trial operation PC and Interface for


[1] use in BACnet via the RS232C cross cable or
the hub using the 100BASE-TX straight cable.

[Trial operation PC and Interface for use in BACnet Connection Diagram]


You can connect the trial operation PC and the Interface for use in BACnet in the following three methods.
Although you can use any of these methods, the method *2 does not allow for BACnet communication.
Therefore, if the object requires BACnet communication, use this method only for the setup before the actual
operation. *3
RS232C cross cable Connector of Interface
for use in BACnet is D-
Trial operation SUB 9-pin male.
PC

*2 RS232C
Ethernet -1
100BASE-TX
Cross cable 100BASE-TX

Ethernet
100BASE-TX HUB (*Procured locally)
*1
Ethernet
100BASE-TX
Ethernet 100BASE-TX straight cable
*: Check the port on the hub to connect
the cable at the site.
* If the hub is faulty or cannot be procured Ethernet
locally, use the Ethernet 100BASE-TX 100BASE-TX
cross cable to directly connect the trial straight cable
operation PC and 100BASE-TX port of (procured
Interface for use in BACnet. locally)
(You can connect the trial operation PC in one of the three ways. You can use any method.):
* 1: Use the 100BASE-TX straight cable. The following conditions must be satisfied when using the 100BASE-TX
straight cable:
● The 100BASE-TX straight cable (LAN straight cable) should be used. (This type of cable is sold at a common
electricalstore.) Also prepare the 100BASE-TX cross cable (LAN cross cable) which can be used when the hub is
faulty.
● One free port should be reserved with the hub (procured locally) shown above. Also, an IP address which can be
temporarily used at the on-site test should be provided (ask the sales division or site).
● You should be able to change the IP address of the trial operation PC and return to the original address after the test
(refer to the next for the procedure).
(Note) If you are executing trial operations for multiple Interface for use in BACnet using the same object, be
sure to keep the Interface for use in BACnet powered off or the 100BASE-TX cable disconnected until the
whole procedure of [4] in this manual has been completed.
(All Interface for use in BACnet have the identical IP address set at the factory. Therefore, if you connect them
to the trial operation PC via the hub using 100BASE-TX, the trial operation may not be executed properly
since their default addresses are the same.)
*: Using the 100BASE-TX straight cable for the trial operation ensures faster communication than using RS232C and
allows quicker settings.
*: If the IP address of Interface for use in BACnet has been changed from the trial operation PC and the new
address is unknown, you can only connect the Interface for use in BACnet and PC using the RS232C cross
cable (method *3).
In this case, be sure to set up the trial operation PC's modem as instructed in "3. Setting the Trial Operation
PC Modem" of [Before Visiting the Site]. (You can change connection to the 100BASE-TX cable once you find
the IP address of Interface for use in BACnet with RS232C cable connection.)

•2: Use the 100BASE-TX cross cable to directly connect


the PC and Interface for use in BACnet.
Refer to *1 for the precautions.

* 3: Use the RS232C cable to connect the PC and


Interface for use in BACnet.
Use the cable with the specifications shown to the right.
: 9-pin (female) - 9-pin (female) cross cable

Daikin Industries, Ltd. CB06A069E


CB06A069E 24/59
[How to set the PC's IP address when connecting the PC and Interface for use in BACnet via
the 100BASE-TX cable]
1. Take a note of the trial operation PC's current IP address.
(Be sure to take a note of the current IP address because this address needs to be restored after the trial
operation.)
1-1. Start the trial operation PC.
(The screens shown below are Windows XP's examples, and the actual screens differ depending on the OS used.)
1-2. Double-click the Network Connections icon on the Control Panel. Click the Local Area Connection and
right-click to choose "Properties". The dialog box 1 below opens.
1-3. Select "Internet Protocol (TCP/IP)" [1] and click the Properties button [2]. The dialog box 2 opens. This dialog
box shows the trial operation PC's current IP address [3], subnet mask [4], and default gateway address [5].
Take a note of this information in Table 1.

Dialog box 1. Local Area Connection Properties Dialog box 2. Internet Protocol (TCP/IP) Properties

3
4
1 5
2

Do not
change
these fields.

7 6
[Table 1: Trial Operation PC's Current Address]
[3] IP address Ex.150.35.20.60

[4] Subnet mask Ex.255.255.255.0

[5] Default gateway address Ex.150.35.20.254

2. Change the trial operation PC's IP address.


*: Use one of the following IP address depending on the current status of the Interface for use in BACnet.
(1): If the IP address of Interface for use in BACnet has not been changed from the factory setting, use the
following:
 IP address: 192.168.0.2
 Subnet mask: 255.255.255.0
 Default gateway address: 192.168.0.100
(2): If the IP address of Interface for use in BACnet has been changed from the factory setting at the site, use the
following:
 IP address shown in the table in "[6]-2. IP address temporarily used for the trial service operation"
on P.11.

2-1. Enter the information above in "IP address" [3], "subnet mask" [4], and "default gateway" [5] in the dialog box 2
of Step 1-3, and press the OK button [6]. The dialog box 1 reappears. Click the OK or Cancel button [7].

2-2. Reboot the PC as required by the PC.


(Reboot may not be necessary depending on the Windows version. Reboot the PC only when requested.)

3. Return the IP address to the original address after the trial operation.
(Be sure to return the trial operation PC's IP address to the original address.)

3-1. Return the trial operation PC's IP address to the original address recorded in Step 1-3, as instructed in Steps
2-1 and 2-2.

Daikin Industries, Ltd. CB06A069E


CB06A069E 25/59

Start the trial operation program.


[2] (On the trial operation PC, double-click SetupBACnet.)
Enter the IP address.

[When connecting the trial operation PC and Interface for use in BACnet via 100BASE-TX]
1. Before starting the trial operation program, check if the local time zone is correctly selected with the PC's "Date and
Time Property". If it is not, the correct time cannot be set.
On the dialog box 1, double-click the trial operation program (SetupBACnet) [1].
The dialog box 2 opens to enter the IP address.
2. Enter the IP address as instructed below in the IP Address field [2].
● When the IP address of Interface for use in BACnet has not been changed from the factory setting
→ Enter "192.168.0.1".
* In this case, change the trial operation PC's IP address to "192.168.0.2" (refer to P.24 for the procedure).
● When the IP address of Interface for use in BACnet has been changed from the factory setting at the site
→ Enter the IP address as instructed in [6]-1 on P.11.
* In this case, change the trial operation PC's IP address to the IP address given in [6] on P.11 (refer to P.24 for
the procedure).
3. Click the OK button [3]. The dialog box 3 at the bottom of this page opens.

Dialog box 1. SetupBACnet.exe Dialog box 2. IP Address Entering Dialog box

* Refer to P.24 for how to change the


IP address.

2 3

Reference: Interface for use in BACnet and trial operation


Dialog box 3. Malfunction History PC's IP addresses
BACnet/Ethernet

HUB

Interface for use Trial operation PC


in BACnet

When connecting the Interface for use in BACnet and the trial operation
PC via Ethernet, they cannot communicate with each other unless the
following IP address settings are used.

IP address of Interface for Trial operation PC's IP


Status use in BACnet address

Interface for use in


BACnet 192.168.0.1 192.168.0.2
Factory setting

IP address of Interface for IP address set for the IP address temporarily used
use in BACnet has been Interface for use in for the trial service
changed at the site BACnet in [6]-1 on P.11. operation in [6]-2 on P.11.

Daikin Industries, Ltd. CB06A069E


CB06A069E 26/59

Start the trial operation program.


