VRF v4 Plus I Series
VRF v4 Plus I Series
VRF v4 Plus I Series
2. Nomenclature ........................................................................................... 3
3. Features ................................................................................................... 4
General Information 1
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
1. Product lineup
380-415V/3Ph/50Hz
Model name External appearance
MDV-730W/DRN1-i(C)
MDV-785W/DRN1-i(C)
MDV-850W/DRN1-i(C)
MDV-900W/DRN1-i(C)
2 General Information
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
2. Nomenclature
Series code
i: Individual type
Refrigerant type
N1: R410A
Power supply
R: 380-415V, 3Ph, 50Hz
D: DC inverter type
W: Outdoor units
Midea
General Information 3
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
3. Features
Wide application range
3.1.1 Wide capacity range
The whole product lineup of V4+I series will be from 7HP to 32HP, which is designed to optimize performance
and better match varieties of application requirement. Especially, the integrated designed V4+I series is focus
on providing better air conditioning system solution for the small and middle-sized buildings in the global
market.
3.1.2 Flexible indoor units connection
A 32HP outdoor unit supports up to 53 indoor units, freeing up
considerable space outside, use your backyard more wisely with much
more space available created by less number of outdoor units.
Maximum 53 indoor units for a 32HP outdoor units installation
Maximum 50 indoor units for a 30HP outdoor units installation
Maximum 46 indoor units for a 28HP outdoor units installation
Maximum 43 indoor units for a 26HP outdoor units installation
COOLING MODE
-5°C OutdoorTemperature 48°C
The V4+I series system operates
stably at extreme temperatures
HEATING MODE
ranging from minus 15°C to 48°C.
-15°C OutdoorTemperature 24°C
-2 0 -1 0 0 10 20 30 40 50
Outdoor temp. °C(D.B.)
4 General Information
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
3.1.5 High external static pressure
40 Pa
High static pressure propeller and optimized fan guard can adapt to
various installation environments.
Midea now offers 40Pa* external pressure for customized
applications. A standard 0-20Pa function is equipped by default
100
AC motor
Efficiency (%)
80
45% DC motor
60
40
20
50
8hrs 10hrs
Noise dB
Start End
Notes:
This function can be activated by setting at site. Temperature (load) curve shown in the graph is just an example.
3.3.3 Intelligent defrosting raises heat capacity
defrost
6 General Information
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
3.4 Easy installation and service
3.4.1 Compact design for effective use of space
Easy to transport
PQE XY E XYE
Wireless & wired controller can query
and modify each indoor unit's address.
General Information 7
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
3.4.4 Auto addressing
8 General Information
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Capacity One-way cassette Two-way cassette Compact four-way cassette Four-way cassette
(×100W)
15 ●
18 ●
22 ● ● ●
28 ● ● ● ●
36 ● ● ● ●
45 ● ● ● ●
56 ● ● ●
71 ● ●
80 ●
90 ●
100 ●
112 ●
140 ●
Duct type
Low static
Capacity Medium static pressure duct High static pressure duct
pressure duct
(×100W)
15 ●
18 ●
22 ● ●
28 ● ●
36 ● ●
45 ● ●
56 ● ●
71 ● ● ●
80 ● ●
90 ● ●
100
112 ● ●
140 ● ●
160 ●
200 ●
250 ●
280 ●
400 ●
450 ●
560 ●
General Information 9
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
22 ● ● ●
28 ● ● ●
36 ● ● ● ●
45 ● ● ● ●
56 ● ● ●
71 ● ● ●
80 ● ● ●
90 ●
112 ●
140 ●
160 ●
15 ●
22 ● ● ●
28 ● ● ●
36 ● ● ●
45 ● ● ●
56 ● ● ●
71 ● ●
80 ●
90 ●
125 ●
140 ●
200 ●
250 ●
280 ●
Note:
Due to continuous improvement, specifications are subject to change without prior notice.
10 General Information
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
2. Dimensions............................................................................................. 14
10.Accessories ........................................................................................... 56
1. Specifications
Model MDV-730W/DRN1-i(C) MDV-785W/DRN1-i(C) MDV-850W/DRN1-i(C) MDV-900W/DRN1-i(C)
Power supply V-Ph-Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50
Capacity kW 73.0 78.5 85.0 90.0
Cooling Power input kW 22.3 24.2 28.3 28.5
EER 3.27 3.24 3.00 3.16
Capacity kW 81.5 87.5 95.0 100.0
Heating Power input kW 20.6 22.4 26.0 26.5
COP 3.96 3.91 3.65 3.77
Model E705DHD-72D2YG E705DHD-72D2YG E705DHD-72D2YG E705DHD-72D2YG
Type Scroll Scroll Scroll Scroll
Brand Hitachi Hitachi Hitachi Hitachi
Quantity 1 1 1 1
Capacity kW 23.250 (At 60rps)
DC inverter
Input kW 7.150 (At 60rps)
compressor
Crankcase
W 33 33 33 33
heater
Refrigerant oil type FVC68D FVC68D FVC68D FVC68D
Refrigerant
ml 500 500 500 500
oil charge
Model E655DH-65D2YG(GC)
Type Scroll Scroll Scroll Scroll
Brand Hitachi Hitachi Hitachi Hitachi
Quantity 3 3 3 3
Capacity kW 17.1×3 17.1×3 17.1×4 17.1×4
Fixed
Input kW 9.6×3 9.6×3 9.6×4 9.6×4
inverter
Crankcase
compressor W 30×2+33×2 30×2+33×2 30×2+33×2 30×2+33×2
heater
Refrigerant oil type FVC68D FVC68D FVC68D FVC68D
Refrigerant
ml 500×3 500×3 500×4 500×4
oil charge
2. Dimensions
3. Service space
Ensure enough space for maintenance. The modules in the same system must be on the same height.
.
One row
Two rows
When the outdoor unit is lower than the surrounding obstacle, refer to the layout used when the outdoor unit
is higher than the surrounding obstacle. However, to avoid cross connection of the outdoor hot air from
affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to
facilitate heat dissipation. See the figure below. The height of the air director is HD(namely H-h).Please
make the air director on site.
4. Piping diagrams
SV6
LC
EXVB
ST1
26-28HP EXVA
RC
SV6
ST2 SV5
SV3
OL SV4
SV2
BP F1 F2 F3
SV6
LC
30-32HP EXVB
ST1
EXVA
RC
SV6
ST2 SV5
SV3
OL SV4
SV2
BP F1 F2 F3 F4
6. Field wiring
The control line should be shielded wire. Using other wiring shall create signal interference, thus leading to
error operation.
The shielded nets at the two sides of shielded wires are either grounded to the earth, or connected with each
other and jointed to the sheet metal along to the earth.
Control wire could not be bound together with refrigerant pipeline and power wire. When power wire and
control wire is distributed in parallel form, keep gap between them above 300mm so as to preventing signal
interference.
Control wire could not form closed loop.
Control wire has polarity, so be careful when connecting.
