Sicam PASmanual
Sicam PASmanual
Sicam PASmanual
Overview
This online help provides information on the parameters of the IEC 61850 Client protocol.
Protocol Properties
Interface Properties
Device Properties
List Properties
Information – Monitoring Direction
Information – Command Direction
Template Protocol Description
Template Device Description
Template Information – Monitoring Direction
Template Information – Command Direction
Template General Recording Channels
Template Triggered Recording Channels only
Protocol Properties
You can define the following Protocol properties:
General Parameters
General Parameters
You can define the following General parameters:
Name
Here, you can enter a project-specific designation for the application. When creating the application, the application type is
entered by default.
Type
Application number
If you want to access the same device from different systems, enter a unique number here. This number is required when
creating report control blocks.
(Default value: 1)
Interface Properties
You can define the following Interface properties:
General Parameters
Transmission Parameters
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 2 of 41
General Parameters
You can define the following General parameters:
Name
Under Name, you can enter a unique name for the interface. The name entered here is adopted from the source in the topology.
The Interface name must be unique within an application. SICAM PAS/PQS tolerates identical interface names for different
communication protocols.
NOTE
This name is used as the directory name for protocols that store fault recordings. Therefore, use neither special
characters nor reserved words such as COM[number], LPT[number], CON, PRN, AUX, or NUL.
Description
Description allows you to enter further information about the interface (e.g. to keep a change history).
Redundancy
Under Redundancy, you define whether the communication takes place via a redundant interface. The parameters of the
redundant interface are displayed in an additional column.
Dependency
NOTE
If you set Dependency to Yes (dependent), the automatic switchover only takes place if the connections to all devices
connected to an interface fail. If the connection to one out of several devices fails, the interface remains active and is not
switched over.
If you set Dependency to No (independent), an automatic switchover is performed for this specific device. If the connection to
one subdevice fails, the communication with this device takes place via the redundant interface.
NOTE
If you use a modem splitter or an RTU with communication interface, select dependent.
Transmission Parameters
You can define the following Transmission parameters:
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 3 of 41
GOOSE monitoring
This parameter defines whether GOOSE data can be imported.
If this parameter is set to Yes, you import GOOSE data by selecting the GOOSE column in the Import - select elements dialog.
The GOOSE parameter cannot be changed after the import of GOOSE data. In order to change the setting, you must delete and
re-import the device with selected/unselected GOOSE column.
NOTE
If GOOSE is configured, you must enable the IEC 61850 GOOSE option in the Feature Enabler. Otherwise the
runtime does not start, also not for configured MMS lists.
(Default value: )
The IP address and Subnet mask parameters act as a common network filter for the devices to be imported. All devices
belonging to the same network are preselected in the import selection dialog provided that they comply with the existing
parameterization context (e.g. the redundancy status).
l MMS list
If the default value 0.0.0.0 is used for both parameters, no network filter is applied. All relevant devices are preselected.
l GOOSE list
If the default value 0.0.0.0 is used, no GOOSE data can be imported. Therefore, the GOOSE column has a dark background
in the Import - select elements dialog. GOOSE data is imported only, if it is available in the specified AP (access point).
NOTE
If the IP address has also been assigned using a system configurator such as DIGSI, you must enter the same IP
address here.
Here,the Activate asset monitoring parameter decides whether asset information (list of variables) is retrieved from devices
connected to this interface:
NOTE
Configure the following parameters only on a computer that time zone is set as on the runtime computer, for
example, during commissioning.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 4 of 41
If you select From point in time, only the recordings in the device will be transmitted from the configured point in time. These
settings can be made under Start date and Start time.
(Value range: All, From point in time)
Start date
With this parameter you define the start date from when recordings in the device will be transmitted. Enter a date later than
1.1.1970.
Start time
With this parameter you define the start time from when recordings in the device will be transmitted.
Here, you enter the period for the cyclical request of fault records and PQ data in minutes.
PQ data and fault records are transmitted:
l spontaneous once a fault has occurred, if you use the …$RcdMade telegram address
If you use the information with the …$RcdMade telegram address of the fault recorder for mapping, you will receive the data
once a fault has occurred, independent of the length of the interrogation cycle defined. In this case, Siemens recommends
setting the interrogation cycle to a high value (for example, 120 minutes) to minimize internal processes for providing PQ data
and to keep the system load low.
If you do not use the information with the …$RcdMade telegram address of the fault recorder for mapping, you will only receive
the data after the expiration of the interrogation cycle period. For a contemporary transmission of fault records, select a short
interrogation cycle period (for example, 5 minutes). This increases the system load.
(Default value: 5)
Here, the Activate fault record transmission parameter setting of the devices of this interface is displayed:
Furthermore, you activate or deactivate the fault record transmission for all the devices of this interface.
However, the activation of the fault record transmission can be set for each device of the interface individually.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 5 of 41
If you set Yes, fault records are stored in the Recpro V6-compatible (source) archive whose path is indicated in the Fault record
directory parameter.
If you set No, fault records are stored in the archive of the station (V7). To this end, the Archive application must have been
inserted in the project and configured accordingly.
The parameters concerning Security – TLS encryption define the encryption on the transport layer.
NOTE
Imported certificates are not permissible for encrypting the IEC 61850 application.
