Modbus Protocol Reference Guide
Modbus Protocol Reference Guide
Modbus Protocol
Reference Guide
PI–MBUS–300 Rev. J
1
Modicon
Modbus Protocol
Reference Guide
PI–MBUS–300 Rev. J
June 1996
DOK- 3
www.PAControl.com
Preface
This guide is written for the person who will use Modicon Modbus protocols and
messages for communication in Modicon programmable controller applications.
It describes how messages are constructed, and how transactions take place
using Modbus protocol.
This guide should be used in conjunction with Modicon user guides for the types
of networks and programmable controllers present in the application. Familiarity
with your network layout, and with your control application, is assumed.
The data and illustrations in this book are not binding. We reserve the right to
modify our products in line with our policy of continuous product improvement.
Information in this document is subject to change without notice and should not
be construed as a commitment by Modicon, Inc., Industrial Automation Systems.
Modicon, Inc. assumes no responsibility for any errors that may appear in this
document. If you have any suggestions for improvements, or have found any
errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means,
electronic or mechanical, without the express written permission of Modicon, Inc.,
Industrial Automation Systems. All rights reserved.
The following are trademarks of Modicon, Inc.:
Modbus 984 P190 SM85
ModConnect BM85 RR85 SQ85
Modcom BP85 SA85
www.PAControl.com
Related Publications
Refer to the following publication for details about the application of Modicon 984
Programmable Controller systems:
Refer to the following publications for details about the application and installation
of the Modbus Plus network and related communications devices:
Refer to the following publication for details about the Modcom III Communications
Software Library for host computer applications:
www.PAControl.com
Contents
www.PAControl.com
Chapter 2 Data and Control Functions . . . . . . . . . . . . . 17
www.PAControl.com
Chapter 3 Diagnostic Subfunctions . . . . . . . . . . . . . . . . 73
Function 08 – Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Diagnostic Codes Supported by Controllers . . . . . . . . . . . . . . . . . . . . . . . . 76
Diagnostic Subfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
00 Return Query Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
01 Restart Communications Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
02 Return Diagnostic Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
03 Change ASCII Input Delimiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
04 Force Listen Only Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10 (0A Hex) Clear Counters and Diagnostic Register . . . . . . . . . . . . . . . 81
11 (0B Hex) Return Bus Message Count . . . . . . . . . . . . . . . . . . . . . . . . . . 82
12 (0C Hex) Return Bus Communication Error Count . . . . . . . . . . . . . . . 82
13 (0D Hex) Return Bus Exception Error Count . . . . . . . . . . . . . . . . . . . . 82
14 (0E Hex) Return Slave Message Count . . . . . . . . . . . . . . . . . . . . . . . . 83
15 (0F Hex) Return Slave No Response Count . . . . . . . . . . . . . . . . . . . . 83
16 (10 Hex) Return Slave NAK Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
17 (11 Hex) Return Slave Busy Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
18 (12 Hex) Return Bus Character Overrun Count . . . . . . . . . . . . . . . . . 84
19 (13 Hex) Return IOP Overrun Count (884) . . . . . . . . . . . . . . . . . . . . . 84
20 (14 Hex) Clear Overrun Counter and Flag (884) . . . . . . . . . . . . . . . . . 85
21 (15 Hex) Get/Clear Modbus Plus Statistics . . . . . . . . . . . . . . . . . . . . . 86
Modbus Plus Network Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Exception Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Exception Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
PI–MBUS–300 Contents ix
www.PAControl.com
Figures
x Contents PI–MBUS–300
www.PAControl.com
Figure 28 Force Multiple Coils – Query . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 29 Force Multiple Coils – Response . . . . . . . . . . . . . . . . . . . . . . 45
PI–MBUS–300 Contents xi
www.PAControl.com
Chapter 1
Modbus Protocol
www.PAControl.com
Introducing Modbus Protocol
Modicon programmable controllers can communicate with each other and with
other devices over a variety of networks. Supported networks include the Modicon
Modbus and Modbus Plus industrial networks, and standard networks such as
MAP and Ethernet. Networks are accessed by built–in ports in the controllers or
by network adapters, option modules, and gateways that are available from
Modicon. For original equipment manufacturers, Modicon ModConnect ‘partner’
programs are available for closely integrating networks like Modbus Plus into
proprietary product designs.
The common language used by all Modicon controllers is the Modbus protocol.
This protocol defines a message structure that controllers will recognize and use,
regardless of the type of networks over which they communicate. It describes the
process a controller uses to request access to another device, how it will respond
to requests from the other devices, and how errors will be detected and reported.
It establishes a common format for the layout and contents of message fields.
The Modbus protocol provides the internal standard that the Modicon controllers
use for parsing messages. During communications on a Modbus network, the
protocol determines how each controller will know its device address, recognize a
message addressed to it, determine the kind of action to be taken, and extract any
data or other information contained in the message. If a reply is required, the
controller will construct the reply message and send it using Modbus protocol.
On other networks, messages containing Modbus protocol are imbedded into the
frame or packet structure that is used on the network. For example, Modicon
network controllers for Modbus Plus or MAP, with associated application software
libraries and drivers, provide conversion between the imbedded Modbus message
protocol and the specific framing protocols those networks use to communicate
between their node devices.
This conversion also extends to resolving node addresses, routing paths, and
error–checking methods specific to each kind of network. For example, Modbus
device addresses contained in the Modbus protocol will be converted into node
addresses prior to transmission of the messages. Error–checking fields will also
be applied to message packets, consistent with each network’s protocol. At the
final point of delivery, however – for example, a controller – the contents of the
imbedded message, written using Modbus protocol, define the action to be taken.
www.PAControl.com
Figure 1 shows how devices might be interconnected in a hierarchy of networks
that employ widely differing communication techniques. In message transactions,
the Modbus protocol imbedded into each network’s packet structure provides the
common language by which the devices can exchange data.
HOST
PROCESSOR
MAP
984–685
(TO MB PLUS) P230
MODBUS
AND PROGRAMMER
MODBUS PLUS
AT/MC–984 984A/B
AND AND BM85
HOST/MMI S985
MODBUS MODBUS
UP TO FOUR
P230 MODBUS DEVICES
PROGRAMMER OR NETWORKS
www.PAControl.com
Introducing Modbus Protocol (Continued)
The master can address individual slaves, or can initiate a broadcast message to
all slaves. Slaves return a message (called a ‘response’) to queries that are
addressed to them individually. Responses are not returned to broadcast queries
from the master.
The Modbus protocol establishes the format for the master’s query by placing into
it the device (or broadcast) address, a function code defining the requested action,
any data to be sent, and an error–checking field. The slave’s response message
is also constructed using Modbus protocol. It contains fields confirming the action
taken, any data to be returned, and an error–checking field. If an error occurred in
receipt of the message, or if the slave is unable to perform the requested action,
the slave will construct an error message and send it as its response.
www.PAControl.com
At the message level, the Modbus protocol still applies the master–slave principle
even though the network communication method is peer–to–peer. If a controller
originates a message, it does so as a master device, and expects a response from
a slave device. Similarly, when a controller receives a message it constructs a
slave response and returns it to the originating controller.
Eight–Bit Eight–Bit
Data Bytes Data Bytes
The Query: The function code in the query tells the addressed slave device what
kind of action to perform. The data bytes contain any additional information that
the slave will need to perform the function. For example, function code 03 will
query the slave to read holding registers and respond with their contents. The
data field must contain the information telling the slave which register to start at
and how many registers to read. The error check field provides a method for the
slave to validate the integrity of the message contents.
The Response: If the slave makes a normal response, the function code in the
response is an echo of the function code in the query. The data bytes contain the
data collected by the slave, such as register values or status. If an error occurs,
the function code is modified to indicate that the response is an error response,
and the data bytes contain a code that describes the error. The error check field
allows the master to confirm that the message contents are valid.
www.PAControl.com
The Two Serial Transmission Modes
The selection of ASCII or RTU mode pertains only to standard Modbus networks.
It defines the bit contents of message fields transmitted serially on those networks.
It determines how information will be packed into the message fields and decoded.
On other networks like MAP and Modbus Plus, Modbus messages are placed into
frames that are not related to serial tranasmission. For example, a request to read
holding registers can be handled between two controllers on Modbus Plus without
regard to the current setup of either controller’s serial Modbus port.
ASCII Mode
www.PAControl.com
RTU Mode
www.PAControl.com
Modbus Message Framing
In either of the two serial transmission modes (ASCII or RTU), a Modbus message
is placed by the transmitting device into a frame that has a known beginning and
ending point. This allows receiving devices to begin at the start of the message,
read the address portion and determine which device is addressed (or all devices,
if the message is broadcast), and to know when the message is completed.
Partial messages can be detected and errors can be set as a result.
On networks like MAP or Modbus Plus, the network protocol handles the framing
of messages with beginning and end delimiters that are specific to the network.
Those protocols also handle delivery to the destination device, making the
Modbus address field imbedded in the message unnecessary for the actual
transmission. (The Modbus address is converted to a network node address and
routing path by the originating controller or its network adapter.)
ASCII Framing
In ASCII mode, messages start with a ‘colon’ ( : ) character (ASCII 3A hex), and
end with a ‘carriage return – line feed’ (CRLF) pair (ASCII 0D and 0A hex).
The allowable characters transmitted for all other fields are hexadecimal 0–9, A–F.
Networked devices monitor the network bus continuously for the ‘colon’ character.
When one is received, each device decodes the next field (the address field) to
find out if it is the addressed device.
Intervals of up to one second can elapse between characters within the message.
If a greater interval occurs, the receiving device assumes an error has occurred.
A typical message frame is shown below.
www.PAControl.com
Exception: With the 584 and 984A/B/X controllers, an ASCII message can
normally terminate after the LRC field without the CRLF characters being sent.
An interval of at least one second must then occur. If this happens, the controller
will assume that the message terminated normally.