6.1 Electric wiring of outdoor/indoor units
Outdoor unit power supply
7. Electric characteristics
-2 24.64 3.63 29.46 4.26 34.15 4.85 36.50 5.09 38.85 5.39 43.54 6.10 48.49 6.58
0 24.64 3.70 29.46 4.33 34.15 4.93 36.50 5.16 38.85 5.45 43.54 6.21 48.49 6.69
2 24.64 3.75 29.46 4.38 34.15 5.02 36.50 5.24 38.85 5.55 43.54 6.23 48.49 6.82
4 24.64 3.78 29.46 4.46 34.15 5.07 36.50 5.30 38.85 5.66 43.54 6.39 48.49 6.99
6 24.64 3.85 29.46 4.53 34.15 5.15 36.50 5.42 38.85 5.76 43.54 6.48 48.49 7.20
8 24.64 3.95 29.46 4.61 34.15 5.24 36.50 5.54 38.85 5.84 43.54 6.59 48.49 7.43
10 24.64 4.03 29.46 4.66 34.15 5.32 36.50 5.63 38.85 6.01 43.54 6.76 48.49 7.54
12 24.64 4.06 29.46 4.72 34.15 5.41 36.50 5.74 38.85 6.13 43.54 6.88 48.49 7.66
14 24.64 4.12 29.46 4.78 34.15 5.47 36.50 5.86 38.85 6.22 43.54 7.00 48.49 7.81
16 24.64 4.18 29.46 4.84 34.15 5.56 36.50 5.95 38.85 6.31 43.54 7.12 48.49 7.93
18 24.64 4.24 29.46 4.93 34.15 5.65 36.50 6.04 38.85 6.43 43.54 7.24 48.49 8.08
20 24.64 4.30 29.46 4.99 34.15 5.74 36.50 6.13 38.85 6.55 43.54 7.36 48.49 8.23
50% 21 24.64 4.33 29.46 5.05 34.15 5.80 36.50 6.19 38.85 6.61 43.54 7.45 48.49 8.32
23 24.64 4.39 29.46 5.11 34.15 5.89 36.50 6.31 38.85 6.73 43.54 7.57 48.49 8.50
25 24.64 4.45 29.46 5.20 34.15 6.01 36.50 6.43 38.85 6.94 43.54 7.96 48.49 9.08
27 24.64 4.54 29.46 5.41 34.15 6.34 36.50 6.85 38.85 7.36 43.54 8.47 48.49 9.68
29 24.64 4.78 29.46 5.71 34.15 6.73 36.50 7.27 38.85 7.84 43.54 9.02 48.49 10.31
31 24.64 5.05 29.46 6.04 34.15 7.12 36.50 7.72 38.85 8.32 43.54 9.59 48.49 10.97
33 24.64 5.35 29.46 6.40 34.15 7.57 36.50 8.17 38.85 8.83 43.54 10.19 48.49 11.66
35 24.64 5.65 29.46 6.76 34.15 7.99 36.50 8.65 38.85 9.35 43.54 10.82 48.49 12.38
37 24.64 5.95 29.46 7.15 34.15 8.47 36.50 9.17 38.85 9.92 43.54 11.48 48.49 13.16
39 24.64 6.28 29.46 7.54 34.15 8.95 36.50 9.71 38.85 10.52 43.54 12.17 48.49 13.97
41 24.64 6.54 29.46 7.87 34.15 9.28 36.50 10.16 38.85 10.97 43.54 12.82 48.49 14.62
43 24.64 6.97 29.46 8.41 34.15 9.60 36.50 10.61 38.85 11.25 43.54 13.47 48.49 15.27
45 24.64 7.13 29.46 8.62 34.15 10.25 36.50 11.44 38.85 11.73 43.54 14.77 48.49 16.57
48 24.64 7.30 29.46 8.87 34.15 10.86 36.50 12.16 38.85 12.25 43.54 15.96 48.49 17.83
TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor)
-2 26.49 3.94 31.68 4.62 36.73 5.26 39.25 5.52 41.77 5.85 46.82 6.62 52.15 7.14
0 26.49 4.01 31.68 4.70 36.73 5.35 39.25 5.60 41.77 5.92 46.82 6.73 52.15 7.26
2 26.49 4.07 31.68 4.75 36.73 5.45 39.25 5.68 41.77 6.02 46.82 6.76 52.15 7.40
4 26.49 4.11 31.68 4.84 36.73 5.50 39.25 5.75 41.77 6.14 46.82 6.93 52.15 7.59
6 26.49 4.18 31.68 4.91 36.73 5.59 39.25 5.88 41.77 6.26 46.82 7.04 52.15 7.81
8 26.49 4.28 31.68 5.00 36.73 5.68 39.25 6.01 41.77 6.34 46.82 7.15 52.15 8.06
10 26.49 4.37 31.68 5.05 36.73 5.77 39.25 6.10 41.77 6.52 46.82 7.34 52.15 8.19
12 26.49 4.40 31.68 5.12 36.73 5.87 39.25 6.23 41.77 6.65 46.82 7.47 52.15 8.32
14 26.49 4.47 31.68 5.19 36.73 5.93 39.25 6.36 41.77 6.75 46.82 7.60 52.15 8.48
16 26.49 4.53 31.68 5.25 36.73 6.03 39.25 6.46 41.77 6.85 46.82 7.73 52.15 8.61
18 26.49 4.60 31.68 5.35 36.73 6.13 39.25 6.55 41.77 6.98 46.82 7.86 52.15 8.77
20 26.49 4.66 31.68 5.41 36.73 6.23 39.25 6.65 41.77 7.11 46.82 7.99 52.15 8.94
50% 21 26.49 4.70 31.68 5.48 36.73 6.29 39.25 6.72 41.77 7.17 46.82 8.09 52.15 9.03
23 26.49 4.76 31.68 5.54 36.73 6.39 39.25 6.85 41.77 7.31 46.82 8.22 52.15 9.23
25 26.49 4.83 31.68 5.64 36.73 6.52 39.25 6.98 41.77 7.53 46.82 8.64 52.15 9.85
27 26.49 4.92 31.68 5.87 36.73 6.88 39.25 7.44 41.77 7.99 46.82 9.20 52.15 10.50
29 26.49 5.19 31.68 6.20 36.73 7.31 39.25 7.89 41.77 8.51 46.82 9.78 52.15 11.19
31 26.49 5.48 31.68 6.55 36.73 7.73 39.25 8.38 41.77 9.03 46.82 10.40 52.15 11.90
33 26.49 5.81 31.68 6.95 36.73 8.22 39.25 8.87 41.77 9.59 46.82 11.06 52.15 12.65
35 26.49 6.13 31.68 7.34 36.73 8.67 39.25 9.39 41.77 10.14 46.82 11.74 52.15 13.44
37 26.49 6.46 31.68 7.76 36.73 9.20 39.25 9.95 41.77 10.76 46.82 12.46 52.15 14.28
39 26.49 6.82 31.68 8.19 36.73 9.72 39.25 10.53 41.77 11.41 46.82 13.21 52.15 15.16
41 26.49 7.10 31.68 8.54 36.73 10.07 39.25 11.03 41.77 11.91 46.82 13.91 52.15 15.87
43 26.49 7.57 31.68 9.12 36.73 10.42 39.25 11.52 41.77 12.21 46.82 14.62 52.15 16.57
45 26.49 7.74 31.68 9.36 36.73 11.13 39.25 12.41 41.77 12.73 46.82 16.03 52.15 17.98
48 26.49 7.92 31.68 9.62 36.73 11.78 39.25 13.20 41.77 13.29 46.82 17.31 52.15 19.35
TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor)
-2 28.69 4.61 34.30 5.40 39.77 6.15 42.50 6.46 45.23 6.84 50.70 7.74 56.47 8.35
