TACHOMETER
TACHOMETER
TACHOMETER
CS2-VA
measurement, display and communication of pulse (Frequency).
; The innovation feature is auto-range input from 0.01Hz~ 100KHz
(option ~140KHz) and the display resolution will auto-change to
show the highest according to input frequency.
They are also building in 4 Relay outputs, 3 External Control Inputs, 1
Analogue output and 1 RS485(Modbus RTU Mode) interface with
FEATURE
● Measuring Frequency AUTO RANGE 0.01~100KHz / ~140KHz(optional) / Contact, NPN, PNP, Voltage pulse
can be switch on rear of meter
● Accuracy: ± 0.005%; Display range: 0~99999; Decimal Point auto moving according to input frequency
● 4 relay can be programmed individual to be a Hi / Lo / Hi Latch / Lo Latch / Go energized with Start Delay /
Hysteresis / Energized & De-energized Delay functions, or to be a remote control.
● Analogue output and RS 485 communication port in option
● 3 external control inputs can be programmed individual to be Tare (Relative PV) / PV Hold / Maximum or
Minimum Hold / DI (remote monitoring) / Reset for Relay Energized Latch….
CS2-RL
● CE Approved & RoHS
ORDERING INFORMATION
CS2−RL− Input
Mode
Input
level −
Relay
Output −
Analogue
Output − RS 485 Port
−
AUX.
POWER −
*Optional Customize function is welcome. Please contact with our
Function sales for detail.
CODE INPUT MODE CODE REALY OUTPUT CODE ANALOG O/P CODE RS 485 PORT CODE AUX. POWER
C 00 Contact N None N None N None A AC115/230V
N NPN R2 2 Relay 0(1) ~ 5 V 8 RS 485 OPTION 4
V 0 ~ 10 V
P PNP R4 4 Relay AC 85~264V
ADH DC 100~300V
Input mode and level V Voltage Pulse 0 ~ 10 mA
I 0(4)~20 mA
can be changed by 05 5V pulse ADL DC 20~56V
dip switches on rear 12 12V pulse
of meter Please specify the range
24 24V pulse
of amplitude, if the input
O xx Specify mode has specified to be
U P Pick Up sensor pick up sensor.
CS2-RL-2010-10-15 C2-11-1/9
CSM-321S
Analogue output(option)
Accuracy: ≤± 0.1% of F.S.; 16 bits DA converter 96.0 100.0
Ripple: ≤± 0.1% of F.S. 8.0 12.0
Response time: ≤100 m-sec. (10~90% of input)
CSM- CSM-321S CSM-
Isolation: AC 2.0 KV between input and output Dimensions: 96mm x 48mm x 120mm
PANEL CUT-OUT 44.0+0.2 Panel Cutout: 93mm x 45mm (advise)
Output range: Specify either Voltage or Current output in ordering
Voltage: 0~5V / 0~10V / 1~5V programmable
Unit: mm
Current: 0~10mA / 0~20mA / 4~20mA programmable 92.0+0.2
Output capability: Voltage: 0~10V: ≥ 1000Ω;
Current: 4(0)~20mA: ≤ 600Ω max
aOhs(output range high): Settable range: -19999~29999
Functions:
aOls(output range Low): Settable range: -19999~29999
INSTALLATION
aOlmt (output High Limit): 0.00~110.00% of output High The meter should be installed in a location that does not exceed the
Digital fine adjust: aOzro: Settable range: -38011~+27524 maximum operating temperature and provides good air circulation.
aOspn: Settable range: -38011~+27524
RS 485 Communication(option)
Modbus RTU mode
COM
Protocol: R
RL
R
C
C
R
1200/2400/4800/9600/19200/38400 programmable
C
Baud rate:
8 bits
2
Kg/cm
Data bits: ENT/FN ? ? ?
CS2-RL
Electrical Safety
Relay 1 Relay 2 Relay 3 Relay 4 RS 485 Analogue
Dielectric strength: AC 2.0 KV for 1 min, Between Power / Input / Output / Case port output
Insulation resistance: ≥100M ohm at 500Vdc, Between Power / Input / Output Terminal blocks:
a c b c a b c a a c A B 10A/300Vac, M2.6,
Isolation: Between Power / Input / Relay / Analogue / RS485 / E.C.I.
