Instruction Book

Download as pdf or txt
Download as pdf or txt
You are on page 1of 110

AIF999999

ZR 200
Instruction book
Atlas Copco

ZR 200
AIF999999

Instruction book
Original instructions

COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and
drawings.

This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as
identified in the Declaration of Conformity.

2020 - 11

www.atlascopco.com
Instruction book

Table of contents

1 Safety precautions..........................................................................................................5

1.1 SAFETY ICONS................................................................................................................................... 5

1.2 GENERAL SAFETY PRECAUTIONS............................................................................................................5

1.3 SAFETY PRECAUTIONS DURING INSTALLATION........................................................................................... 6

1.4 SAFETY PRECAUTIONS DURING OPERATION.............................................................................................. 7

1.5 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR........................................................................... 8

1.6 DISMANTLING AND DISPOSAL...............................................................................................................10

2 General description...................................................................................................... 11

2.1 INTRODUCTION.................................................................................................................................11

2.2 AIR SYSTEM.................................................................................................................................... 13

2.3 COOLING AND CONDENSATE DRAIN SYSTEM........................................................................................... 15

2.4 ELEKTRONIKON REGULATED DRAIN (ERD)............................................................................................16

2.5 OIL SYSTEM.................................................................................................................................... 18

2.6 REGULATING SYSTEM........................................................................................................................ 19

2.7 CONNECTIVITY AND SMARTLINK.....................................................................................................21

3 Elektronikon™ Touch controller................................................................................. 24

3.1 CONTROLLER...................................................................................................................................24

3.2 CONTROL PANEL.............................................................................................................................. 26

3.3 ICONS USED.................................................................................................................................... 27

3.4 MAIN SCREEN..................................................................................................................................31

3.5 QUICK ACCESS SCREEN.....................................................................................................................32

3.6 MENU SCREEN.................................................................................................................................33

3.7 DATA MENU.....................................................................................................................................35

3.8 SERVICE MENU................................................................................................................................ 37

3.9 WEEK TIMER MENU...........................................................................................................................39

3.10 EVENT HISTORY MENU.......................................................................................................................40

2 AIF999999
Instruction book

3.11 MACHINE SETTINGS MENU.................................................................................................................. 41

3.12 CONTROLLER SETTINGS MENU.............................................................................................................44

3.13 ACCESS LEVEL.................................................................................................................................47

4 Installation.....................................................................................................................49

4.1 DIMENSION DRAWING........................................................................................................................ 49

4.2 INSTALLATION PROPOSAL................................................................................................................... 51

4.3 INSTALLATION REQUIREMENTS FOR RUBBER COMPENSATORS.....................................................................53

4.4 ELECTRIC CABLE SIZE, FUSES AND CABLE LENGTH.................................................................................. 60

4.5 ELECTRIC CONNECTION..................................................................................................................... 61

4.6 QUALITY OF SAFETY COMPONENTS.......................................................................................................65

4.7 COOLING WATER REQUIREMENTS.........................................................................................................65

4.8 GENERAL PICTOGRAPHS.................................................................................................................... 70

5 Operating instructions................................................................................................. 72

5.1 INITIAL START-UP..............................................................................................................................72

5.2 BEFORE STARTING............................................................................................................................79

5.3 ROUTINE STARTING...........................................................................................................................81

5.4 STARTING AFTER EMERGENCY STOP OR SHUTDOWN................................................................................ 83

5.5 DURING OPERATION.......................................................................................................................... 84

5.6 CHECKING THE DISPLAY.....................................................................................................................85

5.7 MANUAL LOADING/UNLOADING.............................................................................................................86

5.8 STOPPING.......................................................................................................................................87

5.9 TAKING OUT OF OPERATION................................................................................................................88

6 Maintenance.................................................................................................................. 89

6.1 PREVENTIVE MAINTENANCE SCHEDULE..................................................................................................89

6.2 MOTOR GREASING............................................................................................................................ 91

6.3 OIL SPECIFICATIONS..........................................................................................................................92

6.4 STORAGE AFTER INSTALLATION........................................................................................................... 92

AIF999999 3
Instruction book

7 Servicing procedures................................................................................................... 93

7.1 AIR FILTERS.................................................................................................................................... 93

7.2 OIL AND OIL FILTER CHANGE...............................................................................................................94

7.3 SAFETY VALVES............................................................................................................................... 95

7.4 COOLERS....................................................................................................................................... 95

8 Problem solving............................................................................................................97

8.1 PROBLEM SOLVING........................................................................................................................... 97

9 Technical data...............................................................................................................99

9.1 READINGS.......................................................................................................................................99

9.2 SETTINGS OF SAFETY VALVES............................................................................................................. 99

9.3 SETTINGS FOR OVERLOAD RELAY.........................................................................................................99

9.4 REFERENCE CONDITIONS................................................................................................................. 100

9.5 LIMITATIONS.................................................................................................................................. 100

9.6 COMPRESSOR DATA........................................................................................................................101

10 Pressure equipment directives................................................................................. 102

11 Documentation............................................................................................................104

4 AIF999999
Instruction book

1 Safety precautions

1.1 Safety icons

Explanation

Danger to life

Warning

Important note

1.2 General safety precautions


1. The operator must employ safe working practices and observe all related work safety
requirements and regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter
of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized,
trained, specialized personnel. The personnel should apply safe working practices by use of
personal protection equipment, appropriate tools and defined procedures.
4. The compressor is not considered capable of producing air of breathing quality. For air of
breathing quality, the compressed air must be adequately purified according to the
applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks:
• Stop the machine
• Press the emergency stop button
• Switch off the voltage
• Depressurize the machine
• Lock Out - Tag Out (LOTO):
• Open the power isolating switch and lock it with a personal lock
• Tag the power isolating switch with the name of the service technician.
• On units powered by a frequency converter, wait 10 minutes before starting any
electrical repair.
• Never rely on indicator lamps or electrical door locks before maintenance work, always
disconnect and check with measuring device.

If the machine is equipped with an automatic restart after voltage failure function and if
this function is active, be aware that the machine will restart automatically when the
power is restored if it was running when the power was interrupted!

6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at
people. Never use the air to clean dirt from your clothes. When using the air to clean
equipment, do so with extreme caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and
accessories shall be replaced if unsuitable for safe operation.
8. It is prohibited to walk or stand on the unit or on its components.

AIF999999 5
Instruction book

9. If compressed air is used in the food industry and more specifically for direct food contact, it
is recommended, for optimal safety, to use certified Class 0 compressors in combination
with appropriate filtration depending on the application. Please contact your customer center
for advice on specific filtration.

1.3 Safety precautions during installation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during installation


1. The machine must only be lifted using suitable equipment in accordance with the applicable
safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is
strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and
deceleration must be kept within safe limits. Wear a safety helmet when working in the area
of overhead or lifting equipment.
2. The unit is designed for indoor use. If the unit is installed outdoors, special precautions must
be taken; consult your supplier.
3. In case the device is a compressor, place the machine where the ambient air is as cool and
clean as possible. If necessary, install a suction duct. Never obstruct the air inlet. Care must
be taken to minimize the entry of moisture at the inlet air.
4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting
the pipes.
5. Air hoses must be of correct size and suitable for the working pressure. Never use frayed,
damaged or worn hoses. Distribution pipes and connections must be of the correct size and
suitable for the working pressure.
6. In case the device is a compressor, the aspirated air must be free of flammable fumes,
vapors and particles, e.g. paint solvents, that can lead to internal fire or explosion.
7. In case the device is a compressor, arrange the air intake so that loose clothing worn by
people cannot be drawn in.
8. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to
expand under heat and that it is not in contact with or close to flammable materials.
9. No external force may be exerted on the air outlet valve; the connected pipe must be free of
strain.
10. If remote control is installed, the machine must bear a clear sign stating: DANGER: This
machine is remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and depressurized and that the
electrical isolating switch is open, locked and labelled with a temporary warning before any
maintenance or repair. As a further safeguard, persons switching on or off remotely
controlled machines shall take adequate precautions to ensure that there is no one checking
or working on the machine. To this end, a suitable notice shall be affixed to the start
equipment.
11. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is
available and that the exhausted air does not recirculate to the compressor air inlet or
cooling air inlet.

6 AIF999999
Instruction book

12. The electrical connections must correspond to the applicable codes. The machines must be
earthed and protected against short circuits by fuses in all phases. A lockable power
isolating switch must be installed near the compressor.
13. On machines with automatic start/stop system or if the automatic restart function after
voltage failure is activated, a sign stating "This machine may start without warning" must be
affixed near the instrument panel.
14. In multiple compressor systems, manual valves must be installed to isolate each
compressor. Non-return valves (check valves) must not be relied upon for isolating pressure
systems.
15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure must be protected by a pressure relieving device or devices as
required.
16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be
accidentally touched by personnel in normal operation must be guarded or insulated. Other
high temperature piping must be clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to
be protected by a safety device with set pressure according to the maximum cooling water
inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
19. If the device is a dryer and no free extinguishing system is present in the air net close to the
dryer, safety valves must be installed in the vessels of the dryer.

Also consult following safety precautions: Safety precautions during operation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.4 Safety precautions during operation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during operation


1. Never touch any piping or components of the machine during operation.
2. Use only the correct type and size of hose end fittings and connections. When blowing
through a hose or air line, ensure that the open end is held securely. A free end will whip
and may cause injury. Make sure that a hose is fully depressurized before disconnecting it.
3. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes,
vapors or particles.
5. Never operate the machine below or in excess of its limit ratings.

AIF999999 7
Instruction book

6. Keep all bodywork doors shut during operation. The doors may be opened for short periods
only, e.g. to carry out routine checks. Wear ear protectors when opening a door.
On machines without bodywork, wear ear protection in the vicinity of the machine.
7. People staying in environments or rooms where the sound pressure level reaches or
exceeds 80 dB(A) shall wear ear protectors.
8. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not
rubbing
• No leaks occur
• All fasteners are tight
• All electrical leads are secure and in good order
• Safety valves and other pressure relief devices are not obstructed by dirt or paint
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in
good repair, free of wear or abuse
• Air cooling filters of the electrical cabinet are not clogged
9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a
workroom, take precautions against air pollution and possible contamination of the breathing
air.
10. On water-cooled compressors using open circuit cooling towers, protective measures must
be taken to avoid the growth of harmful bacteria such as Legionella pneumophila bacteria.
11. Do not remove any of, or tamper with, the sound-damping material.
12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure shall be protected by a pressure relieving device or devices as
required.
13. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book
must be respected. Local regulations remain applicable if they are more strict.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.5 Safety precautions during maintenance or repair


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during maintenance or repair


1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes,
etc.).
2. Use only the correct tools for maintenance and repair work.

8 AIF999999
Instruction book

3. Use only genuine spare parts for maintenance or repair. The manufacturer will disclaim all
damage or injuries caused by the use of non-genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached
to the starting equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
7. Close the compressor air outlet valve and depressurize the compressor before connecting
or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all
sources of pressure and relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
precautions against toxic vapors of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
covering the parts and exposed openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
completely purged, e.g. by steam cleaning, before carrying out such operations. Never weld
on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is
overheated, the machine shall be stopped but no inspection covers shall be opened before
sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil
vapor when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure
vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they
function properly. They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating
pressures, temperatures and time settings are correct. Check that all control and shut-down
devices are fitted and that they function correctly. If removed, check that the coupling guard
of the compressor drive shaft has been reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of
the oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture
from entering them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on
the bodywork and in the air inlet and outlet systems of the compressor, is in good condition.
If damaged, replace it by genuine material from the manufacturer to prevent the sound
pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate
bowls.
21. Only if applicable, the following safety precautions are stressed when handling
refrigerant:
• Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin
with water. If liquid refrigerant contacts the skin through clothing, never tear off or
remove the latter; flush abundantly with fresh water over the clothing until all refrigerant
is flushed away; then seek medical first aid.