0 28.69 4.69 34.30 5.49 39.77 6.26 42.50 6.55 45.23 6.92 50.70 7.87 56.47 8.49
2 28.69 4.76 34.30 5.56 39.77 6.37 42.50 6.64 45.23 7.04 50.70 7.91 56.47 8.65
4 28.69 4.80 34.30 5.66 39.77 6.44 42.50 6.72 45.23 7.18 50.70 8.11 56.47 8.88
6 28.69 4.89 34.30 5.74 39.77 6.54 42.50 6.88 45.23 7.31 50.70 8.23 56.47 9.14
8 28.69 5.01 34.30 5.85 39.77 6.65 42.50 7.03 45.23 7.41 50.70 8.36 56.47 9.43
10 28.69 5.11 34.30 5.91 39.77 6.75 42.50 7.14 45.23 7.63 50.70 8.58 56.47 9.57
12 28.69 5.15 34.30 5.99 39.77 6.86 42.50 7.28 45.23 7.78 50.70 8.73 56.47 9.72
14 28.69 5.22 34.30 6.06 39.77 6.94 42.50 7.44 45.23 7.89 50.70 8.89 56.47 9.92
16 28.69 5.30 34.30 6.14 39.77 7.06 42.50 7.55 45.23 8.01 50.70 9.04 56.47 10.07
18 28.69 5.38 34.30 6.25 39.77 7.17 42.50 7.67 45.23 8.16 50.70 9.19 56.47 10.26
20 28.69 5.45 34.30 6.33 39.77 7.28 42.50 7.78 45.23 8.31 50.70 9.34 56.47 10.45
50% 21 28.69 5.49 34.30 6.41 39.77 7.36 42.50 7.86 45.23 8.39 50.70 9.46 56.47 10.56
23 28.69 5.57 34.30 6.48 39.77 7.48 42.50 8.01 45.23 8.54 50.70 9.61 56.47 10.79
25 28.69 5.64 34.30 6.60 39.77 7.63 42.50 8.16 45.23 8.81 50.70 10.11 56.47 11.52
27 28.69 5.76 34.30 6.86 39.77 8.05 42.50 8.70 45.23 9.34 50.70 10.75 56.47 12.28
29 28.69 6.06 34.30 7.25 39.77 8.54 42.50 9.23 45.23 9.95 50.70 11.44 56.47 13.08
31 28.69 6.41 34.30 7.67 39.77 9.04 42.50 9.80 45.23 10.56 50.70 12.17 56.47 13.92
33 28.69 6.79 34.30 8.12 39.77 9.61 42.50 10.37 45.23 11.21 50.70 12.93 56.47 14.80
35 28.69 7.17 34.30 8.58 39.77 10.14 42.50 10.98 45.23 11.86 50.70 13.73 56.47 15.71
37 28.69 7.55 34.30 9.08 39.77 10.75 42.50 11.63 45.23 12.58 50.70 14.57 56.47 16.70
39 28.69 7.97 34.30 9.57 39.77 11.36 42.50 12.32 45.23 13.35 50.70 15.45 56.47 17.73
41 28.69 8.30 34.30 9.98 39.77 11.78 42.50 12.89 45.23 13.92 50.70 16.27 56.47 18.56
43 28.69 8.85 34.30 10.67 39.77 12.19 42.50 13.47 45.23 14.28 50.70 17.09 56.47 19.38
45 28.69 9.05 34.30 10.94 39.77 13.01 42.50 14.51 45.23 14.89 50.70 18.74 56.47 21.03
48 28.69 9.27 34.30 11.25 39.77 13.78 42.50 15.43 45.23 15.55 50.70 20.25 56.47 22.63
TC: Total Capacity (kW); PI: Power Input (kW) (Compressor + Outdoor fan motor)
-2 30.38 4.65 36.32 5.44 42.11 6.19 45.00 6.50 47.89 6.89 53.68 7.80 59.79 8.41
0 30.38 4.72 36.32 5.53 42.11 6.30 45.00 6.59 47.89 6.97 53.68 7.93 59.79 8.55
2 30.38 4.79 36.32 5.60 42.11 6.42 45.00 6.69 47.89 7.09 53.68 7.96 59.79 8.72
4 30.38 4.84 36.32 5.70 42.11 6.48 45.00 6.77 47.89 7.23 53.68 8.16 59.79 8.94
6 30.38 4.93 36.32 5.78 42.11 6.58 45.00 6.92 47.89 7.37 53.68 8.29 59.79 9.20
8 30.38 5.04 36.32 5.89 42.11 6.69 45.00 7.08 47.89 7.47 53.68 8.42 59.79 9.50
10 30.38 5.15 36.32 5.95 42.11 6.80 45.00 7.19 47.89 7.68 53.68 8.64 59.79 9.64
12 30.38 5.19 36.32 6.03 42.11 6.91 45.00 7.34 47.89 7.83 53.68 8.79 59.79 9.79
14 30.38 5.26 36.32 6.11 42.11 6.99 45.00 7.49 47.89 7.95 53.68 8.95 59.79 9.99
16 30.38 5.34 36.32 6.18 42.11 7.11 45.00 7.60 47.89 8.07 53.68 9.10 59.79 10.14
18 30.38 5.42 36.32 6.30 42.11 7.22 45.00 7.72 47.89 8.22 53.68 9.26 59.79 10.33
20 30.38 5.49 36.32 6.38 42.11 7.34 45.00 7.83 47.89 8.37 53.68 9.41 59.79 10.52
50% 21 30.38 5.53 36.32 6.45 42.11 7.41 45.00 7.91 47.89 8.45 53.68 9.52 59.79 10.64
23 30.38 5.61 36.32 6.53 42.11 7.53 45.00 8.07 47.89 8.60 53.68 9.68 59.79 10.87
25 30.38 5.68 36.32 6.64 42.11 7.68 45.00 8.22 47.89 8.87 53.68 10.18 59.79 11.60
27 30.38 5.80 36.32 6.91 42.11 8.10 45.00 8.76 47.89 9.41 53.68 10.83 59.79 12.37
29 30.38 6.11 36.32 7.30 42.11 8.60 45.00 9.29 47.89 10.02 53.68 11.52 59.79 13.17
31 30.38 6.45 36.32 7.72 42.11 9.10 45.00 9.87 47.89 10.64 53.68 12.25 59.79 14.02
33 30.38 6.84 36.32 8.18 42.11 9.68 45.00 10.45 47.89 11.29 53.68 13.02 59.79 14.90
35 30.38 7.22 36.32 8.64 42.11 10.22 45.00 11.06 47.89 11.95 53.68 13.83 59.79 15.82
37 30.38 7.60 36.32 9.14 42.11 10.83 45.00 11.71 47.89 12.67 53.68 14.67 59.79 16.82
39 30.38 8.03 36.32 9.64 42.11 11.44 45.00 12.40 47.89 13.44 53.68 15.55 59.79 17.86
41 30.38 8.36 36.32 10.05 42.11 11.86 45.00 12.99 47.89 14.02 53.68 16.38 59.79 18.69
43 30.38 8.91 36.32 10.75 42.11 12.27 45.00 13.57 47.89 14.38 53.68 17.21 59.79 19.52
45 30.38 9.12 36.32 11.02 42.11 13.10 45.00 14.62 47.89 14.99 53.68 18.87 59.79 21.18
48 30.38 9.33 36.32 11.33 42.11 13.87 45.00 15.54 47.89 15.66 53.68 20.39 59.79 22.79
9. Sound levels
Front
1.3m
1m
Notes:
• Data is valid at free field condition
• Data is valid at nominal operating condition
• Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coefficient) of particular room in which the equipment is installed
• Sound level can be increased in static pressure mode or used air guide.
