Mappa Di Memoria / Memory Map: Gfx4 Access Mode
Mappa Di Memoria / Memory Map: Gfx4 Access Mode
50 – 07/2022
CUSTOM PARAMETERS ZONE 1 PARAMETERS ZONE 2 PARAMETERS ZONE 3 PARAMETERS ZONE 4 PARAMETERS
Data address Data address Data address Data address Data address
S7-7 DESCRIPTION 16 bit 16 bit 16 bit 16 bit 16 bit
Device Device Device Device Device
address address address address address
Data address Data address Data address Data address Data address
1 bit 1 bit 1 bit 1 bit 1 bit
1024 + address from 2048 + address from 4096 + address from 8192 + address from
from CUSTOM MAP ZONE MAP ZONE MAP ZONE MAP ZONE MAP
(16bits access) (16bits access) (16bits access) (16bits access)
OFF
GFX4 standard NODE NODE NODE NODE NODE
(0)
1024 + address from 2048 + address from 4096 + address from 8192 + address from
Disabled ZONE MAP ZONE MAP ZONE MAP ZONE MAP
(1bit access) (1bit access) (1bit access) (1bit access)
NOTE:
The access mode is selected by the dipswitch S7-7 (Modbus address 346 STATUS_JUMPER bit8 read only).
The value from the rotary switches defines the NODE.
1
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
(16bit access)
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
0 P.V. Variabile di Processo Process variable R Lo.S Hi.S dP.S of SPU - S.p.
1 SPA Set Point attivo Active setpoint R Lo.L Hi.L dP.S of SPU - S.p.
5 h.Pb Banda proporzionale di riscaldamento Heating proportional band R/W 0.0 999.9 1 1.0 %
6 c.Pb Banda proporzionale di raffreddamento Cooling proportional band R/W 0.0 999.9 1 1.0 %
7 h.It Tempo integrale di riscaldamento Heating integral time R/W 0.00 99.99 2 4.00 min
8 h.dt Tempo derivativo di riscaldamento Heating derivative time R/W 0.00 99.99 2 1.00 min
9 Ct.1 Tempo di ciclo out1 (fast) Cycle time Out1 (fast) R/W 0 (0.0) 200 (20.0) 0 (1) 2 (0.2) Sec
10 Lo.S Minimo scala Scale minimum limit R/W -1999 9999 DP.S 0 S.p.
11 Hi.S Massimo scala Scale maximum limit R/W -1999 9999 DP.S 1000 S.p.
Allarme 1 (se di tipo relativo) Alarm point 1 ( if relative ) -1999 9999 (999)
12 AL.1 R/W Depending on A1.r 500 S.p.
[se di tipo relativoe simmetrico] [if relative and symmetrical] (-999) [0] [999]
Allarme 2 (se di tipo relativo) Alarm point 2 ( if relative ) -1999 9999 (999)
13 AL.2 R/W Depending on A2.r 100 S.p.
[se di tipo relativo e simmetrico] [if relative and symmetrical] (-999) [0] [999]
Allarme 3 (se di tipo relativo) Alarm point 3 ( if relative ) -1999 9999 (999)
14 AL.3 R/W Depending on A3.r 700 S.p.
[se di tipo relativo e simmetrico] [if relative and symmetrical] (-999) [0] [999]
16 _SP Set point locale Local setpoint R/W Lo.L Hi.L dP.S of SPU 0 S.p.
2
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
18 SP.r Definizione set point remoto Remote setpoint type R/W 0 127 - 0 -
23 oFS. Offset ingresso principale Main input offset correction R/W -999 999 DP.S 0 S.p.
24 Flt Filtro digitale ingresso principale Digital filter on Main input R/W 0.0 20.0 1 0.1 sec
Lower limit for setting setpoint and absolute
25 Lo.L Limite inferiore allarme 1 R/W Lo.S Hi.S dP.S of SPU 0 S.p.
alarms
Upper limit for setting setpoint and absolute
26 Hi.L Limite superiore allarme 1 R/W Lo.S Hi.S dP.S of SPU 1000 S.p.
alarms
Depending on A1.r
27 HY.1 Isteresi per allarme 1 Hysteresis alarm 1 R/W -999 999 -1 S.p.
and A1.t
Lower limit for setting setpoint and absolute
28 Lo.L Limite inferiore allarme 2 R/W Lo.S Hi.S dP.S of SPU 0 S.p.
alarms
Upper limit for setting setpoint and absolute
29 Hi.L Limite superiore allarme 2 R/W Lo.S Hi.S dP.S of SPU 1000 S.p.
alarms
Depending on A2.r
30 HY.2 Isteresi per allarme 2 Hysteresis alarm 2 R/W -999 999 -1 S.p.
and A2.t
31 S.tu Codice selftuning Enabling selftuning, autotuning and softstart R/W 0 141 0 0 -
42 h.P.H Limite Max. potenza riscaldamento Heating maximim power limit R/W 0.0 100.0 1 100.0 %
43 c.P.H Limite Max. potenza raffreddamento Cooling maximum power limit R/W 0.0 100.0 1 100.0 %
44 Lb.t Tempo di intervento allarme LBA Waiting time for L.B.A. alarm intervention R/W 0.0 500.0 1 30.0 min
3
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
Allarme 3 (se di tipo relativo) Alarm point 3 ( if relative ) -1999 9999 (999)
52 AL.3 R/W Depending on A3.r 700 S.p.
[se di tipo relativoe simmetrico] [if relative and symmetrical] (-999) [0] [999]
Depending on A3.r
53 HY.3 Isteresi allarme 3 Hysteresis alarm 3 R/W -999 999 -1 S.p.
and A3.t
54 A3.t Tipo allarme 3 Alarm type 3 R/W 0 479 0 0 -
56 Hb.t Tempo di attesa allarme HB Waiting time for HB alarm intervention R/W 0 999 0 30 sec
76 c.It Tempo integrale di raffreddamento Cooling integral time R/W 0.00 99.99 2 4.00 min
77 c.dt Tempo derivativo di raffreddamento Cooling derivative time R/W 0.00 99.99 2 1.00 min
78 rSt Manual reset Manual reset R/W -999 999 dP.S of SPU 0 S.p.