EMC: EN 55011:2002; EN 61326:2003 21 22 23 24 25 26 27 28 29 30 31 32 33 34 M2.6, 1.3~2.0mm2
(16~22AWG)
Safety(LVD): EN 61010-1:2001
ECI1 ECI2 ECI3 COM
Environmental 11 12 13 14 15 D-S
3 4 5 6 7 8 9 10
Dip-Switch
Operating temp.: 0~60 ˚C
Operating humidity: 20~95 %RH, Non-condensing AC115V
D-S 1 2 3 4 5
AC230V AC 86~265V
+IN
0V
+V
+V
0V
C2-11-2/9 CS2-RL-2010-10-15
Remote Display by RS485 command rs485 :
RS485 Communication Port
The meter will show the value that received from RS485
sending. In past, The meter normally receive 4~20mA or
CS2-VA
Max. Distance: 1200M 0~10V from AO or digital output from BCD module of PLC.
Terminate Resistor
(at latest unit): We support a new solution that PV shows the value from
A B 120~300ohm/0.25W RS485 command of master can so that can be save cost and
(typical: 150ohm)
wiring from PLC.
30 31 32 Other functions : The meter is also support relative PV (∆PV) and PV hold
RS485 Port functions that set in [ eci group]. Please refer to
explain of ECI functions.
CS2-RL
)50 0.50
setting position of decimal point, According to the setting of X1
decimal point. So, it’s possible to show “overflow”, if the input
X1 Low cut
frequency is over the display range. -0.50 function
Manual range manul: The decimal point will be fixed
Time out of input: Low Cut is set for 0.50, if the PV is
from -0.50~+0.50, that display will be 0.
In the case of low frequency, the meter can not to identify that is low
10)00
8)00
Reset the Max
(M ini) H old by
Level O 5%00
EC I or F. Key Trigger N
[ l Osc ]
)00 INPUT _
0V 2.75V 5V 9.00V 10V
CS2-RL-2010-10-15 C2-11-3/9
CSM-321S
Compensation factor: Settable range: 0.001~9.999 Go-1.2 go-!2: This function is programmable in Relay 4 only.
The factor is compensation of display. There are some applications that If the Relay 4 set to be Go function, the relay will compare with
are indirect detection of sensor as like as Gear, wheel. User can set the [ry!sp] and [ry@sp].
CS2-VA
Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 ……. ……. Above cases will alarm in the meter, if the user doesn't figure
out the real reason and re-start the motor. It may damage the
Display Update Value = Display Update Value = motor. The functions of Hi.HLd & Lo.HLd are designed must
(Sample 1 + Sample 2 + Sample 3)/3 (Sample 4 + Sample 5 + Sample 6)/3
be manual reset the alarm after checking out and solving the
Remark: The higher average setting will cause the response time of issue. It's very important idea for electrical safety and human
Relay and Analogue output slower. protection.
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-
Moving average: As the PV Higher (or lower) than set-point, the relay will be
Jittery Display caused by the reasons as like as noise or unstable signal. User can set energized to latch except manual reset by from key in [ user
the times to average the readings, and get smoothly display. level] or [ eci](ECI) set to be rYrst is closed.
The meter’s sampling is 15cycle/sec. If the [ Mavg](Moving Average) set to be 3 Hi(Lo) Energized Latch & Reset
expressed the display update with 15 times/sec., [ry_.sp] Hi Setting
In the first updated display value will be same as average function. In the next updated
display value, the function will get the new fourth sample (sample 4) then throw away the
first sample (sample 1) that the newest 3 samples(sample 2,3,4) will be calculated for the [ry_.md]
updated display value. hIhld Hi.HLd(H igh H old)
Relay Energized ON
Moving Average set to be 3
[ ecI_] Reset the relay Hold ON
Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 ……. ……. Level Trigger
rYrst by ECI or Front Key
In first 3 samples, Display Update Value
= (Sample 1 + Sample 2 + Sample 3)/3 DO function do: The function has been designed not only a meter but also an
Display Update Value
I/O interface. In the case of motor control cabinet can't get the
= (Sample 2 + Sample 3 + Sample 4)/3 remote function. It's very easily to get the ON/OFF status of
Display Update Value switch from CS2 series with RS485 function.
= (Sample 3 + Sample 4 + Sample 5)/3 If the [ry_.md] had been set do, the relay will be
Display Update Value energized by RS485 command directly, but no longer to
= (Sample 4 + Sample 5 + Sample 6)/3 compare with set-point.
Remark: The higher moving average setting wouldn’t cause the Start delay band and Start delay time:
response time of Relay and Analogue output slower after first 3 The functions have Been designed for,
samples. ► To avoid starting current of inductive motor (6 times of rated current)
Digital Filter: The digital filter can reduce the magnetic noise in field. with alarm.