RTU Framing
In RTU mode, messages start with a silent interval of at least 3.5 character times.
This is most easily implemented as a multiple of character times at the baud rate
that is being used on the network (shown as T1–T2–T3–T4 in the figure below).
The first field then transmitted is the device address.
The allowable characters transmitted for all fields are hexadecimal 0–9, A–F.
Networked devices monitor the network bus continuously, including during the
‘silent’ intervals. When the first field (the address field) is received, each device
decodes it to find out if it is the addressed device.
Following the last transmitted character, a similar interval of at least 3.5 character
times marks the end of the message. A new message can begin after this interval.
Similarly, if a new message begins earlier than 3.5 character times following a
previous message, the receiving device will consider it a continuation of the
previous message. This will set an error, as the value in the final CRC field will not
be valid for the combined messages. A typical message frame is shown below.
www.PAControl.com
Modbus Message Framing (Continued)
The address field of a message frame contains two characters (ASCII) or eight
bits (RTU). Valid slave device addresses are in the range of 0 – 247 decimal.
The individual slave devices are assigned addresses in the range of 1 – 247. A
master addresses a slave by placing the slave address in the address field of the
message. When the slave sends its response, it places its own address in this
address field of the response to let the master know which slave is responding.
Address 0 is used for the broadcast address, which all slave devices recognize.
When Modbus protocol is used on higher level networks, broadcasts may not be
allowed or may be replaced by other methods. For example, Modbus Plus uses a
shared global database that can be updated with each token rotation.
The function code field of a message frame contains two characters (ASCII) or
eight bits (RTU). Valid codes are in the range of 1 – 255 decimal. Of these, some
codes are applicable to all Modicon controllers, while some codes apply only to
certain models, and others are reserved for future use. Current codes are
described in Chapter 2.
When a message is sent from a master to a slave device the function code field
tells the slave what kind of action to perform. Examples are to read the ON/OFF
states of a group of discrete coils or inputs; to read the data contents of a group of
registers; to read the diagnostic status of the slave; to write to designated coils or
registers; or to allow loading, recording, or verifying the program within the slave.
When the slave responds to the master, it uses the function code field to indicate
either a normal (error–free) response or that some kind of error occurred (called
an exception response). For a normal response, the slave simply echoes the
original function code. For an exception response, the slave returns a code that is
equivalent to the original function code with its most–significant bit set to a logic 1.
For example, a message from master to slave to read a group of holding registers
would have the following function code:
0000 0011 (Hexadecimal 03)
www.PAControl.com
If the slave device takes the requested action without error, it returns the same
code in its response. If an exception occurs, it returns:
1000 0011 (Hexadecimal 83)
In addition to its modification of the function code for an exception response, the
slave places a unique code into the data field of the response message. This tells
the master what kind of error occurred, or the reason for the exception.
The data field is constructed using sets of two hexadecimal digits, in the range of
00 to FF hexadecimal. These can be made from a pair of ASCII characters, or
from one RTU character, according to the network’s serial transmission mode.
The data field of messages sent from a master to slave devices contains
additional information which the slave must use to take the action defined by the
function code. This can include items like discrete and register addresses, the
quantity of items to be handled, and the count of actual data bytes in the field.
For example, if the master requests a slave to read a group of holding registers
(function code 03), the data field specifies the starting register and how many
registers are to be read. If the master writes to a group of registers in the slave
(function code 10 hexadecimal), the data field specifies the starting register, how
many registers to write, the count of data bytes to follow in the data field, and the
data to be written into the registers.
If no error occurs, the data field of a response from a slave to a master contains
the data requested. If an error occurs, the field contains an exception code that
the master application can use to determine the next action to be taken.
The data field can be nonexistent (of zero length) in certain kinds of messages.
For example, in a request from a master device for a slave to respond with its
communications event log (function code 0B hexadecimal), the slave does not
require any additional information. The function code alone specifies the action.
www.PAControl.com
Modbus Message Framing (Continued)
Two kinds of error–checking methods are used for standard Modbus networks.
The error checking field contents depend upon the method that is being used.
ASCII
When ASCII mode is used for character framing, the error checking field contains
two ASCII characters. The error check characters are the result of a Longitudinal
Redundancy Check (LRC) calculation that is performed on the message contents,
exclusive of the beginning ‘colon’ and terminating CRLF characters.
The LRC characters are appended to the message as the last field preceding the
CRLF characters.
RTU
When RTU mode is used for character framing, the error checking field contains a
16–bit value implemented as two 8–bit bytes. The error check value is the result
of a Cyclical Redundancy Check calculation performed on the message contents.
The CRC field is appended to the message as the last field in the message.
When this is done, the low–order byte of the field is appended first, followed by the
high–order byte. The CRC high–order byte is the last byte to be sent in the
message.
www.PAControl.com
How Characters are Transmitted Serially
www.PAControl.com
Error Checking Methods
Standard Modbus serial networks use two kinds of error checking. Parity checking
(even or odd) can be optionally applied to each character. Frame checking (LRC
or CRC) is applied to the entire message. Both the character check and message
frame check are generated in the master device and applied to the message
contents before transmission. The slave device checks each character and the
entire message frame during receipt.
The master is configured by the user to wait for a predetermined timeout interval
before aborting the transaction. This interval is set to be long enough for any
slave to respond normally. If the slave detects a transmission error, the message
will not be acted upon. The slave will not construct a response to the master.
Thus the timeout will expire and allow the master’s program to handle the error.
Note that a message addressed to a nonexistent slave device will also cause a
timeout.
Other networks such as MAP or Modbus Plus use frame checking at a level above
the Modbus contents of the message. On those networks, the Modbus message
LRC or CRC check field does not apply. In the case of a transmission error, the
communication protocols specific to those networks notify the originating device
that an error has occurred, and allow it to retry or abort according to how it has
been setup. If the message is delivered, but the slave device cannot respond, a
timeout error can occur which can be detected by the master’s program.
Parity Checking
Users can configure controllers for Even or Odd Parity checking, or for No Parity
checking. This will determine how the parity bit will be set in each character.
If either Even or Odd Parity is specified, the quantity of 1 bits will be counted in the
data portion of each character (seven data bits for ASCII mode, or eight for RTU).
The parity bit will then be set to a 0 or 1 to result in an Even or Odd total of 1 bits.
For example, these eight data bits are contained in an RTU character frame:
1100 0101
The total quantity of 1 bits in the frame is four. If Even Parity is used, the frame’s
parity bit will be a 0, making the total quantity of 1 bits still an even number (four).
If Odd Parity is used, the parity bit will be a 1, making an odd quantity (five).
14 Modbus Protocol PI–MBUS–300
www.PAControl.com
When the message is transmitted, the parity bit is calculated and applied to the
frame of each character. The receiving device counts the quantity of 1 bits and
sets an error if they are not the same as configured for that device (all devices on
the Modbus network must be configured to use the same parity check method).
Note that parity checking can only detect an error if an odd number of bits are
picked up or dropped in a character frame during transmission. For example, if
Odd Parity checking is employed, and two 1 bits are dropped from a character
containing three 1 bits, the result is still an odd count of 1 bits.
LRC Checking
The LRC field is one byte, containing an 8–bit binary value. The LRC value is
calculated by the transmitting device, which appends the LRC to the message.
The receiving device calculates an LRC during receipt of the message, and
compares the calculated value to the actual value it received in the LRC field.
If the two values are not equal, an error results.
The LRC is calculated by adding together successive 8–bit bytes of the message,
discarding any carries, and then two’s complementing the result. It is performed
on the ASCII message field contents excluding the ‘colon’ character that begins
the message, and excluding the CRLF pair at the end of the message.
In ladder logic, the CKSM function calculates a LRC from the message contents.
For applications using host computers, a detailed example of LRC generation is
contained in Appendix C.
www.PAControl.com
Error Checking Methods (Continued)
CRC Checking
The CRC field is two bytes, containing a 16–bit binary value. The CRC value is
calculated by the transmitting device, which appends the CRC to the message.
The receiving device recalculates a CRC during receipt of the message, and
compares the calculated value to the actual value it received in the CRC field.
If the two values are not equal, an error results.
The CRC is started by first preloading a 16–bit register to all 1’s. Then a process
begins of applying successive 8–bit bytes of the message to the current contents
of the register. Only the eight bits of data in each character are used for generating
the CRC. Start and stop bits, and the parity bit, do not apply to the CRC.
During generation of the CRC, each 8–bit character is exclusive ORed with the
register contents. Then the result is shifted in the direction of the least significant
bit (LSB), with a zero filled into the most significant bit (MSB) position. The LSB is
extracted and examined. If the LSB was a 1, the register is then exclusive ORed
with a preset, fixed value. If the LSB was a 0, no exclusive OR takes place.
This process is repeated until eight shifts have been performed. After the last
(eighth) shift, the next 8–bit byte is exclusive ORed with the register’s current
value, and the process repeats for eight more shifts as described above. The final
contents of the register, after all the bytes of the message have been applied, is
the CRC value.
When the CRC is appended to the message, the low-order byte is appended first,
followed by the high-order byte.
In ladder logic, the CKSM function calculates a CRC from the message contents.
For applications using host computers, a detailed example of CRC generation is
contained in Appendix C.
www.PAControl.com
Chapter 2
Data and Control Functions
www.PAControl.com
Modbus Function Formats
All data addresses in Modbus messages are referenced to zero. The first
occurrence of a data item is addressed as item number zero. For example:
Holding register 40001 is addressed as register 0000 in the data address field
of the message. The function code field already specifies a ‘holding register’
operation. Therefore the ‘4XXXX’ reference is implicit.
The master query is a Read Holding Registers request to slave device address 06.
The message requests data from three holding registers, 40108 through 40110.
Note that the message specifies the starting register address as 0107 (006B hex).
The slave response echoes the function code, indicating this is a normal
response. The ‘Byte Count’ field specifies how many 8–bit data items are being
returned.