86 S.00 Punto 0 scala custom Custom scale point 0 R/W -1999 9999 dP.S of SPU 0 S.p. √
87 S.01 Punto 1 scala custom Custom scale point 1 R/W -1999 9999 dP.S of SPU 31 S.p. √
4
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
88 S.02 Punto 2 scala custom Custom scale point 2 R/W -1999 9999 dP.S of SPU 62 S.p. √
89 S.03 Punto 3 scala custom Custom scale point 3 R/W -1999 9999 dP.S of SPU 94 S.p. √
90 S.04 Punto 4 scala custom Custom scale point 4 R/W -1999 9999 dP.S of SPU 125 S.p. √
91 S.05 Punto 5 scala custom Custom scale point 5 R/W -1999 9999 dP.S of SPU 156 S.p. √
92 S.06 Punto 6 scala custom Custom scale point 6 R/W -1999 9999 dP.S of SPU 187 S.p. √
93 S.07 Punto 7 scala custom Custom scale point 7 R/W -1999 9999 dP.S of SPU 219 S.p. √
94 S.08 Punto 8 scala custom Custom scale point 8 R/W -1999 9999 dP.S of SPU 250 S.p. √
95 S.09 Punto 9 scala custom Custom scale point 9 R/W -1999 9999 dP.S of SPU 281 S.p. √
96 S.10 Punto 10 scala custom Custom scale point 10 R/W -1999 9999 dP.S of SPU 312 S.p. √
97 S.11 Punto 11 scala custom Custom scale point 11 R/W -1999 9999 dP.S of SPU 344 S.p. √
98 S.12 Punto 12 scala custom Custom scale point 12 R/W -1999 9999 dP.S of SPU 375 S.p. √
99 S.13 Punto 13 scala custom Custom scale point 13 R/W -1999 9999 dP.S of SPU 406 S.p. √
100 S.14 Punto 14 scala custom Custom scale point 14 R/W -1999 9999 dP.S of SPU 437 S.p. √
101 S.15 Punto 15 scala custom Custom scale point 15 R/W -1999 9999 dP.S of SPU 469 S.p. √
102 S.16 Punto 16 scala custom Custom scale point 16 R/W -1999 9999 dP.S of SPU 500 S.p. √
103 S.17 Punto 17 scala custom Custom scale point 17 R/W -1999 9999 dP.S of SPU 531 S.p. √
104 S.18 Punto 18 scala custom Custom scale point 18 R/W -1999 9999 dP.S of SPU 562 S.p. √
105 S.19 Punto 19 scala custom Custom scale point 19 R/W -1999 9999 dP.S of SPU 594 S.p. √
106 S.20 Punto 20 scala custom Custom scale point 20 R/W -1999 9999 dP.S of SPU 625 S.p. √
107 S.21 Punto 21 scala custom Custom scale point 21 R/W -1999 9999 dP.S of SPU 656 S.p. √
108 S.22 Punto 22 scala custom Custom scale point 22 R/W -1999 9999 dP.S of SPU 687 S.p. √
109 S.23 Punto 23 scala custom Custom scale point 23 R/W -1999 9999 dP.S of SPU 719 S.p. √
5
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
110 S.24 Punto 24 scala custom Custom scale point 24 R/W -1999 9999 dP.S of SPU 750 S.p. √
111 S.25 Punto 25 scala custom Custom scale point 25 R/W -1999 9999 dP.S of SPU 781 S.p. √
112 S.26 Punto 26 scala custom Custom scale point 26 R/W -1999 9999 dP.S of SPU 812 S.p. √
113 S.27 Punto 27 scala custom Custom scale point 27 R/W -1999 9999 dP.S of SPU 844 S.p. √
114 S.28 Punto 28 scala custom Custom scale point 28 R/W -1999 9999 dP.S of SPU 875 S.p. √
115 S.29 Punto 29 scala custom Custom scale point 29 R/W -1999 9999 dP.S of SPU 906 S.p. √
116 S.30 Punto 30 scala custom Custom scale point 30 R/W -1999 9999 dP.S of SPU 937 S.p. √
117 S.31 Punto 31 scala custom Custom scale point 31 R/W -1999 9999 dP.S of SPU 969 S.p. √
118 S.32 Punto 32 scala custom Custom scale point 32 R/W -1999 9999 dP.S of SPU 1000 S.p. √
119 Lb.P Potenza da allarme L.B.A. Power limit for L.B.A. alarm condition R/W -100.0 100.0 1 25.0 %
125 - Riservato (Act: Tempo corsa attuatore) Reserved (Act: actuator travel) time) - - - - - -
Riservato (t_LO: Tempo minimo impulso/ Reserved (t_LO: Impulse minimum time/
126 -
tempo corsa attuatore) actuator travel time)
- - - - - -
127 - Riservato (db: Zona morta per valvole) Reserved (db: Valve dead zone) - - - - - -
136 SP.r Definizione set point remoto Remote setpoint type R/W 0 127 0 0 -
137 SPA Set Point attivo Active setpoint R Lo.L Hi.L dP.S of SPU - S.p.
6
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
138 _SP Set point locale Local setpoint R/W Lo.L Hi.L dP.S of SPU 0 S.p.
139 I.tA1 Ingresso TA1 TA1 input value R 0.0 H.tA1 1 - S.p.
146 h.P.H Limite Max Potenza riscaldamento Heating maximum power limit R/W 0.0 100.0 1 100.0 %
147 SoF Tempo di softstart Soft-Start time R/W 0.0 500.0 1 0.0 Min
148 h.Pb Banda proporzionale di riscaldamento Heating proportional band R/W 0.0 999.9 1 1.0 %
149 h.Pb Isteresi riscaldamento (ON/OFF) Hysteresis for heating ( ON/OFF ) R/W 0.0 999.9 1 1.0 %
150 h.It Tempo integrale di riscaldamento Heating integral time R/W 0.00 99.99 2 4.00 Min
151 h.dt Tempo derivativo di riscaldamento Heating derivative time R/W 0.00 99.99 2 1.00 Min
152 Ct.1 Tempo di ciclo out1 (fast) Cycle time Out1 (fast) R/W 0 (0.0) 200 (20.0) 0 (1) 2 (0.2) Sec
159 Ct.2 Tempo di ciclo out2 (fast) Cycle time Out2 (fast) R/W 0 (0.0) 200 (20.0) 0 (1) 20 (2.0) sec
160 rL.1 Riferimento uscita rL.1 RL.1 allocation of reference signal R/W 0 189 0 0 -
163 rL.2 Riferimento uscita rL.2 RL.2 allocation of reference signal R/W 0 189 0 1 -
166 rL.3 Riferimento uscita rL.3 rL.3 allocation of reference signal R/W 2 189 0 2 -
7
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
170 rL.4 Riferimento uscita rL.4 rL.4 allocation of reference signal R/W 2 189 0 35 -
171 rL.5 Riferimento uscita rL.5 rL.5 allocation of reference signal R/W 2 189 0 4 -
172 rL.6 Riferimento uscita rL.6 rL.6 allocation of reference signal R/W 2 189 0 160 -
Allarme 1 (se di tipo relativo) [se di tipo Alarm point 1 ( if relative ) [if relative and -1999 9999 (999)