AIF999999 9
Instruction book

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.6 Dismantling and disposal

Dismantling
Once the end of life of the machine is reached, please follow next steps:
1. Stop the machine.
2. Check all safety precautions mentioned in the previous chapters to secure safe handling
(e.g. LOTO, cool-down, depressurize, discharge, ...).
3. Separate the harmful from the safe components (e.g. drain oil from oil containing parts).
4. Refer to the disposal topic mentioned below.

Disposal of electrical and electronic appliances (WEEE)


This equipment falls under the provisions of the European Directive 2012/19/EU on waste
electrical and electronic appliances (WEEE) and may not be disposed as unsorted waste.

The equipment is labelled in accordance with the European Directive 2012/19/EU with the
crossed-out wheelie bin symbol.
At the end of life-time of the electric and electronic equipment (EEE) it must be taken to separate
collection.
For more information check with your local waste authority, customer center or distributor.

Disposal of other used material


Used filters or any other used material (e.g. filter bags, filter media, desiccant, lubricants,
cleaning rags, machine parts, etc.) must be disposed of in an environmentally friendly and safe
manner, and in line with the local recommendations and environmental legislation.

10 AIF999999
Instruction book

2 General description

2.1 Introduction

General views

General view of ZR 160 up to ZR 275 FF

Ref. Name
AO Compressed air outlet
DRa Condensate drain receiver, aftercooler
DRi Condensate drain receiver, intercooler
MK5 Elektronikon Mk5–Touch regulator
SVh Safety valve, high pressure
SVl Safety valve, low pressure
S2 Emergency stop button
WI Cooling water inlet
WO Cooling water outlet

This unit is a two-stage, electric motor driven screw compressor which delivers oil-free, pulsation-
free air.
ZR compressors are water-cooled.
The compressor is enclosed in a sound-insulated bodywork and includes mainly:

AIF999999 11
Instruction book

• Air filter
• Low-pressure compressor element
• Intercooler
• High-pressure compressor element
• Aftercooler
• Water separators
• Electric motor
• Drive coupling
• Gear casing
• ElektronikonTM control system
• Safety valves

Drive arrangement
On ARR E, the motor is flanged to the gear casing by means of a coupling housing. The motor/
gear casing unit is supported on the frame by vibration dampers.

ElektronikonTM control system


The compressor is controlled by an electronic regulator which:
• Controls the operation of the compressor
• Reduces the power consumption
• Warns the operator in case of an abnormal operating condition
• Protects the compressor
• Monitors components subject to service
• If activated, the regulator can automatically restart the compressor after voltage failure

Connections
ANSI flanges

12 AIF999999
Instruction book

2.2 Air system

Flow diagram

Flow diagram of ZR 110 up to ZR 275 and ZR 132 VSD up to ZR 315 VSD compressors

Reference Name
AF Air filter
AO Air outlet

AIF999999 13
Instruction book

Reference Name
AS Silencer
BV By-pass valve
Ca Aftercooler
Ci Intercooler
Co Oil cooler
CV Check valve
Eh High-pressure compressor element
El Low-pressure compressor element
MTa Moisture trap, aftercooler
MTi Moisture trap, intercooler
OF Oil filter
OP Oil pump

Description
Air drawn through the filter (AF) is compressed in the low-pressure compressor element (El).
On ZR compressors, the compressed air is discharged to the intercooler (Ci).
The cooled air is further compressed in the high-pressure compressor element (Eh) and
discharged through the silencer (AS) and aftercooler (Ca).
On ZR/ZT 110 up to ZR/ZT 275, a check valve (CV) is fitted downstream of the silencer.
The compressed air leaves the compressor via the air outlet (AO).

14 AIF999999
Instruction book

2.3 Cooling and condensate drain system

Flow diagram

Flow diagram of ZR 110 up to ZR 275 compressors

Reference Name
AF Air filter
AO Air outlet

AIF999999 15
Instruction book

Reference Name
AS Silencer
BV By-pass valve
Ca Aftercooler
Ci Intercooler
Co Oil cooler
CV Check valve
Eh High-pressure compressor element
El Low-pressure compressor element
MTa Moisture trap, aftercooler
MTi Moisture trap, intercooler
OF Oil filter
OP Oil pump

Cooling system for ZR compressors


The cooling water flows through oil cooler (Co), the cooling jackets of high-pressure compressor
element (Eh) and low-pressure compressor element (El), as well as through intercooler (Ci) and
aftercooler (Ca).

Condensate drain
Two moisture traps are installed: one downstream of the intercooler (MTi) to prevent condensate
from entering compressor element (Eh) and one downstream of the aftercooler (MTa) to prevent
condensate from entering the air outlet pipe.
On ZR/ZT 110 up to ZR/ZT 275, the moisture traps are connected to an ERD, see section
Elektronikon Regulated Drain.

2.4 Elektronikon regulated drain (ERD)

Description
The drain consists of a capacitive sensor which is incorporated in the drain collector and of a pilot
valve which is placed outside the drain collector. A drain opening delay timer is started when the
collector is filled up to the level of the capacitive sensor. As long as the delay timer is running,
extra condensate will be collected and the level will rise even higher than the position of the
sensor. As soon as the delay timer has expired, the pilot valve (normally open) is deactivated and
the diaphragm opens the outlet, discharging the condensate. From the moment that the sensor is
not detecting any condensate anymore, a drain closing delay timer is started. The pilot valve will
still drain the condensate during the run of this timer to make sure that the remaining amount of
condensate is drained. The pilot valve is activated when the timer has expired, the outlet closes
quickly without wasting compressed air.

16 AIF999999
Instruction book

Reference Description
1 Solenoid valve
2 Connector
3 Sensor
4 Bushing
5 Drain receiver

If the controller detects water in the intercooler or aftercooler drain receiver for too long a period,
a shutdown is generated. If water is detected on the integrated dryer drain receiver for too long a
period, a warning is generated.
The level switch is a capacitive sensor which generates a high signal when no water is present.
The solenoid valves of the intercooler and aftercooler/integrated dryer drains are different. The
solenoid valve of the intercooler drain has a high flow but cannot handle high pressures. The
solenoid valve on the aftercooler/integrated dryer drains has less flow but can handle higher
pressures. It is not allowed to open the valves as they can loose their set point. Special attention
must be paid to the correct wiring of the different level switches and solenoid valves.
The output of the level switch can be called up on the screen of the Elektronikon regulator. The
reading does not indicate whether the solenoid valve is open or closed, but indicates whether the
level switch is detecting water in the collector. Since there is a drain opening delay timer, the
display on the Elektronikon can show "Condensate Drain IC Open", while the solenoid valve is
still closed. Changes to the Elektronikon settings are not allowed. The "Always pressurized" bit
must be activated on aftercooler and integrated dryer drains. On the intercooler it is not allowed
to activate this bit.
A functionality test is possible through the Elektronikon regulator. By performing this test, all
solenoid valves will be opened for a short time (e.g. 15 seconds). Refer to the Elektronikon
chapter for more details.

AIF999999 17
Instruction book

2.5 Oil system

Flow diagram

Flow diagram of ZR 110 up to ZR 275 compressors and ZR 132 VSD up to ZR 315 VSD compressors

Reference Name
AF Air filter
AO Air outlet

18 AIF999999
Instruction book

Reference Name
AS Silencer
BV By-pass valve
Ca Aftercooler
Ci Intercooler
Co Oil cooler
CV Check valve
Eh High-pressure compressor element
El Low-pressure compressor element
MTa Moisture trap, aftercooler
MTi Moisture trap, intercooler
OF Oil filter
OP Oil pump

Description
Oil is circulated by pump (OP) from the sump of the gear casing through cooler (Co).
The oil passes through oil filter (OF) towards the bearings and timing gears.
By-pass valve (BV) opens if the oil pressure should rise above a given value.

2.6 Regulating system

General
The regulator keeps the net pressure within programmable pressure limits by automatically
loading and unloading the compressor depending on the air consumption.

AIF999999 19
Instruction book

During unloading

If the air consumption is less than the air delivery of the compressor, the net pressure increases.
When the net pressure reaches the upper limit of the working pressure (unloading pressure),
solenoid valve (Y1) is de-energised. The plunger of solenoid valve (Y1) moves by spring force
shutting off the control air supply to unloader (UA).

Phase Description
1 Control pressure is vented from chamber (1) of unloader (UA) through solenoid valve
(Y1) and chamber (3) towards the inlet of compressor element (El).
2 As there is no longer any pressure difference between chambers (1 and 3), plunger (2)
returns by spring force keeping full-load/no-load valve (TV) closed and unloading valve
(UV) open.
3 Compressed air between check valve (CV) and valve (UV) is blown off through silencer
(US). Check valve (CV) closes.
4 As vacuum prevails in intercooler (Ci), diaphragm (4) switches to the left.

Air delivery is stopped (0%), the compressor runs unloaded.

20 AIF999999
Instruction book

During loading

When the net pressure decreases to the lower limit of the working pressure (loading pressure),
solenoid valve (Y1) is energised. The plunger of solenoid valve (Y1) moves against the spring
force opening the control air supply port to unloader (UA).

Phase Description
1 Atmospheric pressure is allowed through solenoid valve (Y1) to chamber (1) of unloader
(UA). As this pressure is higher than the pressure in chamber (3), full-load/no-load valve
(TV) starts opening.
2 Intercooler pressure is building up causing diaphragm (4) to switch to the right. As the
pressure difference between chambers (1 and 3) increases, plunger (2) moves further
against the spring force until full-load/no-load valve (TV) is fully open and unloading
valve (UV) closed.

Air delivery is resumed (100%), the compressor runs loaded.

2.7 Connectivity and SMARTLINK

General
The machine comes with an Elektronikon Touch controller which has an internal connectivity
device. The Touch controller allows read-out of a number of parameters of the machine on a user
login-protected web site called SMARTLINK. The Touch controller has an integrated antenna.

AIF999999 21
Instruction book

Safety precautions
It is important to follow all regulations regarding the use of radio equipment, in particular
regarding the possibility of radio frequency (RF) interference. Please follow the safety advice
given below carefully.
• Respect restrictions on the use of radio equipment in fuel depots, chemical plants or other
explosive environments.
• Avoid operation close to inadequately protected personal medical devices such as hearing
aids and pacemakers. Consult the manufacturers of the medical device to determine if it is
adequately protected.
• Avoid operation close to other electronic equipment which may also cause interference if the
equipment is inadequately protected. Observe any warning signs and manufacturer
recommendations.
• Respect a distance from the human body of at least 20 cm (8 inch) during operation.
• Do not operate the device in areas where cellular modems are not advised without proper
device certifications. These areas include environments where cellular radio can interfere,
such as explosive atmospheres, medical equipment, or any other equipment which may be
susceptible to any form of radio interference. The modem can transmit signals that could
interfere with this equipment.