It shows the count of 8–bit bytes to follow in the data, for either ASCII or RTU..
With ASCII, this value is one–half the actual count of ASCII characters in the data.
In ASCII, each 4–bit hexadecimal value requires one ASCII character, therefore
two ASCII characters must follow in the message to contain each 8–bit data item.
www.PAControl.com
For example, the value 63 hex is sent as one 8–bit byte in RTU mode (01100011).
The same value sent in ASCII mode requires two bytes, for ASCII ‘6’ (0110110)
and ‘3’ (0110011). The ‘Byte Count’ field counts this data as one 8–bit item,
regardless of the character framing method (ASCII or RTU).
How to Use the Byte Count Field: When you construct responses in buffers,
use a Byte Count value that equals the count of 8–bit bytes in your message data.
The value is exclusive of all other field contents, including the Byte Count field.
Figure 8 shows how the byte count field is implemented in a typical response.
QUERY
Example ASCII RTU
Field Name (Hex) Characters 8–Bit Field
Total Bytes: 17 8
RESPONSE
Example ASCII RTU
Field Name (Hex) Characters 8–Bit Field
Total Bytes: 23 11
www.PAControl.com
Modbus Function Formats (Continued)
The Slave Address field is converted to a Modbus Plus routing path by the
sending device. The CRC field is not sent in the Modbus message, because it
would be redundant to the CRC check performed at the High–level Data Link
Control (HDLC) level.
The rest of the message remains as in the standard serial format. The application
software (e.g., MSTR blocks in controllers, or Modcom III in hosts) handles the
framing of the message into a network packet.
Figure 9 shows how a Read Holding Registers query would be imbedded into a
frame for Modbus Plus transmission.
www.PAControl.com
HDLC LEVEL:
PREAMBLE OPENING BDCST CLOSING
FLAG ADDRESS MAC / LLC FIELD CRC FLAG
MAC LEVEL:
DEST SOURCE MAC BYTE
ADDRESS ADDRESS FUNCTION COUNT LLC FIELD
LLC LEVEL:
OUTPUT ROUTER TRANS
PATH COUNTER SEQUENCE ROUTING PATH MODBUS FRAME (MODIFIED)
MODBUS MESSAGE:
SLAVE FUNCTION STARTING STARTING NUMBER OF NUMBER OF
ADDR CODE ADDRESS HI ADDRESS LO REGISTERS HI REGISTERS LO
www.PAControl.com
Function Codes Supported by Controllers
The listing below shows the function codes supported by Modicon controllers.
Codes are listed in decimal.
‘Y’ indicates that the function is supported. ‘N’ indicates that it is not supported.
www.PAControl.com
Code Name 384 484 584 884 M84 984
Notes:
www.PAControl.com
01 Read Coil Status
Description
Reads the ON/OFF status of discrete outputs (0X references, coils) in the slave.
Broadcast is not supported.
Query
The query message specifies the starting coil and quantity of coils to be read.
Coils are addressed starting at zero: coils 1–16 are addressed as 0–15.
Here is an example of a request to read coils 20–56 from slave device 17:
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 01
Starting Address Hi 00
Starting Address Lo 13
No. of Points Hi 00
No. of Points Lo 25
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The coil status in the response message is packed as one coil per bit of the data
field. Status is indicated as: 1 = ON; 0 = OFF. The LSB of the first data byte
contains the coil addressed in the query. The other coils follow toward the high
order end of this byte, and from ‘low order to high order’ in subsequent bytes.
If the returned coil quantity is not a multiple of eight, the remaining bits in the final
data byte will be padded with zeros (toward the high order end of the byte). The
Byte Count field specifies the quantity of complete bytes of data.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 01
Byte Count 05
Data (Coils 27–20) CD
Data (Coils 35–28) 6B
Data (Coils 43–36) B2
Data (Coils 51–44) 0E
Data (Coils 56–52) 1B
Error Check (LRC or CRC) ––
The status of coils 27–20 is shown as the byte value CD hex, or binary 1100 1101.
Coil 27 is the MSB of this byte, and coil 20 is the LSB. Left to right, the status of
coils 27 through 20 is: ON–ON–OFF–OFF–ON–ON–OFF–ON.
By convention, bits within a byte are shown with the MSB to the left, and the LSB
to the right. Thus the coils in the first byte are ‘27 through 20’, from left to right.
The next byte has coils ‘35 through 28’, left to right. As the bits are transmitted
serially, they flow from LSB to MSB: 20 . . . 27, 28 . . . 35, and so on.
In the last data byte, the status of coils 56–52 is shown as the byte value 1B hex,
or binary 0001 1011. Coil 56 is in the fourth bit position from the left, and coil 52 is
the LSB of this byte. The status of coils 56 through 52 is: ON–ON–OFF–ON–ON.
Note how the three remaining bits (toward the high order end) are zero–filled.
www.PAControl.com
02 Read Input Status
Description
Reads the ON/OFF status of discrete inputs (1X references) in the slave.
Broadcast is not supported.
Query
The query message specifies the starting input and quantity of inputs to be read.
Inputs are addressed starting at zero: inputs 1–16 are addressed as 0–15.
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 02
Starting Address Hi 00
Starting Address Lo C4
No. of Points Hi 00
No. of Points Lo 16
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The input status in the response message is packed as one input per bit of the
data field. Status is indicated as: 1 = ON; 0 = OFF. The LSB of the first data
byte contains the input addressed in the query. The other inputs follow toward the
high order end of this byte, and from ‘low order to high order’ in subsequent bytes.
If the returned input quantity is not a multiple of eight, the remaining bits in the final
data byte will be padded with zeros (toward the high order end of the byte). The
Byte Count field specifies the quantity of complete bytes of data.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 02
Byte Count 03
Data (Inputs 10204–10197) AC
Data (Inputs 10212–10205) DB
Data (Inputs 10218–10213) 35
Error Check (LRC or CRC) ––
The status of inputs 10204–10197 is shown as the byte value AC hex, or binary
1010 1100. Input 10204 is the MSB of this byte, and input 10197 is the LSB.
Left to right, the status of inputs 10204 through 10197 is: ON–OFF–ON–OFF–
ON–ON–OFF–OFF.
The status of inputs 10218–10213 is shown as the byte value 35 hex, or binary
0011 0101. Input 10218 is in the third bit position from the left, and input 10213 is
the LSB. The status of inputs 10218 through 10213 is: ON–ON–OFF–ON–OFF–
ON. Note how the two remaining bits (toward the high order end) are zero–filled.
www.PAControl.com
03 Read Holding Registers
Description
Reads the binary contents of holding registers (4X references) in the slave.
Broadcast is not supported.
Query
The query message specifies the starting register and quantity of registers to be
read. Registers are addressed starting at zero: registers 1–16 are addressed as
0–15.
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 03
Starting Address Hi 00
Starting Address Lo 6B
No. of Points Hi 00
No. of Points Lo 03
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The register data in the response message are packed as two bytes per register,
with the binary contents right justified within each byte. For each register, the first
byte contains the high order bits and the second contains the low order bits.
Data is scanned in the slave at the rate of 125 registers per scan for 984–X8X
controllers (984–685, etc), and at the rate of 32 registers per scan for all other
controllers. The response is returned when the data is completely assembled.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 03
Byte Count 06
Data Hi (Register 40108) 02
Data Lo (Register 40108) 2B
Data Hi (Register 40109) 00
Data Lo (Register 40109) 00
Data Hi (Register 40110) 00
Data Lo (Register 40110) 64
Error Check (LRC or CRC) ––
The contents of register 40108 are shown as the two byte values of 02 2B hex, or
555 decimal. The contents of registers 40109–40110 are 00 00 and 00 64 hex, or
0 and 100 decimal.
www.PAControl.com
04 Read Input Registers
Description
Reads the binary contents of input registers (3X references) in the slave.
Broadcast is not supported.
Query
The query message specifies the starting register and quantity of registers to be
read. Registers are addressed starting at zero: registers 1–16 are addressed as
0–15.
Here is an example of a request to read register 30009 from slave device 17:
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 04
Starting Address Hi 00
Starting Address Lo 08
No. of Points Hi 00
No. of Points Lo 01
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The register data in the response message are packed as two bytes per register,
with the binary contents right justified within each byte. For each register, the first
byte contains the high order bits and the second contains the low order bits.
Data is scanned in the slave at the rate of 125 registers per scan for 984–X8X
controllers (984–685, etc), and at the rate of 32 registers per scan for all other
controllers. The response is returned when the data is completely assembled.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 04
Byte Count 02
Data Hi (Register 30009) 00
Data Lo (Register 30009) 0A
Error Check (LRC or CRC) ––
The contents of register 30009 are shown as the two byte values of 00 0A hex, or
10 decimal.
www.PAControl.com
05 Force Single Coil
Description
Forces a single coil (0X reference) to either ON or OFF. When broadcast, the
function forces the same coil reference in all attached slaves.
Note The function will override the controller’s memory protect state
and the coil’s disable state. The forced state will remain valid until the
controller’s logic next solves the coil. The coil will remain forced if it is
not programmed in the controller’s logic.
Query
The query message specifies the coil reference to be forced. Coils are addressed
starting at zero: coil 1 is addressed as 0.
The reguested ON/OFF state is specified by a constant in the query data field.
A value of FF 00 hex requests the coil to be ON. A value of 00 00 requests it to be
OFF. All other values are illegal and will not affect the coil.
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 05
Coil Address Hi 00
Coil Address Lo AC
Force Data Hi FF
Force Data Lo 00
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response is an echo of the query, returned after the coil state has
been forced.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 05
Coil Address Hi 00
Coil Address Lo AC
Force Data Hi FF
Force Data Lo 00
Error Check (LRC or CRC) ––
www.PAControl.com
06 Preset Single Register
Description
Presets a value into a single holding register (4X reference). When broadcast, the
function presets the same register reference in all attached slaves.