The digital filter can reduce the influence of spark noise caused by ► If the ry_.md relay energized mode had been set to be lo(Lo) or
magnetic of coil. lOhld(Lo & latch). As the meter is power on and no input to display
If the values of samples are over digital filter band (fix in firmware and about the "0" caused the relay will be energized. User can set a band and
5% of stable reading) 3 times (Digital Filter set to be 3) continuously, the delay time to inhibit the energized of relay.
meter will admit the samples and update the new reading. Otherwise, it Start band rYsb (Fig.2-c): Settable range from 0~9999 Counts
will be as treat as a noise and skip the samples. Start delay time rYsd (Fig.2-d): Settable range from 0.0(s)~9(m)59.9(s);
Start Delay Fig.2
Control Functions(option) Inhibit
Relay energized mode: Hi / Lo / Go-1.2 / Go-2.3 / Hi.HLd / Lo.HLd / DO programmable Inhibit
Hi hi(Fig.1-c): Relay will energize when PV > Set-Point [ry_.sp] Hi Setting
d[ rYsd]
[ry_.sp] Lo Setting
[ry_.md]
hi Hi Relay Energized c ON
lo Lo Relay Energized ON d
C2-11-4/9 CS2-RL-2010-10-15
CSM-321S
Hysteresis ry_.hy (Fig.3-c): Settable range from 0~9999 Counts Hi(Lo) Energized Latch & Reset
As the display value is swing near by the set point to cause the relay on [ry_.sp] H i Setting
and off frequently. The function is to avoid the relay on and off frequently
CS2-VA
such as compressor…….etc.,
Relay energized delay ry_.rd (Fig.3-d): Settable range from 0.0(s)~9(m)59.9(s);
[ry_.md]
The function is to avoid the miss action caused by noise. Sometime, the hIhld H i.H Ld(High H old)
R elay Energized ON
display value will swing caused by spark of contactor…etc.. User can set
a period to delay the relay energized. [ ecI_] Reset the relay Hold ON
Level Trigger
rYrst by ECI or Front Key
Relay de-energized delay ry_.fd (Fig.3-e): Settable range from 0.0(s)~9(m)59.9(s);
Energized / De-energized Fig.3 Debouncing time:
De-energized
Hysteresis
c
delay time
[debnc]set to be 5, it means 5 x 8mseconds = 40mseconds
[ry_.rd] [ry_.fd]
d e Analogue output(option)
Relay Please specify the output type either a 0~10V or 4(0) ~ 20mA in ordering.
Energized ON
The programmable output low and high scaling can be based on various
display values. Reverse slope output is possible by reversing point positions.
Output range: Voltage: 0~5V / 0~10V / 1~5V programmable
External Control Inputs(ECI) Current: 0~10mA / 0~20mA / 4~20mA programmable
The three external control inputs are individually programmable to perform Functions: Output High / Low scale, output limit, fine adjustment
specific meter control or display functions. All E.C.I. have been designed in Output range high [ aOhs]:
level trigger actions. Please pay attention, the ECI1 or ECI2 input will be To setting the Display value High to versus output range
disable while UP or Down Key has been set to be “YES”. High(as like as 20mA in 4~20)
CS2-RL
Functions: Relative PV / PV Hold / Reset Max or Mini. Hold / DI / Reset Output range low [ aOls]:
for Relay Energized latch programmable. To setting the Display value Low to versus output range
Relative PV reLpv or Tare: Low(as like as 4mA in 4~20)
The [ ecI_] can be set to be reLpv function. When the Set Scaling: [ lOsc]: 0.00, [ hIsc]: 199.99;
E.C.I. is closed, the reading will show the differential value. SCALE Output: [ aOls]: 50.00(Display Value Low),
[ aOhs]: 150.00(Display Value High)
Relative PV E C I_ has closed, and 199.99
R elativ e PV 100.00
E C I_ has opened, [ aOls ]
a nd then displa y
s how s PV 50.00
R elativ e
P V(?PV ) b y Level ON [ ecI_] 0.00
ECI or F.Key Trig ger r eL pv 0.00% 50.00% OUTPUT 100.00%
PV Hold pVhld: The [ ecI_] can be set to be pVhld(PV Hold) function. The range between [ aOhs] and [ aOls] should be over
PV Hold & Reset 20% of span at least; otherwise, it will be got less resolution of
analogue output.
Present PV Hold
Value Output High Limit [ aOlmt]:
0.00~110.00% of output High User can set the high limit of
output to avoid a damage of receiver or protection system.