(On the trial operation PC, double-click SetupBACnet.)
[2] Enter the IP address.
(When connecting the PC and Interface for use in BACnet via RS232C,
the IP address is fixed to "192.168.3. 1".)

[When connecting the trial operation PC and Interface for use in BACnet via RS232C]
1. Set up the modem as instructed in "3. Setting the Trial Operation PC Modem" in [Before Visiting the Site].

2. Connect the trial operation PC and RS232C-1 port of Interface for use in BACnet with the RS232C cross cable
(9-pin-9-pin).

3. Double-click the dial-up shortcut ( ) on the desktop.

4. When the dialog box below opens, click the Dial button [1]. The icon shown below right will appear on the task bar
(bottom right of the screen).

5. Before starting the trial operation program, check if the local time zone is correctly selected with the PC's "Date and
Time Property". If it is not, the correct time cannot be set.
On the dialog box 1, double-click the trial operation program (SetupBACnet) [2]. The IP address entering dialog box
opens.
6. Change the IP address to "192.168.3.1" and click the OK button [3].
The dialog box shown at the bottom of this page opens.

Dialog box 1. SetupBACnet.exe Dialog box 2. Entering IP address

2
Dialog box 3. Malfunction History 3

Daikin Industries, Ltd. CB06A069E


CB06A069E 27/59

Select the BACnet menu and configure


the following: Note
1. Select Protocol
2. Set Port Number Be sure that the Backup
3. Instance Number switch on the right side of
[3] 4. COV Output Yes/No
Under Special Setting menu … the Interface for use in
5. Set IP address BACnet is ON. If not, turn it
6. Set Locale
7. Set Current Time ON (by shifting the switch
8. Register Management Point types knob to the bottom
position).
1. Select the BACnet protocol.
1-1. Click the BACnet button [1].
1-2. Click the Protocol button [2].
1-3. The Current protocol of Interface for use in BACnet is shown in [3].
1-4. If the protocol needs to be changed, click the Modify button [4].
1-5. The dialog box 2. "BACnet Protocol Setting" opens. Select "IPv4 BACnet/IP" [5] according to the information in
[1] of "2. Obtaining Object Information", and click the Set button [6].
1-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click
the OK button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On
again.
Dialog box 1. BACnet
1

Dialog box 2. BACnet Protocol Setting Dialog box 3. Reset Request

7
5

6
Daikin Industries, Ltd. CB06A069E
CB06A069E 28/59

Select the BACnet menu and configure


the following:
1. Select Protocol
2. Set Port Number
3. Instance Number
[3] 4. COV Output Yes/No
Under Special Setting menu …
5. Set IP address
6. Set Locale
7. Set Current Time
8. Register Management Point types

2. Set the communication port number.


2-1. Click the BACnet button [1].
2-2. Click the Protocol button [2].
2-3. Current port number of Interface for use in BACnet is shown in [3].
2-4. If the port number needs to be changed, click the Modify button [4].
2-5. The dialog box 2 "BACnet Port No. Setting" opens. Use the ▲▼ buttons to select the port number [5] according to the
information in [1] of "2. Obtaining Object Information", and click the Set button [6].
(Click the Default button to restore the factory setting.)
2-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK
button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.

Dialog box 1. BACnet


1

3
4
Dialog box 2. BACnet Port No. Setting Dialog box 3. Reset Request

5 7

Daikin Industries, Ltd. CB06A069E


CB06A069E 29/59

Select the BACnet menu and configure


* The device instance number is determined by the central control
the following:
panel vendor at the object meeting. This section shows the steps
1. Select Protocol
to set the provided number with the Interface for use in BACnet.
2. Set Port Number
3. Instance Number
[3] 4. COV Output Yes/No
Under Special Setting menu …
5. Set IP address
6. Set Locale
7. Set Current Time
8. Register Management Point types

3. Set the Device instance number of Interface for use in BACnet.


Check the [3] " The device instance number of Interface for use in BACnet" in "2. Obtaining Object Information" of this manual.
The following steps set the instance number with the Interface for use in BACnet.
3-1. Click the BACnet button [1].
3-2. Click the Instance button [2].
3-3. The current device instance number of Interface for use in BACnet is shown in [3].
3-4. If the current device instance number of Interface for use in BACnet is different from the desired number, click the Modify button [4].
(If modification is not required, proceed to the next page.)
3-5. The BACnet Device Setting dialog box opens. Use the ▲▼ buttons to select the device instance number [5] and click the Set
button [6].
3-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.

Dialog box 1. BACnet


1
2

4
Dialog box 2. BACnet Device Setting Dialog box 3. Reset Request

7
5

6
Daikin Industries, Ltd. CB06A069E
CB06A069E 30/59

Select the BACnet menu and configure


•The COV function allows the Interface for use in BACnet to
the following:
automatically transmit data whenever an air conditioner changes its
1. Select Protocol
status.
2. Set Port Number
3. Instance Number When using the BACnet/IP protocol, this
[3] 4. COV Output Yes/No setting is not required because the central
Under Special Setting menu …
5. Set IP address control panel communicates with each air
6. Set Locale conditioner for this setting.
7. Set Current Time
8. Register Management Point types

4. Set the COV output. (When using the BACnet/IP protocol, this setting is not required because the central control
panel communicates with each air conditioner for this setting.)
4-1. Click the BACnet button [1].
4-2. Click the COV button [2].
4-3. Select the COV for each air conditioner or COV for each air conditioner block in [3]. (Block setting may not be
necessary for some cases.)
4-4. The current COV output setting of Interface for use in BACnet is shown in [4]. Use the scroll bar [5] to see the entire list.
4-5. If the current COV output setting of Interface for use in BACnet needs to be changed, click the Modify button [6].
(If modification is not required, proceed to the next page.)
4-6. The dialog box 2 "BACnet COV Setting" opens. Check the box [7] of each item to output COV.
Use the scroll bar [8] to set (or confirm) all the items, click the Set button [9].
4-7. To save the COV output setting data in the trial operation PC, click the Text Save button [10] (this step is optional).
The dialog box "Save As" opens. Enter a unique name to identify the setting data.

Dialog box 1. BACnet


1
2
3

6 4

10
Dialog box 2. BACnet COV Setting
7

9
Daikin Industries, Ltd. CB06A069E
CB06A069E 31/59

Select the BACnet menu and configure


the following: Note: This setting can be changed only when the
1. Select Protocol
2. Set Port Number communication protocol is BACnet/IP, but not for
3. Instance Number other protocols.
4. COV Output Yes/No
[3] Under Special Setting menu …
5. Set IP address
6. Set Locale
7. Set Current Time
8. Register Management Point types

4. Set the COV setting (continued from the previous page).


Refer to [5] "BACnet Broadcast" in "2. Obtaining Object Information" of this manual.
This section shows the steps to set the BACnet broadcast method to the Interface for use in BACnet as required.
4-8. The current BACnet broadcast method of Interface for use in BACnet is shown in [11].
4-9. If the current setting needs to be changed, click the Modify button [12]. The dialog box 2 "BACnet Broadcast Setting“
opens.
4-10. Select "Local" or "Global" in [13], and click the Set button [14].
Dialog box 1. BACnet

12
11

Dialog box 2. BACnet Broadcast Setting

13

14

Daikin Industries, Ltd. CB06A069E


CB06A069E 32/59
Restriction on IPv4 address (The following addresses cannot be used.)

