The document is a tank inspection report from Kalpa Electrikal Pvt. Ltd. for a 40KVA transformer tank. It summarizes the inspection of critical dimensions and checks if they are within specified tolerances. It also details checks of the paint inspection, pressure testing, and visual workmanship check, and notes that no leakages were found and the workmanship was acceptable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views1 page

Kalpa Electrikal PVT - LTD,: H.O: Rajajinagar, Bangalore

The document is a tank inspection report from Kalpa Electrikal Pvt. Ltd. for a 40KVA transformer tank. It summarizes the inspection of critical dimensions and checks if they are within specified tolerances. It also details checks of the paint inspection, pressure testing, and visual workmanship check, and notes that no leakages were found and the workmanship was acceptable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

KALPA ELECTRIKAL PVT.

LTD,
H.O : Rajajinagar,Bangalore.
TANK INSPECTION REPORT
CUSTOMER NAME JAKSON KEPL/F/TIR/01
WO NO 22/5991
QUANTITY 01 no.
DATE:15/03/2023
PRODUCT NAME 40KVA TRANSFORMER TANK
Sl.No. Tank Critical Dimension Tol. Measured Result
1 Transformer Base Chennel
a) Tank base channel - L-630 x W-100 x H-50 ±1.0mm 631*100*50 Within Limit
b) Wheel mounting pitch to pitch-470*470 ±1.0mm 470*471 Within Limit

2 Tank Over all Dimension


a) Tank inside Length-L-665 x W-280 x H-635 ±1.0mm 666*281*635 Within Limit
b) Tank base sheet thickness- 4 ±0.2mm 3.99 Within Limit
c)tank side sheet thickness-4 ±0.2mm 3.99 Within Limit

3 LV Chamber
a) Length-384x Width-65xHeight133 ±1.0mm 384*65*133 Within Limit
b) LV Terminal plate- L-470 x W-216 x Tk-6 ±1.0mm 471*215*6 Within Limit
c) LV Terminal plate hole Ø-28, Qty-4 No's & pitch-92 ±1.0mm Ø-28,4no's&92 Within Limit
d) LV Cable box Length-320 x Width-470 x Height-415 ±1.0mm 320*471*415 Within Limit
e) LV Cable box gland plate - L- 470 x W-320 x T-5 ±1.0mm 471*319*5 Within Limit

4 HV Chamber
a) Length- 1130x Width-200 x Height-210 ±1.0mm 1130*200*211 Within Limit
b) HV Terminal plate Length-1264 x Width-320 x Thck-6 ±1.0mm 1265*320*6 Within Limit
c) HV Terminal plate hole-ɸ 75 and pitch 445 ±1.0mm ɸ 75 & 446 Within Limit
d) HV Cable box Length-1006 x Width-1200 x Height-1540 ±1.0mm 1006*1200*1540 Within Limit
e) HV Cable box gland plate - L-1460 x W-447 x T-3 ±1.0mm 1460*447*3 Within Limit

5 Lifter Width 110 x Height115 x Thck 12 ±1.0mm 111*115*12 Within Limit

6 Top Cover
a) Length-910 x Width-463 x Thck-4 ±1.0mm 910*463*4 Within Limit
b) Filling & darin Boss ɸ-3/4'' ±1.0mm ɸ-3/4'' Within Limit
c) inspection chamber cutout L-190*W-90 ±1.0mm 190*90 Within Limit
d)inspection chamber cover L-240*W-140*T-3 ±1.0mm 241*140*3 Within Limit

7 Conservator
a) Length-700 x ID-230 x Thck-2 ±1.0mm 701*ɸ231*2 Within Limit
b) Conservator POG Plate OD-310 & Thck-4 ±1.0mm 311*4 Within Limit
c) Conservator closing plate-ɸ240& 2 thick ±1.0mm ɸ240*2 Within Limit

8 PAINT INSPECTION
a) Paint Shade RAL 5012 RAL 5012 Ok
b) Paint Thickness Min 100 100-125µ Ok
c) Finishing Painting Painting Ok

9 Pressure Test
Tank subjected to a pressure of 2.5 kg/cm² over ambient
2.5 kg/cm² leakages found attempted well Ok
pressure

10 Visual check for workmanship Found ok

NOTE: All dimensions are in "mm"


Accepted P Pavan
Rejected Checked By
KEPL/F/TIR/01 REV-00 Date:01-01-2018