Session count
This parameter defines how many messages are to be transmitted with the session keys. The session keys will be renewed
automatically as soon as the Session count (i.e. the maximum number of messages exchanged) has been reached.
The value 0 disables the monitoring function. The disaibling of the monitoring function does not correspond to the standard.
This parameter defines the time period during which the session keys are valid. The session keys will be renewed automatically
as soon as this period has expired.
The value 0 disables the monitoring function. The disabling of the monitoring function does not correspond to the standard.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 6 of 41
This parameter restricts the time in seconds which is required for establishing a secure connection.
If the connection could not be established successfully during the specified time period, the connection is cut again.
(Value range: 0...1 000 000)
Expert Parameters
You can define the following Expert parameters:
l The firmware version of the connected device type: Data can be buffered using this firmware version or later versions.
A specific firmware version (or later) is required for data buffering in the device. For more information on firmware versions
supporting data buffering in the device please contact the device manufacturer.
The firmware version is read from the device during operation and compared with the version indicated in the parameter.
If the firmware version of the device is too old and does not support data buffering, the related feature is deactivated (device and
list).
Use this parameter to adjust the mapping of the disturbed and intermediate position of double-point indications to the individual
telecontrol protocol. This does not affect the mapping of ON and OFF.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 7 of 41
Setting the Command actual/setpoint comparison parameter to No enforces a command output if the setpoint value is equal
to the actual value.
(Value range: Yes, No)
(Default value: Yes)
Setting the Chatter blocking held interface parameter to Yes ensures that messages with the Chatter blocking attribute are
transferred as blocked.
Setting the value of the parameter to No ensures that messages with the Chatter blocking attribute are transferred as not
topical.
Here you define whether the items of information in test mode are routed.
If you select No, the items of information marked as test information are not routed. Commands marked as test information are
acknowledged negatively.
Set the Compatibility keys check to No to skip the compatibility check between IEC 61850 devices and SICAM PAS.
(Value range: Yes, No)
Device Properties
NOTE
Devices that communicate with SICAM PAS/PQS via the IEC 61850 Master application insert in your station
configuration by importing it.
The imported configuration file, which was created with the DIGSI or a third party configuration tool, usually
already contains the correctly parameterized device properties. In most cases, therefore, you will only have to
check the device properties for IEC 61850 devices in the Configuration view, but not change them.
You can check the following Device properties here and adjust them in individual cases:
General Parameters
Communication Parameters
PQ Data and Fault Record Transmission
Security Configuration
Security – TLS Encryption
Expert Parameters
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 8 of 41
General Parameters
You can define the following General parameters:
Name
Name contains a unique name for the device taken from the imported file.
NOTE
When inserting the device, the name of the device template or the name from the import file can be applied by
deleting the content of the name field (e.g. "Device").
The device name must be unique below an interface. Identical devices on different interfaces of the IEC 61850 application can
have the same name.
NOTE
Siemens recommends you link identical devices to SICAM PAS/PQS via different interfaces. This will make re-
importing device configurations easier if required at any time later.
NOTE
Using a special character (e.g. / \ * % ") here may result in problems with fault record transmission.
Device Group
This parameter is used to group devices that all have a similar configuration (parameter, mapping, and topology assignment).
Description
Description allows you to enter further information about the device (e.g. to keep a change history).
Device template
The device template is defined once on inserting the device into the configuration tree.
Import file
NOTE
NOTE
SICAM PAS/PQS supports the import of IEC 61850 Ed. 1 ICD files. Instantiate the ICD files of IEC 61850 Ed. 2
via the IEC 61850 System Configurator to import the resulting IID or SCD files into SICAM PAS/PQS.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 9 of 41
NOTE
For this function, the Report Setting: BufTime writeable communication service must be set to Yes. The
parameter is imported from the SCD file and should not be modified.
Data buffering is deactivated if the firmware version is too old and does not support this feature (see properties of
the Interface, Expert Parameters, Manufacturer and Firmware version parameter).
The SCD device name is the unchangeable name of the device in the SCD file. This is taken as a key for updating enable
unique identification of the device in the SCD file again. On non-Siemens devices, the SCD device name and the device name
are identical.
GOOSE monitoring
This parameter shows whether GOOSE data is imported and the GOOSE monitoring is enabled. This is a non-editable field. In
order to change the setting, update the device with the GOOSE column selected/deselected.
Here you enable the option for opening the device home page of IEC 61850 devices. By default the value is set to Yes for the
devices that support web interface.
NOTE
For third-party devices and SIPROTEC 7KE devices, by default the value is set to No.
Communication Parameters
You can define the following Communication parameters:
IP address
The IP address of the Ethernet communication module in the device.
This address is always preset on importing an IEC 61850 device from a SCD or ICD file.
Port
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 10 of 41
IP subnet mask
Subnet mask of the network via which you can communicate with the IEC 61850 devices
Drop buffered
Here, you enter the time interval between cyclic link test telegrams.
SICAM Q100/Q200
SICAM PAS V6 (Recpro COMTRADE COMTRADE -
Legacy Archive)
SICAM PAS/PQS V7 and COMTRADE COMTRADE COMTRADE, SIPROTEC
later
You can define the following parameters for the transmission of PQ data and fault records:
Here you can activate or deactivate the fault record request for this device.