Select the BACnet menu and configure One of the following invalid addresses is used as the IP address:
the following:  An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
 A loop-back address (127.0.0.0 - 127.255.255.255)
1. Select Protocol  An address of which the host portion (hexadecimal "0" portion of subnet mask) contains all "0"s or
2. Set Port Number "1"s
3. Instance Number  An address of which the network portion (hexadecimal "1" portion of subnet mask) contains all "0"s
or "1"s
4. COV Output Yes/No
[3] Under Special Setting menu …
[Example]
 244.1.1.1 -> NG (outside the range of Class A - C addresses)
 127.0.0.1 -> NG (Loop-back address)
5. Set IP address  IP: 198.168.1.0/Subnet: 255.255.255.0 -> NG (host portion contains all "0"s.)
6. Set Locale  IP: 192.168.0.1/Subnet: 192.0.0.0 -> NG (network portion contains all "1"s.)
7. Set Current Time
One of the following invalid addresses is used as the default gateway address:
8. Register Management Point types  An address outside the range of the Class A - C addresses (1.0.0.0 - 223.255.255.255)
 A loop-back address (127.0.0.0 - 127.255.255.255)

An invalid address is used for the subnet mask (outside the range 128.0.0.0 - 255.255.255.255,
hexadecimal "1" portion contain non-sequential value or blank).
[Example]
 255.255.255.244 -> NG (hexadecimal "1" portion contain non-sequential value.)

5. Set the IP address of Interface for use in BACnet, subnet mask, and default gateway address.
Refer to [6] "IPv4 address" in "2. Obtaining Object Information" of this manual.
This section shows the steps to set this IP address data to the Interface for use in BACnet.
5-1. Click the Special Setting button [1].
5-2. Click the IP Address button [2].
5-3. The current IP address of Interface for use in BACnet, subnet mask, and default gateway address are shown in [3].
5-4. If the current IP address of Interface for use in BACnet, subnet mask, and default gateway address are different from the desired
settings, click the Modify button [4].
(If modification is not required, proceed to the next page.)
5-5. The dialog box 2 "IP Address Setting" opens. Enter desired values from the PC's keyboard into [5], then click the Set button [6].
5-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.

Dialog box 1. Special Setting


1

3
4

Dialog box 2. IP Address Setting Dialog box 3. Reset Request

5 7

6
Daikin Industries, Ltd. CB06A069E
CB06A069E 33/59
Acceptable IPv6 address is as follows:
Select the BACnet menu and configure [Address]
the following:  XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:XXXX
1. Select Protocol  XXXX::XXXX
2. Set Port Number  XXXX::
3. Instance Number  ::ddd.ddd.ddd.ddd
4. COV Output Yes/No  XXXX:XXXX:XXXX:XXXX:XXXX:XXXX:ddd.ddd.ddd.ddd
[3] Under Special Setting menu …  XXXX::XXXX:ddd.ddd.ddd.ddd
5. Set IP address  XXXX::ddd.ddd.ddd.ddd
6. Set Locale  ::XXXX:ddd.ddd.ddd.ddd
7. Set Current Time  ::XXXX
8. Register Management Point types * X: Hexadecimal
d: Decimal
* Allowed characters: 0 - 9, A - F (a - f),
colon (:), and period (.)

5. Set the IPv6 self IP address of Interface for use in BACnet and multicast address.
If there is no device performing IPv6 communication on the same network, this
setting is not required.
5-7. Click the Special Setting button [1].
5-8. Click the IP Address button [2].
5-9. The current IPv6 self address of Interface for use in BACnet, multicast address are shown in [3].
5-10. If the current IPv6 self address and multicast address are different from the desired settings, click the Modify button [4].
(If modification is not required, proceed to the next page.)
5-11. The dialog box 2 "IPv6 Address Setting" opens. Enter desired values from the PC's keyboard into [5], then click the Set
button [6].
5-12. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click the OK
button [7].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.
Dialog box 1. Special Setting 1

3
4

Dialog box 2. IPv6 Address Setting Dialog box 3. Reset Request

5 7

6
Daikin Industries, Ltd. CB06A069E
CB06A069E 34/59

[About time Zone]


Select the BACnet menu and configure The Interface for use in BACnet is intended to be an international software
the following: program.
1. Select Protocol Time Zone is popular in oversea markets and used with PC products. This
2. Set Port Number is because time bias selection for Japan is required for the trial operation.
3. Instance Number (GMT+09: 00) Seoul, Yakutsk, and Tokyo
[3] 4. COV Output Yes/No
Under Special Setting menu … [About temperature unit(Celsius/Fahrenheit)]
5. Set IP address
Set the unit for the temperature sent/received to/from the central monitoring
6. Set Locale
panel in BACnet communications to either "Celsius" or "Fahrenheit.“
7. Set Current Time
8. Register Management Point types "Celsius" is set as factory default.

6. Set Locale of Interface for use in BACnet.


6-1. Click the Special Setting button [1].
6-2. Click the Set Locale button [2].
6-3. The current time bias of Interface for use in BACnet is shown in [3] ,
and the current temperature unit(Celsius/Fahrenheit) is shown in [4] and current
6-4. The current time bias is shown for the current location,
and the current temperature unit(Celsius/Fahrenheit) is shown for the the current setting.
If these settings need to be changed, click the Modify button [5].
(If modification is not required, proceed to the next page.)
6-5. The dialog box 2 “Locale" opens. Use the ▼ button [6] to select the location, and Select "Celsius" or "Fahrenheit"
in [7], and click the Set button [8].
6-6. The dialog box 3 opens to request for reset by powering the Interface for use in BACnet Off then On again. Click
the OK button [9].
Reset the Interface for use in BACnet after you completing all the necessary settings.
*: The setting will take effect after the Interface for use in BACnet is reset by powering it Off then On again.
Dialog box 1. Special Setting
1
2

5
Dialog box 2. Locale
Dialog box 3. Reset Request

6
7
9

8
Daikin Industries, Ltd. CB06A069E
CB06A069E 35/59

Select the BACnet menu and configure


the following:
1. Select Protocol
2. Set Port Number
3. Instance Number
[3] 4. COV Output Yes/No
Under Special Setting menu …
5. Set IP address
6. Set Locale
7. Set Current Time
8. Register Management Point types

7. Set the current time to the Interface for use in BACnet.


7-1. Click the Special Setting button [1].
7-2. Click the Clock button [2].
7-3. The current time of Interface for use in BACnet is shown in [3].
7-4. If the time is not correct, click the Modify button [4].
(If modification is not required, proceed to the next page.)
7-5. The dialog box 2 "Clock Setting" opens. Use the ▲▼ buttons [5] to adjust the time and click the Set button [6].
*: The time does not need to be very precise (i.e., difference of around ten seconds is acceptable here).

Dialog box 1. Special Setting


1

4
Dialog box 2. Clock Setting

5 5

Daikin Industries, Ltd. CB06A069E


CB06A069E 36/59

Select the BACnet menu and configure the


following:
1. Select Protocol
2. Set Port Number
3. Set Instance Number
[3] 4. Set COV Output Yes/No
Under Special Setting menu …
5. Set IP address
6. Set Locale
7. Set Current Time
8. Register Management Point Types

8. Update the management point type for each equipment connected to the Interface for use in BACnet.

[When to use this item?]


・ Immediately after installing the Interface for use in BACnet.
・ Immediately after adding a new equipment
・ Immediately after replacing a connected equipment
* Refer to the table on next page for necessary cases of when to use this item.

8-1. Click the Special Setting button [1].


8-2. Click the Update Points button [2].
8-3. The List for update [3] now shows the D III port, central address, and management point type for
each update target device.
8-4. Click the Refresh button [4] to display the most up-to-date list in the dialog box.

* It takes a while for the Interface for use in BACnet to detect connected equipments.
After connecting a equipments, wait for a few minutes, and then click the Refresh button.