177 AL.1 R/W Depending on A1.r 500 S.p.
relativo e simmetrico] symmetrical] (-999) [0] [999]
Allarme 2 (se di tipo relativo) [se di tipo Alarm point 2 ( if relative ) [if relative and -1999 9999 (999)
178 AL.2 R/W Depending on A2.r 100 S.p.
relativo e simmetrico] symmetrical] (-999) [0] [999]
179 Fld Filtro digitale ingresso principale Main input digital filter R/W 0.0 9.9 1 0.5 S.p.
181 tP.2 Funzione ingresso analogico Ausiliario Auxiliary analogue input function R/W 0 3 0 0 -
Depending on A1.r
187 HY.1 Isteresi allarme 1 Hysteresis alarm 1 R/W -999 999 -1 S.p.
and A1.t
Depending on A2.r
188 HY.2 Isteresi allarme 2 Hysteresis alarm 2 R/W -999 999 -1 S.p.
and A2.t
Depending on A3.r
189 HY.3 Isteresi allarme 3 Hysteresis alarm 3 R/W -999 999 -1 S.p.
and A3.t
190 C.Hd Codice configurazione hardware Hardware configuration R 0 16 0 - - √
194 AI.2 Selezione tipo sensore ingresso Ausiliario Probe type for auxiliary input selection R/W 0 99 0 0 -
195 AL.n Abilitazione allarmi Select number of enabled alarms R/W 0 63 0 3 -
8
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
215 A1.r Riferimento per allarme 1 Select reference signal for alarm 1 R/W 0 5 0 0 -
216 A2.r Riferimento per allarme 2 Select reference signal for alarm 2 R/W 0 5 0 0 -
217 A3.r Riferimento per allarme 3 Select reference signal for alarm 3 R/W 0 5 0 0 -
218 A4.r Riferimento per allarme 4 Select reference signal for alarm 4 R/W 0 5 0 0 -
219 Ft.tA1 Filtro ingresso TA TA inputs digital filter R/W 0.0 20.0 1 0.0 sec
220 o.tA1 Offset per ingresso TA1 Offset correction for TA1 input R/W -99.9 99.9 1 0.0 S.p.
225 S.Ou Uscite strumento virtuale Virtual instrument outputs R/W 0 1023 0 0 - √
227 I.tA1 Valore ingresso TA TA1 input value R 0.0 H.tA1 1 - S.p.
228 FA.P Uscita di fault action Power output in fault condition R/W -100.0 100.0 1 0.0 %
Fault action ( sets state in case of broken
229 REL Stato allarmi in fault action R/W 0 15 0 0 -
probe )
230 SP.1 Set point 1 Setpoint 1 R/W Lo.L Hi.L dP.S of SPU 100 S.p.
231 SP.2 Set point 2 Setpoint 2 R/W Lo.L Hi.L dP.S of SPU 200 S.p.
234 G.SP Gradiente di set point Set gradient R/W 0.0 999.9 1 0.0 digit/min
238 - Riservato (ACT: Tempo corsa attuatore) Reserved (ACT: Actuator travel time) - - - - - -
9
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
Riservato (t_Lo: minima variazione potenza Reserved (t_Lo: Impulse minimum time/
239 - - - - - - -
per attivazione valvola actuator travel time
240 - Riservato (t_Hi: Soglia di intervento impulsivo Reserved (t_Hi: Pulse alarm point - - - - - -
241 - Riservato (db: Zona morta per valvole Reserved (db: Valve dead zone - - - - - -
242 - Riservato (Atty: Tipo controllo valvole Reserved (Atty: Valves control type - - - - - -
249 SP.r Definizione set point remoto Remote setpoint type R/W 0 127 0 0 -
250 - Set point remoto da seriale Remote setpoint from serial line R/W Lo.L Hi.L 0 0 S.p.
MAN_POWER: MAN_POWER:
252 - R/W -100.0 100.0 1 0 %
Uscita regolazione manuale Control output value in manual mode
254 h.P.L Limite Min. potenza di riscaldamento Heating minimum power limit R/W 0.0 100.0 1 0.0 %
255 c.P.L Limite Min. potenza di raffredamento Cooling minimum power limit R/W 0.0 100.0 1 0.0 %
259 G.S2 Gradiente di set ausiliario riferito a SP2 Auxiliary set gradient for SP2 R/W 0.0 999.9 1 0.0 digit/min
260 Pf.t Tempo di intervento dell’allarme di potenza Power alarm delay time R/W 0 999 0 0 Sec
261 b.St Banda di stabilità (canali caldi) Steady band (hot runners) R/W 0.0 100.0 1 0.0 %
10
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
262 b.PF Banda di allarme di potenza (canali caldi) Power alarm band (hot runners) R/W 0.0 100.0 1 0.0 %
263 SP.S Set Point soft start (canali caldi) Set Point soft start (hot runners) R/W Lo.L Hi.L dP.S of SPU 0 p.s.
264 So.P Potenza di soft start Soft start power R/W -100.0 100.0 1 0.0 %
265 Hot Selezione funzioni associate ai canali caldi Functions selection for hot runners R/W 0 15 0 0 -
293 S.33 Punto 33 scala custom Custom scale point 33 R/W -1999 9999 2 0.00 mV √
294 S.34 Punto 34 scala custom Custom scale point 34 R/W -1999 9999 2 0.01 mV √
295 S.35 Punto 35 scala custom Custom scale point 35 R/W -1999 9999 3 0.000 mV √
FLG_PID: FLG_PID:
bit3=selftuning attivo, bit3=active selftuning,
296 - R 0 255 0 - -
bit4 = softstart in progress, bit6=autotuning bit4 = softstart in progress, bit6=active
attivo autotuning
11
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
321 - AL4_RAM allarme 4 da seriale AL4_RAM alarm 4 from serial line R/W -1999 9999 Depending on A4.r 0 S.p.