Here you select how fault records and PQ data are transmitted and stored in the archive.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 11 of 41
If you select MMS, the fault records and PQ data are received from the device via the MMS file transfer and stored in the
archive.
If you select FTP, the fault records are received from the FTP directory of the device via the File Transfer Protocol and stored in
the archive.
FTP port
Here, you enter the TCP/IP port number used for device communication.
FTP directory
Here, you enter the directory path of the device where it internally stores the fault records.
NOTE
Only the SIPROTEC 7KE85 device can transmit SIPROTEC fault records to a SICAM PAS/PQS archive V7 and
later.
Here you activate or deactivate the transmission of PQDIF data from the device.
NOTE
Only SICAM P855, SICAM Q100, and SIPROTEC 7KE85 devices can transmit PQDIF data to a SICAM PAS/PQS
archive V7 and later.
Security Configuration
NOTE
The Security configuration section is only enabled if the Device group parameter Fault record transmission
mode is set to FTP.
Here, you enter the user name which is required for the secure communication with the device.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 12 of 41
NOTE
Authentication password
Cipher selection
If you select Integrity check, the data is transmitted without encryption and only verified for integrity.
If you select Integrity check with encryption, the data is transmitted encrypted and verified for integrity.
If you enter a text here, SICAM PAS/PQS checks during each setup of a connection whether this text is included in the Subject
field of the peer’s certificate.
If you enter a text here, SICAM PAS/PQS checks during each setup of a connection whether this text is included in the Alt.
Subject field of the peer’s certificate.
If you enter a text here, SICAM PAS/PQS compares this text during each setup of a connection with both the peer’s DNS name
and the DNS name indicated on the certificate transmitted by the peer.
If you enter an IP address here, SICAM PAS/PQS compares during each setup of a connection whether the entered IP address
corresponds to both the peer’s IP address and the IP address indicated in the certificate transmited by the peer.
Expert Parameters
The parameter requires the protocol stack to be able to establish the link between the client and the server.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 13 of 41
NOTE
The parameter settings are generally taken from the import files (SCD or ICD files). They should only be changed
if they are obviously incorrect.
This value is transmitted from the SCD on link connection. It should only be edited in rare cases.
This value is transmitted from the SCD on link connection. It should only be edited in rare cases.
(Value range: 0...65 535)
(Default value: 0)
This value is transmitted from the SCD on link connection. It should only be edited in rare cases.
This value is transmitted from the SCD on link connection. It should only be edited in rare cases.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 14 of 41
(Default value: 0)
NOTE
The parameter settings are usually taken from the import files (SCD or ICD files). They rarely require adjustment.
They are only adapted if they are incorrect.
DynAssociation
GetDirectory
GetDataObjectDefinition
Service for retrieving a complete list of all DA definitions of the referenced data that are visible and therefore available to the
querying client via the reference LN (logical node).
(Value range: Yes, No)
DataObjectDirectory
GetDataSetValue
Device supports the GetDataSetValue service.
Service for reading all data value referenced by members of the DATA set.
SetDataSetValue
Service for writing all data value referenced by members of the DATA set.
DataSetDirectory
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 15 of 41
Service for reading FCD (functionally constrained DATA) and FCDA (functionally constrained DataAttributes) from members
referenced in the DATA set.
(Value range: Yes, No)
ConfDataSet
If ConfDataSet is specified, then: the preset for the Max attribute is equal to the number of preconfigured DATA sets and they
can be changed.
If ConfDataSet is not specified, new DATA sets can be configured up to a defined Max value; or preconfigured DATA sets can
be modified via SCL in the configuration.
The Max attribute is defined by the device in its ICD file. In the ICD/SCD it is right next to the ConfDataSet attribute.
DynDataSet
DynDataSet controls whether the client is allowed to create DATA sets during runtime.
NOTE
This value is adopted from the SCD file and cannot be edited.
ReadWrite
TimerActivatedControl
SetControlValue
GetControlValue
SGEdit
SGEdit defines whether setting groups can be changed during runtime or are statically drawn from the SCD file.
GSEDir
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 16 of 41
GOOSE
Device supports the GOOSE service (publishing of Generic Object Oriented Substation Event information).
(Value range: Yes, No)
GSSE
Device supports the GSSE service (publishing of Generic Substation Status Events).
FileHandling
This attribute determines the time that a device waits for further changes before sending a report.
(Value range: Yes, No)
This attribute defines the data set that is evaluated for this report.
(Value range: Yes, No)
This attribute determines the time between 2 lower-level general interrogations if the trigger option Integrity was been selected.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 17 of 41
The device supports the writing of the ResvTms attribute when creating a report.
BufMode
Device supports the Unbuffered Reporting or Buffered Reporting service or both services.
Topology Assignment
Assigned to
This field displays the topological path to which items of information are assigned.
If not all items of information have been assigned in the topology, the project is displayed.
List Properties
NOTE
You must not delete scan lists for IEC 61850 devices that are adopted from the device configuration file on device
import in SICAM PAS/PQS.
MMS List
GOOSE List
MMS List
You can define the following list properties:
General Parameters
Trigger Options
Redundancy Parameters
General Parameters
You can define the following General parameters:
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 18 of 41
Name
Under Name, you can enter a unique name for the list.
Description
Description allows you to enter further information about the list (e.g. to keep a change history).
