HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps
Technical data for installation Lamp wiring for HF-P 2..TL5 Lamp wiring to both lamps must be inside
Mains operation one luminaire; length of wires to lamp 1
Rated mains voltage 220 - 240 V must be same (±10%) as length of wires to
with tolerances for safety: +/- 10% 198 - 264 V lamp 2 (wires to terminals 1 and 2 must be
tolerances for performance: +6% -8 202 - 254 V short and equal in length to wires 6 and 7;
Mains frequency 50/60 Hz
Operating frequency See table wires to terminals 3 and 4 must be long
and equal in length to wires to terminals
DC voltage operation during emergency back-up: 4 and 5); max. length of lamp wiring to be
yes for required battery voltage see table. equal to length of longest lamp (35 W/
49 W), plus normal length needed for
Earth leakage current < 0.5 mA per ballast assembly (in practice, max. 1.8 to 2 m).
For HF-P 1..TL5 it is advised to use 500 V
Ignition time < 0.5 s rated components and wiring.
500 V rated components and wiring are
Smart power:
constant light operation in case of mains voltage fluctuations required with HF-P 2..TL5.
within 202 - 254 V, the luminous flux
varies by a maximum of ± 2%
2
HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps
Inrush current
Ballast Max. quantity of Inrush current
ballasts per 1/2 value time
Miniature Circuit at typical
Breaker mains impedance
type B 16 A C 16 A
HF-P 1 14-35 TL5 HE 28 48 24A/250µs
HF-P 2 14-35 TL5 HE 15 20 31A/300µs
HF-P 1 24-39 TL5 HO 28 48 24A/250µs
HF-P 2 24-39 TL5 HO 15 20 31A/300µs
HF-P 149 TL5 HO 28 48 24A/250µs
HF-P 249 TL5 HO 15 20 31A/300µs
HF-P 154 TL5 HO 28 48 24A/250µs
HF-P 254 TL5 HO 15 20 31A/300µs
3
HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps
Connector types:
Wago universal connector. Suitable for both automatic wiring
(ALF and ADS) and manual wiring
Wire lengths:
HF 1
2
1 lamp version: keep wires to terminals 1 and 2 short
BALLAST 3
4
2 lamp version: keep wires to terminals 1, 2, 6 and 7
L short
N
1 lamp Wire cross-section: on the mains side: 0.5 - 1.0 mm2
on the lamp side: 0.5 - 1.0 mm2
Strip length: 8 - 9 mm