* Immediately after installing the Interface for use in BACnet (at factory default), a connected device will be
listed in the dialog box if it is "VENTIAIRE(Heat Reclaim Ventilator)," but it will not be listed in the dialog box
for other device types (VRV System, SkyAir, etc.)

* When an equipment is replaced with the same type of equipment, in such cases as "Indoor" to "Indoor" or
"VENTIAIRE (Heat Reclaim Ventilator) " to "VENTIAIRE (Heat Reclaim Ventilator)," the substituted equipment
will not be listed in the dialog box.

8-5. After the list in the dialog box displays, click the Update button [5].
8-6. The dialog box 2 "Check" opens. Click the Yes button [6].
8-7. The dialog box 3 "SetupBACnet" opens. Click the OK button [7].
Perform power resetting upon completion of the above setting procedure.
* Note that the updated setting is enabled only after power resetting is performed.

Dialog box 1. Special Setting 1 Dialog box 2. Check


2

6
Dialog box 3. SetupBACnet
3
5

4 7

Daikin Industries, Ltd. CB06A069E


CB06A069E 37/59

Select the BACnet menu and configure the


following:
1. Select Protocol
[* Other]
2. Set Port Number
3. Set Instance Number ・ VRV System,
[3] 4. Set COV Output Yes/No
Under Special Setting menu …
・ SkyAir (interface adapter for SkyAir series),
5. Set IP address ・ Outdoor air processing unit,
6. Set Local
・ Packaged air conditioner (central control adapter),
7. Set Current Time
8. Register Management Point Types ・ Wiring adapter for other air conditioner,
・ Split (KRP928)

When Situation Change in equipment connected to Interface for use in BACnet Update required or Management point
not types

Installation Install the Interface for Equipment to be connected Connected equipment


use in BACnet and air
conditioners.
‐ Heat Reclaim Ventilator Required Indoor unit
(No equipment connected to Interface (At factory default)
for use in BACnet) → Heat Reclaim
Ventilator

Other (*) Not required Indoor unit


(At factory default*)

Operation Add new Equipment to be additionally Additionally connected equipment


air conditioners. connected

‐ Heat Reclaim Ventilator Required Indoor unit


(At factory default)
→ Heat Reclaim
Ventilator

Other (*) Not required Indoor unit


(At factory default*)

Operation Remove an existing Equipment to be removed Removed equipment


equipment
(Decrease) Heat Reclaim Ventilator ‐ Not required Heat Reclaim
Ventilator

Other (*) Not required Indoor unit

Operation Replace a equipment Equipment to be replaced Substituted equipment


with another.
(Equipment update) Heat Reclaim Ventilator Other (*) Required Heat Reclaim
Ventilator
→ Indoor unit

Heat Reclaim Ventilator Not required Heat Reclaim


Ventilator

Other (*) Heat Reclaim Ventilator Required Indoor unit


→ Heat Reclaim
Ventilator

Other (*) Not required Indoor unit

Operation Upgrade the software Equipment to be upgraded Upgraded equipment


version to enable
monitor/control
operation with no Heat Reclaim Ventilator Required Indoor unit
change to the installed → Heat Reclaim
equipments. Ventilator
(Upgrade to Ver.
6.34.00 or later) Not required Indoor unit
Other (*)

Daikin Industries, Ltd. CB06A069E


CB06A069E 38/59

1. Reset the Interface for use in BACnet.


1-1. Reset from the trial operation program.
1-2. Reset by powering the device Off/On.
[4]
2. When using the 100BASE-TX straight cable via the hub to
connect the Interface for use in BACnet and trial operation PC,
change the PC's IP address.

You can reset the Interface for use in BACnet in two methods as described in this page and next page. You
can use either method.

1-1. To make the new settings effective, reset the Interface for use in BACnet from the trial operation PC.
1-1-1. Click the Special Setting button [1].
1-1-2. Click the Reboot button [2].
1-1-3. Click the Reboot button [3] at the bottom right of the screen. The dialog box 2 "Warning" opens.
1-1-4. Click the OK button [4]. The dialog box 3 "Warning" opens.
1-1-5. Click the OK button [5]. The dialog box 4 "Reboot" opens.
1-1-6. The Interface for use in BACnet will reboot and the dialog box 5 opens to indicate termination of the trial
operation program.
1-1-7. Click the OK button [6] to terminate the trial operation program.

Dialog box 1. Special Setting Dialog box 2. Warning

1
2

4
Dialog box 3. Warning

5
3
Dialog box 4. Reboot Dialog box 5. Exiting from Program

Daikin Industries, Ltd. CB06A069E


CB06A069E 39/59

1. Reset the Interface for use in BACnet.


1-1. Reset from the trial operation program.
1-2. Reset by powering the device Off/On.
[4]
2. When using the 100BASE-TX cable to connect the Interface for
use in BACnet and trial operation PC, change the PC's IP address.

You can reset the Interface for use in BACnet in two methods as described in the previous page and this page. You can use
either method.

1-2. To make the new settings effective, reset the Interface for use in BACnet by powering it Off then On.
1-2-1. Terminate the trial operation program. Click the Exit button [1]. The dialog box 2 opens to confirm the termination.
1-2-2. Click the OK button [2] to terminate the trial operation program.

1-2-3. When you are connecting the PC and the Interface for use in BACnet via RS232C, double-click the icon at
the bottom right of the PC screen (i.e., on the task bar).

The dialog box 3 "Interface for use in BACnet Status" opens.


Click the Disconnect button [3] and wait until the device is disconnected and the dialog box 3 disappears.

1-2-4. Power Off then On the Interface for use in BACnet to reset it. The Power switch is located at [4] of the Photo 1 below. Turn
this switch
Off, then turn it On again after one second.
Dialog box 1. Trial operation program Dialog box 2. Termination confirmation

Dialog box 3. Interface for use in BACnet Status Photo 1. Outer view of Master Station III

4
3

Daikin Industries, Ltd. CB06A069E


CB06A069E 40/59

1. Reset the Interface for use in BACnet.


1-1. Reset from the trial operation program.
1-2. Reset by powering the device Off/On.
[4]
2. When using the 100BASE-TX cable to connect the Interface for
use in BACnet and trial operation PC, change the PC's IP address.

3. When using the 100BASE-TX cable to connect the Interface for use in BACnet and trial operation
PC, change the PC's IP address.
*: This procedure is not necessary when connecting them via RS232C.
(The screens shown below are Windows XP's examples, and the actual screens differ depending on the OS used.)
3-1. Double-click the Network Connections icon on the Control Panel. Click the Local Area Connection and right-click
to choose "Properties". The dialog box 1 below opens.
3-2. Select "Internet Protocol (TCP/IP)" [1] and click the Properties button [2]. The dialog box 2 opens. This dialog
box shows the trial operation PC's current IP address [3], subnet mask [4], and default gateway address [5].
3-3. Refer to the table in "[6]-2. IP address temporarily used for the trial service operation" of “2. Obtaining
Object Information”, and enter the information above in "IP address" [3], "subnet mask" [4], and
"default gateway" [5], then click the OK button [6].
The dialog box 1 reappears. Click the OK button [7].
3-4. Reboot the PC as required by the PC.
(Reboot may not be necessary depending on the Windows version. Reboot the PC only when requested.)

Dialog box 1. Local Area Connection Properties Dialog box 2. Internet Protocol (TCP/IP) Properties

3
4
1 5
2

Do not change
these fields.

7 6
(Note) Be sure to return the IP address to the original address after the trial operation.
Return the trial operation PC's address to the original address recorded in Table 1 on P.24, as
directed in Steps 3-1 through 3-4 above.

Daikin Industries, Ltd. CB06A069E


CB06A069E 41/59

Start the trial operation program.