341 - AL1_RAM allarme 1 da seriale AL1_RAM alarm 1 from serial line R/W -1999 9999 Depending on A1.r 0 S.p.
12
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
342 - AL2_RAM allarme 2 da seriale AL2_RAM alarm 2 from serial line R/W -1999 9999 Depending on A2.r 0 S.p.
343 - AL3_RAM allarme 3 da seriale AL3_RAM alarm 3 from serial line R/W -1999 9999 Depending on A3.r 0 S.p.
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
14
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
402 Hi.S Massimo scala Scale maximum limit R/W -1999 9999 DP.S 1000 S.p.
403 dP.S Posizione del punto decimale Decimal point position R/W 0 3 - 0 -
404 LS.2 Minimo scala per l’ingresso Ausiliario Auxiliary input minimum range R/W -1999 9999 dP.2 0 S.p.
410 HS.tV1 Max scala ingresso ausiliario TV Auxiliary input TV scale maximum limit R/W 0.0 999.9 1 530.0 S.p.
411 oF.tV1 Offset ingresso ausiliario TV Auxiliary input TV offset correction R/W -99.9 99.9 1 0.0 S.p.
412 Ft.tV1 Filtro digitale ingressi ausiliari TV TV inputs digital filter R/W 0.0 20.0 1 0.0 sec
Max scala ingresso ausiliario TA2 zona 2 (per Auxiliary input maximum range TA2 of zone 2 100.0
413 H.tA2 R/W 0.0 999.9 1 (20.0/40.0/ S.p. √
GFX4 con potenza 30KW / 60KW / 80KW) (for GFX4 with power 30KW / 60KW/ 80KW) 60.0)
15
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
Max scala ingresso ausiliario TA3 zona 3 (per Auxiliary input maximum range TA3 of zone 3 100.0
414 H.tA3 R/W 0.0 999.9 1 (20.0/40.0/ S.p. √
GFX4 con potenza 30KW / 60KW/ 80KW)) (for GFX4 with power 30KW / 60KW/ 80KW) 60.0)
415 o.tA2 Offset per ingresso ausiliario TA2 zona 2 Auxiliary input offset correction TA2 of zone 2 R/W -99.9 99.9 1 0.0 S.p. √
416 o.tA3 Offset per ingresso ausiliario TA3 zona 3 Auxiliary input offset correction TA3 of zone 3 R/W -99.9 99.9 1 0.0 S.p. √
417 H.tV2 Max scala ingresso ausiliario TV2 zona 2 Auxiliary input maximum range TV2 of zone 2 R/W 0.0 999.9 1 530.0 S.p. √
418 H.tV3 Max scala ingresso ausiliario TV3 zona 3 Auxiliary input maximum range TV3 of zone 3 R/W 0.0 999.9 1 530.0 S.p. √
419 o.tV2 Offset per ingresso ausiliario TV2 zona 2 Auxiliary input offset correction TV2 of zone 2 R/W -99.9 99.9 1 0.0 S.p. √
420 o.tV3 Offset per ingresso ausiliario TV3 zona 3 Auxiliary input offset correction TV3 of zone 3 R/W -99.9 99.9 1 0.0 S.p. √
16
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
17
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
STATUS_STRUMENTO1: INSTRUMENTS STATUS1:
bit0 = (AL1 or AL2 or AL3 or AL4 or ALHB. bit0 = (AL1 or AL2 or AL3 or AL4 or ALHB.
TA1 or ALHB.TA2 or ALHB.TA3 or POWER_ TA1 or ALHB.TA2 or ALHB.TA3 or POWER_
FAULT), FAULT),
bit1 = input Lo, bit1 = input Lo,
bit2 = input Hi, bit2 = input Hi,
bit3 = input Err, bit3 = input Err,
bit4 = input Sbr, bit4 = input Sbr,
469 - bit7 = LBA, bit7 = LBA, R 0 65535 0 - -
bit8 = AL1, bit8 = AL1,
bit9 = AL2, bit9 = AL2,
bit10 = AL3, bit10 = AL3,
bit11 = AL4, bit11 = AL4,
bit12 = ALHB.TA1, bit12 = ALHB.TA1,
bit13 = ALHB.TA2, bit13 = ALHB.TA2,
bit14 = ALHB.TA3, bit14 = ALHB.TA3,
bit15 = active selftuning bit15 = active selftuning
470 P.V. Variabile di Processo Process variable R Lo.S Hi.S dP.S of SPU - S.p.
472 _SP Set point locale Local setpoint R/W Lo.L Hi.L dP.S of SPU 0 S.p.
473 I.tA1 Valore ingresso TA1 TA1 input value R 0 H.tA1 1 - S.p.
18
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
STATUS_STRUMENTO: INSTRUMENTS STATUS:
bit0 = (AL1 or AL2 or AL3 or AL4 or ALHB. bit0 = (AL1 or AL2 or AL3 or AL4 or ALHB.
TA1 or ALHB.TA2 or ALHB.TA3 or POWER_ TA1 or ALHB.TA2 or ALHB.TA3 or POWER_
FAULT), FAULT),
bit1 = input Lo, bit1 = input Lo,
bit2 = input Hi, bit2 = input Hi,
bit3 = input Err, bit3 = input Err,
bit4 = input Sbr, bit4 = input Sbr,
bit5 = heat, bit5 = heat,
477 - bit6 = cool, bit6 = cool, R 0 65535 0 - -
bit7 = LBA, bit7 = LBA,
bit8 = AL1, bit8 = AL1,
bit9 = AL2, bit9 = AL2,
bit10 = AL3, bit10 = AL3,
bit11 = AL4, bit11 = AL4,
bit12 = ALHB or POWER_FAULT, bit12 = ALHB or POWER_FAULT,
bit13 = ON/OFF, bit13 = ON/OFF,
bit14 = AUTO/MAN, bit14 = AUTO/MAN,
bit15 = LOC/REM bit15 = LOC/REM
478 - Uscita regolazione manuale Control output value in manual mode R/W -100.0 100.0 1 - %
Allarme 3 (se di tipo relativo) Alarm point 3 ( if relative ) -1999 9999 (999)