Type
NOTE
Only lists defined by the user (User-defined MMS list (dataset)) can be changed in SICAM PAS/PQS.
The lists predefined by the device (Device-defined MMS list (dataset), Device-defined GOOSE list (dataset)) can
be changed via the device-specific editing tool.
(Value range: User-defined MMS list (dataset), Device-defined MMS list (dataset), Device-defined GOOSE list (dataset))
The buffer time is the time the device waits for arrival of a spontaneous information item before sending the information item.
This enables further value changes occurring during this buffer time to be transmitted in a report.
NOTE
For this function, the communication parameter Report Setting: BufTime writeable must be set to Yes. The
parameter is imported from the SCD file and should not be changed.
Data buffering is deactivated if the firmware version is too old and does not support this feature (see properties of
the Interface, Expert parameters, Manufacturer and Firmware version parameter).
Only valid if the Integrity parameter is set to Yes under Trigger options.
(Value range: 1...2 147 483)
This option deactivates the old/new comparison in the protocol driver upon the reception of information. This also allows the
cyclic transmission of items of information whose value has not changed.
It is also possible to specify larger intervals for items of information subject to frequent value changes.
l Periodic transmission of the actVal metered value with the Integrity period interval (e. g. 15 min) although the value does
not change.
l To prevent that the value instMag (which changes frequently) is transmitted too often via the Data change trigger option. If
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 19 of 41
this option is ticked, the value can be transmitted periodically or with the Integrity period interval (e. g. 10 s) upon restore.
The cause of transmission is spontaneous even if the value has not changed.
(Value range: Yes, No)
(Default value: No)
Buffered reporting
For user-defined lists, it is possible to choose between buffered and unbuffered reporting here.
If the list has been imported from an SCD file and in pre-defined lists for dynamic reporting, this parameter cannot be changed.
Trigger Options
Under Trigger options you can enter when data are transmitted.
NOTE
The Trigger option parameters can be changed during runtime, if the Report setting:TrgOps writeable
parameter of the device is set to Yes.
Data change
Quality change
Data update
This parameter specifies whether data are transmitted on each freeze, even if no change occurs.
Integrity
This parameter specifies whether the server sends the data of the scan list to the client periodically. The period is defined by the
General parameter Integrity period [s].
General interrogation
This parameter specifies whether a complete value table will be sent during device start-up.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 20 of 41
Redundancy Parameters
NOTE
MMS address
Manufacturing Message Specification
Address of a variables list which has either already been created in the device or is created by the IEC 61850 client (requires the
DynDataSet service).
This list furthermore is an integral part of the Report control block or is entered in this block by the IEC 61850 client (requires
the DynReportControl service).
l @<List> assigns the list to a connection-specific area. (Does not apply to devices that support Buffered Reporting.)
l <DEVICE><LD>/<LNode>$<LIST> assigns the list to a defined logical device. This requires that the LD already exists.
Example: 7SJ63_2Prot/LLN0$Liste1
Report identifier
Unique string that identifies the reports to the receiver. The unique BRCB address is usually used here.
The parameter is imported from the SCD file and should not be changed.
Configuration revision
This version number from the SCD must match the version number in the BRCB of the device. The parameter is imported from
the SCD file and should not be changed.
(Default value: 1)
This parameter specifies with which report control block the list will be connected during runtime.
If you do not make an entry, a report control block will be selected automatically.
Normally the report control block is automatically entered by the SCD import. For automatically created lists, no change should
be made here.
For user-created lists, the entry must remain empty if possible. If an entry is made here, you must search for an unused report
control block for this device in the SCD file and enter its address in the field.
If there are several IEC 61850 clients, it is important to ensure that a report control block is only used by one client. (This is
especially important when copying redundant stations.)
GOOSE List
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 21 of 41
General Parameters
You can define the following General parameters:
Name
A unique list name is shown. The name is generated from IED Name, LDevice inst, and cbName as configured in the imported
SCD file.
NOTE
The configured name must comply the following rules: The first character must be a letter (A-Z or a-z) followed by
letters or numerics. The maximal name length is 115 characters.
Description
Description allows you to enter further information about the list (e.g. to keep a change history).
Type
NOTE
Only lists defined by the user (User-defined MMS list (dataset)) can be changed in SICAM PAS/PQS.
The lists predefined by the device (Device-defined MMS list (dataset), Device-defined GOOSE list (dataset)) can
be changed via the device-specific editing tool.
(Value range: User-defined MMS list (dataset), Device-defined MMS list (dataset), Device-defined GOOSE list (dataset))
GOOSE monitoring
If the parameter is set to Yes, 2 system messages are generated to report the status of the list:
l SysGooseStat_[ListName] indicates whether the GOOSE list is received periodically.
l SysGooseEna_[ListName] indicates whether the publisher has enabled or disabled the list.
Redundancy Parameters
NOTE
The combination of Application ID, Destination MAC address, and GOOSE identifier must be unique within the
system.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 22 of 41
Application ID 1-4
This parameter imported shows the Application ID which is used by the subscriber.
(Value range: 0...16 383)
Dataset 1 - 4
This parameter imported shows the DataSet GOOSE address which is used for this list.
GOOSE identifier 1 - 4
This parameter imported shows the unique identifier that helps the subscriber to identify the GOOSE list.