SMARTLINK
The machine is SMARTLINK-ready.
SMARTLINK is Atlas Copco’s web-based platform to monitor compressed air installations. It is
available in 3 product levels:
• SMARTLINK Service
SMARTLINK Service rules out all uncertainties. Scheduling maintenance visits becomes as
simple and easy as it should be; the service log book is always just one click away and the
online link with Atlas Copco allows to request and quickly receive quotes for spare parts or
additional services.
This product level is free of charge and available for 3 years following the machine
purchase.
• SMARTLINK Uptime
SMARTLINK Uptime keeps your compressors up and running. By e-mail and/or text, you
receive all relevant machine indications (warnings and shutdowns) in advance. Based on
this information, you can then take all necessary actions and measures to avoid the risk of a
breakdown.
This product level is available as a free of charge 3-month trial.
• SMARTLINK Energy
SMARTLINK Energy safeguards the performance of your equipment. It enables you to
continuously monitor and analyze the energy efficiency of the compressor room. You decide
which performance indicators, benchmarks and reports are created. You can make accurate
and immediate improvements when needed. The results can be used for energy monitoring
according to ISO50001.
This product level is available as a free of charge 3-month trial.
Once a SMARTLINK level is chosen, gaining access is the next step. To gain access at least one
machine SMARTLINK-ready component (compressor, dryer, ...) is required. Follow the next
steps:
• Gather the information about the SMARTLINK-ready machine(s) (e.g. picture of the data
plate; invoice,…)
• Go to the SMARTLINK web site http://www.atlascopco.com/smartlink
• Click on the left button in the screen below.

22 AIF999999
Instruction book

• Use the data of the SMARTLINK–ready machine to register as a user.

• You will receive an e-mail with login credentials.


• Go to the SMARTLINK web site http://www.atlascopco.com/smartlink, log in with the user
credentials.
• Enjoy SMARTLINK!
• In case more SMARTLINK-ready machines are available, you can add these via My Profile.

AIF999999 23
Instruction book

3 Elektronikon™ Touch controller

3.1 Controller

The Elektronikon™ Touch controller

Introduction
The controller has the following functions:
• Controlling the unit
• Protecting the unit
• Monitoring components subject to service
• Automatic restart after voltage failure (ARAVF)

Automatic control of the unit


The controller maintains the net pressure between programmable limits by automatically loading
and unloading the unit (fixed speed units) or by adapting the motor speed (units with frequency
converter).
A number of programmable settings, e.g. the unloading and loading pressures (for fixed speed
units), the setpoint (for units with frequency converter), the minimum stop time, the maximum
number of motor starts and several other parameters are taken into account.
The controller stops the unit whenever possible to reduce the power consumption and restarts it
automatically when the net pressure decreases. If the expected unloading period is too short, the
unit is kept running to prevent too short standstill periods.

A number of time based automatic start/stop commands may be programmed. Take into
account that a start command will be executed (if programmed and activated), even after
manually stopping the unit.

24 AIF999999
Instruction book

Protecting the unit


Shutdown
Several sensors are provided on the unit. If one of the measured signals exceeds the
programmed shutdown level, the unit will be stopped.
Example: If the element outlet temperature exceeds the programmed shutdown level, the unit will
be stopped. This will be indicated on the display of the controller.
The unit will also be stopped in case of overload of the drive motor or fan motor.

Before remedying, consult the Safety precautions.


Before resetting a warning or shutdown message, always solve the problem. Frequently
resetting these messages without remedying may damage the unit.

Shutdown warning
A shutdown warning level is a programmable level below the shutdown level.
If one of the measurements exceeds the programmed shutdown warning level, a message will
appear on the display and the general alarm LED will light up to warn the operator before the
shutdown level is reached.
The message disappears as soon as the warning condition disappears.
When the shutdown warning is shown, press stop button to stop the unit and wait until the unit
has stopped. Switch off the voltage, inspect the unit and remedy if necessary. The warning
message will disappear as soon as the warning condition disappears.

Service warning
A number of service operations are grouped as a Service Plan. Each Service Plan has a
programmed time interval. If the service timer exceeds a programmed value, this will be indicated
on the display to warn the operator to carry out the service actions belonging to that Service Plan.
When the service warning is shown, stop the unit, switch off the voltage and carry out the
required service actions. See section Preventive Maintenance.

Automatic restart after voltage failure (ARAVF)


The controller has a built-in function to automatically restart the unit when the voltage is restored
after voltage failure.
For units leaving the factory, this function is made inactive. If desired, the function can be
activated. Consult your supplier.

If the function is activated and provided the regulator was in the automatic operation
mode, the unit will automatically restart if the supply voltage to the module is restored.
The ARAVF label shall be glued near to the controller.

AIF999999 25
Instruction book

3.2 Control panel

Control panel

Parts and functions

Reference Designation Function


1 Touch screen Shows the unit operating condition and several icons
to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down and is lit in case of a
warning condition.
3 Service sign Lit when service is needed.
4 Operation sign Lit when the unit is running in automatic operation.
5 Voltage sign Indicates that power is switched on.
6 Stop button Stops the unit.
7 Start button Starts the unit. The operation sign (4) lights up. The
controller is operative.

26 AIF999999
Instruction book

3.3 Icons used

Menu icons

Menu Icon Menu Icon Menu Icon


Data Status

Inputs

Outputs

Counters

Aux. Equipment Converters


Parameters

Service Service Overview

Service Plan

Service History

Service
functions

Clean Screen

Week Timer Week

Remaining
Running Time

Event History Saved Data

AIF999999 27
Instruction book

Menu Icon Menu Icon Menu Icon


Machine Alarms
Settings

Regulation

Control
Parameters

Aux. Equipment Converter(s)


Parameters

Fan

Internal
SmartBox

Auto Restart

Controller Network Ethernet


Settings Settings Settings

CAN Settings

Localisation Language

Date/Time

Units

User Password

Help

Information

Status icons

Icon Description
Motor Stopped

28 AIF999999
Instruction book

Motor Stopped Wait

Running Unloaded

Manual Unload

Running Unloaded Wait

Running Loaded

Failed to Load

Running Loaded Wait

Manual Stop

Machine Control Mode, Local

Machine Control Mode, Remote

Machine Control Mode, LAN

Automatic Restart After Voltage Failure

Week Timer Active

System icons

Icon Description
Basic User

Advanced User

Service User

Antenna 25%

AIF999999 29
Instruction book

Antenna 50%

Antenna 75%

Antenna 100%

Change between screens (indication)

Energy recovery

Dryer

Element

Drain(s)

Analogue Output

Menu

Reset

Auto Restart

Filter(s)

Cooler

Valve(s)

Power Meter

Input icons

Icon Description
Pressure

30 AIF999999
Instruction book

Temperature

Special Protection

Open

Closed

This chapter gives a general survey of available icons. Not all icons mentioned in this
chapter are applicable to every machine.

3.4 Main screen

Function
The Main screen is the screen that is shown automatically when the voltage is switched on. It is
switched off automatically after a few minutes when there is no touch input.

Description

Reference Designation Function


1 Home button The home button is always shown and can
be tapped to return to the main screen.
2 Screen information On the main screen, the screen information
bar shows the serial number of the machine.
When scrolling through menus, the name of
the current menu is shown.
3 Access level button The access level button is always shown and
can be tapped to change the current user
access level.

AIF999999 31
Instruction book

Reference Designation Function


4 Alarm button The alarm button can be tapped to show the
current alarms. If an alarm occurs, the icon
on the button will be red.
5 Service button The service button can be tapped to show
the service information.
6 Status This icon shows the current status of the unit.
7 Page indicator Indicates which page you currently see. The
middle indication is the main screen, left is
the menu screen and at the right the quick
access screen.
Swipe left or right to go to another screen.
8, 9, 10, 11 These fields can contain a history chart, an Tap the field to view the type of
input or a counter value, depending on the measurement. This will be shown in the
type of the machine. screen information bar.
Examples of inputs:
• Ambient temp
• Outlet
• Dryer dewpoint
Examples of counters:
• Running hours
• Load relay
• Loaded hours
12 Menu button The menu button is always shown and can
be tapped to go to the menu.

3.5 Quick access screen

Function
The screen is used to directly access some frequently used functions.

Procedure
The Quick access screen can be viewed by swiping left, starting from the main screen.

Description

Through this screen, several important settings can be viewed and modified.

32 AIF999999
Instruction book

Function Description
Setpoints Several setpoints can be modified by tapping this icon.
Control mode The control mode can be changed by tapping this icon.
• Local control via start/stop buttons
• Remote control via digital input(s)
• LAN control via the network.
When in Remote or LAN control, the start/stop buttons on the controller will not work.
Display language The display language of the controller can be changed by tapping this icon.
Manual unload (only When tapped, the machine will go in Manual unload mode until the icon is tapped
on fixed speed units) again.
Week timer Week timers can be set by tapping this icon.
Remaining running The Remaining running time can be set and modified by tapping this icon.
time
Internal SmartBox The reception quality of the internal antenna can be monitored.

Each bar represents 25% reception strength. If the four bars are filled, the reception
strength is 100%. If only one bar is filled, the reception strength is just 25%.
Auto restart Auto restart can be activated by tapping this icon.

3.6 Menu screen

Function
This screen is used to display the different menus where settings can be viewed or changed.

Procedure
The Menu screen can be viewed by tapping the Menu button or by swiping right, starting from the
main screen.

Description

Reference Designation Function


(1) Data The data menu contains the status of the unit, information about the
Inputs, Outputs and Counters. The Auxiliary equipment can also be
viewed through this menu.

AIF999999 33
Instruction book

Reference Designation Function


(2) Service The service menu contains the Service information. The ‘Clean
screen’ function can be used to clean the touchscreen.
(3) Week timer Multiple Week timers and a Remaining running time can be set
through this menu.
(4) Event history In case of an alarm, the Status information of the unit is saved and
can be viewed through this menu.
(5) Machine settings Alarms settings, Regulation settings and Control parameters can be
changed through this menu. Auxiliary equipment parameters can
also be changed.
The Auto restart function can be set through this menu. This function
is password protected.
(6) Controller settings Network settings, Localisation settings and a User password can be
set through this menu. There is also a Help page available and the
Controller information can be shown.

Menu structure
Operating the controller can be done by swiping through screens and tapping icons or menu
items.

This is the main menu structure. The structure can be different depending on the configuration of
the unit.

34 AIF999999
Instruction book

3.7 Data menu

Function
This screen is used to display the following submenus:
• Status
• Inputs
• Outputs
• Counters
• Aux. Equipment
These submenus can be entered by tapping the icons.

Procedure
To enter the Data menu screen:
1. Tap the Menu button
2. Tap the Data icon

Description

Reference Designation
(1) Status menu
(2) Inputs menu
(3) Outputs menu
(4) Counters menu
(5) Auxiliary equipment menu

Status menu
Tap the Status icon to enter the Status menu.

This menu shows the current status of the unit.

AIF999999 35
Instruction book

If an alarm is active, it can be viewed by tapping the alarm message. To reset an alarm, tap the
reset button (1).

Before remedying, consult the Safety precautions.


Before resetting a warning or shutdown message, always solve the problem. Frequently
resetting these messages without remedying may damage the unit.

Inputs menu
Tap the Inputs icon to enter the Inputs menu.

This menu shows information about all the inputs.

Outputs menu
Tap the Outputs icon to enter the Outputs menu.

This menu shows information about all the outputs.

Voltage-free outputs may only be used to control or monitor functional systems.


They should NOT be used to control, switch or interrupt safety related circuits.
Check the maximum allowed load on the label.
Stop the unit and switch off the supply before connecting external equipment. Check the
Safety precautions.

Counters menu
Tap the Counters icon to enter the Counters menu.

36 AIF999999
Instruction book

This menu shows an overview of all actual hours and counters of the unit and controller.

Auxiliary equipment menu


Tap the Aux. Equipment icon to enter the Aux. equipment menu.

This menu shows an overview of all auxiliary equipment fitted.