Sound pressure level
Model
d(B)A
MDV-730W/DRN1-i(C) 64
MDV-785W/DRN1-i(C) 64
MDV-850W/DRN1-i(C) 65
MDV-900W/DRN1-i(C) 65
Sound pressure spectrum
MDV-730W/DRN1-i(C); MDV-785W/DRN1-i(C) MDV-850W/DRN1-i(C); MDV-900W/DRN1-i(C)
70 70
60 60
50 50
40 40
30 30
20 20
Audibility limits of Audibility limits of
continuous white sound continuous white sound
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency(Hz) Octave band center frequency(Hz)
Specifications & Performances 55
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
10. Accessories
Selection Procedure 57
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
1. Introduction
Model selection procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown
below.
-conditioning load, Calculate the maximum air-conditioning load for each room or
zone.
Selection of an air conditioning system
Design of the control system
Preliminary selection of indoor and outdoor units
Check of the tubing length and elevation difference
Check that the length of refrigerant tubing and the elevation difference are within the allowable ranges
Calculation of the corrected outdoor unit capacity
Capacity correction coefficient for model, outdoor temperature conditions, tubing length and elevation
difference.
Calculation of the actual capacity for each indoor unit
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the
total corrected capacity of all indoor units in the same system.
Recheck of the actual capacity for each indoor unit
If the capacity is inadequate, reexamine the unit combinations.
1.2 Indoor unit selection
Enter INDOOR UNIT CAPACITY TABLES at given indoor and outdoor temperature. Select the unit that the
capacity is the nearest to and greater than given load.
Note:
Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be calculated according to the
combination by using outdoor unit capacity table.
Calculation of actual capacity of indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length,
elevation difference and other factors, select the correct model after taking into account the various correction
values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit.
Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the
actual final capacity of each indoor unit.
Find the indoor unit capacity correction coefficient for the following items:
Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics, use the indoor temperature to find the capacity correction
coefficient.
Capacity distribution ratio based on the indoor unit tubing length and elevation difference.
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor
unit to find the correction coefficient from the graph of capacity change characteristics
Capacity distribution ratio for each indoor unit=Correction coefficient for that indoor unit / Correction coefficient for the
outdoor unit
1.3 Outdoor unit selection
Allowable combinations are indicated in INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE.
In general, outdoor unit can be selected as follows though the location of the unit, zoning and usage of the
58 Selection Procedure
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
rooms may be considered.
The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to
and smaller than the capacity index at 100% combination ratio of each outdoor unit. Up to 8~16 indoor units
can be connected to one outdoor unit. It is recommended to choose a larger outdoor unit if the installation
space is large enough.
If the combination ratio is greater than 100%, the indoor unit selection shall be reviewed by using actual
capacity of each indoor unit.
INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE
Indoor Unit Combination Ratio (kW)
Outdoor Unit
130% 120% 110% 100% 90% 80% 70% 60% 50%
26HP 94.9 87.6 80.3 73 65.7 58.4 51.1 43.8 36.5
28HP 102.1 94.2 86.4 78.5 70.7 62.8 55.0 47.1 39.3
30HP 110.5 102 93.5 85 76.5 68 59.5 51 42.5
32HP 117 108 99 90 81 72 63 54 45
INDOOR UNIT CAPACITY INDEX
Model Model Model Model Model Model Model Model Model Model
Unit Size
18 22 28 36 45 56 71 80 90 112
Capacity Index (kW) 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2
Selection Procedure 59
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
H(m)
70
60
50
40
30
20
10
100%
85
89
87
99
97
83
92
94
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
-110
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 L(m)
H(m)
70
60
50
40
30
20
10
100%
0
98
95
99
97
96
93
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
-110
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 L(m)
Selection Procedure 61
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
2.4 Conclusion
Generally, we think this result is acceptable, so we can think we have accomplished the calculation. But if you
think this result is not acceptable, you can repeat the above process.
Remark: In this sample, the other capacity modification indexes don’t be considered and are assumed as 1.0.
For more details about the effect factor such as outside ambient/inside ambient DB/WD, please refer to the
performance table of indoor and outdoor units.
62 Selection Procedure
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Part 4 Installation
1. Select installation position ....................................................................... 64
Installation 63
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
A solid, correct base can: Avoid the outdoor unit from sinking and avoid the abnormal noise generated due
to base.
Base types: Steel structure base or concrete base (See the figure below for the general making method)
64 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Distance between foot screws is shown as follow. The spacing between the two cement piers shall not be
exceeded over than 650mm.
3. Installation space
Ensure enough space for maintenance. The modules in the same system must be on the same height.
When installing the unit, leave enough space for maintenance.
Installation 65
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
When the outdoor unit is higher than the surrounding obstacle
One row
Two rows
66 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot
air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the
outdoor unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely
H-h). Please make the air director on site.
If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm below the top of
the outdoor unit. Otherwise, a mechanic exhaust device must be added.
D
A
C
B
A
A
B B
A >45° B >300mm
C >1000mm D Airflow deflector
4. Lifting method
Do not remove any package before the hoisting. Use two ropes to hoist the machine, keep the machine in
balance, and then raise it safely and steadily. In case of no package or if the package is damaged, use
plates or packing material to protect it.
When conveying and hoisting the outdoor unit, keep it upright, ensure that the slope does not exceed 30°,
and keep safety in mind.
Steel wire can be used for conveying:
Use 4 steel wires of the size above Φ6mm to convey the outdoor unit. Pay attention to the gravity center
and prevent sliding and tip-over of the outdoor unit.