Configuration revision 1 - 4
This parameter imported shows the configuration revision number which is transmitted in the GOOSE control block. Thus, the
subscriber can check whether the configuration has been changed. The value 0 is provided for special tasks. The configuration
revision number must be identical for both publisher and subscriber.
This parameter imported shows the control block GOOSE address which is used for this list.
This parameter imported shows the multicast MAC address to which the receiver subscribes.
In the LN-State tab, all process information is grouped which describes the state of a Logical Node (LN). The state is influenced
by the DOs (Data Objects) Mod (Mode), Health, and EEHealth (External equipment health) and represented by the DO Beh
(Behaviour). The DO Beh is created automatically by the Slave protocol.
NOTE
The information on the LN state tab are not necessary selected for the correct function.
NOTE
You cannot change table entries with a dark background in the Mapping view. The entries are defined via the
device template.
They can only be changed in the device template. The change is then applied to all devices which are inserted
into the configuration tree based on this device template.
l Showing/Hiding Columns
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 23 of 41
Use
If you activate Use, the information item written in the row is used for transmission.
Name
The following status and statistical messages are created during the import:
Message Meaning
SYS_LastStopError This numerical value is set if the protocol reports an error.
An associated unique Protocol information type is used for transmission with the defined protocol.
In the SICAM PAS/PQS system, a unique Information type is assigned to each Protocol information type.
For each common data class according to IEC 61850-7-3 one or more protocol information types are defined.
The following Protocol information type / Information type combinations are possible:
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 24 of 41
SEQ MF Sequence
SPC_ST SP Single-point control status
SPG_ST SP Single-point setting status
SPS SP Single-point status
STATUS ORG Status indication is generated by PAS
protocol.
WYE MF Phase to ground related measured
values of a 3-phase system
Command assignment
If this information is used as feedback for a command in the monitoring direction, the associated command will be displayed
under Command assignment.
Telegram address
The telegram address contains the MMS communication address as an ASCII string with the following structure:
LogicalDevice/LogicalNode$FunctionalConstraint$DataObject
Position
The position denotes the data attribute within the data object as an ASCII string.
Blocking
This option specifies the effectiveness of bay/telecontrol blocking for each individual item of information.
The following settings are possible:
l Ignore all
Bay and telecontrol blocking are ignored for this item of information.
l Check all
Bay and telecontrol blocking are checked and considered for this item of information.
Bay blocking is checked and considered for this item of information. Telecontrol blocking is ignored.
ReportingCapability
This column entry automatically results from assignment of a value to lists of type Buffered or Unbuffered.
Buffered
Selection of Buffered is only possible if Buffered or Both is output in the ReportingCapability column.
With this parameter, you define the time in milliseconds during which the intermediate position (value 00) of a double-point
indication (infotyp DP) is suppressed. If this time is elapsed and the switch position has not changed to Open or Closed, the
intermediate position is processed. In general, the field unit suppresses the intermediate position.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 25 of 41
The value 0 disables the suppression. The intermediate position is processed immediately.
If the value is set to -1 and the indication is assigned to a command, the appropriate Command monitoring time [ms] is used for
the suppression. If no command is assigned, the intermediate position is not suppressed.
(Value range: -1, 0, 1...60 000)
(List name)
For each list which you have defined under the device in the Configuration view , a column with the same name is shown in the
Mapping view in Monitoring direction.
If you activate the column entry under the list name, the information described in the row will be used for transmission in the list
with the same name.
Normalization
Normalization converts the value of the information item to another value (e.g. for conversion of the value or for measured
value filtering).
Possible normalizations are defined under Normalizations in the Template tree in the Templates view.
NOTE
For more detailed information on normalization, refer to the online help: Configuration > Working with
Normalizations.
MMS address
In the LN-State tab, all process information is grouped which describes the state of a Logical Node (LN). The state is influenced
by the DOs (Data Objects) Mod (Mode), Health, and EEHealth (External equipment health) and represented by the DO Beh
(Behaviour). The DO Beh is created automatically by the Slave protocol.
NOTE
The information on the LN state tab are not necessary selected for the correct function.
NOTE
You cannot change table entries with a dark background in the Mapping view. The entries are defined via the
device template.
They can only be changed in the device template. The change is then applied to all devices which are inserted
into the configuration tree based on this device template.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 26 of 41
l Incorrect Entry
Use
If you activate Use, the information item written in the row is used for transmission.
Name
Commands Meaning
c_sys_ClearSessionManagement This command deletes the session management of the
device in the fault record archive.
NOTE
An associated unique Protocol information type is used for transmission with the defined protocol.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 27 of 41
In the SICAM PAS/PQS system, a unique Information type is assigned to each Protocol information type.
For each common data class according to IEC 61850-7-3 one or more protocol information types are defined.
The following Protocol information type / Information type combinations are possible:
Feedback assignment
This field displays the information that is used as feedback for the command in the monitoring direction.
Telegram address
The telegram address contains the MMS communication address as an ASCII string with the following structure:
LogicalDevice/LogicalNode$FunctionalConstraint$DataObject
Position
The position denotes the data attribute within the data object as an ASCII string.
Interlock
If Interlock is active, SICAM PAS/PQS performs an interlock check before executing the command. The interlock check is
performed by the automation (SoftPLC). If no automation is running, the command is not executed.
States how long the client waits for command transmission from the server. The client then terminates transmission.