Set Scaling: [ lOsc]: 0.00, [ hIsc]: 199.99;
Reset PV Hold Output: [ aOls]: 50.00(Display Value Low),
by E.C.I. or
O ON Level ON [ ecI_]
N Trigger SCALE [ aOhs]: 150.00(Display Value High)
Front Key pVhld [aOlmt]: 80.00%( of Output Range)
199.99
Reset for Maximum or Minimum Hold Mrst: [ aOhs] Ao.LMt: 80.00%
When the [dsply] function in [input group] selected 150.00
maXhd or miNhd, the display will show Maximum or
100.00
Minimum value. [ aOls ]
The [ ecI_] function can be set to be Mrst 50.00
function to reset the maximum and minimum value 0.00 OUTPUT
in [User Level] by terminals of ECI (close). Please refer 0.00% 50.00% 80.00% 100.00%
[aOlmt]
to the figure as below.
Max. ( Mini.) Hold & Reset Fine zero & span adjustment:
M axi in User Level Users can get Fine Adjustment of analogue output by front key of the
Prese nt
Value meter. Please connect standard meter to the terminal of analogue output.
To press the front key (up or down key) of meter to adjust and check the
Reset the max storage output.
when ECI has closed
Zero adjust [aOzro]: Fine Zero Adjustment for Analog Output;
Reset the Max. [ ecI_]
(M ini.) storage
L evel O Settable range: -38011~27524;
by E.C .I. Trigg er N M rst
Span adjust [aOspn]: Fine Span Adjustment for Analog Output;
DI di : The E.C.I can be set to be di function, when the meter Settable range: -38011~27524;
building in RS485 port. It is easier to get remote monitoring a
switch status through the meter as like as DI of PLC.
Reset for Relay Energized Latch rYrst:
If the relay energized mode has been set to be
hIhld(Energized latch), and the [ ecI_] can be set to be
rYrst(Reset the Relay energized latch). When the PV
meets the condition of relay energizing, the relay will be
energized and latch until the ECI is to be closed.
CS2-RL-2010-10-15 C2-11-5/9
CSM-321S
(Supervisor Control And Data Acquisition) system. The baud rate can be output from BCD module of PLC .We support a new solution that PV
up to 38400 bps. It's not only can be read the measured value and DI shows the value from RS485 command of master so that can be save
(external control inputs) status but also controls the relays output (DO) cost and wiring from PLC.
by RS485 communication ports. When the [ dsply] set to be RS485, it means, the PV screen will show the
CS2-PR & SC2-RL APPLICATION MEASURING & RS485 COMMUNICATION number from RS485 command & data. The data(number) will be same as
RS485 wiring 1.2KM maximum
Terminate Resistor: PV that will compare with set-point, analogue output and ECI functions so
RS 485 Modbus RTU Mode (up to 38400bps)
CSM- CSM-321S CSM-
ECI1
RL1
RL2
COM
ECI1
RL3 ECI2 RL3 ECI2
RL4 ECI3 RL4 ECI3
2 2
ENT/FN ◄ ▲ ▼ Kg/cm ENT/FN ◄ ▲ ▼ Kg/cm
Optional Function
Customize function with quantities is welcome. Please contact with our
sales for detail. The appendix code of optional function will be added
CS2-RL
ERROR MESSAGE
BEFORE POWER ON, PLEASE CHECK THE SPECIFICATION AND CONNECTION AGAIN.
SELF-DIAGNOSIS AND ERROR CODE:
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-
-ovfl Display is negative-overflow (Signal is under display range) (Please check the input signal)
ADC is positive-overflow (Signal is higher than input range
ovfl high 20%)
(Please check the input signal)
ADC is negative-overflow (Signal is lower than input range low
-ovfl -20%)
(Please check the input signal)
eep fail EEPROM occurs error (Please send back to manufactory for repaired)
aiCng pv Calibrating Input Signal do not process (Please process Calibrating Input Signal)
aic fail Calibrating Input Signal error (Please check Calibrating Input Signal)
aoCng pv Calibrating Output Signal do not process (Please process Calibrating Output Signal)
aoc fail Calibrating Output Signal error (Please check Calibrating Output Signal)
C2-11-6/9 CS2-RL-2010-10-15
CSM-321S
FRONT PANEL:
Max. Hold status Operating Key: 4 keys for Enter(Function) / Shift(Escape) /
CS2-VA
Relay status
Indication R L1 COM
M.H
Comm. status Up key / Down key
RL2 CI11
2
RL3
RL4
CI2
CI3
Control Input Setting Status Function Index
M.H status Increase number Go back to previous
Display screen Up key
ENT/FN ? ? ? RPM Mini. Hold status function index
Operation Key
Engineer Unit Down key Decrease number Go to next
CS2-RL
● Programming Level eng: Programming level lock.