In order to prevent scratch and deformity the outdoor unit, apply a guard board to the surface of contact
between the steel wire and the air conditioner.
Remove the cushion for use in the transport after finishing the transport.
Fork lifter can be used for conveying.
Installation 67
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
The ventilation assembly is provided at the field installation. When installing, please take off the mesh cover
firstly, and then install the unit as the following method.
68 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Size (mm)
A A≥300
B B≥250
C C≤10000
D 600≤D≤760
θ θ≤15o
Installation 69
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
7. Refrigerant piping installation
7.1 Valve instructions
(Unit:mm)
70 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Permitted
Piping length Piping
value
L1+(L2+L3+L4+L5+L6+L7+L8)×2
Actual total piping length 1000m
+a+b+c+d+e+f+g+h+i
Maximum single Actual length 165m
Piping length
L1+L5+ L8+L9+j
piping length Equivalent length 190m
Maximum piping length from the first
40/90m L5+L8+L9+j
branch joint to the farthest indoor unit
Level difference Outdoor unit up 50m /
difference
Installation 71
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
Increasing size as the following:
Φ9.5→Φ12.7 Φ12.7→Φ15.9 Φ15.9→Φ19.1 Φ19.1→Φ22.2 Φ 22.2→Φ25.4 Φ25.4→Φ28.6
Φ28.6→Φ31.8 Φ31.8→Φ38.1 Φ38.1→Φ41.3 Φ41.3→Φ44.5 Φ44.5→Φ54.0
When counting the total piping length, the actual length of above distribution pipes must be doubled. (Expect the main pipe
and the distribution pipes): Total piping length=1+(L2+L3+L4+L5+L6+L7+L8+L9)×2+a+b+c+d+e+f+g+h+i+j≤1000m
The length from the indoor unit to the nearest branch joint assembly or MS≤40m.a,b,c,d,e,f,g,h,I,j≤40m
The length difference between (the outdoor unit to the farthest indoor unit) and (the outdoor unit to the nearest indoor unit) ≤
40m. [(L1+L5+L8+L9+j)-(L1+L2+L3+a)]≤40m
7.3 Refrigerant piping selection
Pipe name
Main pipe L1
Indoor unit main pipe L2, L3, L4, L5, L6
Indoor unit branch pipe a, b, c, d, e, f, g
Indoor unit branch pipe assembly A, B, C, D, E, F
Table1: Indoor unit branch pipe selection (a~i)
Capacity of indoor unit Branching pipe length≤10m Branching pipe length≥10m
(A×100W) Gas side Liquid side Gas side Liquid side
A≤45 Φ12.7 Φ6.4 Φ15.9 Φ9.5
A≥56 Φ15.9 Φ9.5 Φ19.1 Φ12.7
Table 2: Indoor unit main pipe selection (L1~L8)
Capacity of indoor unit Indoor unit main pipe (mm)
(A×100W) Gas side Liquid side Available branching pipe
A<166 Φ15.9 Φ9.5 FQZHN-01D
166≤A<230 Φ19.1 Φ9.5 FQZHN-01D
230≤A<330 Φ22.2 Φ9.5 FQZHN-02D
330≤A<460 Φ28.6 Φ12.7 FQZHN-03D
460≤A<660 Φ28.6 Φ15.9 FQZHN-03D
72 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
660≤A<920 Φ31.8 Φ19.1 FQZHN-03D
920≤A<1080 Φ38.1 Φ19.1 FQZHN-04D
Installation 73
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
For the capacity of outdoor unit is 32HP, the equivalent length of all pipes in this system is larger than 90m,
refer to table 3, the main pipe L1 is Φ38.1/Φ22.2.
As the main pipe L1 is selected as Φ31.8/Φ19.1 from step 2, and Φ31.8/Φ19.1 from step 3, we finally select
the larger pipe Φ38.1/Φ22.2 as main pipe L1.
Note: For the detail dimension and installation information pipe, please read the branch pipe installation manual carefully.
74 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
The branching pipe must be installed horizontally and error angle of it should not be larger than 10°. Otherwise,
refrigerant assignment will be uneven and malfunction will be caused.
A direction view
Wrong Correct
10°
10°
Horizontal surface
Make sure there is no any dirt or water in the pipe before connecting the piping to the outdoor units.
Wash the piping with high pressure nitrogen, never use refrigerant of the outdoor unit to do that.
Connect pipe on hi-pressure side with hi-pressure valve.(For multi-modules parallel connection, please
connect gas balance valves).
Weld the piping on low-pressure side with gauge joint.
Charge nitrogen from hi-pressure valve core to gauge joint.
After airtight test, weld low-pressure ball valve and piping on low-pressure side.
Note:
2 2
The air tightness test is conducted by pressurized nitrogen (R22 system: 28kgf/cm , R410A system: 40kgf/cm ).
It is not allowed to adopt oxide, flammable gas and toxic gas to conduct air tightness test.
It’s not allowable to welding low pressure ball valve with low pressure side piping before charge nitrogen.
Wrap the lo-valve and the balance valve by wet cloth for protection when welding..
Installation 75
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
Connect with vacuum pump
Calculate the additional refrigerant charge according to the diameter and the length of the liquid side pipe of
the outdoor/indoor unit connection. The refrigerant is R410A.
Pipe size of liquid side Additional refrigerant charge per meter (kg)
Φ6.4 0.022
Φ9.5 0.057
Φ12.7 0.110
Φ15.9 0.170
Φ19.1 0.260
Φ22.2 0.360
Φ25.4 0.520
Φ28.6 0.680
When all the indoor units are in cooling or heating mode, the system will be in refrigerant volume judgment
mode automatically. If the system judges that the refrigerant volume is normal, the system will operate normally,
no error code will display. If the system judges that the refrigerant volume is abnormal, corresponding error
code will display on digital tube.
When only partial indoor units are in cooling or heating mode, the system will not judge the refrigerant volume
and the digital tube will reserve the last judging result.
Error code Content
r1 Lack of refrigerant
r2 Obvious lack of refrigerant
r3 Serious lack of refrigerant
R1 Too much refrigerant
R2 Serious too much refrigerant
76 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
A B C N
Installation 77
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
14.2.2 Indoor unit powering supply wiring
Note:
Set refrigerant piping system, signal wires between indoor units and signal wires between outdoor units into one system.
Power must unified supply to all indoor units in the one system.
Please do not put the signal wires and power wires in the same wire tube; keep distance between the two tubes. (Keep
distance above 300mm, when current capacity of power supply less than 10A, and Keep distance above 500mm, when current
capacity of power supply less than 50A)
14.3 Signal wiring installation
14.3.1 Signal wire between outdoor unit and indoor unit
Signal wire of indoor/outdoor unit adopts 3-core shielded wire (≥0.75mm2) which has polarity, please connect
it correctly.