Command termination must be signaled within the Command monitoring time [ms].
Blocking
This option specifies the effectiveness of bay/telecontrol blocking for each individual item of information.
l Ignore all
Bay and telecontrol blocking are ignored for this item of information.
l Check all
Bay and telecontrol blocking are checked and considered for this item of information.
Bay blocking is checked and considered for this item of information. Telecontrol blocking is ignored.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 28 of 41
Telecontrol blocking is checked and considered for this item of information. Bay blocking is ignored.
With this selection, you can assign the relevant command to the pool of concurrently executable commands.
The number for the pool of concurrently executable commands can be specified in the Command execution mode parameter
in the properties of the SICAM PAS/PQS project.
Authority check
In this column, you can select for individual commands from devices and substations whether the command output is subject to
a switching authority check.
If the column entry is activated, the switching authority of the topological level to which the information is assigned will become
effective.
Parameters for the switching authority itself can be defined in the Topology view for each structure level.
The AuthorityValue xx switching authority tags are created. The switching authority tags are set during the system runtime by
SICAM SCC, a control center or the Value Viewer with the current value of the switching authority, e. g. Local 1 or Remote 2.
Normalization
Normalization converts the value of the information item to another value (e.g. for conversion of the value or for measured
value filtering).
NOTE
For more detailed information on normalization, refer to the online help: Configuration > Working with
Normalizations.
MMS address
The MMS communication address of the information item is shown here.
General Parameters
General Parameters
The following General parameters are displayed:
Name
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 29 of 41
You can insert new devices in your station configuration at any time by importing SCD or ICD files. You should not use device
templates when creating IEC 61850 devices in your station configuration.
Unlike other protocols, here only one device may be created for each device description.
Devices that were imported via an SCD file are not general templates but instantiated devices that, for example, already contain
an IP address. It is therefore not permissible to create several instances of such a device. To ensure this, the device template is
deleted when the instance is deleted.
The _Iec61850SystemDevice is a virtual device containing system and status indications of the driver. Because this is not a IEC
61850 device, the device template is not deleted when the instance is deleted.
To display the parameters of the device description template, click on the arrow above Properties in the right-hand margin bar
of the SICAM PAS/PQS UI - Configuration. To close the window, click on the arrow again.
General Parameters
Compatibility Keys (1st to 4th Interface)
General Parameters
The following General parameters are displayed:
Name
Under Name, you can enter a unique name for the device description template. The name is displayed in the template tree.
Description
Description lets you display an explanatory text for the device template. (e.g. to keep a change history.)
defaultBRCB
With new lists, the defaultBRCB is automatically entered as the MMS address and as the BRCB address, if
l an unused BRCB is found on importing a device
SCDIedName
SystemDevice
This parameter is used to distinguish the virtual SystemDevice from real devices irrespective of the name of the current
instance of the device.
This parameter is only set to Yes for the _iec61850SystemDevice device template.
ApplicationDefinition
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 30 of 41
Type
The name of the type is shown here.
With a change of the device configuration the version key of the device is changed automatically.
You find out the device compatibility key with the IEC browser.
Logical device
Value
The value of the of compatibility key that is assigned to the Logical device is displayed here.
This category contains the compatiblity keys of the Logical devices that are connected to the secondary interface of the primary
system.
This category contains the compatiblity keys of the Logical devices that are connected to the primary interface of the secondary
system.
This category contains the compatiblity keys of the Logical devices that are connected to the secondary interface of the
secondary system.
You can insert new devices in your station configuration at any time by importing SCD or ICD files. You should not use device
templates when creating IEC 61850 devices in your station configuration.
l Showing/Hiding Columns
l Sorting Information
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 31 of 41
l Incorrect Entry
Name
Message Meaning
SYS_LastStopError This numerical value is set if the protocol reports an error.
In the SICAM PAS/PQS system, a unique Information type is assigned to each Protocol information type.
For each common data class according to IEC 61850-7-3 one or more protocol information types are defined.
The following Protocol information type / Information type combinations are possible:
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 32 of 41
protocol.
WYE MF Phase to ground related measured
values of a 3-phase system
Command assignment
If this information is used as feedback for a command in the monitoring direction, the associated command will be displayed
under Command assignment.
The Feedback assignment is automatically updated under Information - Command direction.
Telegram address
The telegram address contains the MMS communication address as an ASCII string with the following structure:
LogicalDevice/LogicalNode$FunctionalConstraint$DataObject
Position
The position denotes the data attribute within the data object as an ASCII string.
Blocking
This option specifies the effectiveness of bay/telecontrol blocking for each individual item of information.
l Ignore all
Bay and telecontrol blocking are ignored for this item of information.
l Check all
Bay and telecontrol blocking are checked and considered for this item of information.
Bay blocking is checked and considered for this item of information. Telecontrol blocking is ignored.
Telecontrol blocking is checked and considered for this item of information. Bay blocking is ignored.
The following parameter are provided as default values of the MMS addresses which you configure in the Mapping view of the
IEC 61850 Server protocol.
NOTE
If the configuration of an IEC 61850 object is incomplete, the corresponding cell is highlighted in yellow. In
addition, the beginning of the line is also highlighted in yellow.