3.8 Service menu

Function
This screen is used to display the following submenus:
• Service
• Service functions (Only visible as advanced user)
• Clean screen
These submenus can be entered by tapping the icons.

Procedure
To enter the Service menu screen:
1. Tap the Menu button
2. Tap the Service icon

AIF999999 37
Instruction book

Description

Reference Designation
(1) Service
(2) Service functions (Only visible as advanced user)
(3) Clean screen

Service menu
Tap the Service icon to enter the Service menu.

This menu shows the remaining Running Hours and the remaining Real Time Hours until the next
service. The first row (A) shows the Running Hours when the first service is needed (green), the
second row shows the Real Time Hours (blue)
A service overview can be viewed by tapping icon (1).
The service plan can be viewed by tapping icon (2). Through this menu, the service plan can be
modified:
1. Tap the desired service plan. A selection screen will pop up.
2. Change the Running Hours by tapping ‘–’ or ‘+’.
3. Confirm by tapping ‘V’ or decline by tapping ‘X’.
The service history can be viewed by tapping icon (3).
When a service plan interval is reached, a message will appear on the screen. When service has
been performed, the service timer can be reset by tapping the reset button (4).

Service functions (Only visible as advanced user)


Tap the Service Functions icon to enter the Service Functions menu.

38 AIF999999
Instruction book

Depending on the machine, this menu can have a different set of functions. Many of them are
password protected, as they are only accessible for authorized personnel.

Clean screen
Tap the Clean Screen icon to start the 15 seconds countdown to perform cleaning of the
touchscreen.

The touchscreen and the start and stop button become inactive for 15 seconds.

3.9 Week timer menu

Function
This screen is used to set up to 4 different week timers with each up to 8 settings per day.
The week timers can be activated through this screen.
A Remaining Running Time can be set from 5 up to 240 minutes.

Procedure
To enter the Week Timer menu screen:
1. Tap the Menu button
2. Tap the Week Timer icon

AIF999999 39
Instruction book

Description

Reference Designation Function


(1) Add or select week If less than 4 weeks are programmed, tap the ‘+’ button to add a
week.
(2) Remove week Tap to remove a programmed week timer.
(3) Activate week timer A selection screen pops up. The user can choose the correct week
by tapping ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by
tapping ‘X’.
(4) Remaining running A selection screen pops up. The user can change the remaining time
time by tapping ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by
tapping ‘X’.
(5) Add setting A selection screen pops up. The user can change the setting by
swiping up or down and confirm by tapping ‘V’ or decline by tapping
‘X’.

3.10 Event history menu

Function
This screen is used to display the saved data in case of an alarm.
These submenus can be entered by tapping the icons.

Procedure
To enter the Event history menu screen:
1. Tap the Menu button
2. Tap the Event History icon

Description

40 AIF999999
Instruction book

Reference Designation
(1) Saved Data

Saved data
Tap the Saved Data icon to enter the Saved Data menu.

Scroll through the items swiping up and down in this list. The event date and time is shown at the
right side of the screen.
Press on one of the items in the list for more information reflecting the status of the unit when the
shutdown occurred.

3.11 Machine settings menu

Function
This screen is used to display the following submenus:
• Alarms
• Regulation
• Control Parameters
Only visible if the machine has adaptable parameters.
• Aux. Equipment parameters
• Auto Restart
These submenus can be entered by tapping the icons.

Procedure
To enter the Machine settings menu screen:
1. Tap the Menu button
2. Tap the Machine Settings icon

AIF999999 41
Instruction book

Description

Reference Designation
(1) Alarms menu
(2) Regulation menu
(3) Control Parameters menu
(4) Aux. Equipment Parameters menu
(5) Auto Restart menu

Alarms menu
Tap the Alarms icon to enter the Alarms menu.

A list of all alarms is shown.


When pressing on one of the items in this list, the warning and/or shutdown levels are shown for
this alarm.

Regulation menu
Tap the Regulation icon to enter the Regulation menu.

Setpoints or pressure bands can be modified through this menu.


Modify a setting

42 AIF999999
Instruction book

When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

Control parameters menu


Tap the Control Parameters icon to enter the Control Parameters menu.

This menu shows information about the Control Parameters.


Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

Auxiliary equipment parameters menu


Tap the Aux. Equipment Parameters icon to enter the auxiliary equipment parameters menu.

This menu shows an overview of all the auxiliary equipment fitted.


Through this menu, the parameters of the auxiliary equipment can be changed.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

Auto restart menu


Tap the Auto restart icon to enter the Auto Restart menu.

AIF999999 43
Instruction book

Through this menu, the automatic restart can be activated. The activation is password protected.
The automatic restart settings can also be changed.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Modify a setting
When clicking a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

3.12 Controller settings menu

Function
This screen is used to display the following submenus:
• Network Settings
• Localisation
• User Password
• Help
• Information
These submenus can be entered by tapping the icons.

Procedure
To enter the Controller Settings menu screen:
1. Tap the Menu button
2. Tap the Controller Settings icon

Description

44 AIF999999
Instruction book

Reference Designation
(1) Network Settings menu
(2) Localisation menu
(3) User Password menu
(4) Help menu
(5) Information menu

Network settings menu


Tap the Network Settings icon to enter the Network Settings menu.

Ethernet Settings
The list of Ethernet Settings is shown. When ethernet is turned off, the settings can be modified.
CAN Settings
The list of CAN Settings is shown. When CAN is turned off, the settings can be modified.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

Localisation menu
Tap the Localisation icon to enter the Localisation menu.

Language
The language setting of the controller can be modified through this menu.
Date/Time

AIF999999 45
Instruction book

The date and time settings of the controller can be modified through this menu.
Units
The units displayed can be modified through this menu.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

User password menu


Tap the User Password icon to enter the User Password menu.

The user password can be activated or deactivated through this menu. Enter and confirm a user
password to activate, repeat to deactivate.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.

Help menu
Tap the Help icon to enter the Help menu.

This menu can show a link to the web page of your supplier, a helpdesk phone number or other
helpful information.

Information menu
Tap the Information icon to enter the Information menu.

46 AIF999999
Instruction book

This menu shows information about the controller.

3.13 Access level

Function
Through this pop-up screen the access level settings can be viewed or changed.

Procedure
The Access Level screen can be viewed or changed by tapping the Access Level button at the
upper right corner of the screen.

Description

Reference Designation Function


(1) User A basic set of parameters is visualized, no password required.
(2) Service A basic set of parameters can be modified, no password required.
(3) Full This access level is not accessible to end users.
(4) Decline Tap to decline the selected user level.
(5) Confirm Tap to confirm the selected user level.

AIF999999 47
Instruction book

Service access level

Tap the Service access level icon (1) and confirm (2).

The screen information bar (1) now shows the current status of the unit instead of the machine
serial number.
The Received Signal Strength Indicator (RSSI) value is now shown in the Internal SmartBox
menu. See Quick access screen.
In the service menu, an extra menu item is now available. See Service menu.

48 AIF999999
Instruction book

4 Installation

4.1 Dimension drawing

Dimensions

Dimension drawing of ZR 160 up to ZR 275 Pack and ZR 250/315 VSD Pack compressors (in imperial units)

AIF999999 49
Instruction book

Reference Description
1 Right side view
2 Front view
3 Motor cooling air outlet
4 Compressed air inlet
5 Motor cooling air inlet (only for option: separate air intake)
6 Motor cooling air inlet + compressor air inlet (for standard unit)
17 Automatic drain of intercooler G 1/2" (female)
18 Automatic drain of aftercooler G 1/2" (female)
20 Voltage supply: entrance for fixed speed compressors with supply ≤ 690 V
21 Voltage supply entrance:
• for fixed speed compressors with supply > 690 V
• VSD compressors (possibility 1)
• compressors with foot mounted motors
22 Top view
24 Compressed air outlet DN 80 PN 16 acc. DIN 2633 (Scale 1:5)
25 Compressed air outlet 3" 150 Lbs acc. ANSI B16.5 (Scale 1:5)
30 Compressed air outlet
36 Rear side view
37 Grating only for option: separate air intake
38 Voltage supply: entrance for VSD compressors (possibility 2)
41 Opening for transportation
42 4 slotted holes to pull the compressor out of a container
43 Net mass of a standard compressor
44 Net mass of a compressor without a motor
51 Center of gravity Z 160-275
52 Center of gravity Z 250/315 VSD
53 Left side view (for hot air version)
54 Hot air version
55 Standard version
56 Water in/out DN 50 PN 16 acc. DIN 2633 (Scale 1:5)
57 1540 lb should be added in case of a high ambient temperature compressor or an
oversized motor or a motor with supply voltage > 690 V
58 Automatic drain of aftercooler G 1/2" (female) (not for hot air version)

50 AIF999999
Instruction book

4.2 Installation proposal

Compressor room example

Installation proposal for ZR 160 Pack up to ZR 275 Pack (in inch)

(1) Minimum free area to be reserved.


(2) Ventilation proposal.

AIF999999 51
Instruction book

(3) Rear side view.


(4) Ventilation proposal (without option separate air intake).
(5) Ventilation proposal (with option separate air intake).
(6) Common ducting for multiple units is not allowed.
(7) Reverse side view.

Description

The compressor must only be moved or lifted as described in the section Initial start-up.

1. Install the compressor on a level floor suitable for taking its weight. The recommended
minimum distance between the top of the body and the ceiling is 1200 mm (47 in).
2. Remove the plastic plug (if provided) from the compressor air outlet pipe and install an air
outlet valve. Close the valve and connect it to the air net.
3. The maximum total length of the air delivery pipe can be calculated as follows:
For British/American Units:
Lmax= (1470 x d5 x p x dp) / Qc1.85

Symbol Explanation
d Inner diameter of the outlet pipe in inch
dp Pressure drop (recommended maximum = 1.45 psi)
L Length of outlet pipe in ft
p Absolute pressure at the compressor outlet in psi(g)
Qc Free air delivery of the compressor in cfm

It is strongly recommended to make the connection of the compressor air outlet pipe on top
of the main air net pipe in order to minimize carry-over of possible condensate residue.
As a rule of thumb, the following formula can be used to calculate the recommended volume
of the air net:
V = (30 x C x p x Q) / dp

Symbol Explanation
C Correction factor
dp Pressure difference between unloading and loading pressures in bar (recommended
minimum = 0.6)
p Compressor inlet pressure in bar absolute
Q Free air delivery of compressor in l/s
V Recommended air net volume in l

Air consumption divided by compressor free air Correction factor C


delivery
0.9 0.10
0.8 0.15
0.7 0.20

52 AIF999999
Instruction book

Air consumption divided by compressor free air Correction factor C


delivery
0.5 0.25
0.3 0.20
0.2 0.15
0.1 0.10

4. The inlet grids and ventilation fan should be installed in such a way that any recirculation of
cooling air to the compressor is avoided. The maximum air velocity through the grids is 5
m/s (16.5 ft/s).
The required ventilation capacity (per compressor installed) to limit the compressor room
temperature can be calculated as follows:
For ZR compressors:
• For British/American Units: Qv = 284.5 N/dT

Symbol Explanation
dT Temperature increase in compressor room
• For British/American Units: in °F
N Shaft input of compressor
• For British/American Units: in hp
Qv Required ventilation capacity
• For British/American Units: in cfm

If cooling air ducts are installed, the maximum allowable pressure drop over the ducts is 30
Pa (0.12 in wc). Common ducting for several compressors is not allowed.
5. Lay out the drain piping from the condensate outlets towards the condensate collector. The
drain pipes must not dip into the water in the collector. It is recommended to provide a funnel
to allow visual inspection of the condensate flow.
6. Elektronikon control system with control panel.
7. See Electric cable size, fuses and cable length for the recommended size of the supply
cables.
Check that the electrical connections meet local codes. The installation must be earthed and
protected against short circuits by fuses in all phases. An isolating switch must be installed
near the compressor.
8. Install a condensate drain valve in the lower part of the air net piping.
9. On ZR compressors, remove the plastic plugs (if fitted) from the compressor water pipes (WI
and WO) and connect the pipes to the cooling water circuit. Fit a valve in the compressor
water inlet pipe and outlet pipe.