[5] (On the trial operation PC, double-click SetupBACnet.)
Enter the IP address.

[When connecting the trial operation PC and Interface for use in BACnet via 100BASE-TX]
1. Double-click the trial operation program (SetupBACnet) icon [1] on the dialog box 1. Dialog box 2 to enter the IP
address opens.
2. Enter the IP address in [2] according to the information in [6]-1 “IP address for Interface for use in BACnet" of "2.
Obtaining
Object Information".
* The IP address of the trial operation PC needs to be changed to the address shown in [6]-2 of "2. Obtaining
Object Information".
3. Click the OK button [3]. The dialog box 3 at the bottom of this page opens.

Dialog box 1. SetupBACnet.exe Dialog box 2. Entering IP address

* Refer to P.24 for how to change


the IP address.

2 3

Reference: Interface for use in BACnet and trial operation


Dialog box 3. Malfunction History PC's IP addresses
BACnet/Ethernet

HUB

Interface for use Trial operation PC


in BACnet

When connecting the Interface for use in BACnet and the trial operation
PC via Ethernet, they cannot communicate with each other unless the
following IP address settings are used.

IP address of Interface for Trial operation PC's IP


Status use in BACnet address

Interface for use in


BACnet 192.168.0.1 192.168.0.2
Factory setting

IP address of Interface for IP address set for the IP address temporarily used
use in BACnet has been Interface for use in for the trial service
changed at the site BACnet in [6]-1 on P.11. operation in [6]-2 on P.11.

Daikin Industries, Ltd. CB06A069E


CB06A069E 42/59

Start the trial operation program.


[5] (On the trial operation PC, double-click SetupBACnet.)
Enter the IP address.

[When connecting the trial operation PC and Interface for use in BACnet via RS232C]
1. Set up the modem as instructed in "3. Setting the Trial Operation PC Modem" in [Before Visiting the Site].

2. Connect the trial operation PC and RS232C-1 port of Interface for use in BACnet with the RS232C cross cable
(9-pin-9-pin).

3. Double-click the dial-up shortcut ( ) on the desktop.

4. When the dialog box below opens, click the Dial button [1]. The icon shown below right will appear on the task bar
(bottom right of the screen).

5. Double-click the trial operation program (SetupBACnet) icon [2].


The dialog box to enter the IP address opens.
6. Change the IP address to "192.168.3.1" and click the OK button [3].
The dialog box shown at the bottom of this page opens.

Dialog box 1. SetupBACnet.exe Dialog box 2. Entering IP address

2
Dialog box 3. Malfunction History 3

Daikin Industries, Ltd. CB06A069E


CB06A069E 43/59

Select the Operation Status menu and check the following:


 Operation status of all the air conditioners with the D III-NET concentrated addresses can be
[6] properly monitored.
 All the D III-NET concentrated devices used with the Interface for use in BACnet can be properly
monitored.

Check that the D III-NET communication cabling and address assignment for the air conditioners are correctly done.
1. Check that the operation status of the air conditioners and other concentrated devices connected can be properly
monitored.
1-1. Click the Operating State button [1]. Select the D III NET communication port of the Interface for use in BACnet to check
communication in
[2]. The dialog box 1 "Operating State" opens.
1-2. Operation status of the air conditioners and concentrated devices connected to the port selected in Step 1-2 is shown in [3].
Check if other connected concentrated devices can be monitored in this dialog box.
1-3. Start and stop each air conditioner to check if the cabling and address assignment for it are correctly done.
This step needs two persons. One person operates the trial operation PC, while the other person checks each indoor unit to
check cabling and address assignment. Start and stop each indoor unit to check whether or not it is correctly instructed and/or
monitored.
You can use one of the following two methods:
1. Use the remote controller to start/stop the indoor unit and check if the status is reflected on the trial operation PC.
 Check [4] in the screen below while operating the indoor unit to start/stop with the remote controller.
2. If the remote controller is not provided, start/stop the indoor unit from the trial operation PC and check if the air conditioner
actually starts/stops by checking the fan rotation of the indoor unit.
 Select the indoor unit to check in [5] and click the Aircon Control button [6]. The dialog box 2 "Air Conditioner Control" opens.
Select "ON" or "OFF" in [7] and select "No Change" in [8]. Finally, click the Set button [9].
Check if the indoor unit actually starts or stops.
1-4. Repeat Steps 1-1 through 1-3 to check all the air conditioners.
Dialog box 1. Operating State

1 If an air conditioner cannot


2 be started/stopped with
the current address,
assign the address again
3 to that indoor unit.

5
4

Dialog box 2. Air Conditioner Control

Daikin Industries, Ltd. CB06A069E


CB06A069E 44/59

Check the registration of management point types.


[7] ・ Check that the management point types have been registered correctly.

Check that the Management point type registered correctly for each connected device.
*Refer to the page 36,37 for necessary cases of when to register the Management point type for connected equipments.

1-1. Click [1] Operating State button.


Then, select the D III NET port to which the air conditioners you want to check for successful
registration are connected in [2].
Then, click the Detail button [3].
The dialog box 1 "Operating State Monitor (Detail)" opens.

1-2. The operating state of each air conditioner connected to the port selected in 1-1 is shown in [4].
Check [5] Management point types to make sure that the management point types are registered
correctly for each connected air conditioner.

Dialog box 1 Operating State Monitor (Detail)


1
2
4 5

Daikin Industries, Ltd. CB06A069E


CB06A069E 45/59

Check the all points from the central control panel.


[8]  Check whether or not all the air conditioners are properly
monitored/controlled from the central control panel.

Check if each air conditioner operates as instructed from the central control panel.
1. Check if the air conditioner can be properly controlled from the central control panel.
1-1. Check the items which are designated by the manufacturer to be monitored/controlled from the central control panel in the table of
[5] Items monitored/controlled from the central control panel for air conditioners in "2. Obtaining Object Information". Be sure to
keep records of the items checked, so that which items were checked (for the reference in case if a trouble
occurs after delivery).
● Check if the air conditioner operates as instructed from the central control panel in one of the following methods:
1. Check with the trial operation PC of Interface for use in BACnet (see below for the procedure).
2. Check with the air conditioner's remote controller.
3. Check with another concentrated device (e.g., central remote controller) (when other concentrated devices are used together)

The procedure to check the operation status of the air conditioner using the trial operation PC of Interface for use in BACnet is
described below.
Access to the Operating State dialog box for the air conditioners as instructed on the previous page.
You can toggle the display between the simple and detailed formats by clicking the Simple button [1] or Detail button [2].
Each format lists the following items.

Dialog box 1. Simple

[Simple format items]


The following items are listed for each indoor unit:
 Start/stop
1 2  Cooling/heating selection
 Outdoor unit system address
 Product code (VRV, etc.)
 Model code*
 Capacity*
 Model*
Note: Items marked with * may not be shown
depending on the model.

[Detailed format items]


The following items are listed for each indoor unit:
 On/Off
 Filter sign
Dialog box 2. Detail  Element sign
 Malfunction code (for air conditioner failure)
 Room temperature (suction temperature)
1  Set temperature
2  Upper limit of set temperature
 Lower limit of set temperature
 Step for setting temperature
 Thermostat step
 Automatic air conditioning
 Operation mode (air conditioning mode)
 Remote controller on permit/prohibit
 Remote controller off permit/prohibit
 Remote controller temperature setting
permit/prohibit
 Remote controller air-conditioning mode change
permit/prohibit
Air flow direction
 Fan speed
 Main/sub remote controller
 Forced thermo stop
 Energy-saving operation
 Ventilation mode
 Ventilation amount
 Management point types

Note: temperature is displayed in Celsius or


Fahrenheit.

