HF-PERFORMER electronic standard ballasts (flat)


for TL5 lamps NEW

Definition • Airports, railway stations


Flat, Slim, multi wattage, • Office buildings, for example,
lightweight high-frequency insurance companies, banks,
electronic ballast for TL5 government ministries
fluorescent lamps. • Hospitals
• Hotels
Description • Suitable for emergency
• The combination HF- installations with VDE 0108 with
PERFORMER and TL5 lamps re-ignition < 0.5 s.
offers opportunities for • Suitable for use with infrared
miniaturisation and reduced remote control systems
cost of ownership, thanks to the
limited dimensions and the high Philips quality
system efficacy This implies optimum quality
• Programmed start: warm start regarding:
circuit preheating the lamp • System supplier
electrodes; this enables the As manufacturers of lamps and
lamps to be switched on and electronic control gear, Philips
off without reducing useful life ensures that, from the earliest
Dimensions in mm • Equipped with electrode development stage, optimum
heating cut-off circuit, ensuring lamp/ballast performance is
optimal lamp operation with maintained
respect to lumen curve of lamp • International standards
350 and reduction in system energy Philips HF electronic ballasts
losses comply with all relevant
• Low energy consumption international rules and
4.2

• Smart power: constant light regulations.


30

independent of mains voltage


fluctuations Compliances and approvals
• Unit is protected against • RFI < 30 MHz EN 55015
excessive mains voltages and • RFI > 30 MHz EN 55022 A
incorrect connections • Harmonics EN 61000-3-2
• Automatic stop circuit is • Immunity EN 61547
21

activated within five seconds in • Safety EN 60928


359 case of lamp failure (safety • Performance EN 60929-1E
stop); once the lamp has been • Vibration & bump tests
replaced, the ballast resets IEC 68-2-6 FC
automatically. IEC 68-2-29 Eb
• Equipped with terminations • Quality standard ISO 9001
HF-P 1 lamp version suitable for automatic wiring • Environmental standard
machines ISO 14001
• Approval marks ENEC
Applications VDE-EMV
415 Typical areas of application • CE marking.
include: • Temperature declared
• Department stores, shops, thermally protected
4.2

supermarkets IEC 61347-1


30
21

425

HF-P 2 lamp version

1
HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps

Technical data (all typical values at Vmains = 230V)


Lamp Qty. of Ballast System Lamp Ballast Lamp EEI
lamps power Power losses Lumen
W W W lm
TL5 HE 14W 1 HF-P 1 14-35 TL5 HE 18 15 2.6 1440 A2
TL5 HE 14W 2 HF-P 2 14-35 TL5 HE 32 15 2.8 1440 A2
TL5 HE 21W 1 HF-P 1 14-35 TL5 HE 25 22 2.9 2200 A2
TL5 HE 21W 2 HF-P 2 14-35 TL5 HE 46 21 3.6 2100 A2
TL5 HE 28W 1 HF-P 1 14-35 TL5 HE 33 30 3.5 3120 A2
TL5 HE 28W 2 HF-P 2 14-35 TL5 HE 62 29 5.0 3020 A2
TL5 HE 35W 1 HF-P 1 14-35 TL5 HE 40 36 3.4 3750 A2
TL5 HE 35W 2 HF-P 2 14-35 TL5 HE 77 35 6.7 3640 A2
TL5 HO 24W 1 HF-P 1 24-39 TL5 HO 28 24 4.0 1990 A2
TL5 HO 24W 2 HF-P 2 24-39 TL5 HO 51 23 4.8 1910 A2
TL5 HO 39W 1 HF-P 1 24-39 TL5 HO 45 40 4.2 3600 A2
TL5 HO 39W 2 HF-P 2 24-39 TL5 HO 83 39 5.9 3510 A2
TL5 HO 49W 1 HF-P 149 TL5 HO 56 51 4.8 5100 A2
TL5 HO 49W 2 HF-P 249 TL5 HO 111 51 8.8 5100 A2
TL5 HO 54W 1 HF-P 154 TL5 HO 61 55 6.0 5125 A2
TL5 HO 54W 2 HF-P 254 TL5 HO 118 55 8.0 5125 A2
* Typical values for /830 and /840 colours at 35˚C lamp ambient temperature