479 AL.3 R/W Depending on A3.r 700 S.p.
[se di tipo relativoe simmetrico] [if relative and symmetrical] (-999) [0] [999]
Allarme 4 (se di tipo relativo) Alarm point 4 ( if relative ) -1999 9999 (999)
480 AL.4 R/W Depending on A4.r 800 S.p.
[se di tipo relativoe simmetrico] [if relative and symmetrical] (-999) [0] [999]
481 SPA Set Point attivo Active setpoint R Lo.L Hi.L dP.S of SPU 400 S.p.
482 SP.1 Set point 1 Setpoint 1 R/W Lo.L Hi.L dP.S of SPU 100 S.p.
483 SP.2 Set point 2 Set point 2 R/W Lo.L Hi.L dP.S of SPU 200 S.p.
Setpoint for cooling relative to heating
484 c.SP Set Point di raffreddamento R/W -25.0 25.0 1 0.0 %
setpoint
485 I.TV1 Valore ingresso TV1 TV1 input value R 0 H.TV1 1 - S.p.
19
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
490 I.tA2 Valore ingresso ausiliario TA fase 2 zona 2 Auxiliary input value TA 2 of zone 2 R 0.0 H.tA2 1 - S.p. √
491 I.tA3 Valore ingresso ausiliario TA fase 3 zona 3 Auxiliary input value TA 3 of zone 3 R 0.0 H.tA3 1 - S.p. √
492 I.tV2 Valore ingresso ausiliario TV fase 2 zona 2 Auxiliary input value TV 2 of zone 2 R 0.0 H.tV2 1 - S.p. √
493 I.tV3 Valore ingresso ausiliario TV fase 3 zona 3 Auxiliary input value TV 3 of zone 3 R 0.0 H.tV3 1 - S.p. √
494 I.AF2 VAL_TA2_F (valore dopo filtro Ft.tA) zona 2 VAL_TA2_F (value after filter Ft.tA) of zone 2 R/W 0 H.tA2 1 - - √
495 I.AF3 VAL_TA3_F (valore dopo filtro Ft.tA) zona 2 VAL_TA3_F (value after filter Ft.tA) of zone 3 R/W 0 H.tA3 1 - - √
496 I.VF2 VAL_TV2_F (valore dopo filtro Ft.tV) zona 2 VAL_TV2_F (value after filter Ft.tV) of zone 2 R/W 0 H.tV2 1 - - √
497 I.VF3 VAL_TV3_F (valore dopo filtro Ft.tV) zona 3 VAL_TV3_F (value after filter Ft.tV) of zone 3 R/W 0 H.tV3 1 - - √
502 A.Hb2 Allarme HB TA2 zona 2 Alarm HB TA2 of zone 2 R/W 0.0 H.tA2 1 10.0 S.p. √
503 A.Hb3 Allarme HB TA3 zona 3 Alarm HB TA3 of zone 3 R/W 0.0 H.tA3 1 10.0 S.p. √
20
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
Stato allarmi HB ALSTATE_HB: Alarm status HB ALSTATE_HB: bit0= HB TA2
bit0= HB TA2 tempo on, time on,
bit1= HB TA2 tempo off, bit1= HB TA2 time off,
504 - bit2= allarme HB TA2 bit2= alarm HB TA2 R 0 255 0 - -
bit3= HB TA3 tempo on, bit3= HB TA3 time on,
bit4= HB TA3 tempo off, bit4= HB TA3 time off,
bit5= allarme HB TA3 bit5= alarm HB TA3
Tensione di riferimento per correzione Reference voltage for manual power
505 RIF R/W 0.0 999.9 1 0.0 S.p.
potenza manuale correction
506 Cor Correzione potenza manuale Manual power correction R/W 0.0 100.0 1 0.0 %
507 - Potenza salvata in ON-OFF = OFF Power saved in ON-OFF = OFF R -100.0 100.0 1 - %
Stato allarmi ALSTATE: bit4 = allarme HB Alarms status ALSTATE: bit4 = alarm HB on
512 - tempo on, bit5 = allarme HB tempo off, bit6 = time, bit5 = alarm HB off time, bit6 = alarm R 0 255 0 - -
allarme HB HB
516 P.rS Potenza di reset Reset power R/W -100.0 100.0 1 0.0 %
517 - POWER_SET (canali caldi) POWER_SET (hot runners) R/W -100.0 100.0 1 0.0 %
519 oFS. Offset ingresso principale Offset correction for MAIN input R/W -999 999 DP.S 0 S.p.
21
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
603 HS.2 Massimo scala ingresso ausiliario Auxiliay input max scale R/W -1999 9999 dP.2 1000 S.p.
604 Flt.2 Filtro ingresso ausiliario Auxiliary input digital filter R/W 0.0 20.0 1 0.1 sec
605 oFS.2 Offset per ingresso ausiliario Auxiliary input offset correction R/W -999 999 dP.2 0 S.p.
606 Er.2 Codice errore ingresso ausiliario Auxiliary input self-diagnostic error code R 0 20 0 - -
22
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
1(zone1),
Attribuzione della variabile di processo di 2 (zone 2),
617 SPU Allocation of zone process variable R/W 0 4 0 -
zona 3 (zone 3),
4 (zone 4)
618 dIG.2 Attribuzione stato ingresso digitale DI2 Allocation of digital input 2 status R/W 0 62 0 0 - √
628 S.LI Led e ingressi digitali strumento virtuale Virtual instrument led and digital input R/W 0 1023 0 0 - √
629 P.SoF Tempo di softstart di fase Phase softstart time R/W 0 20.0 1 0 sec
630 P.S.Hi Fase massima di softstart Max phase softstart R/W 0 100.0 1 0 %
23
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
24
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
25
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
664 - Stato uscite out.x MASKOUT_GFX4 Output out.x status MASKOUT_GFX4 R 0 1024 0 - - √
26
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
680 Hd.3 Abilitazione gestione potenza euristica Heuristic power managing enable R/W 0 15 0 0 - √
681 I.HEU Corrente massima gestione potenza euristica Heuristic power managing max current R/W 0.0 999.9 1 0.0 - √
682 Hd.4 Abilitazione gestione potenza eterogenea Heterogeneous power managing enable R/W 0 15 0 0 - √
691 S.Ou Uscite strumento virtuale Virtual instrument outputs R/W 0 1023 0 0 - √
693 Upd.F Versione software scheda fieldbus Fieldbus board software version R - - 2 - - √
696 Bau.F Baud rate scheda fieldbus Fieldbus board baud rate R - - 0 - - √
697 Upd.F Versione software scheda fieldbus Fieldbus board software version R - - 2 - - √
27
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
STATUS_W_EEP: STATUS_W_EEP:
bit1= SP1/SP2, bit1= SP1/SP2,
bit2= start/stop selftuning, bit2= start/stop selftuning,
698 - R 0 - 0 - - -
bit3 = ON/OFF, bit4 = AUTO/MAN, bit3 = ON/OFF, bit4 = AUTO/MAN,
bit5= start/stop autotuning, bit5= start/stop autotuning,
bit6 = LOC/REM. bit6 = LOC/REM.