Daikin Industries, Ltd. CB06A069E


CB06A069E 46/59

Check the all points from the central control panel.


[8]  Check whether or not all the air conditioners are properly
monitored/controlled from the central control panel.

Check if operation status of the air conditioner can be properly monitored from the central control panel.
1. Check if operation status of the air conditioner can be properly monitored from the central control panel.
1-1. Check the items which are designated by the manufacturer to be monitored/controlled from the central control panel in the table of
[5] Items monitored/controlled from the central control panel for air conditioners in "2. Obtaining Object Information". Be sure to
keep records of the items checked, so that which items were checked (for the reference in case if a trouble
occurs after delivery).
● You need to change the operation status of the air conditioner for this check. Change the operation status of the air conditioner
in one of the following methods:
1. Change with the trial operation PC of Interface for use in BACnet (see below for the procedure).
2. Change with the air conditioner's remote controller.
3. Change with another concentrated device (e.g., central remote controller) (when other concentrated devices are used
together)
4. The only way to check failure notification is to make an air conditioner failure to actually happen. Therefore, you need to do
some work such as removing the sensor from the outdoor unit.
*: Be sure to restore the air conditioner to the original status. Note that you cannot check the filter and element signs.
The following shows how to change operation status of the air conditioner from the trial operation PC of Interface for use in BACnet.
1-1-1. Select the indoor unit to check in [1] and click the Aircon Control button [2]. The dialog box 2 "Air Conditioner Control" opens.
1-1-2. Select items to change in [3] and click the Set button [5].
(Select "No Change" for items you do not want to change in [3]. You can select multiple items at the same time.)
To apply the same change to multiple air conditioners, check them in [4]. The items shown right below can be changed from the
trial operation PC.

Dialog box 1. Operating State


[Items which can be changed
from trial operation PC]
 On/Off
 Set temperature
 Air conditioning mode
1  Remote controller on
permit/prohibit
 Remote controller off
permit/prohibit
 Remote controller temperature
setting permit/prohibit
 Remote controller air-
conditioning mode change
permit/prohibit
2  Air flow direction
 Fan speed
 Energy-saving operation
 Forced thermo stop
Dialog 2. Air Conditioner Control  Ventilation mode
 Ventilation amount

3 Note: temperature is displayed in


4 Celsius or Fahrenheit.

3
5

Daikin Industries, Ltd. CB06A069E


CB06A069E 47/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.

[To open this dialog box]


Function Config box BACnet→Function Config
[The factory setting]
・Event Notification:
Disabled(BTL)
・COV Notification when Status_Flags was changed:
Enabled(BTL)

[About Function Config]


・Event Notification
It specifies whether to notify or not with EventNotification
service about occurrence of or recovery from device
abnormality, changes in filter sign, occurrence of or
画面差し替え recovery from communication abnormality, and monitoring
of upper and lower limits of actual room temperature
value.
※In order for the specification of BACnet to conform
to BTL, set this function to “Disabled(BTL).”
・COV Notification when Status_Flags was changed
It specifies whether to send COV Notification or not in
response to changes in Status_Flags.
※In order for the specification of BACnet to conform
to BTL, set this function to “Enabled(BTL).”
When it is set to “Enabled,” and it is configured to send
COV (by registering with SubscribeCOV service from
central control panel, or by configuring COV without
registration with this trial operation tool), a large
number of COV will be sent upon occurrence of
communication abnormality among all air
conditioning equipment.(If all objects among 256 air
conditioning equipment are registered to send COV,
the number will be up to about 6600). It may be a
burden on the devices on receiving side or the
network.If it is actually being a burden on devices or
network, it is necessary to consult with the
manufacturers which are connected to the network in
order to reduce the number of objects configured to
send COV.

Daikin Industries, Ltd. CB06A069E


CB06A069E 48/59
Function Config box
[To open this dialog box]
BACnet→Function Config→Common
[The factory setting]
・ Automatic Air flow rate + Air-Conditioning mode
[Dry]:Enabled
[About Automatic Air flow rate + Air-Conditioning mode [Dry] ]
This function is interchangeable the software of Ver6.30
or after with the software of Ver6.20 or before.
This function can set "Enabled/Disabled" to the settings
in monitoring and setting of "Middle" Air flow rate of an air-
conditioning unit which have 3 levels Air flow rate,
and of "Automatic" Air flow rate of an air-conditioning
unit which have Automatic Air flow rate,and of "Dry" operation
of an air-conditioning unit.
When the settings are set to "Enabled", the Interface for use in
BACnet responds the value of the property similar to the value
used in Ver6.20 or before (2 levels Air flow rate,
operation mode : Cool/Heat/Fan ) unless this setting never
causes the unexpected error in the "Central Monitoring
Device“ by responding the enhanced values of the property in
"Middle" and "Automatic" Air flow rate, and in "Dry" operation.

Daikin Industries, Ltd. CB06A069E


CB06A069E 49/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.

Timeout dialog box


[To open this dialog box]
Select BACnet → Timeout.
[The factory setting]
 Time out period: 6 seconds
 Number of retries: 3
[About timeout]
The timeout period is the time for which the Interface for
use in BACnet waits for a response message after it has
sent a request message to another BACnet device
(available setting range: 1 - 120 seconds).
The number of retries is the count for which the Interface
for use in BACnet retries sending the same request
message after timeout (available setting range: 0 - 7).
•These values need to be increased when the other party
in the communication is slow. However, since it is
difficult to know the other party's communication speed,
change them only when the timeout period and the
number of retries are specified by the manufacturer of the
other party.

Segment dialog box


[To open this dialog box]
Select BACnet → Segment.
[The factory setting]
 Segment timeout period: 2 seconds
[About segment]
The Interface for use in BACnet support segmentation
defined by the BACnet standard, and divides a message
longer than one packet into multiple packets when
sending and receiving it. The segment timeout period is
the time for which the Interface for use in BACnet waits
for a response from the other party in segmented
communication (available setting range: 1 - 10 seconds).
* Change this value only when the other BACnet device's
manufacturer specifies the value because that BACnet
device requires segmentation but it is slow, and so on.

Daikin Industries, Ltd. CB06A069E


CB06A069E 50/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.

F.Dev box
[To open this dialog box]
BACnet→F.Dev
[The factory setting]
・Registration as a Foreign:Disabled
[About Foreign Device]
If there is no BBMD(BACnet/IP Broadcast Management
Device) on the same subnet as Interface for use in BACnet,
it cannot receive broadcast messages from other subnets.
So the Interface for use in BACnet need to be set to behave
as a “Foreign Device (see BACnet Standards Annex-J ).”
By operating as a Foreign Device, it can receive broadcast
messages sent from other IP subnets via BBMD.

(a) Register to BBMD as a Foreign Device (at startup of Master Station, and thereafter at a regular interval)

Router IP Subnet1

BBMD Device

① Registration (Register-Foreign-Device)

IP Subnet2
Router
Foreign Device(Interface for use in BACnet)

(b) Broadcast messages forwarded via BBMD


② Broadcasting of BACnet service

Router IP Subnet1

BBMD Device

③ Forwarding BACnet service (Forwarded-NPDU)

IP Subnet2
Router
Foreign Device(Interface for use in BACnet)

(c) Send its own broadcast messages to other devices on other subnets via BBMD

⑤ Broadcasting

Router IP Subnet1
In the case of Foreign Device, Distribute-Broadcast-To-Network is
sent to BBMD instead of Original-Broadcast-NPDU which is used
BBMD Device normally to send broadcast messages.
④ Broadcast message distribution request
(Distribute-Broadcast-To-Network)
IP Subnet2
Router
Foreign Device(Interface for use in BACnet)

Daikin Industries, Ltd. CB06A069E


CB06A069E 51/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.
COS Output Mask
[To open this dialog box]
Select L0 Communicate → COS Output Mask.
[The factory setting]
The settings shown to the left.
[About L0 communication COS output mask]
This setting is required when RS232C
communication is used rather than BACnet
communication to connect to the central control
panel.
You can specify, for each item, whether or not to
notify the central control panel of any change of air
conditioner's operation status.