4.3 Installation requirements for rubber compensators

Types and sizes


Atlas Copco oil-free air products with aftercooler are equipped with rubber compensators on the
air outlet and water connections.

Types of misalignments
The supplied compensators can cope with 2 types of minor misalignments when the customer
pipe end is mounted:

AIF999999 53
Instruction book

• Axial ΔL
• Lateral ΔR

Drawing reference Description


A Atlas Copco compressor pipe end
B Customer installation pipe end

Angular misalignments Δα are NOT allowed!

54 AIF999999
Instruction book

Misalignment tolerances
• Single direction misalignments

Axial 1: ΔL in 0.8
Lateral: ΔR in 0.8
Δα2 ° 0
1 = stretch or compression
2 = NO angular misalignment is tolerated!

• Combined direction misalignments

Drawing reference Description


(1) Compression
(2) Stretch

Do NOT operate outside of the black polygon.

Do NOT exceed the misalignment tolerances to avoid compensator damage! The piping
system of the customer should be designed to fit the misalignment tolerances both during
standstill and operation.

Temperature correction factors

Medium temperature Correction factor for maximum working pressure of


(°F) the compensator
32 1

AIF999999 55
Instruction book

Medium temperature Correction factor for maximum working pressure of


(°F) the compensator
122 1
176 1
185 0.92
194 0.83
203 0.75
212 0.67
221 0.6
230 0.54

Torque values
Compensator bolts should be torqued in 3 successive steps
• Step 1: Hand-tighten each bolt.
• Step 2: Torque the bolts crosswise up to the value mentioned in the table below and allow a
stabilization period of 30 minutes before moving to step 3.
• Step 3: Torque the bolts crosswise up to the value mentioned in the table below.

• Mind the parallelism of the sealing.


• Excessive torque will damage the sealing.

DN Step 1 Step 2 Step 3


(inch) (lbfin) (lbfin)
2–3 hand tight 443 708
4 – 12 hand tight 443 885
14 – 20 hand tight 443 1551

Do's and don'ts


The supplied compensators are NOT designed:
• to carry the weight of the mounted customer pipe end.
• to work as a damper for unanchored pipe ends.
• to carry the thrust forces of the compressed air.
Therefore, adequate supporting and anchoring of the customer pipe end should be foreseen to
avoid compensator damage.

56 AIF999999
Instruction book

The compensator loads (Fg and Ft) that are mentioned on the drawing are strictly forbidden:
• Weight loads Fg
• Thrust forces Ft

For the design of piping and supporting structures, use an approved standard code (e.g. EN
13480 or ASME 16.5/B31.3).

Mind that the connected pipe at customer side does not create any flow restriction
caused by e.g. section reduction.

While installing the compensator, please mind the following check points to avoid sealing
damage.

AIF999999 57
Instruction book

Situation Description
A Flat DIN flanges prevent damage of the rubber sealings.
B Collared flanges prevent premature wear.
C Add a flat sealing or if necessary a metal disc with flat seal in case of damage risk.
D Avoid excessive torque to prevent damage to the bended pipes or the sealings.
Rubber sealings will get damaged when the inner pipe diameter exceeds the inner sealing
E diameter.
F Rough pipe ends will damage the rubber sealing.
G Avoid contact between the pipe end and the rubber sealing.

Refer to the pictures below for a visual overview of 5 do's and don'ts when installing rubber compensators:
• WRONG installation!

58 AIF999999
Instruction book

• CORRECT installation!

AIF999999 59
Instruction book

Drawing reference Description


(1) Larger than maximum allowed installation length.
(2) Less than or equal to maximum allowed installation length
(3) Minimum 1 mm of free space

Do NOT:
• Paint the rubber bellows of the expansion joint since:
• Solvents can damage the rubber cover.
• The colored coating avoids decent visual inspection of the rubber condition.
• Weld, cut or grind without protecting the rubber bellows
• Expose the compensator to permanent radiation heat above 90 °C (194 °F)

4.4 Electric cable size, fuses and cable length

General

Local regulations remain applicable if they are stricter than the values proposed below.

The voltage drop must not exceed 10 % of the nominal voltage. It may be necessary to
use cables with a larger size than those stated to comply with this requirement.

CSA/UL compressors
• Cables calculated according to CEC C22.1/NFPA 70
• Multicore cables on perforated tray or ladder system.
• Use 90 °C (194 °F) cables (Type R90, RW90, T90)
• 2 sets of fuses to be placed in series in order to meet the SCCR rating of 65kA (before
model year 2014)
• Cables have to be recalculated if the fuses that are used are bigger than the fuses that are
proposed.

Abbreviation Description
FLA Full Load Ampacity
MCA Minimum Circuit Ampacity
Icc Rated conditional short circuit current
SCCR Short Circuit Current Rating

460 V - 60 Hz CSA/UL
Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE2 motors

Type Fuses LPJ Maximum cable


Cables (90° cable) CEC Fuses RK5 (A) length
C22.1 (A) (m)
2 x (3x MCM 250 + AWG
ZR/ZT 110 3) 2X (3X 175) 2X (3X 600) 193

60 AIF999999
Instruction book

Type Fuses LPJ Maximum cable


Cables (90° cable) CEC Fuses RK5 (A) length
C22.1 (A) (m)
ZR/ZT 145 4 x (3xAWG 000 + AWG 2) 2X (3X 250) 2X (3X 600) 120
ZR/ZT 160 4 x (3xAWG 000 + AWG 2) 2X (3X 250) 2X (3X 600) 120
ZR/ZT 200 4 x (3xAWG 250 + AWG 0) 2X (3X 300) 2X (3X 600) 184
ZR/ZT 250 4 x (3xAWG 300 + AWG 0) 2X (3X 350) 2X (3X 600) 207
ZR/ZT 275 4 x (3xAWG 300 + AWG 0) 2X (3X 350) 2X (3X 600) 207

Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE3 motors

Type FLA MCA Proposed cable Maximum Proposed Maximum SCCR


(mm²) cable fuses (A) fuse (A)
length (m) (LPJ) (LPJ)
ZT/ZR 110 211 233 2 X (3 X00+4AWG) 180 2 x(3 X 600 65 kA
150)
ZT/ZR 145 273 300 2 X (3 X0000+2AWG) 208 2 x(3 X 600 65 kA
200)
ZT/ZR 160 305 336 2 X (3 X0000+2AWG) 183 2 x(3 X 600 65 kA
225)
ZT/ZR 200 365 402 2 X (3 X 300MCM 149 2 x(3 X 600 65 kA
+2AWG) 300)
ZT/ZR 250 425 468 4 X (3 X 00+4AWG) 121 2 x(3 X 600 65 kA
300)
ZT/ZR 275 502 552 4 X (3 X 000+4AWG) 114 2 x(3 X 600 65 kA
350)

FLA and MCA based on an air-cooled full option compressor.


SCCR only achieved with recommended fuses.
FLA and MCA based on an air-cooled full option compressor.
SCCR only achieved with recommended fuses.

4.5 Electric connection

Attention

For the selection of the correct cables, refer to: Electric cable size, fuses and cable
length .

AIF999999 61
Instruction book

Electric connections

Electric connections for compressors with star-delta starter (Model year 2003)

62 AIF999999
Instruction book

Electric connections for compressors with star-delta starter (Model year 2014)

AIF999999 63
Instruction book

Electric connections

Electric connections for compressors with star-delta starter (Model year 2019)

Text on figures

Reference Text on figure


(1) Customer’s installation
(2) K21, K23 larger than or equal to 56 with 6 type “2” fuses
(3) K21, K23 larger than or equal to 56 with 3 type “1” fuses
(4) K21, K23 smaller than 56 with 3 type “2” fuses
(5) Compressor motor
(6) Fan motor, dryer, not for ZR compressors
(7) Fan motor, not for ZR compressors
(8) Fan motor, only for units without compressor motor
(9) To be installed by the customer
(10) Dryer heater
(11) Connection only to be made for CSA/UL
(12) Fan motor in motor hood of ZR/ZT without a motor
(13) Wound anti-clockwise low-pressure side
(14) Wound anti-clockwise high-pressure side
(15) Main motor
(16) Extra set of fuses for CSA/UL certified compressors

64 AIF999999
Instruction book

Reference Text on figure


(17) Customer's motor starter
(18) Separate low voltage supply or transformer
(19) For compressors with motor supply voltage > 690 V
(20) 6 Fuses

4.6 Quality of safety components


When installing a remote emergency button or a motor contactor, the following B10d values are
advised:
• Emergency stop button: 500 000
• Main contactor: 933 333

4.7 Cooling water requirements

General
Cooling water needs to fulfill requirements in order to avoid problems of scaling, fouling,
corrosion or bacterial growth. No general recommendation can encompass the effects of all
combinations of the various compounds, solids and gases typically found in cooling water in
interaction with different materials. Therefore the recommendations formulated in our cooling
water specifications are a general guide line for acceptable coolant quality. However, where strict
limits apply, a statement is made in the specification.
The water requirements refer to untreated water. When water is treated, some parameters will
change. Water treatments should be carried out by a specialized water treatment company,
taking the responsibility for the performance of the treated cooling water and the compatibility
with the materials in the cooling circuit. This includes not only the selection of the appropriate
additives, but also the correct application, monitoring of concentrations and properties, prevention
of sludge formation and maintenance of the system. This applies also to treatment with anti-
freeze products. They should be provided with suitable stabilizers and inhibitors.
Specifications also depend on the criteria mentioned below:
• the type of cooling circuit:
• open
• Single Pass

• recirculation with cooling tower

AIF999999 65
Instruction book

• closed loop

Reference Description
(1) Machine
(2) Heat exchanger
(3) Cooling tower
(4) Make up water
(5) Blowdown
(6) Standard Atlas Copco specification

• the application:
• standard (max water temperature 65°C / 149°F at the outlet)
• Energy Recovery (water temperature up to 95°C / 203°F)

Water quality
A full instruction for handling cooling water data is available at Atlas Copco.
In case water is not in line with recommended values or if any doubt, please refer to Atlas Copco.