702
… - Reserved (GFX4-IR) Reserved (GFX4-IR) - - - - - - √
764
765 P.PEr Percentuale di potenza di uscita Output power percentage R/W 0.0 200.0 1 100.0 %
766 P.oFS Offset di potenza di uscita Output power offset R/W -100.0 100.0 1 0.0 %
767
… - Reserved (GFX4-IR) Reserved (GFX4-IR) - - - - - - √
769
770 In.1 Valore ingresso principale Main input value R Lo.S Hi.S dP.S - S.p.
771
… - Reserved (GFX4-IR) Reserved (GFX4-IR) - - - - - - √
769
802 ZC.01 Variabile zone custom 1 Zone custom variable 1 (1) (1) (1) (1) (1) (1) (1)
803 ZC.02 Variabile zone custom 2 Zone custom variable 2 (1) (1) (1) (1) (1) (1) (1)
804 ZC.03 Variabile zone custom 3 Zone custom variable 3 (1) (1) (1) (1) (1) (1) (1)
805 ZC.04 Variabile zone custom 4 Zone custom variable 4 (1) (1) (1) (1) (1) (1) (1)
28
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
806 ZC.05 Variabile zone custom 5 Zone custom variable 5 (1) (1) (1) (1) (1) (1) (1)
807 ZC.06 Variabile zone custom 6 Zone custom variable 6 (1) (1) (1) (1) (1) (1) (1)
808 ZC.07 Variabile zone custom 7 Zone custom variable 7 (1) (1) (1) (1) (1) (1) (1)
809 ZC.08 Variabile zone custom 8 Zone custom variable 8 (1) (1) (1) (1) (1) (1) (1)
810 ZC.09 Variabile zone custom 9 Zone custom variable 9 (1) (1) (1) (1) (1) (1) (1)
811 ZC.10 Variabile zone custom 10 Zone custom variable 10 (1) (1) (1) (1) (1) (1) (1)
812 ZC.11 Variabile zone custom 11 Zone custom variable 11 (1) (1) (1) (1) (1) (1) (1)
813 ZC.12 Variabile zone custom 12 Zone custom variable 12 (1) (1) (1) (1) (1) (1) (1)
814 ZC.13 Variabile zone custom 13 Zone custom variable 13 (1) (1) (1) (1) (1) (1) (1)
815 ZC.14 Variabile zone custom 14 Zone custom variable 14 (1) (1) (1) (1) (1) (1) (1)
816 ZC.15 Variabile zone custom 15 Zone custom variable 15 (1) (1) (1) (1) (1) (1) (1)
817 ZC.16 Variabile zone custom 16 Zone custom variable 16 (1) (1) (1) (1) (1) (1) (1)
818 AZC.01 Indirizzo della variabile zone custom 1 Address of zone custom variable 1 R/W 0 1023 - 0 - -
819 AZC.02 Indirizzo della variabile zone custom 2 Address of zone custom variable 2 R/W 0 1023 - 0 - -
820 AZC.03 Indirizzo della variabile zone custom 3 Address of zone custom variable 3 R/W 0 1023 - 0 - -
821 AZC.04 Indirizzo della variabile zone custom 4 Address of zone custom variable 4 R/W 0 1023 - 0 - -
822 AZC.05 Indirizzo della variabile zone custom 5 Address of zone custom variable 5 R/W 0 1023 - 0 - -
823 AZC.06 Indirizzo della variabile zone custom 6 Address of zone custom variable 6 R/W 0 1023 - 0 - -
824 AZC.07 Indirizzo della variabile zone custom 7 Address of zone custom variable 7 R/W 0 1023 - 0 - -
825 AZC.08 Indirizzo della variabile zone custom 8 Address of zone custom variable 8 R/W 0 1023 - 0 - -
826 AZC.09 Indirizzo della variabile zone custom 9 Address of zone custom variable 9 R/W 0 1023 - 0 - -
827 AZC.10 Indirizzo della variabile zone custom 10 Address of zone custom variable 10 R/W 0 1023 - 0 - -
29
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
828 AZC.11 Indirizzo della variabile zone custom 11 Address of zone custom variable 11 R/W 0 1023 - 0 - -
829 AZC.12 Indirizzo della variabile zone custom 12 Address of zone custom variable 12 R/W 0 1023 - 0 - -
830 AZC.13 Indirizzo della variabile zone custom 13 Address of zone custom variable 13 R/W 0 1023 - 0 - -
831 AZC.14 Indirizzo della variabile zone custom 14 Address of zone custom variable 14 R/W 0 1023 - 0 - -
832 AZC.15 Indirizzo della variabile zone custom 15 Address of zone custom variable 15 R/W 0 1023 - 0 - -
833 AZC.16 Indirizzo della variabile zone custom 16 Address of zone custom variable 16 R/W 0 1023 - 0 - -
890 C.E.t Timeout per errore di comunicazione Timeout for communication error R/W 0 121 - 0 sec √
891 C.E.m Modalita’ per errore di comunicazione Communication error mode R/W 0 17 - 0 - -
Potenza di uscita quando l’errore di Output power when communication error is
892 C.E.P R/W -100.0 100.0 1 0.0 % -
comunicazione e’ attivo active
894 F.SIZE Dimensione I/O data per fieldbus Fieldbus I/O data size R/W 0 1 0 0 - √
32768
… - Riservato fieldbus Fieldbus reserved - - - - - - √
33023
30
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Unità di
Indirizzo Sigla Punto Decinale misura
Descrizione Description R/W Min Max Default Global
Address Item Decimal point Unit of
measure
NOTE:
(1) Depending on the relative address AZC.xx
26 Stato allarme HB (OR TA1-TA2-TA3) OR FAULT_POWER Alarm status HB (OR TA1-TA2-TA3) OR FAULT_POWER R
28 Autotuning attivo Autotuning active R
31
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Indirizzo
Descrizione Description R/W
Address
32
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Indirizzo
Descrizione Description R/W
Address
33
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Indirizzo
Descrizione Description R/W
Address
34
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
35
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
36
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
37
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
38
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
39
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
200 Indirizzo della variabile custom 1 Address of custom variable 1 1024+0 1 Pointer
201 Indirizzo della variabile custom 2 Address of custom variable 2 1024+1 1 Pointer
202 Indirizzo della variabile custom 3 Address of custom variable 3 1024+16 1 Pointer
203 Indirizzo della variabile custom 4 Address of custom variable 4 1024+602 1 Pointer