Example:
The LN (logical node) CSWI requires the stVal and ctlVal DA (data attributes) for the Pos DO (data object). If
only one single DA is configured, the DO cell is highlighted in yellow in order to indicate that the configuration of
the DO is incomplete.
SICAM PAS IEC 61850 Server can also work with incompletely configured objects. Siemens recommends the
complete configuration of the object model.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 33 of 41
l place the cursor of your mouse over the cell highlighted in yellow.
If you click on the warning in this text box, a link will take you directly to the position of the error in the table.
The number of errors is shown in the table footer.
Clicking on Previous or Next takes you straight to the position of the error.
LD Instance
LD Name
Here you can enter the IEC 61850 address information Logical Device.
LN prefix
Here you can enter the IEC 61850 address information Logical Node Prefix.
LN
Here you can enter the IEC 61850 address information Logical Node.
The possible Logical Nodes are defined in the IEC 61850 Edition 2 standard.
LN suffix
Here you can enter the IEC 61850 address information Logical Node Suffix.
FC
Here you can enter the IEC 61850 address information Functional Constraint. The selection of FC depends on the selection of
Logical Node.
The possible Functional Constraint are defined in the IEC 61850 Edition 2 standard.
DO
Here you can enter the IEC 61850 address information Data Object.
The selection of the DO depends on the selection of Logical Node and Functional Constraint.
The possible Data Object are defined in the IEC 61850 Edition 2 standard.
DO instance
Here you can enter the IEC 61850 address information Data Object Instance.
According to the IEC 61850 Edition 2 standard, only specific Data Objects can be created as multiple instances. Hence you can
not enter a value for all parameterized Data Objects.
DA
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 34 of 41
Here you can enter the IEC 61850 address information Data Attribute. The selection of the DA depends on the selection of
Logical Node, Functional Constraint, and Data Object.
The possible Data Attribute are defined in the IEC 61850 Edition 2 standard.
Enum
Here you can enter the IEC 61850 address information Enumeration. The selection of the Enum depends on the selection of
Logical Node, Functional Constraint, Data Object, and Data Attribute.
The possible Enumeration are defined in the IEC 61850 Edition 2 standard.
MMS address
CF parameters
With this parameter you can set additional configuration parameters for the Data Object.
The parameters are described in the IEC norm (IEC 61850-7-3 Table 64-Semantics of Data Attributes and Data).
You can insert new devices in your station configuration at any time by importing SCD or ICD files. You should not use device
templates when creating IEC 61850 devices in your station configuration.
l Showing/Hiding Columns
l Defining User-defined Filters
l Sorting Information
l Incorrect Entry
Name
Commands Meaning
c_sys_ClearSessionManagement This command deletes the session management of the
device in the fault record archive. As a result of this, the IEC
61850 Client requests all fault records of that device again.
c_sys_RetrieveRecords NOTE
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 35 of 41
An associated unique Protocol information type is used for transmission with the defined protocol.
In the SICAM PAS/PQS system, a unique Information type is assigned to each Protocol information type.
For each common data class according to IEC 61850-7-3 one or more protocol information types are defined.
The following Protocol information type / Information type combinations are possible:
Feedback assignment
Here, you select the information used as command feedback in the monitoring direction.
Telegram address
The telegram address contains the MMS communication address as an ASCII string with the following structure:
LogicalDevice/LogicalNode$FunctionalConstraint$DataObject
Position
The position denotes the data attribute within the data object as an ASCII string.
Interlock
If Interlock is active, SICAM PAS/PQS performs an interlock check before executing the command. The interlock check is
performed by the automation (SoftPLC). If no automation is running, the command is not executed.
States how long the client waits for command transmission from the server. The client then terminates transmission.
Command termination must be signalled within the Command monitoring time [ms].
Blocking
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 36 of 41
This option specifies the effectiveness of bay/telecontrol blocking for each individual item of information.
The following settings are possible:
l Ignore all
Bay and telecontrol blocking are ignored for this item of information.
l Check all
Bay and telecontrol blocking are checked and considered for this item of information.
l Check bay blocking
Bay blocking is checked and considered for this item of information. Telecontrol blocking is ignored.
Telecontrol blocking is checked and considered for this item of information. Bay blocking is ignored.
The ’M of N’ check column entry activates the command processing mode for the parameters selected from the list.
With this selection, you can assign the relevant command to the pool of concurrently executable commands.
The number for the pool of concurrently executable commands can be specified in the Command execution mode parameter
in the properties of the SICAM PAS/PQS project.
Authority check
In this column, you can select for individual commands from devices and substations whether the command output is subject to
a switching authority check.
If the column entry is activated, the switching authority of the topological level to which the information is assigned will become
effective.
Parameters for the switching authority itself can be defined in the Topology view for each structure level.
The AuthorityValue xx switching authority tags are created. The switching authority tags are set during the system runtime by
SICAM SCC, a control center or the Value Viewer with the current value of the switching authority, e. g. Local 1 or Remote 2.
The following parameter are provided as default values of the MMS addresses which you configure in the Mapping view of the
IEC 61850 Server protocol.
NOTE
If the configuration of an IEC 61850 object is incomplete, the corresponding cell is highlighted in yellow. In
addition, the beginning of the line is also highlighted in yellow.
Example:
The LN (logical node) CSWI requires the stVal and ctlVal DA (data attributes) for the Pos DO (data object). If
only one single DA is configured, the DO cell is highlighted in yellow in order to indicate that the configuration of
the DO is incomplete.