Technical specifications

Parameter Unit Single Pass Single Pass Recirculating Closed Closed


(65°C / (95°C / (65°C / 149°F) System System
149°F) 203°F) (65°C / (95°C /
149°F) 203°F)
1 pH 6.8 - 9.3 6.8 - 9.3 6.8 - 9.3 7.5 - 9.3 7.5 - 9.3
2 Conductivity µS / cm < 1500 < 600 < 4000 < 1500 50 - 600
3 Total Dissolved mg / L TDS to be measured for calculating RSI.
Solids
4 Ca-hardness ppm < 500 <2 < 500 < 1000 < 50
CaCO3

66 AIF999999
Instruction book

Parameter Unit Single Pass Single Pass Recirculating Closed Closed


(65°C / (95°C / (65°C / 149°F) System System
149°F) 203°F) (65°C / (95°C /
149°F) 203°F)
5 Total Alkalinity ppm No limits indicated. To be measured for calculating RSI.
CaCO3
6 Ryznar Stability 5.6 - 7.5 N.A. 5.6 - 7.5 5.6 - 7.5 5.6 - 7.5
Index (RSI)
7 Chlorine ppm < 0.5 — < 0.5 — —
8 Chlorides ppm < 500 (*) < 100 < 500 (*) < 500 (*) < 100
9 Nitrates ppm No limits indicated. To be measured for calculating RSI.
10 Sulphates ppm < 1000 < 200 < 1000 < 400 < 200
11 Chemical <5 <1 <5 <1 <1
Corrosion Index
12 Iron ppm <1 < 0.2 <1 <1 < 0.2
13 Manganese ppm < 0.2 < 0.05 < 0.2 < 0.2 < 0.05
14 Copper ppm <1 < 0.2 <1 <1 < 0.2
15 Ammonium ppm < 0.5 < 0.5 < 0.5 < 0.5 < 0.5
16 Suspended ppm < 10 <1 < 10 < 10 <1
Solids (max
10µ)
17 Oil or Grease ppm <1 <1 <1 <1 <1
18 Biology CFU / < 10 5 < 10 3 < 10 5 < 10 3 < 10 3
mL

Remarks on the technical specifications

Parameter Remarks
1 pH For stainless steel systems without other materials, pH can be
down to 6.
For closed loop systems, higher pH values are possible
2 Conductivity Conductivity and TDS linked with conversion factor (theoretical
factor possible, but practical determination recommended at
least once)
6 Ryznar Stability Index (RSI) Recommended actions : see table for RSI
7 Chlorine or shock treatment max. 2 ppm for 30 min/day
8 Chlorides (*) Limit 200 ppm applicable when RSI < 5.6 or RSI > 7.5
10 Sulphates Rejection < 2000 ppm. To be measured for calculating RSI.
11 Chemical Corrosion Index Index = (Chlorides + Sulphates + Nitrates) / (M-Alkalinity) (all
expressed in meq/l)
15 Ammonium limit not applicable for Cu-free systems
16 Suspended Solids (max No particles > 10µ allowed. (Particles <0.5µ not considered).
10µ)
18 Biology Anaerobic biology in closed system never allowed.

AIF999999 67
Instruction book

Ryznar Stability Index (RSI)


The Ryznar Stability Index (RSI) is a parameter for predicting whether water will tend to dissolve
or precipitate calcium carbonate. The adhesion of scaling deposits and their effect are different
on different materials, but the equilibrium of the water (scaling or corrosive) is only determined by
its actual pH value and by the saturation pH value (pHs).
The saturation pH value is determined by the relationship between the calcium hardness, the
total alkalinity, the total solids concentration and the temperature.
The Ryznar Stability Index is calculated as follows :
RSI = 2*pHs - pH

Symbol Explanation
pH Measured pH (at room temperature) of water sample
pHs pH at saturation

The pHs is calculated by using :


pHs = (9.3 + A + B) - (C + D)

Symbol Calculation
A (10log(TDS) - 1) / 10
B 13.12 x 10log(°C+273) + 34.55
C 10

log(Ca2+) - 0.4 (Ca2+ expressed as ppm CaCO3)


D 10

log(M-Alkalinity) (M-Alkalinity expressed as ppm CaCO3)

RSI and chloride limitation


Single Pass system

RSI Chloride Water condition Maximum 65°C / Maximum 95°C / 203


limit 149°F °F
RSI<3.9 200 ppm Very high scale formation Water cannot be used. Not applicable.
4.0<RSI<5.5 200 ppm High scale formation Regular control and Not applicable.
descaling operation
necessary.
Not recommended for
plate heat exchangers
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not Not applicable.
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not Water treatment not
necessary. necessary.
Occasional inspection Occasional inspection
recommended. recommended.

68 AIF999999
Instruction book

RSI Chloride Water condition Maximum 65°C / Maximum 95°C / 203


limit 149°F °F
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not Water treatment not
necessary. necessary.
Occasional inspection Occasional inspection
recommended. recommended.
7.6<RSI<9.0 200 ppm Strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation
9.1<RSI<11 200 ppm Very strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation
RSI>11 200 ppm Very strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation

Recirculating system, with cooling tower

RSI Chloride Water condition Maximum 65°C / 149°F


limit
RSI<3.9 200 ppm Very high scale formation Water cannot be used.
4.0<RSI<5.5 200 ppm High scale formation Regular control and descaling
operation necessary.
Not recommended for plate
heat exchangers
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not
necessary.
Occasional inspection
recommended.
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not
necessary.
Occasional inspection
recommended.
7.6<RSI<9.0 200 ppm Strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
9.1<RSI<11 200 ppm Very strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
RSI>11 200 ppm Very strong corrosion Water cannot be used.

AIF999999 69
Instruction book

Closed loop system

RSI Chloride Water condition Maximum 65°C / 149°F and


limit 95°C / 203°F
RSI<3.9 200 ppm Very high scale formation Water cannot be used.
4.0<RSI<5.5 200 ppm High scale formation Treat water to reduce scaling
character
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not
necessary.
Occasional inspection
recommended.
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not
necessary.
Occasional inspection
recommended.
7.6<RSI<9.0 200 ppm Strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
9.1<RSI<11 200 ppm Very strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
RSI>11 200 ppm Very strong corrosion Water cannot be used.

4.8 General pictographs

Pictographs

Reference Name
1 Condensate valve, intercooler
2 Automatic condensate outlet, intercooler
3 Automatic condensate outlet, aftercooler
4 Condensate valve, aftercooler
5 Warning: under tension
6 Read Instruction manual before starting the compressor
7 Switch off the voltage and depressurize the compressor before maintenance or repair

70 AIF999999
Instruction book

Reference Name
8 Before connecting the compressor electrically, consult the Instruction manual for the
motor rotation direction
9 Torques for steel (Fe) or brass (CuZn) bolts
10 Consult the Instruction manual before greasing
11 Switch off the voltage before removing the protecting cover inside the electric cabinet
12 Oil the gaskets, screw on the filters and tighten by hand (approx. one half turn)
13 Consult the Instruction manual before maintenance or repair
14 Cooling water outlet
15 Cooling water inlet
16 Unit is remotely controlled and can start without warning (ARAVF)

AIF999999 71
Instruction book

5 Operating instructions

5.1 Initial start-up

Safety precautions

The operator must apply all relevant Safety precautions.

Ambient conditions / altitude opeartion


Refer to Limitations for the limits of ambient conditions and altitude operation. If the compressor
is operated beyond these limits, precautions must be taken. If this is the case, consult your Atlas
Copco Customer Center.

Moving/lifting
In order not to damage the frame, the compressor must be moved either by a lift truck or by using
lifting equipment as described below.
When moving the compressor with a lift truck, use the slots in the frame. Make sure that the forks
protrude from the other side of the frame. When moving the compressor with a lifting device,
insert beams in the slots. Make sure that the beams cannot slide and that they protrude from the
frame equally. The chains must be held parallel to the bodywork by chain spreaders in order not
to damage the compressor. The lifting equipment must be placed in such a way that the
compressor is lifted perpendicularly. Lift gently and avoid twisting.

General preparation
Make sure that the compressor is installed correctly.
See Dimension drawing, Installation proposal and Electric cable size, fuses and cable length.
A sticker summarizing the operating instructions is delivered with the compressor. Affix the
sticker next to the control panel.
A number of VCI (Volatile Corrosion Inhibitor) plates are available inside the bodywork to protect
the compressor against corrosion during transport. Remove these plates.

Protection during transport


The compressor and motor are secured to the frame, immobilizing the vibration dampers during
transport. All transport fixtures are painted red and must be removed.

72 AIF999999
Instruction book

Transport fixtures on the motor side in ZR/ZT 110 up to ZR/ZT 275

On the motor side, the dampers are secured by means of bolts/spacers. Remove the bolts and
spacers (1 and 2).

Transport fixtures on the gear casing side in ZR/ZT 110 up to ZR/ZT 275

On ZR/ZT 110 up to ZR/ZT 275, a transport support (1) is fitted to the gear casing. Remove the
support.

AIF999999 73
Instruction book

Silica gel bags

Position of silica gel bags on ZR 160 up to ZR 275

Remove flange (1) and take out the silica gel bags. Refit the flange.

Water circuit of ZR compressors

Water drain plug, HP element of ZR 110 up to 275

74 AIF999999
Instruction book

Water drain plug, LP element of ZR 110 up to 275

Water drain plugs, coolers of ZR 110 up to 275

Water drain plug, cooler block of ZR 110 up to 275

AIF999999 75
Instruction book

Water drain plug, oil cooler of ZR 110 up to 275

Step Action
1 Fit the water drain plugs (DP2 up to DP6) that are attached to the water pipe of one of
the compressor elements (El and Eh) in a plastic bag. The plugs are painted green and
their positions are shown on the illustrations above.
2 Check that the cooling water drain valves (customer's installation) in the inlet and outlet
lines are closed.
3 Open the water inlet valve and outlet valve (customer's installation) and check for water
flow.
4 Check the water flow.

76 AIF999999
Instruction book

Oil circuit

Position of oil level sight-glass on ZR 110 up to ZR 275

Check that oil is visible in sight-glass (SG).

AIF999999 77
Instruction book

Start-up

Electric cabinet of compressor with starter

1. Check that the voltage selecting wires on transformer T1 are connected correctly. An
instruction label is provided.
2. Check that the electrical installation meets local regulations.
3. On compressors with a starter, check the overload relay setting (F21) and check that the
relay is set for automatic resetting.
See Settings for overload relay.
Switch on the voltage.
4. Check that the gear casing is filled with oil.
5. Start the motor and stop it immediately.
6. Check that the direction of rotation is correct (as indicated by the arrow): anti-clockwise
looking at the motor drive shaft (there may also be an arrow on the coupling housing). A
grating through which the coupling can be observed is fitted. If the direction of rotation is
wrong, switch off the voltage and reverse two electric inlet connections.
7. Run the compressor for a few minutes.
8. Stop the compressor and check the oil level.
On ZR/ZT 110 up to ZR/ZT 275, the oil level after stopping must be in the middle of the
sight-glass (in the case of longer standstill, the oil level in the sight-glass may increase).
Top up, if necessary, with the correct type of oil.

78 AIF999999
Instruction book

5.2 Before starting

The operator must apply all relevant Safety precautions.


If the water system has been drained, close the drain valves and fit the drain plugs or
pipe.

Oil level

Oil system components, ZR 110 up to ZR 275

On ZR/ZT 110 up to ZR/ZT 275, the oil level must be in the middle of the sight-glass (SG) after
stopping (in the case of longer standstill, the oil level may increase in the sight-glass).
Top up, if necessary, with the correct type of oil.

AIF999999 79
Instruction book

Condensate drains

Drain connections on ZR 160 Pack up to ZR 275 Pack

Reference Description
AO Compressed air outlet
Daa Automatic drain, aftercooler
Daea Automatic drain, extra aftercooler (for Energy Recovery option only)
Dai Automatic drain, intercooler
WI Water inlet
WO Water outlet

Open the water inlet valve and outlet valve (customer's installation).

On ZR compressors, opening of the water outlet valve can be overlooked if, after
previous operation, the setting of this valve has not been disturbed.

80 AIF999999
Instruction book

5.3 Routine starting

Control panel

Control panel of Elektronikon controller

AIF999999 81
Instruction book

Procedure

Step Action
1 Open the air outlet valve (customer's installation).
2 Switch on the voltage and check that voltage on sign (5) lights up.
3 Press start button (7). The compressor starts running in unloaded condition and
operation sign (4) lights up.
4 Approx. 25 seconds later (programmable), the compressor starts running loaded.
5 Regulate the water flow with the compressor running loaded. The aim is to obtain a
cooling water temperature rise over the complete compressor unit of 15 K.