Block Reading dialog box

[To open this dialog box]


Select L0 Communicate → Block Reading.
[The factory setting]
This is a monitor item and therefore has not factory
setting.
[About L0 communication block read]
Check this item when RS232C communication is
used rather than BACnet communication to connect
to the central control panel and a failure has
occurred. When RS232C communication is used,
the central control panel monitors or control air
conditioners per block, not per D3-NET address.
You can register up to 32 groups (i.e., D3-NET
addresses) of indoor units in one block, from the
central control panel to the Interface for use in
BACnet. When no registration has been done, each
block contains one group.

Communication State dialog box

[To open this dialog box]


Select L0 Communicate → Communication State.
[The factory setting]
This is a monitor item and therefore has not factory
setting.
[About L0 communication status]
Check this item when RS232C communication is
used rather than BACnet communication to connect
to the central control panel and a failure has occurred.
When communication between the Interface for use
in BACnet and the central control panel is healthy,
"Normal" is shown. If the communication is
disconnected for 30 seconds or longer, "Host Down"
is shown. In this case, check the connection of the
RS232C communication lines and other errors.

Daikin Industries, Ltd. CB06A069E


CB06A069E 52/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.
Malfunction Mask dialog box
[To open this dialog box]
Select Special Setting → Malfunction Mask.
[The factory setting]
The settings shown to the left.
[About malfunction mask]
Interface for use in BACnet has a function to detect
its own abnormality, turn the relay output (Do-1) of
Interface for use in BACnet to ON, and let the CPU
ALARM LED blink. The abnormality of its own
includes the items shown on the figure left, and it is
possible to mask them in order to avoid turning Do-
1 to ON and CPU ALARM LED from blinking upon
occurrence of each item.
This is the screen to change that mask setting.
Setting is changed when location specific problem
and the like occur.

Pi Unit dialog box


[To open this dialog box]
Select Special Setting → Pi Unit.
[The factory setting]
 No D III Pi
[Note]
This function is used only in Japan.

Pulse Rate
[To open this dialog box]
Select Special Setting → Plus Rate.
[The factory setting]
The settings shown to the left.
[About pulse rate]
The Interface for use in BACnet can proportionally
distribute power to the air conditioners from the
central control panel, by performing proportional
power distribution in the trial operation.
This dialog box is used to change the pulse rate of
the power meter connected to each power pulse
input terminal of the Interface for use in BACnet.
*: Body Di: power pulse input of Interface for use in
BACnet
Extension Di: Power pulse input 1 - 12 of the
optional Di board

Daikin Industries, Ltd. CB06A069E


CB06A069E 53/59
[Reference: Items which do not need to be changed from the factory settings]
Among the items shown on the trial operation PC's screen, the following items are typically not required to be
changed. The following explains the meanings of these items.

Light Malfunction Reset

[To open this dialog box]


Select Special Setting → Light Malfunction Reset.
[The factory setting]
This only resets the device and therefore has not
factory setting.
[About light malfunction reset]
The Interface for use in BACnet can detect its
malfunction and turns On the Master Station III's
relay output (Do-1). (Refer to the previous page
for details.) Since this malfunction greatly
affects the entire system, Do-1 relay remains
On once it has been activated. The light
malfunction reset resets this failure output to
Off. (You can also reset this output by
powering the Interface for use in BACnet Off
and On).

Malfunction Error画面
[To open this dialog box]
Select Special Setting → Malfunction Error
[The factory setting]
Error type of Notification:Error OR Warning
[About Malfunction Error]
This function is a setting up function of the
"Warning" signal send to the "Central Monitoring
Device " due to the change of the specification of
the handling of "Warning" of the air-conditioning
unit. It becomes possible to notify the " Central
Monitoring Device" of the crisis situation of the
system that ends to "Error" by setting this item to
"Error" +"Warning" beforehand.
Set it to "Error" when you exchange Interface for
use in BACnet in use.

Daikin Industries, Ltd. CB06A069E


CB06A069E 54/59

[Q & A]

Question Answer
I cannot control or monitor air 1. Is the Interface for use in BACnet powered On?
2. Is the Ethernet cable connected to the Interface for use in BACnet and the central
conditioners from the central control control panel? (Refer to P.5.)
panel at all. What are the possible 3. Is the hub powered On?
causes? 4. Are the IP address, subnet mask, and default gateway address correct?
5. Is the device instance number of Interface for use in BACnet correct? (Refer to
P.29)
6. Is the air conditioner's concentrated address correct? (Refer to P.43)
7. Has the point list of air conditioners been supplied to the central control panel
manufacturer?
(If not, contact the sales person for the object.)
*: When using BACnet communication to connect to the central control panel,
this point list is used to configure the communication. This list should be
created by the sales division for each object and supplied to the central
control panel manufacturer.

● Point list sample


Object Instance
Project Point Name Object ID Object Name Type Number
1F Start/Stop(Setting) 16777217 StartStopCommand_000 4 1
1F Start/Stop(Monitaring) 12582914 StartStopStatus_000 3 2
1F Trip 12582915 Alarm_000 3 3
1F Malfunction Code 54525956 MalfunctionCode_000 13 4
1F Temperature Adjust 8388618 TempAdjust_000 2 10
1F R/C Mode Setting(Start/Stop) 20971533 RemoteControlStart_000 5 13
1F R/C Mode Setting(Air Conditianer Mode) 20971534 RemoteControlAirConModeSet_000 5 14
1F R/C Mode Setting(Temperature Adjust) 20971536 RemoteControlTempAdjust_000 5 16
1F Communication State 12582932 CommunicationStatus_000 3 20
2F Start/Stop(Setting) 16777473 StartStopCommand_001 4 257
2F Start/Stop(Monitaring) 12583170 StartStopStatus_001 3 258
2F Trip 12583171 Alarm_001 3 259
2F Malfunction Code 54526212 MalfunctionCode_001 13 260

I cannot control or monitor some 1. Has the central control panel manufacturer registered correct air conditioner
items of the air conditioner from the items (from the point list) which cannot be controlled or monitored from the
central control panel?
central control panel. What are the → Ask the central control panel manufacturer.
possible causes? 2. Has the Daikin's sales person listed correct air conditioner items (on the point
list) which cannot be controlled or monitored from the central control panel?
→ Ask the sales person for the object.
3. Are the items in question allowed to be controlled or monitored from the
central control panel?
→ Refer to the Engineering Data for the air conditioner, D-BACS
Engineering data, or other ones.

Status of the air conditioner is not The COV function selectively enables or disables each status items for report to
reported to the central control panel. the central control panel via the Interface for use in BACnet. Check with the
central control panel manufacturer for the current COV settings.
What are the possible causes?

Daikin Industries, Ltd. CB06A069E


CB06A069E 55/59

[Q & A]

Question Answer
The Interface for use in BACnet and
trial operation PC cannot be
connected. What are the possible
causes?
1. When using the RS232C cross cable
 Has the dial-up modem of the PC been properly set up? (Refer to P.12- 21 for details.)
 Is the correct RS232C cable type used? Is it a cross cable?
 Is the PC's RS232C communication port functioning?