Ballast Lamp Qty. of Power Max. cable cap1) Tc Oper


lamps factor lp-lp/lp-gnd max Freq. kHz
pF ˚C
HF-P 1 14-35 TL5 HE TL5 HE 14W 1 0.91 150/150 75 50
HF-P 2 14-35 TL5 HE TL5 HE 14W 2 0.95 150/150 75 47
HF-P 1 14-35 TL5 HE TL5 HE 21W 1 0.96 150/150 75 49
HF-P 2 14-35 TL5 HE TL5 HE 21W 2 0.97 150/150 75 47
HF-P 1 14-35 TL5 HE TL5 HE 28W 1 0.98 150/150 75 48
HF-P 2 14-35 TL5 HE TL5 HE 28W 2 0.99 150/150 75 47
HF-P 1 14-35 TL5 HE TL5 HE 35W 1 0.98 150/150 75 48
HF-P 2 14-35 TL5 HE TL5 HE 35W 2 0.99 150/150 75 47
HF-P 1 24-39 TL5 HO TL5 HO 24W 1 0.96 150/150 75 53
HF-P 2 24-39 TL5 HO TL5 HO 24W 2 0.98 150/150 75 51
HF-P 1 24-39 TL5 HO TL5 HO 39W 1 0.99 150/150 75 46
HF-P 2 24-39 TL5 HO TL5 HO 39W 2 0.99 150/150 75 45
HF-P 149 TL5 HO TL5 HO 49W 1 0.99 150/150 75 45
HF-P 249 TL5 HO TL5 HO 49W 2 0.99 150/150 75 48
HF-P 154 TL5 HO TL5 HO 54W 1 0.99 150/150 75 52
HF-P 254 TL5 HO TL5 HO 54W 2 0.99 150/150 75 53
* On the HF-P 2 14-35 TL5 HE any combination of HE lamps can be used (e.g. 14&28; 35&21; etc)
1
) lp-lp = between lamp wires Typical wire capacitance 50 pF/m (spacing between wires 0.5 mm)
lp-lgnd = between lamp wires and ground Typical wire capacitance 72 pF/m (spacing between wires 0.5 mm)

Technical data for installation Lamp wiring for HF-P 2..TL5 Lamp wiring to both lamps must be inside
Mains operation one luminaire; length of wires to lamp 1
Rated mains voltage 220 - 240 V must be same (±10%) as length of wires to
with tolerances for safety: +/- 10% 198 - 264 V lamp 2 (wires to terminals 1 and 2 must be
tolerances for performance: +6% -8 202 - 254 V short and equal in length to wires 6 and 7;
Mains frequency 50/60 Hz
Operating frequency See table wires to terminals 3 and 4 must be long
and equal in length to wires to terminals
DC voltage operation during emergency back-up: 4 and 5); max. length of lamp wiring to be
yes for required battery voltage see table. equal to length of longest lamp (35 W/
49 W), plus normal length needed for
Earth leakage current < 0.5 mA per ballast assembly (in practice, max. 1.8 to 2 m).
For HF-P 1..TL5 it is advised to use 500 V
Ignition time < 0.5 s rated components and wiring.
500 V rated components and wiring are
Smart power:
constant light operation in case of mains voltage fluctuations required with HF-P 2..TL5.
within 202 - 254 V, the luminous flux
varies by a maximum of ± 2%

2
HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps

Dual fixture; Notes:


master-slave operation not advised 1. Data is based on a mains supply with an impedance of 400 mΩ (equal
to 15 m cable of 2.5 mm2 and another 20 m to the middle of the
Automatic restart after yes: tested with a dip down to 30% with power distribution), under worst case conditions.With an impedance of
lamp replacement or a duration of 10 mains cycles 800 mΩ the number of ballasts can be increased by 10%.
voltage dip 2. In some cases the maximum number of ballasts is not determined by
the MCB but by the maximum electrical load of the lighting installation.
Overvoltage protection 48 hr at 320 V AC 3. Note that the maximum number of ballasts is given when these are all
2 hr at 350 V AC switched on at the same moment, i.e. by a wall switch.
4. Measurements were carried out on single-pole MCB’s. For multi-pole
Insulation resistance test 500 V DC from Line/Neutral to Earth
(not between Line and Neutral)
Note: Ensure that the neutral is
reconnected again after abovementioned
test is carried out and before the
installation is put into operation.

The ballasts that are thermally protected use a protective method of


another type providing equivalent thermal protection.

Conversion table for max. quantities of ballasts on other types of


Mains current / Emergency operation Miniature Circuit Breaker
Ballast Input current (A) DC emergency operation* MCB type Relative number of
Ignition Normal ballasts
operation B 16 A 100% (see table above)
HF-P 1 14-35 TL5 HE (14W) 0.08 198-254V 176-254V B 10 A 63%
HF-P 2 14-35 TL5 HE (14W) 0.15 198-254V 176-254V C 10 A 104%
HF-P 1 14-35 TL5 HE (21W) 0.11 198-254V 176-254V L, I 16 A 108%
HF-P 2 14-35 TL5 HE (21W) 0.20 198-254V 176-254V L, I 10 A 65%
HF-P 1 14-35 TL5 HE (28W) 0.15 198-254V 176-254V G, U, II 16 A 212%
HF-P 2 14-35 TL5 HE (28W) 0.27 198-254V 176-254V G, U, II 10 A 127%
HF-P 1 14-35 TL5 HE (35W) 0.18 198-254V 176-254V K, III 16 A 254%
HF-P 2 14-35 TL5 HE (35W) 0.34 198-254V 176-254V K, III 10 A 154%
HF-P 1 24-39 TL5 HO (24W) 0.12 198-254V 176-254V
HF-P 2 24-39 TL5 HO (24W) 0.23 198-254V 176-254V
HF-P 1 24-39 TL5 HO (39W) 0.20 198-254V 176-254V
HF-P 2 24-39 TL5 HO (39W) 0.35 198-254V 176-254V
HF-P 149 TL5 HO 0.25 198-254V 176-254V
HF-P 249 TL5 HO 0.49 198-254V 176-254V
HF-P 154 TL5 HO 0.27 198-254V 176-254V
HF-P 254 TL5 HO 0.54 198-254V 176-254V
* Ballasts are tested not to fail at a DC operation with a duration of 48hrs at
maximum ballast ambient temperature. No guarantees for DC operation longer
than 48hrs.
* For continuous DC operation an extra external fuse should be used for safety
reasons
* Continuous low DC voltages (< 198 V) can influence the lifetime of the ballast