See section Readings for the cooling water temperature.


See section Compressor data for the cooling water consumption.

If the motor is stopped and operation sign (4) is alight, the motor may start
automatically.
If the start/stop timer is active, the compressor can start automatically, even if it was
stopped manually.

82 AIF999999
Instruction book

5.4 Starting after emergency stop or shutdown

Control panel

Control panel of controller

Procedure

Step Action
1 Press the emergency stop button (if not yet done).
2 Switch off the voltage and then depressurize the compressor.
3 Remedy the fault.
4 Unlock the emergency stop button by pulling it back.
5 Reset the protection warning in the Elektronikon controller.
6 Restart the compressor. Check the section Routine starting.

If the automatic restart function after voltage failure is activated and the duration of
repair is shorter than the programmed power recovery time, reset the display after
remedying the fault.

Minimum stop time


The compressor will not be allowed to restart within a programmed time (20 s) after a stop for any
reason at all. A start command given during the minimum stop time will be memorized; operation
sign (4) lights up. The compressor will start when the minimum stop time has run out.

AIF999999 83
Instruction book

Manual restart
In automatic operation, the regulator limits the number of motor starts.

5.5 During operation

Control panel

Control panel of Elektronikon controller

Procedure

When operation sign (4) is alight, starting and stopping of the motor is automatically
controlled: when the motor is stopped, it may restart automatically.

Step Action
1 Check the readings on the touchscreen (1).
2 When reaching the preset unloading pressure, shown on the touchscreen (1), the
compressor will start running unloaded. From now on, the electronic control module will
calculate the optimum moment to stop and restart the compressor motor automatically,
depending on the maximum permissible number of motor starts and on the air
consumption.
3 To unload the compressor manually, select Unload on the touchscreen.
To put the compressor back into automatic operation, select Load on the touchscreen.

84 AIF999999
Instruction book

5.6 Checking the display

Control panel

Control panel of controller

Procedure
1. Regularly check the display for readings and messages. Normally, the main display is
shown.
2. Always check the display and remedy the trouble if warning sign (2) is alight or blinks.
The display will show a service message if a service plan interval has been exceeded or if a
service level for a monitored component has been exceeded. Carry out the service actions
of the indicated plans or replace the component and reset the relevant timer.
Regularly check the Inputs and Outputs menus for a quick look at the compressor status.

AIF999999 85
Instruction book

5.7 Manual loading/unloading

Control panel

Control panel of controller

General
Normally, the compressor runs in automatic operation, i.e. the electronic regulator loads, unloads,
stops and restarts the compressor automatically. Sign (4) is then alight.
If required, the compressor can be unloaded manually. In this case, the compressor is switched
out of automatic operation i.e. the compressor remains running unloaded unless it is loaded
again manually.

Manual unloading
Starting from the main screen, select Unload. The compressor starts running unloaded and sign
(4) fades. The message Manual Unload appears on the display.

Manual loading
Starting from the main screen, select Load. Sign (4) lights up and the compressor starts running
loaded in case the air net pressure drops below the programmed level. The message Load
appears on the display.

86 AIF999999
Instruction book

5.8 Stopping

Control panel

Control panel of Elektronikon controller

Procedure

The operator must apply all relevant safety precautions.


Frequently stopping the compressor using the emergency stop button may damage the
compressor. Only use the emergency stop button in case of emergency.

Step Action
1 Press stop button (6). The compressor will run unloaded for 3 seconds and then stop.
2 Close the air outlet valve.
3 To stop the compressor in case of emergency, press the emergency stop button.
Warning sign (2) starts flashing. After remedying the trouble, unlock the emergency stop
button by pulling it back.
4 Close the cooling water inlet valve after stopping.

If the compressor is installed in a room where freezing temperatures are


expected, drain the cooling system completely:
• By opening the main drain valves in the water inlet and outlet pipes (customer's
installation).
• By removing drain plugs. Refer to Initial start-up for the position of the plugs.

AIF999999 87
Instruction book

5.9 Taking out of operation

Procedure
At the end of the service life of the compressor, proceed as follows:

Step Action
1 Close the air outlet valve and stop the compressor.
On compressors with an Elektronikon regulator, press the emergency stop button.
2 Switch off the voltage and disconnect the compressor from the mains.
3 Shut off and depressurize the part of the air net which is connected to the outlet valve.
4 Disconnect the compressor air outlet pipe from the air net.
5 Drain the oil and condensate circuits. Catch the oil in a receptacle.
6 Disconnect the compressor condensate piping from the condensate drain net.
7 On ZR compressors, drain the cooling water system and disconnect the cooling water
pipes from the compressor.

88 AIF999999
Instruction book

6 Maintenance

6.1 Preventive maintenance schedule

Safety precautions

• Before starting any maintenance or repairs, stop the compressor.


• Depressurize the air system as follows:
• Close the air outlet valve.
• Press the emergency stop button.
• On compressors equipped with Electronic Water Drains (EWD), press the
test buttons on top of the electronic water drains.
• Open the isolating switch (customer's installation) to switch off the voltage to the
compressor, and lock it (Lock Out - Tag Out procedure, LOTO).
• Repairs inside the speed regulation cabinet must only be carried out by Atlas
Copco.
• Wait at least 6 minutes before starting any electrical repairs as hazardous high
voltage remains on the condensers of the variable speed drive for 6 minutes after
switching off the voltage.
• The operator must apply all relevant safety precautions.

Service agreements
Atlas Copco Customer Centers have a range of service agreements to suit your needs:
• An Inspection plan
• A Preventive maintenance plan
• A Total responsibility plan
Contact your Customer Center to agree on a tailor-made service agreement. It will ensure
optimum operational efficiency, minimize downtime and reduce the total life cycle costs and
ensure that all warranties are validated.

Warranty-Product Liability
Use only authorized parts at the correct intervals (check with your local Atlas Copco Service
center). Any damage or malfunction caused by the use of unauthorized parts or unqualified
personnel is not covered by Warranty or Product Liability. In the event of any extended warranty,
the end user must ensure that all required maintenance actions are performed when indicated on
the Elektronikon display (see table below) or, alternatively, use an Atlas Copco Service
agreement.

Service kits
Atlas Copco Customer Centers will be glad to provide you with a wide range of service kits.
Service kits comprise all parts needed for servicing components and offer the benefits of genuine
Atlas Copco parts while keeping the maintenance budget low.

Regular checks
The following checks should be carried out regularly to ensure safe operation and long service
life. Depending on the environmental and working conditions of the compressor, the local Atlas

AIF999999 89
Instruction book

Copco Service center may overrule the standard maintenance schedule; always check if in
doubt.
Please keep following checks in mind:
• Regularly test the water drains

Period Running hours Operation


-- At initial start Check the dryer adjustment as specified in Initial start-up .
Daily 8 Check the Elektronikon display for warnings.
Check that condensate is discharged from the drain receivers
Daily 8
during loading.
Before stopping:
Daily -- • Drain the aftercooler drain receiver
• Drain the intercooler drain receiver
Weekly -- Check the oil level. Refer to Before starting .
Weekly -- Drain condensate from the air receiver, if installed.
Check for leaks. Tighten leaking connections and replace
Weekly --
damaged/leaking parts.
3-monthly -- Clean compressor.
3-monthly 500 Check coolers, clean if necessary.
2-yearly 16000 Replace the demister sponge of the integrated dryer.
2-yearly 16000 Inspect the dryer heater
2-yearly 16000 Inspect the dryer rotor
Carry out service actions according to the displayed service
When displayed --
warnings or service plans as shown below.

• When operating in a dusty atmosphere, inspect the air filters more frequently. Always
use Atlas Copco filters to guarantee the performance of your compressor.
• Grease the motor bearings at the correct interval and with the correct grease type and
quantity as mentioned on the motor data plate. If in doubt, consult your Atlas Copco
Service center.

Service plan
A number of service operations are grouped (called level A, level B, level C, ...). Each level
stands for a number of service actions to be carried out at the time intervals programmed in the
Elektronikon regulator.
When a level is reached, a message will appear on the screen. After carrying out all service
actions, reset the interval timers using the "Reset" key in the "Service" menu.

Activities Level A Level B Level C


Take service readings (air, oil, water temperature and X X X
pressure)
Check cooler functions (approach temperature) and clean if X X X
necessary
Change intercooler condensate check valve X X X
Check intercooler blowdown valve X X X
Check for air, water and oil leakage X X X

90 AIF999999
Instruction book

Activities Level A Level B Level C


Check critical bolt/coupling connections X X X
Check operation of safety valves X X X
Check for presence of water in lube oil X X X
Change Roto Z oil (16000 hrs or 2-yearly) - - X
Inspect/change air filter element(s) X X X
Check condition of air intake chamber X X X
Change compressor oil filter (4000 hrs or annually) X X X
Replace filter element of gear case breather X X X
Check cycle of air intake throttle valve X X X
Replace diaphragm of air throttle valve X X
Overhaul air intake valve X
Check functioning of check valve (8000 hrs or annually) X X X
Overhaul check valve X
Check condition of balance piston diaphragm X X -
Change balance piston diaphragm - X X
Check/Service condensate drain(s) X X X
Overhaul drain(s) - X X
Grease main drive motor bearings (according to motor data X X X
plate)
Clean fan cowl of electric motor X X X
Check rubber inserts of drive coupling (arr. E) X X
Replace inserts of drive coupling (arr. E) X
Check condition of drive gear teeth X X
Take and record all S.P.M. readings. On VSD compressors X X X
also register the motor speed
Inspect electrical contactors X X X
Check all electrical connections X X
On VSD compressors, if applicable, replace motor carbon X
brush
On VSD compressors, if necessary, clean electrical cabinet X X X
with vacuum cleaner
Check oil quantity X X X
Replace shaft seal - - X

6.2 Motor greasing

General

Stop the compressor and follow the LOTO procedure (Lock Out - Tag Out) (refer to
General Safety Precautions) before greasing.
Never mix greases of different brands or types.

AIF999999 91
Instruction book

Main motor bearings


Refer to the motor re-greasing data plate for the recommended grease type, the greasing
quantity and interval for the motor bearings.

Fan motor bearings of ZT compressors


The bearings of the fan motor are greased for life.

6.3 Oil specifications

Roto-Z lubricating oil


Use Atlas Copco Roto-Z oil which is specially developed for oil-free rotary compressors. This oil
has a long service life and ensures optimum lubrication.
Atlas Copco Roto-Z oil can be ordered in following quantities:

Quantity (US gal) Ordering number


1.32 US gal can 2908 8503 00
5.28 US gal can 2908 8501 01
55.18 US gal drum 2908 8500 00

6.4 Storage after installation


Run the compressor, e.g. twice a week, until warm.
If the compressor is going to be stored without running from time to time, protective measures
must be taken. Consult Atlas Copco.

92 AIF999999
Instruction book

7 Servicing procedures

7.1 Air filters

Location of the air filters

Air filter of ZR/ZT 110 up to ZR/ZT 275

Procedure

The filters must be serviced regularly; consult section Preventive maintenance schedule.
Never install damaged or clogged filters.

Procedure for ZR/ZT 110 up to ZR/ZT 275 and ZR/ZT 132 VSD up to ZR/ZT 315 VSD

Step Action
1 Stop the compressor and press the emergency stop button.
2 Switch off the voltage and follow the LOTO procedure. (Refer to the Safety Precautions
before acting.)
3 Remove nuts (1).
4 Loosen clamps (2).
5 Take out filter housing (3) with filter element (4).
6 Replace the dirty filter element with a new one.
7 Put the filter housing with the filter element back into place.
8 Tighten clamps (2) and nuts (1).
9 Switch on the voltage.
10 Unlock the emergency stop button and reset the air filter service warning.