Note The function will override the controller’s memory protect state.
The preset value will remain valid in the register until the controller’s
logic next solves the register contents. The register’s value will remain
if it is not programmed in the controller’s logic.
Query
The query message specifies the register reference to be preset. Registers are
addressed starting at zero: register 1 is addressed as 0.
The reguested preset value is specified in the query data field. M84 and 484
controllers use a 10–bit binary value, with the six high order bits set to zeros.
All other controllers use 16–bit values.
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 06
Register Address Hi 00
Register Address Lo 01
Preset Data Hi 00
Preset Data Lo 03
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response is an echo of the query, returned after the register contents
have been preset.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 06
Register Address Hi 00
Register Address Lo 01
Preset Data Hi 00
Preset Data Lo 03
Error Check (LRC or CRC) ––
www.PAControl.com
07 Read Exception Status
Description
Reads the contents of eight Exception Status coils within the slave controller.
Certain coils have predefined assignments in the various controllers. Other coils
can be programmed by the user to hold information about the contoller’s status,
for example, ‘machine ON/OFF’, ‘heads retracted’, ‘safeties satisfied’, ‘error
conditions exist’, or other user–defined flags. Broadcast is not supported.
The function provides a simple method for accessing this information, because the
Exception Coil references are known (no coil reference is needed in the function).
The predefined Exception Coil assignments are:
Query
Here is an example of a request to read the exception status in slave device 17:
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 07
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response contains the status of the eight Exception Status coils.
The coils are packed into one data byte, with one bit per coil. The status of the
lowest coil reference is contained in the least significant bit of the byte.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 07
Coil Data 6D
Error Check (LRC or CRC) ––
In this example, the coil data is 6D hex (0110 1101 binary). Left to right, the coils
are: OFF–ON–ON–OFF–ON–ON–OFF–ON. The status is shown from the
highest to the lowest addressed coil.
If the controller is a 984, these bits are the status of coils 8 through 1.
If the controller is a 484, these bits are the status of coils 264 through 257. In this
example, coil 257 is ON, indicating that the controller’s batteries are OK.
www.PAControl.com
11 (0B Hex) Fetch Comm Event Counter
Description
Returns a status word and an event count from the slave’s communications event
counter. By fetching the current count before and after a series of messages, a
master can determine whether the messages were handled normally by the slave.
Broadcast is not supported.
The controller’s event counter is incremented once for each successful message
completion. It is not incremented for exception responses, poll commands, or
fetch event counter commands.
The event counter can be reset by means of the Diagnostics function (code 08),
with a subfunction of Restart Communications Option (code 00 01) or Clear
Counters and Diagnostic Register (code 00 0A).
Query
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 0B
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response contains a two–byte status word, and a two–byte event
count. The status word will be all ones (FF FF hex) if a previously–issued
program command is still being processed by the slave (a busy condition exists).
Otherwise, the status word will be all zeros.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 0B
Status HI FF
Status Lo FF
Event Count Hi 01
Event Count Lo 08
Error Check (LRC or CRC) ––
In this example, the status word is FF FF hex, indicating that a program function is
still in progress in the slave. The event count shows that 264 (01 08 hex) events
have been counted by the controller.
www.PAControl.com
12 (0C Hex) Fetch Comm Event Log
Description
Returns a status word, event count, message count, and a field of event bytes
from the slave. Broadcast is not supported.
The status word and event count are identical to that returned by the Fetch
Communications Event Counter function (11, 0B hex).
The message counter contains the quantity of messages processed by the slave
since its last restart, clear counters operation, or power–up. This count is identical
to that returned by the Diagnostic function (code 08), subfunction Return Bus
Message Count (code 11, 0B hex).
The event bytes field contains 0-64 bytes, with each byte corresponding to the
status of one Modbus send or receive operation for the slave. The events are
entered by the slave into the field in chronological order. Byte 0 is the most recent
event. Each new byte flushes the oldest byte from the field.
Query
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 0C
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response contains a two–byte status word field, a two–byte event
count field, a two–byte message count field, and a field containing 0-64 bytes of
events. A byte count field defines the total length of the data in these four fields.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 0C
Byte Count 08
Status HI 00
Status Lo 00
Event Count Hi 01
Event Count Lo 08
Message Count Hi 01
Message Count Lo 21
Event 0 20
Event 1 00
Error Check (LRC or CRC) ––
In this example, the status word is 00 00 hex, indicating that the slave is not
processing a program function. The event count shows that 264 (01 08 hex)
events have been counted by the slave. The message count shows that 289
(01 21 hex) messages have been processed.
The most recent communications event is shown in the Event 0 byte. Its contents
(20 hex) show that the slave has most recently entered the Listen Only Mode.
The previous event is shown in the Event 1 byte. Its contents (00 hex) show that
the slave received a Communications Restart.
The layout of the response’s event bytes is described on the next page.
www.PAControl.com
12 (0C Hex) Fetch Comm Event Log (Continued)
An event byte returned by the Fetch Communications Event Log function can be
any one of four types. The type is defined by bit 7 (the high–order bit) in each
byte. It may be further defined by bit 6. This is explained below.
This type of event byte is stored by the slave when a query message is received.
It is stored before the slave processes the message. This event is defined by bit 7
set to a logic ‘1’. The other bits will be set to a logic ‘1’ if the corresponding
condition is TRUE. The bit layout is:
Bit Contents
0 Not Used
1 Communications Error
2 Not Used
3 Not Used
4 Character Overrun
5 Currently in Listen Only Mode
6 Broadcast Received
7 1
This type of event byte is stored by the slave when it finishes processing a query
message. It is stored if the slave returned a normal or exception response, or no
response. This event is defined by bit 7 set to a logic ‘0’, with bit 6 set to a ‘1’.
The other bits will be set to a logic ‘1’ if the corresponding condition is TRUE.
The bit layout is:
Bit Contents
0 Read Exception Sent (Exception Codes 1-3)
1 Slave Abort Exception Sent (Exception Code 4)
2 Slave Busy Exception Sent (Exception Codes 5-6)
3 Slave Program NAK Exception Sent (Exception Code 7)
4 Write Timeout Error Occurred
5 Currently in Listen Only Mode
42 Data and Control Functions PI–MBUS–300
www.PAControl.com
6 1
7 0
This type of event byte is stored by the slave when it enters the Listen Only Mode.
The event is defined by a contents of 04 hex. The bit layout is:
Bit Contents
0 0
1 0
2 1
3 0
4 0
5 0
6 0
7 0
This type of event byte is stored by the slave when its communications port. is
restarted. The slave can be restarted by the Diagnostics function (code 08), with
subfunction Restart Communications Option (code 00 01).
That function also places the slave into a ‘Continue on Error’ or ‘Stop on Error’
mode. If the slave is placed into ‘Continue on Error’ mode, the event byte is
added to the existing event log. If the slave is placed into ‘Stop on Error’ mode,
the byte is added to the log and the rest of the log is cleared to zeros.
The event is defined by a contents of zero. The bit layout is:
Bit Contents
0 0
1 0
2 0
3 0
4 0
5 0
6 0
7 0
www.PAControl.com
15 (0F Hex) Force Multiple Coils
Description
Forces each coil (0X reference) in a sequence of coils to either ON or OFF. When
broadcast, the function forces the same coil references in all attached slaves.
Note The function will override the controller’s memory protect state
and a coil’s disable state. The forced state will remain valid until the
controller’s logic next solves each coil. Coils will remain forced if they
are not programmed in the controller’s logic.
Query
The query message specifies the coil references to be forced. Coils are addressed
starting at zero: coil 1 is addressed as 0.
The reguested ON/OFF states are specified by contents of the query data field.
A logical ‘1’ in a bit position of the field requests the corresponding coil to be ON.
A logical ‘0’ requests it to be OFF.
The following page shows an example of a request to force a series of ten coils
starting at coil 20 (addressed as 19, or 13 hex) in slave device 17.
The query data contents are two bytes: CD 01 hex (1100 1101 0000 0001 binary).
The binary bits correspond to the coils in the following way:
Bit: 1 1 0 0 1 1 0 1 0 0 0 0 0 0 0 1
Coil: 27 26 25 24 23 22 21 20 – – – – – – 29 28
The first byte transmitted (CD hex) addresses coils 27-20, with the least significant
bit addressing the lowest coil (20) in this set.
The next byte transmitted (01 hex) addresses coils 29-28, with the least significant
bit addressing the lowest coil (28) in this set. Unused bits in the last data byte
should be zero–filled.
www.PAControl.com
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 0F
Coil Address Hi 00
Coil Address Lo 13
Quantity of Coils Hi 00
Quantity of Coils Lo 0A
Byte Count 02
Force Data Hi (Coils 27-20) CD
Force Data Lo (Coils 29-28) 01
Error Check (LRC or CRC) ––
Response
The normal response returns the slave address, function code, starting address,
and quantity of coils forced.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 0F
Coil Address Hi 00
Coil Address Lo 13
Quantity of Coils Hi 00
Quantity of Coils Lo 0A
Error Check (LRC or CRC) ––
www.PAControl.com
16 (10 Hex) Preset Multiple Registers
Description
Presets values into a sequence of holding registers (4X references). When
broadcast, the function presets the same register references in all attached slaves.
Note The function will override the controller’s memory protect state.
The preset values will remain valid in the registers until the controller’s
logic next solves the register contents. The register values will remain
if they are not programmed in the controller’s logic.
Appendix B lists the maximum parameters supported by various controller models.
Query
The query message specifies the register references to be preset. Registers are
addressed starting at zero: register 1 is addressed as 0.
The requested preset values are specified in the query data field. M84 and 484
controllers use a 10–bit binary value, with the six high order bits set to zeros.
All other controllers use 16–bit values. Data is packed as two bytes per register.