78 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
14.3.2 Example connection of wiring
Installation 79
R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
Besides, CCM03 can also connect indoor units via the port X Y E of indoor unit. However, one more group of
wire(X Y E between indoor units) is needed; it is more complex and not suggested. Anyway, the diagram below
shows the connection of signal wire in this case:
80 Installation
MCAC-VTSM-2014-04 R410A DC Inverter VRF V4 Plus Individual Series 50Hz
Model(indoor unit)
Room Name
Eg: Indoor unit (A) of the
first system on second floor
is recorded as:-2F-1A
Calculate the critical thickness through following steps, and take necessary actions.
1. Calculate the refrigerant charge (A [kg])
2. Total refrigerant charge = delivered refrigerant charge (nameplate) + supplemental refrigerant charge
3. Calculate the indoor volume (B [m3]) (as the minimum volume)
4. Calculate the refrigerant thickness.
A kg
≤ critical thickness 0.3kg/m3
B m3
Countermeasure to overhigh refrigerant thickness
1. Install mechanical ventilator to reduce the refrigerant thickness
under critical level. (Ventilate regularly)
2. Install leakage detector alarming device related to mechanical
ventilator if you cannot regularly ventilate.
Installation 81
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
Part 5 Troubleshooting
5. Troubleshooting ............................................................................... 94
82 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
1. Outdoor electric control box assembly instructions
1.7
1.9
1.12.1 1.13
1.12.2 1.5
1.1
1.12.3 1.10
1.4
1.8
1.6 1.3
1.11
1.14
1.2
2.2 2.4
Troubleshooting 83
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
NO. Content
84 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
2. Main board ports instructions
Troubleshooting 85
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
Main board ports instruction
No. Content
1 Discharge temp. sensed port of the inverter compressor 19 Null line terminal
2 Discharge temp. sensed port of the No.1 fixed compressor 20 Low speed output terminal of Fan 4
3 Discharge temp. sensed port of the No.2 fixed compressor 21 High speed output terminal of Fan 4
4 Discharge temp. sensed port of the No.3 fixed compressor 22 Low speed output terminal of Fan 3
5 Discharge temp. sensed port of the No.4 fixed compressor 23 Power input terminal of Fan 3 and Fan 4
6 Reserve 24 High speed output terminal of Fan 3
7 Reserve 25 Power output of the No.1 transformer
Wiring port for communication between indoor and outdoor
8 units, indoor unit network, outdoor unit network and network 26 Power output of the No.2 transformer
accounting
9 Three-phase detection port 27 Port for inverter module voltage inspection
10 Power input of the No.1 transformer 28 The sensor of inverter module current
11 Power input of the No.2 transformer 29 Activation port of inverter module
12 Heat output terminal of inverter compressor 30 Null line control port
Power supply connected port of the main control
13 Power control output terminal 31
panel
ON/OFF signal input port for system low
14 Fixed compressor control output terminal 32
pressure inspection
ON/OFF signal input port for system high
15 Solenoid valve output terminal 33
pressure inspection
16 EXV B driving port 34 Input port for system high pressure inspection
17 EXV A driving port 35 Current inspection port of the fixed compressors
36 Current inspection port of the inverter
18 Port for fan 1 and fan 2 control
compressors
37 Inspection port for temp. of outdoor ambient and
19 Null line terminal
condenser coil
86 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
3. Main board parts instructions
3.1 SW1
Constraint Cooling
Once pressing the constraint cooling button (see the chart on the right), all the indoor unit will be on forced
cooling mode and the wind speed is HIGH.
6 5-- Total requirement of indoor unit capacity Available for main unit
7 6-- Total requirement of main unit corrected capacity Available for main unit
Troubleshooting 87
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
11 10-- Speed of fan B
34 33-- DC voltage
35 34-- Reserve
If there is no protection or error,
36 35-- The last-time error or the protection code
the panel will display 8.8.8
37 -- Check end
88 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
3.3 System setting dial switches instructions
Outdoor
address
dial switch
Outdoor power
SW2:Query
dial switch
button
Quantity setting
dial switch of
indoor units
SW1:Constraint
cooling
S1 definition
S2 definition S3 definition
Night time selection is 6h/10h(Default the Factory Set) Night silent mode(Default the Factory Set)
Troubleshooting 89
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
S4 definition
Static pressure mode is low pressure(Reserve position, use for customized unit)
Static pressure mode is medium pressure(Reserve position, use for customized unit)
Static pressure mode is high pressure(Reserve position, use for customized unit)
S5 definition S6 definition
90 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
S8 definition S10 definition
reserve reserve
ENC4 definition
Troubleshooting 91
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
3.3 Function setting dial switches instructions
LED3
LED5
LED2
LED4
LED1
LED1: Power supply indicator lamp of network centralized control chip. The lamp will be on if the power
supply is normal.
LED2: Running indicator lamp of network centralized control chip. The lamp will be on if the system running
is normal.
LED3: Malfunction indicator lamp of network centralized control chip. The lamp will flash in Three-phase
phase sequence protection.
LED4: Malfunction indicator lamp of inverter module. The lamp will flash if the inverter module is faulty and
the error code will display on digital tube.
LED5: Running indicator lamp of inverter module. The lamp will be on if the compressor is running.
4. Error/Protection code table
No. Error code Error or protection type Note
2 E1 Phase protection
92 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
4 E3 Reserve
7 E6 Reserve
9 E8 Reserve
10 H0 COMM. Error(IR341&MC9S08AC128)
11 H1 COMM. Error(0537&MC9S08AC128)
26 XP7 No.X fixed compressor current protection X stand for the fixed compressor No.
27 P8 Reserve
28 P9 Reserve
34 L3 Reserve
Troubleshooting 93
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
35 L4 MCE error/synchronization/closed-loop
36 L5 Zero-speed protection
37 L6 Reserve
41 dF Defrosting(DSP1:Df,DSP2:frequency)
42 d0 Oil returning(DSP1:d0,DSP2:frequency)
*The error code of L0-L9 won’t display directly on the digital tube, you should press the check button after P6 disappear in one
minute.
5. Troubleshooting
5.1 E0: Communication error between outdoor units (Only display on faulty slave unit, all the ODU in
standby)
No
No
Yes
MC9S08AC128 chip is disabled
No
94 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.2 E1: Phase sequence error (Display on faulty unit, all the ODU in standby)
No
No
Yes
MC9S08AC128 chip is disabled
No
Note:
If the wiring connection of each outdoor unit is according to A, B, C phase sequence, when the quantity of
outdoor units is large, the current difference between C phase and A, B phase will be very large for the
power supply load of each outdoor unit is on C phase, it is very easy to lead to air switch break and wiring
terminal burnout. So when the quantity of outdoor units is large, the phase sequence should be staggered,
then the current can be distributed to the three phases equally.
Troubleshooting 95
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.3 E2: Indoor units and master unit communication error (Only display on master unit, all the ODU
in standby)
No
Signal wires are not connected in Yes Connect the signal wires in line
series shape
No
No
No
The length of communication wire is Yes Adjust the wire length to less than
over 1200m 1200m or strengthen the signal
No
No
96 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
1. Pressing the manual button continued for 5 seconds, it will display the indoor units communication
address.