2. When using the Ethernet (LAN)


 Is the IP address set for the PC correct? (Refer to P.24 for the correct IP address and setting procedure.)
 Is the cable type correct?
[1] When connecting via the hub: Straight cable
[2] When connecting the Interface for use in BACnet and trial operation PC directly: Cross cable
 Is the PC's LAN communication port functioning?
 When using the hub, is the hub powered On?
 Can PING be executed from the trial operation PC? (See below.)
[How to execute PING]
1. From the PC's desktop, select "Start", "Program", "Accessories", and "Command Prompt". The dialog box shown below opens.
2. Use the PC's key board, enter the IP address of Interface for use in BACnet in [1].
Ex. When IP address of Interface for use in BACnet is "150.35.20.62", enter "ping 150.35.20.62" and press the Return key.
3. If you can see information as shown in [2], the LAN connection is established. Start the trial operation program and try connection
again.
If you see information as shown in [3], the LAN connection is not established for some reason. Check the PC's settings, etc. again.

1
2

Daikin Industries, Ltd. CB06A069E


CB06A069E 56/59

[Q & A]

Question Answer
1. Create the point list for the new air conditioner and supply it to the central
control panel manufacturer (by sales division).
I must add an air conditioner after 2. Assign the address to the air conditioner at the site, and register the
management point types and check the connection to the air conditioner from
delivery. What should I do? the trial operation PC of Interface for use in BACnet.
(Refer to P.36, P.37 ,P.43, P44 for details.)
3. Check the connection between the new air conditioner and the central control
panel (Refer to P.45 and P.46 for details.)
4. Make the settings of PPD again.
Notice:Make it only after outputting the current charging data by the building
owner,because the integrated value becomes 0 when setting it again.

I must remove an air conditioner after 1. Inform the central control panel manufacturer of the air conditioner removed
delivery for movement. What should from the point list (by sales division).
I do? 2. Power the Interface for use in BACnet Off then On again to reset it.
3. Make the settings of PPD again.
Notice:Make it only after outputting the current charging data by the building
owner,because the integrated value becomes 0 when setting it again.

Daikin Industries, Ltd. CB06A069E


CB06A069E 57/59

[Q & A]

Question Answer
My customer told that an air 1. Is the remote controller used to stop the air conditioner?
conditioner automatically stops. 2. Is another connected concentrated device used to stop the air conditioner?
What are the possible causes? 3. Is the central control panel used to stop the air conditioner?
4. Did power failure occur at the air conditioner location?
→ Unless the indoor unit is configured to restart automatically after power
failure (using the remote controller in the on-site mode), the air
conditioner remains stopped after recovery from power failure.

My customer told that an air 1. Is the remote controller used to start the air conditioner?
conditioner automatically starts. 2. Is another connected concentrated device used to start the air conditioner?
What are the possible causes? 3. Is the central control panel used to start the air conditioner?

My customer told that an air 1. Are the central control panel and Interface for use in BACnet connected
conditioner cannot be controlled from correctly?
2. Is the central control panel functioning?
the central control panel. What are 3. Is the forced stop contact input of the Interface for use in BACnet
the possible causes? activated?
4. Are the air conditioner which cannot be controlled and Interface for use in
BACnet communicated correctly? (Is there any communication error?)

When I connect the previous trial A value and unit of Temperatures displayed on the trial operation(Ver. 6.3.2.0)
will be represented in Celsius.
operation(Ver. 6.3.2.0) to the
software for Interface for use in
(Note)
BACnet main unit in Fahrenheit
version (Ver. 6.33.00), what However, the value of temperatures displayed in "the BACnet history" may not
be shown correctly.
phenomenon happens?
Because the value recorded in Fahrenheit with the software for the main unit
(Ver. 6.33.00) is displayed in the trial operation (Ver. 6.3.2.0), the "value" in
Fahrenheit will be displayed with unit "°C".
For example, the History of changing the set temperature to "70°F" will be
displayed as "70°C".

Daikin Industries, Ltd. CB06A069E


CB06A069E 58/59

[Q & A]

Question Answer
1. Investigate the objections thoroughly.
Objections were made that BACnet  What phenomenon?
communication does not work. (Ex. Can the air conditioner be monitored or controlled? What is its address?
What should I check for? What model? Who is the central control panel manufacturer? What is
the central control panel model? etc.)
 Determine when the communication error occurred.
(Ex. What year, hour, and minute?)
 Determine the frequency of the error.
(Ex. Once a month)
 Determine the object name and its delivery (test operation) date.
→ If you can troubleshoot the cause and determine the counter measure from
the objections, you need not proceed to the following steps.
2. Check if there was any problem in the trial operation with the check record.
(Refer to P.43 - 46.)
3. Check and save data related to BACnet stored in the Interface for use in
BACnet from the trial operation PC.
3-1. Save the BACnet history data in the trial operation PC.
3-1-1. Connect the trial operation PC and Interface for use in BACnet, and
start the trial operation program. Click the BACnet button [1] to open
the following dialog box.
3-1-2. Click the History button [2] and select 10000 [3], and click the Update
button [4].
3-1-3. Click the Text Save button [5] and enter a name which can easily
identify the data. (This data is used by the quality control ,design
dept ., etc. of the factory to analyze the failure when it cannot be
analyzed at the site.)

5
1

(Note) A temperature value conforms to the "Celsius/Fahrenheit setting" of the


Interface for use in BACnet at the time of storing.
A displayed unit conforms to the “Celsius/Fahrenheit setting” of the Interface
for use in BACnet at the time of display.
For this reason, if “Celsius/Fahrenheit setting” of the Interface for use in
BACnet is changed after starting operation at a location, the value and
the unit do not match.

For example, after switching from Celsius to Fahrenheit,


a history before the change is displayed as "a Celsius
temperature" with "°F".

Daikin Industries, Ltd. CB06A069E


CB06A069E 59/59

[Q & A]

Question Answer
Objections were made for the 1. Investigate the objections thoroughly.
Interface for use in BACnet from the  What phenomenon?
(Ex. Can the air conditioner monitored or controlled? What is its address?
site after delivery. What information What model? Who is the central control panel manufacturer? What is the
or data should I correct? central control panel model? etc.)
 Determine when the communication error occurred.
(Ex. What year, month, and day?)
 Determine the frequency of the error.
(Ex. Once a month)
 Determine the object name and its delivery date.
→ If you can troubleshoot the cause and determine the counter measure from
the objections, you need not proceed to the following steps.

2. Check and save data stored in the Interface for use in BACnet from the trial
operation PC.
2-1. Save the BACnet malfunction history data in the trial operation PC.
2-1-1. Connect the trial operation PC and Interface for use in BACnet, and
start the trial operation program. The following dialog box opens.
2-1-2. This dialog box displays history including air conditioner failures and
power ON/OFF status. Check the history and search for data related
to the objections.
2-1-3. Save the malfunction history data in the trial operation PC.
Click the Text Save button [1] and enter a name which can design
dept.,etc. easily identify the data. (This data is used by the quality
control division etc. of the factory to analyze the failure when it cannot
be analyzed at the site.)
The History Reset button [2] erases the malfunction history data stored
in the Interface for use in BACnet. However, because you usually
need not erase the history, do not click this button.
2-1-4. Check and save (if necessary) detailed malfunction history for each D3-
NET communication port in [3].
(Note 1): The malfunction history contains the latest 40 occurrences for
each category in [3] (main unit and ports 1 through 4).
(Note 2): To save the malfunction history, click the Text Save button [1]
for each category in [3] (main unit and ports 1 through 4).
3

1 2

3. Save the BACnet history in the trial operation PC as instructed in Step 3


on the previous page.

Daikin Industries, Ltd. CB06A069E