Here is an example of a request to preset two registers starting at 40002 to 00 0A
and 01 02 hex, in slave device 17:
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 10
Starting Address Hi 00
Starting Address Lo 01
No. of Registers Hi 00
No. of Registers Lo 02
Byte Count 04
Data Hi 00
Data Lo 0A
Data Hi 01
Data Lo 02
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response returns the slave address, function code, starting address,
and quantity of registers preset.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 10
Starting Address Hi 00
Starting Address Lo 01
No. of Registers Hi 00
No. of Registers Lo 02
Error Check (LRC or CRC) ––
www.PAControl.com
17 (11 Hex) Report Slave ID
Description
Returns a description of the type of controller present at the slave address, the
current status of the slave Run indicator, and other information specific to the
slave device. Broadcast is not supported.
Query
Here is an example of a request to report the ID and status of slave device 17:
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 11
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The format of a normal response is shown below. The data contents are specific
to each type of controller. They are listed on the following pages.
RESPONSE
These are the Slave ID codes returned by Modicon controllers in the first byte of
the data field:
Slave ID Controller
0 Micro 84
1 484
2 184/384
3 584
8 884
9 984
www.PAControl.com
17 (11 Hex) Report Slave ID (Continued)
184/384
The 184 or 384 controller returns a byte count of either 4 or 74 (4A hexadecimal).
If the controller’s J347 Modbus Slave Interface is setup properly, and its internal
PIB table is normal, the byte count will be 74. Otherwise the byte count will be 4.
Byte Contents
1 Slave ID (2 for 184/384). See bytes 3, 4 for further definition.
2 RUN indicator status (0 = OFF, FF = ON)
3, 4 Status word:
Bit 0 = 0
Bit 1 = Memory Protect status (0 = OFF, 1 = ON)
Bit 2, 3 = Controller type: Bit 2 = 0 and Bit 3 = 0 indicates 184
Bit 2 = 1 and Bit 3 = 0 indicates 384
Bits 4 - 15 = Unused
The additonal 70 bytes returned for a correct J347 setup and normal PIB are:
Byte Contents
5, 6 PIB table starting address
7, 8 Controller serial number
9, 10 Executive ID
Bytes 11 - 74 contain the PIB table. This data is valid only if the
controller is running (as shown in Byte 2). The table is as follows:
11, 12 Maximum quantity of output coils
13, 14 Output coil enable table
15, 16 Address of input coil/run table
17, 18 Quantity of input coils
19, 20 Input coil enable table
21, 22 First latch number (must be multiple of 16)
23, 24 Last latch number (must be multiple of 16)
50 Data and Control Functions PI–MBUS–300
www.PAControl.com
25, 26 Address of input registers
27, 28 Quantity of input registers
29, 30 Quantity of output and holding registers
31, 32 Address of user logic
33, 34 Address of output coil RAM table
35, 36 Function inhibit mask
37, 38 Address of extended function routine
39, 40 Address of data transfer routine
41, 42 Address of traffic cop
43, 44 Unused
45, 46 Function inhibit mask
47, 48 Address of ‘A’ Mode history table
49, 50 Request table for DX printer
51, 52 Quantity of sequence groups
53, 54 Address of sequence image table
55, 56 Address of sequence RAM
57, 58 Quantity of 50XX registers
59, 60 Address of 50XX table
61, 62 Address of output coil RAM image
63, 64 Address of input RAM image
65, 66 Delayed output start group
67, 68 Delayed output end group
69, 70 Watchdog line
71, 72 RAM Address of latches
73, 74 Quantity of delayed output groups
www.PAControl.com
17 (11 Hex) Report Slave ID (Continued)
584
Byte Contents
1 Slave ID (3 for 584)
2 RUN indicator status (0 = OFF, FF = ON)
3 Quantity of 4K sections of page 0 memory
4 Quantity of 1K sections of state RAM
5 Quantity of segments of user logic
Byte 6:
Bit 15 (MSB of byte 6) = Port 1 setup
Bit 14 = Port 2 setup
Bit 13 = Port 1 address set
Bit 12 = Port 2 address set
Bit 11 = Unassigned
Bit 10 = Constant Sweep status (0 = Constand Sweep OFF, 1 = ON)
Bit 9 = Single Sweep status (0 = Single Sweep OFF, 1 = ON)
Bit 8 = 16/24-bit nodes (0 = 24-bit nodes, 1 = 16-bit nodes)
Byte 7:
Bit 7 (MSB of byte 7) = Power ON (1 = ON, should never = ‘OFF’)
Bit 6 = RUN indicator status (0 = ON, 1 = OFF)
Bit 5 = Memory Protect status (0 = ON, 1 = OFF)
Bit 4 = Battery OK (0 = OK, 1 = Not OK)
Bits 3 - 0 = Unassigned
www.PAControl.com
8, 9 Machine stop code (configuration table word 105, 69 hex).
The word is organized as follows:
Byte 8:
Bit 15 (MSB of byte 8) = Peripheral port stop (controlled stop)
Bit 14 = Unassigned
Bit 13 = Dim awareness
Bit 12 = Illegal peripheral intervention
Bit 11 = Multirate solve table invalid
Bit 10 = Start of Node did not start segment
Bit 9 = State RAM test failed
Bit 8 = No End of Logic detected, or bad quantity of segments
Byte 9:
Bit 7 (MSB of byte 9) = Watchdog timer expired
Bit 6 = Real time clock error
Bit 5 = CPU diagnostic failed
Bit 4 = Invalid traffic cop type
Bit 3 = Invalid node type
Bit 2 = Logic checksum error
Bit 1 = Backup checksum error
Bit 0 = Illegal configuration
www.PAControl.com
17 (11 Hex) Report Slave ID (Continued)
984
Byte Contents
1 Slave ID (9 for 984)
2 RUN indicator status (0 = OFF, FF = ON)
3 Quantity of 4K sections of page 0 memory
4 Quantity of 1K sections of state RAM
5 Quantity of segments of user logic
Byte 6:
Bit 15 (MSB of byte 6) = Unassigned
Bits 14 - 11 = Unassigned
Bit 10 = Constant Sweep status (0 = Constand Sweep OFF, 1 = ON)
Bit 9 = Single Sweep status (0 = Single Sweep OFF, 1 = ON)
Bit 8 = 16/24-bit nodes (0 = 24-bit nodes, 1 = 16-bit nodes)
Byte 7:
Bit 7 (MSB of byte 7) = Power ON (1 = ON, should never = ‘OFF’)
Bit 6 = RUN indicator status (0 = ON, 1 = OFF)
Bit 5 = Memory Protect status (0 = ON, 1 = OFF)
Bit 4 = Battery OK (0 = OK, 1 = Not OK)
Bits 3 - 1 = Unassigned
Bit 0 = Memory downsize flag (0 = NO, 1 = Downsize
Memory Downsize: Bit 0 of the Machine State word defines the use of the
memory downsize values in words 99, 100, and 175 (63, 64, and AF hexadecimal)
of the configuration table. If bit 0 = logic 1, downsizing is calculated as follows:
Page 0 size (16-bit words) = (Word 99 * 4096) – (Word 175 low byte * 16)
State table size (16 bit words) = (Word 100 * 1024) – (Word 175 high byte * 16)
www.PAControl.com
8, 9 Machine stop code (configuration table word 105, 69 hex).
The word is organized as follows:
Byte 8:
Bit 15 (MSB of byte 8) = Peripheral port stop (controlled stop)
Bit 14 (984A, B, X) = Extended memory parity failure
Bit 14 (Other 984) = Bad IO traffic cop
Bit 13 = Dim awareness
Bit 12 = Illegal peripheral intervention
Bit 11 = Bad segment scheduler table
Bit 10 = Start of Node did not start segment
Bit 9 = State RAM test failed
Bit 8 = No End of Logic detected, or bad quantity of segments
Byte 9:
Bit 7 (MSB of byte 9) = Watchdog timer expired
Bit 6 = Real time clock error
Bit 5 (984A, B, X) = CPU diagnostic failed
Bit 5 (Other 984) = Bad coil used table
Bit 4 = S908 remote IO head failure
Bit 3 = Invalid node type
Bit 2 = Logic checksum error
Bit 1 = Coil disabled while in RUN mode
Bit 0 = Illegal configuration
www.PAControl.com
17 (11 Hex) Report Slave ID (Continued)
Micro 84
Byte Contents
1 Slave ID (0 for Micro 84)
2 RUN indicator status (0 = OFF, FF = ON)
3 Current port number
4 Memory size (1 = 1K, 2 = 2K)
5 Unused (all zeros)
484
Byte Contents
1 Slave ID (1 for 484)
2 RUN indicator status (0 = OFF, FF = ON)
3 System state
4 First configuration byte
5 Second configuration byte
www.PAControl.com
884
Byte Contents
1 Slave ID (8 for 884)
2 RUN indicator status (0 = OFF, FF = ON)
3 Current port number
4 Size of user logic plus state RAM, in kilobytes (1 word = 2 bytes)
5 Reserved
6 Hook bits:
Bits 0 - 2 = Reserved
Bit 3 = Mapper bypass: 1 = Do not execute standard mapper
Bit 4 = End of Scan tests: 1 = Test end of scan hooks
Bit 5 = Reserved
Bit 6 = Logic Solver bypass: 1 = Do not execute standard
logic solver
Bit 7 = Reserved
7, 8 Reserved
www.PAControl.com
20 (14Hex) Read General Reference
Description
The function can read multiple groups of references. The groups can be separate
(non–contiguous), but the references within each group must be sequential.
Query
The query contains the standard Modbus slave address, function code, byte
count, and error check fields. The rest of the query specifies the group or groups
of references to be read. Each group is defined in a separate ‘sub-request’ field
which contains 7 bytes:
The quantity of registers to be read, combined with all other fields in the expected
response, must not exceed the allowable length of Modbus messages: 256 bytes.