SICAM PAS IEC 61850 Server can also work with incompletely configured objects. Siemens recommends the
complete configuration of the object model.
l place the cursor of your mouse over the cell highlighted in yellow.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 37 of 41
If you click on the warning in this text box, a link will take you directly to the position of the error in the table.
LD Instance
LD Name
Here you can enter the IEC 61850 address information Logical Device.
LN prefix
Here you can enter the IEC 61850 address information Logical Node Prefix.
LN
Here you can enter the IEC 61850 address information Logical Node.
The possible Logical Nodes are defined in the IEC 61850 Edition 2 standard.
LN suffix
Here you can enter the IEC 61850 address information Logical Node Suffix.
FC
Here you can enter the IEC 61850 address information Functional Constraint. The selection of FC depends on the selection of
Logical Node.
The possible Functional Constraint are defined in the IEC 61850 Edition 2 standard.
DO
Here you can enter the IEC 61850 address information Data Object.
The selection of the DO depends on the selection of Logical Node and Functional Constraint.
The possible Data Object are defined in the IEC 61850 Edition 2 standard.
DO instance
Here you can enter the IEC 61850 address information Data Object Instance.
According to the IEC 61850 Edition 2 standard, only specific Data Objects can be created as multiple instances. Hence you can
not enter a value for all parameterized Data Objects.
DA
Here you can enter the IEC 61850 address information Data Attribute. The selection of the DA depends on the selection of
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 38 of 41
Enum
Here you can enter the IEC 61850 address information Enumeration. The selection of the Enum depends on the selection of
Logical Node, Functional Constraint, Data Object, and Data Attribute.
The possible Enumeration are defined in the IEC 61850 Edition 2 standard.
MMS address
CF parameters
With this parameter you can set additional configuration parameters for the Data Object.
The parameters are described in the IEC norm (IEC 61850-7-3 Table 64-Semantics of Data Attributes and Data).
l Showing/Hiding Columns
l Sorting Information
l Incorrect Entry
Group name
Reverse measurement
With Reverse measurement set to Yes, the signs of the captured signals of a group will be inverted.
Network type
Star, Delta, Monophase, or undefined
Channel name
NOTE
For the SIMEAS R Master application, Channel name is a combination of the R PAR parameters Channel,
Channel Description, and Abbreviation.
Channel index
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 39 of 41
SICAM PAS/PQS can assign correct names to fault record channels for a wide range of devices using built-in default settings.
For non-default channel names you have to specify the name and the channel index explicitly.
The channel index must be unique within the device.
NOTE
The 108 channel index is not available as a fault record channel for the IEC 60870-5-103 Master protocol.
NOTE
This is only valid for the IEC 60870-5-103 Master, SIPROTEC 4 Service IF Master, and SINAUT LSA ILSA Master
applications:
For the channel name settings to take effect the template's general parameter RECORDING_CONFIGURATION
must be set to YES.
More details are available in the section on General Parameters of the Template Device Description.
The channel index is calculated from the Function type and Info number of the information:
Phase
NOTE
For PQDIF import data, the phase must be set depending on the Network type.
For the Star network type, you select the phase-to-ground voltage.
For the Delta network type, you select the phase-to-phase voltage.
Unit
Characteristic
Scaling type
Absolute or relative.
In the case of relative scaling, this is a percentage with reference to the operating value.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 40 of 41
Operational value
The operational value is the desired value defined for system operation. It can deviate from the nominal value.
NOTE
For PQDIF import data, the operational value of the voltage depends on the Network type.
For the Star network type: operational value = nominal value / √3
Averaging time
Time period for the mean value calculation, in seconds.
Default
The default value only needs to be specified in order to define the characteristic, the measured value type and the scaling type
although no other parameter exists for the channel.
Frequency
Frequency of the spectral portion (of the current, voltage, etc.) on which this measurement is based.
Each table row describes an item of information which you can parameterize for Triggered recording channels only.
l Showing/Hiding Columns
l Sorting Information
l Incorrect Entry
Channel name
Channel index
NOTE
This is only valid for the IEC 60870-5-103 Master, SIPROTEC 4 Service IF Master, and SINAUT LSA ILSA Master
applications:
For the channel name settings to take effect the template's general parameter RECORDING_CONFIGURATION
must be set to YES.
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022
IEC 61850 Client Page 41 of 41
More details are available in the section on General Parameters of the Template Device Description.
The channel index is calculated from the Function type and Info number of the information:
Phase
Pickup
SICAM PAS/PQS can calculate the trigger time of the fault record when the fault record is received from the device.
To be able to do this, the channel that indicates that the fault record was triggered (“pickup channel“) must be specified in the
Triggered recording channels only tab.
NOTE
This is only valid for the IEC 60870-5-103 Master, SIPROTEC 4 Service IF Master, and SINAUT LSA ILSA Master
applications:
For the pickup settings to take effect the template's general parameter RECORDING_CONFIGURATION must be
set to YES.
More details are available in the section on General Parameters of the Template Device Description.
Only 1 channel may be set to Y. For all other triggered recording channels, Pickup must be set to N.
(Value range: Y, N)
file:///C:/Users/Administrator/AppData/Local/Temp/2/~hh201D.htm 14/1/2022