Inrush current
Ballast Max. quantity of Inrush current
ballasts per 1/2 value time
Miniature Circuit at typical
Breaker mains impedance
type B 16 A C 16 A
HF-P 1 14-35 TL5 HE 28 48 24A/250µs
HF-P 2 14-35 TL5 HE 15 20 31A/300µs
HF-P 1 24-39 TL5 HO 28 48 24A/250µs
HF-P 2 24-39 TL5 HO 15 20 31A/300µs
HF-P 149 TL5 HO 28 48 24A/250µs
HF-P 249 TL5 HO 15 20 31A/300µs
HF-P 154 TL5 HO 28 48 24A/250µs
HF-P 254 TL5 HO 15 20 31A/300µs

3
HF-PERFORMER electronic standard ballasts (flat)
for TL5 lamps

Connector types:
Wago universal connector. Suitable for both automatic wiring
(ALF and ADS) and manual wiring

Wire lengths:
HF 1
2
1 lamp version: keep wires to terminals 1 and 2 short
BALLAST 3
4
2 lamp version: keep wires to terminals 1, 2, 6 and 7
L short
N
1 lamp Wire cross-section: on the mains side: 0.5 - 1.0 mm2
on the lamp side: 0.5 - 1.0 mm2
Strip length: 8 - 9 mm

Technical data for design and mounting HF ballasts


in fixtures:
Temperatures
Temperature range to -15 to +50 °C
1 ignite lamp with ignition aid
2
HF 3
BALLAST 4 Max. tcase = 75˚C
5
L
N 6 Lifetime of a ballast depends on the temperature of the ballast.This
7 means there is a relation between the Tc point on the ballast and its
L
N lifetime. For more information regarding this subject consult the Philips
2 lamps Application guide to fluorescent lamp control gear.

Class II luminaires EMI precautions have to be taken


Wiring diagrams
Outdoor ballast IP=23. In outdoor the luminaire
has to be sufficiently IP rated
Permitted humidity is tested according
to EN 60928 par. 12. Note that no
moisture or condensation may enter
the ballast.

Ignition aid for optimum ignition the TL5 lamps


should be mounted at a maximum
distance of 6 mm from a metal plate.
The metal plate should be electrically
connected to the ballast housing

Earthing earthing of the HF ballast in a luminaire


is necessary for EMC (electromagnetic
compatibility)
Hum and noise level inaudible

Permitted humidity is tested according to EN 60928 par. 12.


Note that no moisture or condensation may enter the ballast.

The ballasts that are thermally protected use a protective method of


another type providing equivalent thermal protection.

Ordering and packing data


Ballast 1 Piece Bulk packing
EAN code Weight Qty. Dimensions Volume Weight EAN code EOC
lxwxh gross
kg pcs. cm m3 kg
HF-P 1 14-35 TL5 HE 8711500 928559 0.25 12 40.8x20.8x8.7 0.0074 3.3 8711500 928566 928559
HF-P 2 14-35 TL5 HE 8711500 928634 0.31 12 46.2x20.8x8.7 0.0090 4.0 8711500 928641 928634
HF-P 1 24-39 TL5 HO 8711500 928573 0.25 12 40.8x20.8x8.7 0.0074 3.3 8711500 928580 928573
HF-P 2 24-39 TL5 HO 8711500 928658 0.31 12 46.2x20.8x8.7 0.0090 4.0 8711500 928665 928658
HF-P 149 TL5 HO 8711500 928597 0.25 12 40.8x20.8x8.7 0.0074 3.3 8711500 928603 928597
HF-P 249 TL5 HO 8711500 928672 0.31 12 46.2x20.8x8.7 0.0090 4.0 8711500 928689 928672
HF-P 154 TL5 HO 8711500 928610 0.25 12 40.8x20.8x8.7 0.0074 3.3 8711500 928627 928610
HF-P 254 TL5 HO 8711500 928696 0.31 12 46.2x20.8x8.7 0.0090 4.0 8711500 928702 928696