The available quantity of Extended Memory files depends upon the installed size
of Extended Memory in the slave controller. Each file except the last one contains
10,000 registers, addressed as 0000-270F hexadecimal (0000-9999 decimal).
www.PAControl.com
For controllers other than the 984–785 with Extended Registers, the last (highest)
register in the last file is:
For the 984–785 with Extended Registers, the last (highest) register in the last file
is shown in the two tables below.
User State
Logic RAM Ext Mem Size Last File Last Register (Decimal)
32K 32K 0 0 0
16K 64K 72K 8 3727
User State
Logic RAM Ext Mem Size Last File Last Register (Decimal)
48K 32K 24K 3 4575
32K 64K 96K 10 8303
Examples of a query and response are provided starting on the next page.
www.PAControl.com
20 (14 Hex) Read General Reference (Continued)
Group 1 consists of two registers from file 4, starting at register 1 (address 0001).
Group 2 consists of two registers from file 3, starting at register 9 (address 0009).
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 14
Byte Count 0E
Sub–Req 1, Reference Type 06
Sub–Req 1, File Number Hi 00
Sub–Req 1, File Number Lo 04
Sub–Req 1, Starting Addr Hi 00
Sub–Req 1, Starting Addr Lo 01
Sub–Req 1, Register Count Hi 00
Sub–Req 1, Register Count Lo 02
Sub–Req 2, Reference Type 06
Sub–Req 2, File Number Hi 00
Sub–Req 2, File Number Lo 03
Sub–Req 2, Starting Addr Hi 00
Sub–Req 2, Starting Addr Lo 09
Sub–Req 2, Register Count Hi 00
Sub–Req 2, Register Count Lo 02
Error Check (LRC or CRC) ––
Figure 34 Read General Reference – Query
www.PAControl.com
Response
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 14
Byte Count 0C
Sub–Res 1, Byte Count 05
Sub–Res 1, Reference Type 06
Sub–Res 1, Register Data Hi 0D
Sub–Res 1, Register Data Lo FE
Sub–Res 1, Register Data Hi 00
Sub–Res 1, Register Data Lo 20
Sub–Res 2, Byte Count 05
Sub–Res 2, Reference Type 06
Sub–Res 2, Register Data Hi 33
Sub–Res 2, Register Data Lo CD
Sub–Res 2, Register Data Hi 00
Sub–Res 2, Register Data Lo 40
Error Check (LRC or CRC) ––
www.PAControl.com
21 (15Hex) Write General Reference
Description
The function can write multiple groups of references. The groups can be separate
(non–contiguous), but the references within each group must be sequential.
Query
The query contains the standard Modbus slave address, function code, byte
count, and error check fields. The rest of the query specifies the group or groups
of references to be written, and the data to be written into them. Each group is
defined in a separate ‘sub-request’ field which contains 7 bytes plus the data:
The quantity of registers to be written, combined with all other fields in the query,
must not exceed the allowable length of Modbus messages: 256 bytes.
The available quantity of Extended Memory files depends upon the installed size
of Extended Memory in the slave controller. Each file except the last one contains
10,000 registers, addressed as 0000-270F hexadecimal (0000-9999 decimal).
www.PAControl.com
For controllers other than the 984–785 with Extended Registers, the last (highest)
register in the last file is:
For the 984–785 with Extended Registers, the last (highest) register in the last file
is shown in the two tables below.
User State
Logic RAM Ext Mem Size Last File Last Register (Decimal)
32K 32K 0 0 0
16K 64K 72K 8 3727
User State
Logic RAM Ext Mem Size Last File Last Register (Decimal)
48K 32K 24K 3 4575
32K 64K 96K 10 8303
Examples of a query and response are provided starting on the next page.
www.PAControl.com
21 (15 Hex) Write General Reference (Continued)
The group consists of three registers in file 4, starting at register 7 (address 0007).
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 15
Byte Count 0D
Sub–Req 1, Reference Type 06
Sub–Req 1, File Number Hi 00
Sub–Req 1, File Number Lo 04
Sub–Req 1, Starting Addr Hi 00
Sub–Req 1, Starting Addr Lo 07
Sub–Req 1, Register Count Hi 00
Sub–Req 1, Register Count Lo 03
Sub–Req 1, Register Data Hi 06
Sub–Req 1, Register Data Lo AF
Sub–Req 1, Register Data Hi 04
Sub–Req 1, Register Data Lo BE
Sub–Req 1, Register Data Hi 10
Sub–Req 1, Register Data Lo 0D
Error Check (LRC or CRC) ––
www.PAControl.com
Response
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 15
Byte Count 0D
Sub–Req 1, Reference Type 06
Sub–Req 1, File Number Hi 00
Sub–Req 1, File Number Lo 04
Sub–Req 1, Starting Addr Hi 00
Sub–Req 1, Starting Addr Lo 07
Sub–Req 1, Register Count Hi 00
Sub–Req 1, Register Count Lo 03
Sub–Req 1, Register Data Hi 06
Sub–Req 1, Register Data Lo AF
Sub–Req 1, Register Data Hi 04
Sub–Req 1, Register Data Lo BE
Sub–Req 1, Register Data Hi 10
Sub–Req 1, Register Data Lo 0D
Error Check (LRC or CRC) ––
www.PAControl.com
22 (16Hex) Mask Write 4X Register
Description
Modifies the contents of a specified 4XXXX register using a combination of an
AND mask, an OR mask, and the register’s current contents. The function can be
used to set or clear individual bits in the register. Broadcast is not supported.
Query
The query specifies the 4XXXX reference to be written, the data to be used as the
AND mask, and the data to be used as the OR mask.
Note that if the Or_Mask value is zero, the result is simply the logical ANDing of
the current contents and And_Mask. If the And_Mask value is zero, the result is
equal to the Or_Mask value.
Note that the contents of the register can be read with the Read Holding Registers
function (function code 03). They could, however, be changed subsequently as
the controller scans its user logic program.
An example of a Mask Write to register 5 in slave device 17, using the above
mask values, is shown on the next page.
www.PAControl.com
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 16
Reference Address Hi 00
Reference Address Lo 04
And_Mask Hi 00
And_Mask Lo F2
Or_Mask Hi 00
Or–Mask Lo 25
Error Check (LRC or CRC) ––
Response
The normal response is an echo of the query. The response is returned after the
register has been written.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 16
Reference Address Hi 00
Reference Address Lo 04
And_Mask Hi 00
And_Mask Lo F2
Or_Mask Hi 00
Or–Mask Lo 25
Error Check (LRC or CRC) ––
www.PAControl.com
23 (17Hex) Read/Write 4X Registers
Description
Performs a combination of one read and one write operation in a single Modbus
transaction. The function can write new contents to a group of 4XXXX registers,
and then return the contents of another group of 4XXXX registers. Broadcast is
not supported. This function is supported in the 984–785 controller only.
Query
The query specifies the starting address and quantity of registers of the group to
be read. It also specifies the starting address, quantity of registers, and data for
the group to be written. The byte count field specifies the quantity of bytes to
follow in the write data field.
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 17
Read Reference Address Hi 00
Read Reference Address Lo 04
Quantity to Read Hi 00
Quantity to Read Lo 06
Write Reference Address Hi 00
Write Reference Address Lo 0F
Quantity to Write Hi 00
Quantity to Write Lo 03
Byte Count 06
Write Data 1 Hi 00
Write Data 1 Lo FF
Write Data 2 Hi 00
Write Data 2 Lo FF
Write Data 3 Hi 00
Write Data 3 Lo FF
Error Check (LRC or CRC) ––
www.PAControl.com
Response
The normal response contains the data from the group of registers that were read.
The byte count field specifies the quantity of bytes to follow in the read data field.
Here is an example of a response to the query on the opposite page:
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 17
Byte Count 0C
Read Data 1 Hi 00
Read Data 1 Lo FE
Read Data 2 Hi 0A
Read Data 2 Lo CD
Read Data 3 Hi 00
Read Data 3 Lo 01
Read Data 4 Hi 00
Read Data 4 Lo 03
Read Data 5 Hi 00
Read Data 5 Lo 0D
Read Data 6 Hi 00
Read Data 6 Lo FF
Error Check (LRC or CRC) ––
www.PAControl.com
24 (18Hex) Read FIFO Queue
Description
The function reads the queue contents, but does not clear them. Broadcast is not
supported.
Query
The query specifies the starting 4XXXX reference to be read from the FIFO queue.
This is the address of the pointer register used with the controller’s FIN and FOUT
function blocks. It contains the count of registers currently contained in the queue.
The FIFO data registers follow this address sequentially.
An example of a Read FIFO Queue query to slave device 17 is shown below. The
query is to read the queue starting at the pointer register 41247 (04DE hex).
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 18
FIFO Pointer Address Hi 04
FIFO Pointer Address Lo DE
Error Check (LRC or CRC) ––
www.PAControl.com
Response
In a normal response, the byte count shows the quantity of bytes to follow,
including the queue count bytes and data register bytes (but not including the error
check field).
The queue count is the quantity of data registers in the queue (not including the
count register).
If the queue count exceeds 31, an exception response is returned with an error
code of 03 (Illegal Data Value).
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 18
Byte Count Hi 00
Byte Count Lo 08
FIFO Count Hi 00
FIFO Count Lo 03
FIFO Data Reg 1 Hi 01
FIFO Data Reg 1 Lo B8
FIFO Data Reg 2 Hi 12
FIFO Data Reg 2 Lo 84
FIFO Data Reg 3 Hi 13
FIFO Data Reg 3 Lo 22
Error Check (LRC or CRC) ––
In this example, the FIFO pointer register (41247 in the query) is returned with a
queue count of 3. The three data registers follow the queue count. These are:
41248 (contents 440 decimal -- 01B8 hex); 41249 (contents 4740 -- 1284 hex);
and 41250 (contents 4898 -- 1322 hex).
www.PAControl.com
Chapter 3
Diagnostic Subfunctions
www.PAControl.com
Function 08 – Diagnostics
Description
The function uses a two–byte subfunction code field in the query to define the
type of test to be performed. The slave echoes both the function code and
subfunction code in a normal response.