COM will flash when the meter is receive or send data, and COM flash User can get into programming level for checking but setting.
quickly means the data transient quicker. ● ALL all: All lock. User can get into all level for checking but
● Max/Mini Hold indication: 2 square orange LEDs setting.
CO M.H displayed: When the display function has been selected in Front Key Function
Maximum or Minimum Hold function. ● The Key can be set to be the same function as the setting of ECI1.
CS2-RL-2010-10-15 C2-11-7/9
CSM-321S
OPERATING DIAGRAM (The detail description of operation, please refer to operating manual.)
User Level
CS2-VA
Power ON
Press for 1 sec. can back to Measuring
If the [dsply]
***** Self-diagnosis
299(9 10000 ry$sp: Relay 4
no Mrst: Reset the
0−0−1
0−4
0−8
function has Set-point saved value of
pv been set rs485 ry$sp -19999~29999 Mrst Maximum &
CSM- CSM-321S CSM-
0−5
0−9
number Set-point for energized firmware
ry!sp -19999~29999 rYrst Latch of Relay cs@rl version
Checking only
yes / no
ver!4 Show
10000 ry@sp: Relay 2
)0000 min: the
299(9 Cyclic to first
0−2
0−6
0−0−1
the firmware Set-point Minimum value page
version ry@sp -19999~29999 min of PV saving pv
Checking only
MEASURING
10000 ry#sp: Relay 3
29999 max: the
0−3
0−7
PAGE
299(9 ry#sp
Set-point Maximum value
ENT
Press 1sec -19999~29999 max of PV saving
Checking only
Press 1sec
Enter the
enter password to
CS2-RL
access Engineer
Pcode Level
ENT
NO
Pass Code Programming Level
YES
▼
▲
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-
▼
INPUT RELAY EXTERNAL ANALOGUE
GROUP GROUP CONTROL OUTPUT
▲
▲
group group group INPUT (E.C.I)
group GROUP
ENT ENT ENT ENT
GROUP
pVtyp: Present rYsb: Start band ecI1: External aOtyp: Analogue
lNspd Value type 0 for Relay reLpv Control Input 1 A4-20 Output type
A−1
B−1
C−1
D−1
energized selection
pVtyp lNspd /
rps /
rpm /
hz /
rYsb 0~9999counts
ecI1 none / reLpv /
pVhld / Mrst /
aOtyp V0-10 / V 0-5 /
khz rYrst / di V 1-5 / A0-10 /
A0-20 / A4-20
If [pVtyp] has rYsd: Start delay ecI2: External aOls: Analogue
1 )0)0 pVhld )0
A−2−1
B−2
C−2
D−2
B−3
C−3
D−3
B−4
C−4
D−4
B−5
C−5
D−5
C2-11-8/9 CS2-RL-2010-10-15
CSM-321S
factr: ry!fd: Relay 1 E2=dn: ECI.2 set ZSclr: Zero &
!000 )0)0 no none
A−4
B−6
C−6
D−6
Compensation de-energized to be Down Key Span Clear for
Factor delay time Adjustment
factr 0.001~9.999
ry!fd 0.00.0~
E2=dn function
yes / no
ZSclr none / aOzro /
CS2-VA
9(M).59.9(S) aOspn / both
pVspn: Fine ry@md: Relay 2 aOlmt: Analog
0 hi 11)00
A−5
B−7
D−7
High point energized mode Output High
Adjustment for Limit
pVspn PV display
ry@md off / lo /
hi / lOhld /
aOlnt 0.00~110.00%
0~+99999 hIhld / do
yes / no
dsply: Display ry@rd: Relay 2
pv )0)0
A−7
B−9
B−10
Function de-energized
delay time GROUP
lOcut 0~99999
ry@fd 0.00.0~
group
ENT
9(M).59.9(S)
itOmd: Input ry#md: Relay 3 adres: Device
auto hi 1
A−9
B−11
CS2-RL
time out Mode number of the
E−1
energized mode
meter
itOmd auto / manul
ry#md off / lo / adres 1~255
hi / lOhld /
hIhld / do
If [itOmd] has ry#hy: Relay 3 baud: Baud
)0 0 9600
A−10
B−12
E−2
been selected Hysteresis rate
ito manul, This
ry#hy 0~5000 counts baud 1200 / 2400 /
B−13
E−3
B−14
B−15
B−16
filter Hysteresis
Dfilt 0(None)/1~
99 times
ry$hy 0~5000 counts
B−17
B−18
Level Lock
Flock none / user /
eng / all
CS2-RL-2010-10-15 C2-11-9/9