204 Indirizzo della variabile custom 5 Address of custom variable 5 1024+139 1 Pointer
205 Indirizzo della variabile custom 6 Address of custom variable 6 1024+12 1 Pointer
206 Indirizzo della variabile custom 7 Address of custom variable 7 1024+13 1 Pointer
207 Indirizzo della variabile custom 8 Address of custom variable 8 1024+407 1 Pointer
208 Indirizzo della variabile custom 9 Address of custom variable 9 1024+408 1 Pointer
209 Indirizzo della variabile custom 10 Address of custom variable 10 1024+195 1 Pointer
210 Indirizzo della variabile custom 11 Address of custom variable 11 1024+55 1 Pointer
211 Indirizzo della variabile custom 12 Address of custom variable 12 1024+2 1 Pointer
212 Indirizzo della variabile custom 13 Address of custom variable 13 1024+252 1 Pointer
213 Indirizzo della variabile custom 14 Address of custom variable 14 1024+305 1 Pointer
214 Indirizzo della variabile custom 15 Address of custom variable 15 1024+467 1 Pointer
215 Indirizzo della variabile custom 16 Address of custom variable 16 1024+469 1 Pointer
216 Indirizzo della variabile custom 17 Address of custom variable 17 1024+632 1 Pointer
217 Indirizzo della variabile custom 18 Address of custom variable 18 1024+633 1 Pointer
218 Indirizzo della variabile custom 19 Address of custom variable 19 1024+634 1 Pointer
219 Indirizzo della variabile custom 20 Address of custom variable 20 1024+400 1 Pointer
220 Indirizzo della variabile custom 21 Address of custom variable 21 1024+180 1 Pointer
221 Indirizzo della variabile custom 22 Address of custom variable 22 1024+31 1 Pointer
222 Indirizzo della variabile custom 23 Address of custom variable 23 1024+181 1 Pointer
223 Indirizzo della variabile custom 24 Address of custom variable 24 1024+160 1 Pointer
224 Indirizzo della variabile custom 25 Address of custom variable 25 1024+163 1 Pointer
40
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
225 Indirizzo della variabile custom 26 Address of custom variable 26 1024+166 1 Pointer
226 Indirizzo della variabile custom 27 Address of custom variable 27 1024+170 1 Pointer
227 Indirizzo della variabile custom 28 Address of custom variable 28 1024+9 1 Pointer
228 Indirizzo della variabile custom 29 Address of custom variable 29 1024+159 1 Pointer
229 Indirizzo della variabile custom 30 Address of custom variable 30 2048+0 2 Pointer
230 Indirizzo della variabile custom 31 Address of custom variable 31 2048+1 2 Pointer
231 Indirizzo della variabile custom 32 Address of custom variable 32 2048+16 2 Pointer
232 Indirizzo della variabile custom 33 Address of custom variable 33 2048+602 2 Pointer
233 Indirizzo della variabile custom 34 Address of custom variable 34 2048+139 2 Pointer
234 Indirizzo della variabile custom 35 Address of custom variable 35 2048+12 2 Pointer
235 Indirizzo della variabile custom 36 Address of custom variable 36 2048+13 2 Pointer
236 Indirizzo della variabile custom 37 Address of custom variable 37 2048+407 2 Pointer
237 Indirizzo della variabile custom 38 Address of custom variable 38 2048+408 2 Pointer
238 Indirizzo della variabile custom 39 Address of custom variable 39 2048+195 2 Pointer
239 Indirizzo della variabile custom 40 Address of custom variable 40 2048+55 2 Pointer
240 Indirizzo della variabile custom 41 Address of custom variable 41 2048+2 2 Pointer
241 Indirizzo della variabile custom 42 Address of custom variable 42 2048+252 2 Pointer
242 Indirizzo della variabile custom 43 Address of custom variable 43 2048+305 2 Pointer
243 Indirizzo della variabile custom 44 Address of custom variable 44 2048+467 2 Pointer
244 Indirizzo della variabile custom 45 Address of custom variable 45 2048+469 2 Pointer
245 Indirizzo della variabile custom 46 Address of custom variable 46 2048+632 2 Pointer
246 Indirizzo della variabile custom 47 Address of custom variable 47 2048+633 2 Pointer
247 Indirizzo della variabile custom 48 Address of custom variable 48 2048+634 2 Pointer
248 Indirizzo della variabile custom 49 Address of custom variable 49 2048+400 2 Pointer
249 Indirizzo della variabile custom 50 Address of custom variable 50 2048+180 2 Pointer
41
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
250 Indirizzo della variabile custom 51 Address of custom variable 51 2048+31 2 Pointer
251 Indirizzo della variabile custom 52 Address of custom variable 52 2048+181 2 Pointer
252 Indirizzo della variabile custom 53 Address of custom variable 53 2048+160 2 Pointer
253 Indirizzo della variabile custom 54 Address of custom variable 54 2048+163 2 Pointer
254 Indirizzo della variabile custom 55 Address of custom variable 55 2048+166 2 Pointer
255 Indirizzo della variabile custom 56 Address of custom variable 56 2048+170 2 Pointer
256 Indirizzo della variabile custom 57 Address of custom variable 57 2048+9 2 Pointer
257 Indirizzo della variabile custom 58 Address of custom variable 58 2048+159 2 Pointer
258 Indirizzo della variabile custom 59 Address of custom variable 59 4096+0 3 Pointer
259 Indirizzo della variabile custom 60 Address of custom variable 60 4096+1 3 Pointer
260 Indirizzo della variabile custom 61 Address of custom variable 1 4096+16 3 Pointer
261 Indirizzo della variabile custom 62 Address of custom variable 62 4096+602 3 Pointer
262 Indirizzo della variabile custom 63 Address of custom variable 63 4096+139 3 Pointer
263 Indirizzo della variabile custom 64 Address of custom variable 64 4096+12 3 Pointer