Most of the diagnostic queries use a two–byte data field to send diagnostic data or
control information to the slave. Some of the diagnostics cause data to be returned
from the slave in the data field of a normal response.
In general, issuing a diagnostic function to a slave device does not affect the
running of the user program in the slave. User logic, like discretes and registers,
is not accessed by the diagnostics. Certain functions can optionally reset error
counters in the slave.
A slave device can, however, be forced into ‘Listen Only Mode’ in which it will
monitor the messages on the communications system but not respond to them.
This can affect the outcome of your application program it it depends upon any
further exchange of data with the slave device. Generally, the mode is forced to
remove a malfunctioning slave device from the communications system.
An example diagnostics query and response are shown on the opposite page.
These show the location of the function code, subfunction code, and data field
within the messages.
www.PAControl.com
Query
QUERY
Example
Field Name (Hex)
Slave Address 11
Function 08
Subfunction Hi 00
Subfunction Lo 00
Data Hi A5
Data Lo 37
Error Check (LRC or CRC) ––
Response
The normal response to the Return Query Data request is to loopback the same
data. The function code and subfunction code are also echoed.
RESPONSE
Example
Field Name (Hex)
Slave Address 11
Function 08
Subfunction Hi 00
Subfunction Lo 00
Data Hi A5
Data Lo 37
Error Check (LRC or CRC) ––
The data fields in responses to other kinds of queries could contain error counts or
other information requested by the subfunction code.
www.PAControl.com
DiagnosticCodes Supportedby Controllers
The listing below shows the subfunction codes supported by Modicon controllers.
Codes are listed in decimal.
‘Y’ indicates that the subfunction is supported. ‘N’ indicates that it is not supported.
Notes:
www.PAControl.com
Diagnostic Subfunctions
The data passed in the query data field is to be returned (looped back) in the
response. The entire response message should be identical to the query.
The slave’s peripheral port is to be initialized and restarted, and all of its
communications event counters are to be cleared. If the port is currently in Listen
Only Mode, no response is returned. This function is the only one that brings the
port out of Listen Only Mode. If the port is not currently in Listen Only Mode, a
normal response is returned. This occurs before the restart is executed.
When the slave receives the query, it attempts a restart and executes its
power–up confidence tests. Successful completion of the tests will bring the port
online.
A query data field contents of FF 00 hex causes the port’s Communications Event
Log to be cleared also. Contents of 00 00 leave the log as it was prior to the
restart.
www.PAControl.com
08 Diagnostics (Continued)
The contents of the slave’s 16–bit diagnostic register are returned in the response.
The assignment of diagnostic register bits for Modicon controllers is listed below.
In each register, bit 15 is the high–order bit. The description is TRUE when the
corresponding bit is set to a logic ‘1‘.
Bit Description
0 Continue on Error
1 Run Light Failed
2 T–Bus Test Failed
3 Asynchronous Bus Test Failed
4 Force Listen Only Mode
5 Not Used
6 Not Used
7 ROM Chip 0 Test Failed
8 Continuous ROM Checksum Test in Execution
9 ROM Chip 1 Test Failed
10 ROM Chip 2 Test Failed
11 ROM Chip 3 Test Failed
12 RAM Chip 5000-53FF Test Failed
13 RAM Chip 6000-67FF Test Failed, Even Addresses
14 RAM Chip 6000-67FF Test Failed, Odd Addresses
15 Timer Chip Test Failed
www.PAControl.com
484 Diagnostic Register
Bit Description
0 Continue on Error
1 CPU Test or Run Light Failed
2 Parallel Port Test Failed
3 Asynchronous Bus Test Failed
4 Timer 0 Test Failed
5 Timer 1 Test Failed
6 Timer 2 Test Failed
7 ROM Chip 0000-07FF Test Failed
8 Continuous ROM Checksum Test in Execution
9 ROM Chip 0800-0FFF Test Failed
10 ROM Chip 1000-17FF Test Failed
11 ROM Chip 1800-1FFF Test Failed
12 RAM Chip 4000-40FF Test Failed
13 RAM Chip 4100-41FF Test Failed
14 RAM Chip 4200-42FF Test Failed
15 RAM Chip 4300-43FF Test Failed
www.PAControl.com
08 Diagnostics (Continued)
Bit Description
0 Modbus IOP Overrun Errors Flag
1 Modbus Option Overrun Errors Flag
2 Modbus IOP Failed
3 Modlbus Option Failed
4 Ourbus IOP Failed
5 Remote IO Failed
6 Main CPU Failed
7 Table RAM Checksum Failed
8 Scan Task exceeded its time limit - too much user logic
9 Not Used
10 Not Used
11 Not Used
12 Not Used
13 Not Used
14 Not Used
15 Not Used
www.PAControl.com
03 Change ASCII Input Delimiter
The character ‘CHAR’ passed in the query data field becomes the end of message
delimiter for future messages (replacing the default LF character). This function is
useful in cases where a Line Feed is not wanted at the end of ASCII messages.
Forces the addressed slave to its Listen Only Mode for Modbus communications.
This isolates it from the other devices on the network, allowing them to continue
communicating without interruption from the addressed slave. No response is
returned.
When the slave enters its Listen Only Mode, all active communication controls are
turned off. The Ready watchdog timer is allowed to expire, locking the controls off.
While in this mode, any Modbus messages addressed to the slave or broadcast
are monitored, but no actions will be taken and no responses will be sent.
The only function that will be processed after the mode is entered will be the
Restart Communications Option function (function code 8, subfunction 1).
For controllers other than the 584 or 984, clears all counters and the diagnostic
register. For the 584 or 984, clears the counters only. Counters are also cleared
upon power–up.
www.PAControl.com
08 Diagnostics (Continued)
The response data field returns the quantity of messages that the slave has
detected on the communications system since its last restart, clear counters
operation, or power–up.
The response data field returns the quantity of CRC errors encountered by the
slave since its last restart, clear counters operation, or power–up.
The response data field returns the quantity of Modbus exception responses
returned by the slave since its last restart, clear counters operation, or power–up.
Exception responses are described and listed in Appendix A.
www.PAControl.com
14 (0E Hex) Return Slave Message Count
The response data field returns the quantity of messages addressed to the slave,
or broadcast, that the slave has processed since its last restart, clear counters
operation, or power–up.
The response data field returns the quantity of messages addressed to the slave
for which it returned no response (neither a normal response nor an exception
response), since its last restart, clear counters operation, or power–up.
The response data field returns the quantity of messages addressed to the slave
for which it returned a Negative Acknowledge (NAK) exception response, since its
last restart, clear counters operation, or power–up. Exception responses are
described and listed in Appendix A.
www.PAControl.com
08 Diagnostics (Continued)
The response data field returns the quantity of messages addressed to the slave
for which it returned a Slave Device Busy exception response, since its last
restart, clear counters operation, or power–up. Exception responses are
described and listed in Appendix A.
The response data field returns the quantity of messages addressed to the slave
that it could not handle due to a character overrun condition, since its last restart,
clear counters operation, or power–up. A character overrun is caused by data
characters arriving at the port faster than they can be stored, or by the loss of a
character due to a hardware malfunction.
The response data field returns the quantity of messages addressed to the slave
that it could not handle due to an 884 IOP overrun condition, since its last restart,
clear counters operation, or power–up. An IOP overrun is caused by data
characters arriving at the port faster than they can be stored, or by the loss of a
character due to a hardware malfunction. This function is specific to the 884.
www.PAControl.com
20 (14 Hex) Clear Overrun Counter and Flag (884)
Clears the 884 overrun error counter and resets the error flag. The current state
of the flag is found in bit 0 of the 884 diagnostic register (see subfunction 02).
This function is specific to the 884.
www.PAControl.com
08 Diagnostics (Continued)
Returns a series of 54 16-bit words (108 bytes) in the data field of the response
(this function differs from the usual two-byte length of the data field). The data
contains the statistics for the Modbus Plus peer processor in the slave device.
In addition to the Function code (08) and Subfunction code (00 15 hex) in the
query, a two-byte Operation field is used to specify either a ‘Get Statistics’ or a
‘Clear Statistics’ operation. The two operations are exclusive - the ‘Get’ operation
cannot clear the statistics, and the ‘Clear’ operation does not return statistics prior
to clearing them. Statistics are also cleared on power-up of the slave device.
The operation field immediately follows the subfunction field in the query:
–– A value of 00 03 specifies the ‘Get Statistics’ operation.
–– A value of 00 04 specifies the ‘Clear Statistics’ operation.
GET STATISTICS RESPONSE: This is the field sequence in the normal response
to a Get Statistics query:
Function Subfunction Operation Byte Count Data
08 00 15 00 03 00 6C Words 00 - 53
www.PAControl.com
Modbus Plus Network Statistics
01 0 ... 11 Software version number in hex (to read, strip bits 12–15 from word)
12 ... 14 Reserved
15 Defines Word 15 error counters (see Word 15)
www.PAControl.com
08 Diagnostics (Continued)
Modbus Plus Network Statistics (Continued)
Word Bits Meaning
05 Token pass counter; increments each time this station gets the token
www.PAControl.com
Word Byte Meaning
www.PAControl.com
08 Diagnostics (Continued)
Modbus Plus Network Statistics (Continued)
Word Bits Meaning
www.PAControl.com
Word Bits Meaning
www.PAControl.com
Appendix A
Exception Responses
Exception Responses
Exception Codes
www.PAControl.com
Exception Responses
Except for broadcast messages, when a master device sends a query to a slave
device it expects a normal response. One of four possible events can occur from
the master’s query:
If the slave device receives the query without a communication error, and can
handle the query normally, it returns a normal response.
If the slave does not receive the query due to a communication error, no
response is returned. The master program will eventually process a timeout
condition for the query.