2. Pressing the manual button continued for 10 seconds, it will display the capacity of indoor units.
Dial code Capacity (×100W) HP
0 22 0.8
1 28 1.0
2 36 1.2
3 45 1.6
4 56 2.0
5 71 2.5
6 80 3.0
7 90 3.2
8 112 4.0
9 140 5.0
A 160 6.0
B 160 6.0
C 160 6.0
D 160 6.0
E 160 6.0
F 160 6.0
Troubleshooting 97
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
For example
Pressing the manual button continued for 10 seconds:
If all the LED lights turn off, that means the capacity code is 0 and the capacity of indoor units is
22×100W(0.8HP);
If the “Timer” and “Alarm” lights are normally on, that means the capacity code is 5=(4+1) and the
capacity of indoor unit is 71×100W(2.5HP);
If the “Operation” and “Alarm” lights are normally on, that means the capacity code is 9=(8+1) and the
capacity of indoor unit is 140×100W(5.0HP);
If all the LED lights turn on, that means the capacity code is F=(8+4+2+1) and the capacity of indoor unit
is 160×100W(6.0HP).
The above basic principle just applies to single PCB, if the indoor unit has more than one PCB, or one PCB
can achieve a virtual multi blocks function, you must use the basic principle to calculate the achievable
capacity of single PCB at first, then add all the value as the capacity of the indoor unit .
For example
The high static pressure duct has capacity of 20kW, 25kW, 28kW and larger capacity of 40kW, 45kW, 56kW.
The “Operation” light is normally on, that means the capacity code is 8 and the achievable capacity of
single PCB is 112×100W(4.0HP), then add the value of two PCB, so the capacity of indoor unit is
200×100W(8.0HP);
The “Operation” and “Alarm” lights are normally on, that means the capacity code is 9=(8+1) and the
achievable capacity of single PCB is 140×100W(5.0HP), then add the value of two PCB, so the capacity
of indoor unit is 280×100W(10HP);
The “Operation” light is normally on, that means the capacity code is 8 and the achievable capacity of
single PCB is 112×100W(4.0HP), then add the value of four PCB, so the capacity of indoor unit is
450×100W(16HP);
The “Operation” and “Alarm” lights are normally on, that means the capacity code is 9=(8+1) and the
achievable capacity of single PCB is 140×100W(5.0HP), then add the value of four PCB, so the
capacity of indoor unit is 560×100W(20HP).
3. If the signal is weak, connect a 120Ω resistor between P and Q of the farthest indoor unit, or connect a
0.5-1.5uF capacitor between P and Q of outdoor unit. Installation refers to the following picture:
Capacitor
R=120Ω
Outdoor Unit
Indoor Unit Indoor Unit Indoor Unit Indoor Unit
Note:
Signal wires should be shield wire and indoor units should be connected in series.
98 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.4 E4: Pipe temperature T3/Ambient temperature sensor (T4) error (Display on faulty unit, all the
ODU in standby)
No
Yes
MC9S08AC128chip is disabled
No
Case: There is no display on main board of one system, and the problem still exists after replacing main
board. Voltage values on measuring plate (such as 220V, 5V, 12V, etc.) are normal; after measuring
resistance value of sensor, find that T4 thermo-bulb is earth-continuity, and further discover that the
thermal cable of T4 sensor is punched by bolt, as follows:
Note:
①
1. How to check whether the compressor is short circuit :
The normal resistance value of inverter compressor among U V W is 0.7~1.5Ω, and infinity to earth. If the resistance value is
out of the range, the compressor is abnormal.
②
2. How to check whether the fan motor is short circuit :
The normal value of DC fan motor coil among U V W is less than 10Ω, and the value of AC fan motor coil is from a few ohm to
hundreds of ohm for different fan motor model. If the measured value is 0Ω, the fan motor is short circuit.
③
3. How to check whether the inverter module is output error :
Let PN and UVW of inverter module short circuit, then dial multimeter to buzzer file, if the multimeter is ring, the inverter
module is output error.
Troubleshooting 99
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.5 H0/H1
H0: IR341 and MC9S08AC128 communication error (Display on faulty unit, all the ODU in standby)
H1: 0537 and MC9S08AC128 communication error (Display on faulty unit, all the ODU in standby)
IR341 chip: IR 341chip is used for inverter compressor drive.
0537 chip: 0537chip is used for control the communication between indoor unit and outdoor unit, and the
communication between outdoors
MC9S08AC128 chip: MC9S08AC128 chip is the main chip, it used for the whole system control.
H0/H1
No
No
No
Yes
MC9S08AC128 chip is disabled
No
100 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.6 H6: Quantity of indoor units decrease error (Only display on master unit, all the ODU in standby)
“H7” error will display when the quantity of indoor units decrease above 3 minutes.
No
Some IDU are assigned the Yes Set the IDU addresses differently
same address
No
No
① Yes
Transformer of IDU is disabled Replace the transformer
No
Yes Insure all the IDU be unified
IDU are not unified power supply* power supply
No
②
485 communication IC is disabled
Note:
①
1. How to check whether the transformer of IDU is disabled
The voltage input for IDU transformer is 220V, the voltage output of is AC9V (yellow-yellow) and AC13.5V (brown-brown)
②
2. How to check whether the 485 communication IC is disabled
The normal voltage between “P” and “GND” is DC2.5~2.7V, between “Q” and “GND” is DC2.5~2.7V. If the voltage is out of the
normal range, the 485 communication IC is disabled.
P Q E terminals
*Indoor units should be unified power supply, which can prevent compressor from liquid hammer caused by dropped indoor
units with EXV unclosed.
Troubleshooting 101
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.7 H8: High pressure sensor error
When the discharge pressure is lower than 0.3MPa, the system will display H8 error, the ODU in standby.
When the discharge pressure is back to normal, H8 disappears and normal operation resumes.
No
No
The low pressure side is blocked③ Make sure all valves are open, clean
Yes
for squashed pipe, closed EXV, the filter, if the filter is blocked by ice,
closed strop valve, dirty filter, etc. the system should be clean
No
No
Note:
1. How to check whether the high pressure sensor is short circuit or disabled①
Measure the resistance among the three terminals of the pressure sensor, if the resistance value is megohm or infinite, the
pressure sensor is disabled, otherwise, it may be normal.
2. The phenomenon of lack of refrigerant②:
Top temperature and discharge temperature of all compressors are higher than normal value, discharge pressure and suction
pressure are both lower than normal value, current is lower than normal value, suction pipe may be frosting. All the
phenomenon will disappear after recharging refrigerant.
3. The phenomenon of the low pressure side is blocked③:
The discharge temperature is higher than normal value*, low pressure is lower than normal value*, current is lower than
normal value* and suction pipe may be frosting.
*The normal system running parameters please refer to attached table 3.
102 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.8 P0/P4/H6: High temperature protection (Display on faulty unit, all the ODU in standby)
P0: Inverter compressor top temperature protection
When the top temperature is over 120℃, the operation will stop, when the temperature goes back to normal
range, P0 disappear and normal operation resumes.
