0% found this document useful (0 votes)
52 views3 pages

Lab Analysis Schedule

The document outlines an analysis schedule for sampling various locations in a sewage treatment plant three times per week. Samples will be taken from the influent and effluent waste water before and after treatment processes to test for parameters including temperature, pH, dissolved oxygen, BOD, COD, and coliforms. Additional sampling of influent and effluent streams for processes like the facultative aerobic lagoon and chlorine contact tank will also be conducted once per week. The schedule is intended to monitor water quality at key stages of treatment.

Uploaded by

Maku Rajkumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views3 pages

Lab Analysis Schedule

The document outlines an analysis schedule for sampling various locations in a sewage treatment plant three times per week. Samples will be taken from the influent and effluent waste water before and after treatment processes to test for parameters including temperature, pH, dissolved oxygen, BOD, COD, and coliforms. Additional sampling of influent and effluent streams for processes like the facultative aerobic lagoon and chlorine contact tank will also be conducted once per week. The schedule is intended to monitor water quality at key stages of treatment.

Uploaded by

Maku Rajkumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

HMWS & SB

Analysis Schedule

Sl. Description of Location of Type of


Frequency Test to be done
No sample sampling sample
On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Volatile Suspended
Influent waste Three times a Before Solids, BOD (Total), BOD
1 Composition
water week Screening (Filter), COD (Total),COD
(Filter), On One
Sample per week
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms

On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Influent waste Three times a Before Volatile Suspended
2 Grab Solids, BOD (Total), BOD
water week Screening
(Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms

Operation and Maintenance Manual for 339 MLD STP at Amberpet Page 93
HMWS & SB

On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Volatile Suspended
Effluent waste Three times a After Chlorine Solids, BOD (Total), BOD
3 Composition
water week contact tank (Filter), COD (Total),COD
(Filter), On One
Sample per week
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms

On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Effluent waste Three times a After Chlorine Volatile Suspended
4 Grab Solids, BOD (Total), BOD
water week contact tank
(Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms

On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Effluent waste Volatile Suspended
Once in a week for
5 water from Effluent gutter Grab Solids, BOD (Total), BOD
each reactor
reactor (Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms
6 Influent to FAL Once in a week Inlet launder Grab Dissolved Oxygen
Effluent from
7 Once in a week Outlet launder Grab Dissolved Oxygen
FAL

Operation and Maintenance Manual for 339 MLD STP at Amberpet Page 94
HMWS & SB

On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Volatile Suspended
8 Influent to FPU Once in a week Inlet Grab Solids, BOD (Total), BOD
(Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms
On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Effluent from Volatile Suspended
9 Once in a week Outlet Grab
FPU Solids, BOD (Total), BOD
(Filter), COD (Total),COD
(Filter), Alkalinity,
Sulphate, Sulphide, VFA,
Feacal Coliforms
On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Volatile Suspended
10 Influent to CCT Once in a week Inlet Grab Solids, BOD (Total), BOD
(Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms
On every sample
Temperature, pH,
Dissolved Oxygen,
Suspended Solids,
Volatile Suspended
Effluent from
11 Once in a week Outlet Grab Solids, BOD (Total), BOD
CCT
(Filter), COD (Total),COD
(Filter),
Alkalinity, Sulphate,
Sulphide, VFA, Feacal
Coliforms
Effluent from
12 Once in a day Outlet Grab
CCT Residual chlorine

Operation and Maintenance Manual for 339 MLD STP at Amberpet Page 95