264 Indirizzo della variabile custom 65 Address of custom variable 65 4096+13 3 Pointer
265 Indirizzo della variabile custom 66 Address of custom variable 66 4096+407 3 Pointer
266 Indirizzo della variabile custom 67 Address of custom variable 67 4096+408 3 Pointer
267 Indirizzo della variabile custom 68 Address of custom variable 68 4096+195 3 Pointer
268 Indirizzo della variabile custom 69 Address of custom variable 69 4096+55 3 Pointer
269 Indirizzo della variabile custom 70 Address of custom variable 70 4096+2 3 Pointer
270 Indirizzo della variabile custom 71 Address of custom variable 71 4096+252 3 Pointer
271 Indirizzo della variabile custom 72 Address of custom variable 72 4096+305 3 Pointer
272 Indirizzo della variabile custom 73 Address of custom variable 73 4096+467 3 Pointer
273 Indirizzo della variabile custom 74 Address of custom variable 74 4096+469 3 Pointer
274 Indirizzo della variabile custom 75 Address of custom variable 75 4096+632 3 Pointer
42
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
275 Indirizzo della variabile custom 76 Address of custom variable 76 4096+633 3 Pointer
276 Indirizzo della variabile custom 77 Address of custom variable 77 4096+634 3 Pointer
277 Indirizzo della variabile custom 78 Address of custom variable 78 4096+400 3 Pointer
278 Indirizzo della variabile custom 79 Address of custom variable 79 4096+180 3 Pointer
279 Indirizzo della variabile custom 80 Address of custom variable 80 4096+31 3 Pointer
280 Indirizzo della variabile custom 81 Address of custom variable 81 4096+181 3 Pointer
281 Indirizzo della variabile custom 82 Address of custom variable 82 4096+160 3 Pointer
282 Indirizzo della variabile custom 83 Address of custom variable 83 4096+163 3 Pointer
283 Indirizzo della variabile custom 84 Address of custom variable 84 4096+166 3 Pointer
284 Indirizzo della variabile custom 85 Address of custom variable 85 4096+170 3 Pointer
285 Indirizzo della variabile custom 86 Address of custom variable 86 4096+9 3 Pointer
286 Indirizzo della variabile custom 87 Address of custom variable 87 4096+159 3 Pointer
287 Indirizzo della variabile custom 88 Address of custom variable 88 8192+0 4 Pointer
288 Indirizzo della variabile custom 89 Address of custom variable 89 8192+1 4 Pointer
289 Indirizzo della variabile custom 90 Address of custom variable 90 8192+16 4 Pointer
290 Indirizzo della variabile custom 91 Address of custom variable 91 8192+602 4 Pointer
291 Indirizzo della variabile custom 92 Address of custom variable 92 8192+139 4 Pointer
292 Indirizzo della variabile custom 93 Address of custom variable 93 8192+12 4 Pointer
293 Indirizzo della variabile custom 94 Address of custom variable 94 8192+13 4 Pointer
294 Indirizzo della variabile custom 95 Address of custom variable 95 8192+407 4 Pointer
295 Indirizzo della variabile custom 96 Address of custom variable 96 8192+408 4 Pointer
296 Indirizzo della variabile custom 97 Address of custom variable 97 8192+195 4 Pointer
297 Indirizzo della variabile custom 98 Address of custom variable 98 8192+55 4 Pointer
298 Indirizzo della variabile custom 99 Address of custom variable 99 8192+2 4 Pointer
299 Indirizzo della variabile custom 100 Address of custom variable 100 8192+252 4 Pointer
43
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
Default
Indirizzo Tipo
Descrizione Description
Address Type
Descrizione/Description Zona/Zone
300 Indirizzo della variabile custom 101 Address of custom variable 101 8192+305 4 Pointer
301 Indirizzo della variabile custom 102 Address of custom variable 102 8192+467 4 Pointer
302 Indirizzo della variabile custom 103 Address of custom variable 103 8192+469 4 Pointer
303 Indirizzo della variabile custom 104 Address of custom variable 104 8192+632 4 Pointer
304 Indirizzo della variabile custom 105 Address of custom variable 105 8192+633 4 Pointer
305 Indirizzo della variabile custom 106 Address of custom variable 106 8192+634 4 Pointer
306 Indirizzo della variabile custom 107 Address of custom variable 107 8192+400 4 Pointer
307 Indirizzo della variabile custom 108 Address of custom variable 108 8192+180 4 Pointer
308 Indirizzo della variabile custom 109 Address of custom variable 109 8192+31 4 Pointer
309 Indirizzo della variabile custom 110 Address of custom variable 110 8192+181 4 Pointer
310 Indirizzo della variabile custom 111 Address of custom variable 111 8192+160 4 Pointer
311 Indirizzo della variabile custom 112 Address of custom variable 112 8192+163 4 Pointer
312 Indirizzo della variabile custom 113 Address of custom variable 113 8192+166 4 Pointer
313 Indirizzo della variabile custom 114 Address of custom variable 114 8192+170 4 Pointer
314 Indirizzo della variabile custom 115 Address of custom variable 115 8192+9 4 Pointer
315 Indirizzo della variabile custom 116 Address of custom variable 116 8192+159 4 Pointer
316 Indirizzo della variabile custom 117 Address of custom variable 117 1024+140 1…4 Pointer
317 Indirizzo della variabile custom 118 Address of custom variable 118 1024+618 1…4 Pointer
318 Indirizzo della variabile custom 119 Address of custom variable 119 1024+190 1…4 Pointer
319 Indirizzo della variabile custom 120 Address of custom variable 120 1024+508 1…4 Pointer
44
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
NOTES
45
80289C_GFX4-GFXTERMO4 - MODBUS MEMORY MAP V.2.50 – 07/2022
GEFRAN spa
via Sebina, 74 - 25050 Provaglio d’Iseo (BS) Italy
Tel. +39 0309888.1 - Fax +39 0309839063
[email protected] - http://www.gefran.com
46