If the slave receives the query, but detects a communication error (parity, LRC,
or CRC), no response is returned. The master program will eventually process
a timeout condition for the query.
If the slave receives the query without a communication error, but cannot
handle it (for example, if the request is to read a non–existent coil or register),
the slave will return an exception response informing the master of the nature of
the error.
The exception response message has two fields that differentiate it from a normal
response:
Function Code Field: In a normal response, the slave echoes the function code
of the original query in the function code field of the response. All function codes
have a most–significant bit (MSB) of 0 (their values are all below 80 hexadecimal).
In an exception response, the slave sets the MSB of the function code to 1. This
makes the function code value in an exception response exactly 80 hexadecimal
higher than the value would be for a normal response.
With the function code’s MSB set, the master’s application program can recognize
the exception response and can examine the data field for the exception code.
Data Field: In a normal response, the slave may return data or statistics in the
data field (any information that was requested in the query). In an exception
response, the slave returns an exception code in the data field. This defines the
slave condition that caused the exception.
www.PAControl.com
Figure 46 shows an example of a master query and slave exception response.
The field examples are shown in hexadecimal.
QUERY
1 Slave Address 0A
2 Function 01
3 Starting Address Hi 04
4 Starting Address Lo A1
5 No. of Coils Hi 00
6 No. of Coils Lo 01
7 LRC 4F
EXCEPTION RESPONSE
1 Slave Address 0A
2 Function 81
3 Exception Code 02
4 LRC 73
In this example, the master addresses a query to slave device 10 (0A hex). The
function code (01) is for a Read Coil Status operation. It requests the status of the
coil at address 1245 (04A1 hex). Note that only that one coil is to be read, as
specified by the number of coils field (0001).
If the coil address is non–existent in the slave device, the slave will return the
exception response with the exception code shown (02). This specifies an illegal
data address for the slave. For example, if the slave is a 984–385 with 512 coils,
this code would be returned.
www.PAControl.com
Exception Codes
www.PAControl.com
07 NEGATIVE ACKNOWLEDGE The slave cannot perform the program
function received in the query. This
code is returned for an unsuccessful
programming request using function
code 13 or 14 decimal. The master
should request diagnostic or error
information from the slave.
www.PAControl.com
Appendix B
Application Notes
www.PAControl.com
Maximum Query/Response Parameters
The listings in this section show the maximum amount of data that each controller
can request or send in a master query, or return in a slave response. All function
codes and quantities are in decimal.
184/384
www.PAControl.com
484
These values are for an 8K controller. See the 484 User’s Guide for limits of
smaller controllers.
www.PAControl.com
Maximum Q/R Parameters (Continued)
584
Notes:
(1) The maximum length of the entire message must not exceed 256 bytes.
www.PAControl.com
884
Notes:
(1) The maximum length of the entire message must not exceed 256 bytes.
www.PAControl.com
Maximum Q/R Parameters (Continued)
M84
Notes:
(1) The maximum length of the entire message must not exceed 256 bytes.
984
104 Application Notes PI–MBUS–300
www.PAControl.com
Function Description Query Response
Notes:
(1) The maximum length of the entire message must not exceed 256 bytes.
www.PAControl.com
Estimating Serial Transaction Timing
2. The master device modem RTS and CTS status are checked. ( A )
6. The slave device modem RTS and CTS status are checked. ( A )
8. The master application acts upon the response and its data.
Timing Notes
( A ) If the RTS and CTS pins are jumpered together, this time is negligible.
For J478 modems, the time is about 5 ms.
( C ) The Modbus message is processed at the end of the controller scan. The
worst–case delay is one scan time, which occurs if the controller has just
begun a new scan. The average delay is 0.5 scan time.
The time allotted for servicing Modbus ports at the end of the controller
scan (before beginning a new scan) depends upon the controller model.
Timing for each model is described on the next page.
www.PAControl.com
( C ) Continued:
For 484 controllers the time is approximately 1.5 ms. The Modbus port is
available on a contention basis with any J470/J474/J475 that is present.
For 584 and 984 controllers the time is approximately 1.5 ms for each
Modbus port. The ports are serviced sequentially, starting with port 1.
For 184/384 controllers the time varies according to the amount of data
being handled. It ranges from a minimum of 0.5 ms to a maximum of about
6.0 ms (for 100 registers), or 7.0 ms (for 800 coils). If a programming panel
is currently being used with the controller, the Modbus port is locked out.
The amount of data that can be processed during one service period at the
Modbus port is as follows:
Discretes Registers
Micro 84 16 4
184/384 800 100
484 32 16
584 64 32
984A/B/X 64 32
984–X8X 1000 125
For the 884, the processing time for multiple data is as follows:
Read 768 coils: 14 scans Force single coil: 3 scans
Read 256 inputs: 7 scans Preset registers: 3 scans
Read 125 output registers: 5 scans Force 768 coils: 18 scans
Read 125 input registers: 8 scans Preset 100 registers: 10 scans
( E ) LRC calculation time is less than 1 ms. CRC calculation time is about
0.3 ms for each 8 bits of data to be returned in the response.
www.PAControl.com
Notes for the 584 and 984A/B/X
These application notes apply only to Modicon 584 and 984A/B/X controllers.
Baud Rates: When using both Modbus ports 1 and 2, the maximum allowable
combined baud rate is 19,200 baud.
Port Lockups: When using ASCII, avoid sending ‘zero data length’ messages,
or messages with no device address. For example, this is an illegal message:
www.PAControl.com
Appendix C
LRC/CRC Generation
LRC Generation
CRC Generation
www.PAControl.com
LRC Generation
The Longitudinal Redundancy Check (LRC) field is one byte, containing an 8–bit
binary value. The LRC value is calculated by the transmitting device, which
appends the LRC to the message. The receiving device recalculates an LRC
during receipt of the message, and compares the calculated value to the actual
value it received in the LRC field. If the two values are not equal, an error results.
The LRC is calculated by adding together successive 8–bit bytes in the message,
discarding any carries, and then two’s complementing the result. The LRC is an
8–bit field, therefore each new addition of a character that would result in a value
higher than 255 decimal simply ‘rolls over’ the field’s value through zero. Because
there is no ninth bit, the carry is discarded automatically.
1. Add all bytes in the message, excluding the starting ‘colon’ and ending
CRLF. Add them into an 8–bit field, so that carries will be discarded.
2. Subtract the final field value from FF hex (all 1’s), to produce the
ones–complement.
When the the 8–bit LRC (2 ASCII characters) is transmitted in the message, the
high–order character will be transmitted first, followed by the low–order character.
For example, if the LRC value is 61 hex (0110 0001):
6 1
www.PAControl.com
Example
{
unsigned char uchLRC = 0 ; /* LRC char initialized */
www.PAControl.com
CRC Generation
The Cyclical Redundancy Check (CRC) field is two bytes, containing a 16–bit
binary value. The CRC value is calculated by the transmitting device, which
appends the CRC to the message. The receiving device recalculates a CRC
during receipt of the message, and compares the calculated value to the actual
value it received in the CRC field. If the two values are not equal, an error results.
The CRC is started by first preloading a 16–bit register to all 1’s. Then a process
begins of applying successive 8–bit bytes of the message to the current contents
of the register. Only the eight bits of data in each character are used for generating
the CRC. Start and stop bits, and the parity bit, do not apply to the CRC.
During generation of the CRC, each 8–bit character is exclusive ORed with the
register contents. Then the result is shifted in the direction of the least significant
bit (LSB), with a zero filled into the most significant bit (MSB) position. The LSB is
extracted and examined. If the LSB was a 1, the register is then exclusive ORed
with a preset, fixed value. If the LSB was a 0, no exclusive OR takes place.
This process is repeated until eight shifts have been performed. After the last
(eighth) shift, the next 8–bit character is exclusive ORed with the register’s current
value, and the process repeats for eight more shifts as described above. The final
contents of the register, after all the characters of the message have been applied,
is the CRC value.
1, Load a 16–bit register with FFFF hex (all 1’s). Call this the CRC register.
2. Exclusive OR the first 8–bit byte of the message with the low–order byte
of the 16–bit CRC register, putting the result in the CRC register.
3. Shift the CRC register one bit to the right (toward the LSB), zero–filling the
MSB. Extract and examine the LSB.
5. Repeat Steps 3 and 4 until 8 shifts have been performed. When this is
done, a complete 8–bit byte will have been processed.
www.PAControl.com
6. Repeat Steps 2 through 5 for the next 8–bit byte of the message.
Continue doing this until all bytes have been processed.
8. When the CRC is placed into the message, its upper and lower bytes
must be swapped as described below.
When the 16–bit CRC (two 8–bit bytes) is transmitted in the message, the
low-order byte will be transmitted first, followed by the high-order byte.
For example, if the CRC value is 1241 hex (0001 0010 0100 0001):
Data CR CR
Addr Func Data Data Data Data CLo CHi
Count
41 12
Example
An example of a C language function performing CRC generation is shown on the
following pages. All of the possible CRC values are preloaded into two arrays,
which are simply indexed as the function increments through the message buffer.
One array contains all of the 256 possible CRC values for the high byte of the
16–bit CRC field, and the other array contains all of the values for the low byte.
Indexing the CRC in this way provides faster execution than would be achieved by
calculating a new CRC value with each new character from the message buffer.
Note This function performs the swapping of the high/low CRC bytes
internally. The bytes are already swapped in the CRC value that is
returned from the function.
Therefore the CRC value returned from the function can be directly
placed into the message for transmission.
www.PAControl.com
CRC Generation (Continued)
Example (Continued)
{
unsigned char uchCRCHi = 0xFF ; /* high byte of CRC initialized */
unsigned char uchCRCLo = 0xFF ; /* low byte of CRC initialized */
unsigned uIndex ; /* will index into CRC lookup table */
www.PAControl.com
High-Order Byte Table
www.PAControl.com