AIF999999 93
Instruction book

7.2 Oil and oil filter change

Oil system

Oil system components, ZR 110 up to ZR 275

Procedure

Step Action
1 Run the compressor until warm.
2 Stop the compressor.
Press the emergency stop button.
3 Switch off the voltage and follow the LOTO procedure. (Refer to the Safety Precautions
before acting.)
4 The filler plug and drain points are painted yellow.
Remove filler plug (FC). Drain the compressor sump by opening drain valve (Dmo).
On ZR compressors, drain the oil cooler by opening drain valve (Dmc).
Close the drain valves and tighten the drain plugs after draining.
5 Remove the oil filters (OF). Clean the filter seats, oil the gaskets of the new filters and
screw the filters into place until the gaskets contact the seats. Then tighten by hand.
6 On ZR 110 up to ZR 275, fill the compressor sump to the middle of the oil level sight-
glass (SG).
See Oil specifications for the correct type of oil.
7 Reinstall the filler plug.
8 Switch on the voltage.
Unlock the emergency stop button and reset the oil and oil filter service warnings.
9 Run the compressor for a few minutes.
10 Stop the compressor.

94 AIF999999
Instruction book

Step Action
11 On ZR 110 up to ZR 275 and ZT 110 up to ZT 275, check that the oil level is in the
middle of sight-glass (SG) after stopping (at longer standstill the level may rise in the
sight-glass).
Top up, if necessary.

7.3 Safety valves

Testing
The valves can be tested on a separate compressed air line. If a valve does not open at the
pressure specified in Settings of safety valves, consult Atlas Copco.

Never run the compressor without safety valves.


No adjustments are allowed.

7.4 Coolers

Testing

The coolers must be serviced regularly; refer to Preventive maintenance schedule .


Never install damaged or clogged coolers.

AIF999999 95
Instruction book

Coolers of water-cooled Full-Feature compressors

Drawing reference Description


AC Aftercooler
AC (ER) Extra aftercooler in case of the energy recovery option
IC Intercooler
OC Oil cooler
RC Regeneration cooler (only on Full-Feature compressors)

Keep the coolers clean to ensure cooling efficiency.

96 AIF999999
Instruction book

8 Problem solving

8.1 Problem solving


• Before starting any maintenance or repairs, stop the compressor.
• Depressurize the air system as follows:
• Close the air outlet valve.
• On compressors equipped with Electronic Water Drains (EWD), press the
test buttons on top of the electronic water drains.
• Press the emergency stop button.
• Open the isolating switch (customer's installation) to switch off the voltage to the
compressor, and lock it (Lock Out - Tag Out procedure, LOTO).
• Repairs inside the speed regulation cabinet must only be carried out by Atlas
Copco.
• Apply all relevant safety precautions.
• Wait at least 6 minutes before starting any electrical repairs as hazardous high
voltage remains on the condensers of the variable speed drive for 6 minutes after
switching off the voltage.

Control panel

Control panel of controller

Faults and remedies

Condition Fault Remedy


Compressor starts running,
Pressure in air net is above Compressor will load when pressure in air
but does not load after a delay
pre-set loading pressure net drops to pre-set loading pressure
time

AIF999999 97
Instruction book

Condition Fault Remedy


Loading solenoid valve
Check and replace the valve as necessary
inoperative
Full-load/no-load valve
Have the valve inspected
malfunctioning
Compressor capacity or
Air consumption exceeds
working pressure lower than Check pneumatic plant
capacity of compressor
normal
Check for leaks. Tighten leaking
Leaking connections and
connections and replace damaged/leaking
damaged/leaking parts
parts.
Top up level as described in section Before
Oil pressure too low Oil level too low
starting.
Oil filters clogged Replace filters
Inlet temperature too high due
Improve ventilation in compressor room
Air temperature above normal to bad room ventilation or
and prevent recirculation of cooling air
recirculation of cooling air
On ZR compressors, Check water temperature and increase
insufficient cooling water flow cooling water flow
On ZR compressors,
restriction in cooling water
Consult the Atlas Copco Customer Center
system due to formation of
scale or dirt deposits
Unloading pressure incorrectly
Check the controller setting.
set
Condensate is not discharged
from condensate traps during Drain/pipe clogged Check and correct
operation
Frozen drain piping Check and correct
Venting lines not/badly
Check and correct
assembled
Only on IC drain : intercooler
condensate check valve
Check and correct
defect/dirty/wrongly
assembled
Solenoid valve defect/dirty Check and correct
Manually operated solenoid
Set valve to automatic operation
valve
Level sensor defect/dirty Clean sensor or replace as necessary
Damaged/poor assembled
Drain continuously discharges
condensate drain (housing/ Check and correct
air
seals/valve/…)
Solenoid valve defect/dirty Check and correct
Level sensor defect/dirty Clean sensor or replace as necessary

98 AIF999999
Instruction book

9 Technical data

9.1 Readings

Important

The readings below are indicative values when operating at reference conditions. Check
the section Reference conditions. These values are no rejection limits. In case of doubt,
consult your Atlas Copco Customer Center.

For the maximum working pressure and the outlet pressure, consult the section Compressor
data.
Pressure readings

Item Reading
dp of air filter Below 0.64 psi
Intercooler pressure (loaded condition) 24.6-43.5 psig
Intercooler pressure (unloaded condition) (-9.43)-(-10.15) psig
Oil pressure (depends on climatic conditions) 26.1-50.8 psig

Temperature readings for ZR compressors

Item Reading
Oil temperature Approx 104 ˚F
Air outlet temperature Approx. 77 ˚F
Cooling water inlet temperature Below 104 ˚F
Cooling water outlet temperature Below 122 ˚F

9.2 Settings of safety valves

Item Opening pressure


Low-pressure safety valve(s) for 7 up to 10.4 bar (101.5 up to 54 psig
151 psi) compressors
High-pressure safety valve(s) for 7 and 8.6 bar (101.5 and 125 135 psig
psi) compressors

9.3 Settings for overload relay

60 Hz compressors
ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE2
motor

AIF999999 99
Instruction book

Supply voltage Recommended overload setting F21


(V) (A)
460 209

ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE3
motor

Supply voltage Recommended overload setting F21


(V) (A)
460 197

9.4 Reference conditions

Absolute inlet pressure 14.5 psi(a)


Ambient temperature 68 °F
Air inlet temperature 68 °F
Effective working pressure 102 psi(g) for 102/109/125 psi compressors
Temperature of cooling medium (water or air) inlet 68 °F
Temperature rise of cooling water of ZR Pack 27 °F
compressors
ZR / ZT 160-275
Motor shaft speed for 60 Hz fixed speed compressors 1780
(rpm)

9.5 Limitations
Minimum - maximum ambient temperature (for 32- 104 °F
standard compressors)
Minimum - maximum temperature of air inlet (for 32- 104 °F
standard compressors)
Maximum altitude 3281 ft
Minimum temperature of cooling medium (water or 32 °F
air) inlet
Maximum temperature of cooling air inlet (for 104 °F
standard compressors)
Maximum temperature of cooling water inlet - open 104 °F
circuit
Maximum temperature of cooling water outlet 122 °F
Maximum rise of cooling water temperature (for up to 63 °F
compressors without Energy Recovery)
Maximum pressure of cooling water inlet 145 psi(g)
Minimum - maximum oil pressure 17.4–65.3 psi(g)

100 AIF999999
Instruction book

Minimum - maximum oil temperature (for standard 32- 158 °F


compressors)

Working pressure: Minimum- Pack


Maximum (psi(g))
125 psi - 50/60 Hz 58–125

Item Reading in psi(g)


Pressure drop over air filter Below 0.64
Intercooler pressure (loaded condition) 24.6-43.5
Intercooler pressure (unloaded condition) (-9.43)-(-10.15)
Oil pressure (depends on climatic conditions) 17.4-65.3

9.6 Compressor data


ZR compressors

Temperature Reading
Oil Approx. 104 ˚F
Outlet of low pressure stage 248-428 °F
Outlet of high pressure stage 212-428 °F
Air outlet Approx. 77 ˚F
Inlet of cooling water Below 104 ˚F
Outlet of cooling water Below 122 ˚F

Oil quantity in the lubrication system of the compressor

Compressor type US gal


ZR 160, ZR 200, ZR 250, ZR 275 15.85

AIF999999 101
Instruction book

10 Pressure equipment directives


ZR 160 Pack up to ZR 275 Pack compressors are a pressure assembly of cat. II according to
2014/68/EU.
Parts of article 4.3 of 2014/68/EU are subject to Sound Engineering Practice (SEP).
Parts of category I according to 2014/68/EU are integrated into the machine and fall under the
exclusion of article 1.2, (f)(i).
Parts subject to the Simple Pressure Vessel Directive 2014/29/EU are excluded from 2014/68/EU
according to article 1.2 (c).

The following pressure bearing parts are of category higher than I :

Compressor type Pressure bearing part


ZR/ZT 110 up to ZR/ZT 275 Safety valve: Category IV
• Design code: AD-Merkblätter, A2
ZR 160 up to ZR 275 Compressor
Heat exchanger at compressed air side (aftercooler)
• Design pressure 13.7 bar(e)
• Design code: ASME BPVC section VIII div. 1.
• Volume 17.6 l.
ZR/ZT 160 up to ZR/ZT 275 IMD 600
Compressed air dryer vessel
• Category IV
• Design pressure 11 bar(e)
• Design code: ASME BPVC section VIII div. 1.
• Material (housing and cover): SA-395.
• When pressurized, vessel remains under pressure.

Heat exchanger ZR 160 up to ZR 275

102 AIF999999
Instruction book

Reference Name
1 Intercooler
2 Aftercooler
3 Position of data plate

Heat exchanger ZR 160-275


PED Category CAT II
Design code ASME BPVC Section VIII, div 1
Material SA-395
Bolts 8.8
Interval of periodic 5 years or the frequency as given in national legislation
inspection by 3rd
party (1)
Intercooler Aftercooler
Casting factor 0.8 0.8
Minimum wall Covers : 8 mm Covers : 8 mm
thickness after Shell : 10 mm Shell : 10 mm
corrosion
Shellside Tubeside Shellside Tubeside
Medium Water, group 2 Air, group 2 Water, group 2 Air, group 2
Volume 92 l 21.4 l See intercooler 17.6 l
Design pressure 15 bar 4.5 bar 15 bar 13.7 bar
Design temperature 95 °C 240 °C 95°C 240 °C

(1) The maintenance instructions given in the user manual must be applied by the user.

AIF999999 103
Instruction book

11 Documentation

Declaration of conformity
Typical example of a Declaration of Conformity document

(1): Manufacturer
(2): Applicable directives
(3): Standards used
(4): Technical file holder

104 AIF999999
Instruction book

(5): Contact address of the manufacturer


On the Declaration of Conformity, the harmonized and/or other standards that have been used
for the design are shown and/or referred to.
The Declaration of Conformity is part of the documentation that is supplied with this device.

AIF999999 105
We stand by our responsibilities towards our customers, towards the environment and
the people around us.
We make performance stand the test of time.
This is what we call - Sustainable Productivity.

Atlas Copco Airpower


Oil-free Air Division, Boomsesteenweg 957, 2610 Wilrijk, Belgium
Phone: +32 (0)3 870 21 11

Atlas Copco Airpower NV. All rights reserved. Designs and specifications are subject to change without notice or obligation.

You might also like