P4: High discharge temperature protection
When the discharge temperature of any compressor is over 120℃, the operation will stop, when the
temperature goes back to normal range, P4 disappear and normal operation resumes.
H6: When system appear 3 times P4 protection in 100 minutes
It cannot resume automatically, and it can resume only by restarting the machine.
P0/P4/H6
No
③
The low pressure side is blocked Yes Make sure all valves are open, clean the
for squashed pipe, closed EXV, filter, if the filter is blocked by ice, the
closed strop valve, dirty filter, etc. system should be clean
No
Yes Make sure the ratio of connectable IDU is
④
The indoor load is too large less than 130% or add ODU
No
Discharge the entire refrigerant. Then vacuum
⑤ Yes
System contains air or nitrogen the system and refill the refrigerant. Add oil to
the system if it leaks.
No
Yes
MC9S08AC128 chip is
disabled
No
Main board is disabled Replace main board
Note:
①
1. How to check whether the T7/T7C1/T7C2 sensor is short circuit or disabled :
Using a multimeter to measure resistance, if the resistance is too small, the sensor is short circuit, if the resistance in certain
temperature is not consistent with attached table 2, the sensor is disabled
②
2. The phenomenon of lack of refrigerant :
Top temperature and discharge temperature of all compressors are higher than normal value, discharge pressure and suction
pressure are both lower than normal value, current is lower than normal value, suction pipe may be frosting. All the
phenomenon will disappear after recharging refrigerant.
③
3. The phenomenon of the low pressure side is blocked :
The discharge temperature is higher than normal value*, low pressure is lower than normal value*, current is lower than
normal value* and suction pipe may be frosting.
④
4. The phenomenon of the indoor load is too large :
The suction temperature and discharge temperature are both higher than normal value.
⑤
5. The phenomenon of the system contains air or nitrogen :
The high pressure is higher than normal value, current is larger than normal value, discharge temperature is higher than
normal value, compressor makes noise, pressure meter do not display steady.
*The normal system running parameters please refer to attached table 3.
Troubleshooting 103
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.9 P1: High pressure protection (Display on faulty unit, all the ODU in standby)
When the pressure is over 4.4MPa, the system will display P1 protection, all the ODU in standby. When the pressure is lower
than 3.2MPa, P1 disappearing and normal operation resumes.
No
The high pressure side of the system is Yes Make sure all valves are open,
①
blocked for squashed pipe, blocked check the system, and remove
valve or closed stop valve the obstacle
No
②
Yes Discharge part of the refrigerant. Add
Refrigerant is excess
some oil if it leaks during the discharge
No
③ Yes Discharge the entire refrigerant. Then
System contains air or nitrogen vacuum the system and refill the refrigerant.
Add oil to the system if it leaks.
No
Yes
MC9S08AC128 chip is
disabled
No
104 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.10 P2/H5: Low pressure protection (Display on faulty unit, all the ODU in standby)
When the pressure is lower than 0.05MPa, the system will display P2 protection, all the ODU in standby.
When the pressure is higher than 0.15MPa, P2 disappear and resumes normal operation.
H5 error will display when system appear 3 times P2 protection in 60 minutes, it cannot resume
automatically, and it can resume only by restarting the machine.
P2/H5: Low pressure protection
No
No
Yes
MC9S08AC128 chip is
disabled
No
Note:
①
1. The phenomenon of lack of refrigerant :
Top temperature and discharge temperature of all compressors are higher than normal value, discharge pressure and suction
pressure are both lower than normal value, current is lower than normal value, suction pipe may be frosting. All the
phenomenon will disappear after recharging refrigerant.
②
2. The phenomenon of the low pressure side is blocked :
The discharge temperature is higher than normal value*, low pressure is lower than normal value*, current is lower than
normal value* and suction pipe may be frosting.
*The normal system running parameters please refer to attached table 3.
*If the system install three-phase protector, and the three-phase protector connect with high pressure switch in series
connection, the system will display P1 protection when fist power on, and P1 protection will disappear after system is steady.
*If the system install three-phase protector, and the three-phase protector connect with low pressure switch in series
connection, the system will display P2 protection when fist power on, and P2 protection will disappear after system is steady.
Troubleshooting 105
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.11 P3/XP7/P8: Compressor current protection (Display on faulty unit, all the ODU in standby)
P3: Current protection of inverter compressor
When the current of inverter compressor is over12A, the system will display P3 protection, all the ODU in
standby. When the current goes back to normal range, P3 disappear and normal operation resumes.
No
The high pressure side of the system is Yes Make sure all valves are open,
②
blocked for squashed pipe, blocked check the system, and remove
valve or closed stop valve the obstacle
No
③
Yes Discharge part of the refrigerant. Add
Refrigerant is excess
some oil if it leaks during the discharge
No
④ Yes Discharge the entire refrigerant. Then
System contains air or nitrogen vacuum the system and refill the refrigerant.
Add oil to the system if it leaks.
No
High voltage short circuit or Yes Make sure the high voltage circuit is normal,
⑤
compressor error or replace the compressor
No
Yes
MC9S08AC128 chip is
disabled
No
106 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.12 P5: Condenser temperature T3 protection (Display on faulty unit, all the ODU in standby)
When condenser temperature is over 65℃, the system will display P5 protection, all the ODU in standby.
When the temperature goes back to normal range, P5 disappear and normal operation resumes.
Yes
T3 port on Main board is loose Fasten the T3 port
No
① Yes
T3 sensor is short circuit or disabled Replace the sensor
No
②
Yes Make sure the ratio of connectable
The indoor load is too large IDU is less than 130% or add ODU
No
No
The high pressure side of the system is Yes Make sure all valves are open,
③
blocked for squashed pipe, blocked check the system, and remove
valve or closed stop valve the obstacle
No
④ Yes Discharge the entire refrigerant. Then
System contains air or nitrogen vacuum the system and refill the refrigerant.
Add oil to the system if it leaks.
No
Yes
MC9S08AC128 chip is
disabled
No
Note:
①
1. How to check whether the T3 sensor is circuit or disabled :
Using a multimeter to measure resistance, if the resistance is too small, the sensor is short circuit, if the resistance in certain
temperature is not consistent with attached table 1, the sensor is disabled
②
2. The phenomenon of the indoor load is too large :
The suction temperature and discharge temperature are both higher than normal value.
③
3. The phenomenon of The high pressure side of the system is blocked :
The high pressure is higher than normal value, the low pressure is lower than normal value, and the discharge temperature is
higher than normal value.
④
4. The phenomenon of the system contains air or nitrogen :
The high pressure is higher than normal value, current is larger than normal value, discharge temperature is higher than
normal value, compressor makes noise, pressure meter do not display steady.
Troubleshooting 107
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
5.13 P6/H4: Inverter module protection (Display on faulty unit, all the ODU in standby)
If the system display three times P6 protection in 60 minutes, the system will stop and display H4 error code.
When the system displays H4 error code, the system can resume only by restarting the machine. At this time,
malfunction should be disposed promptly to avoid further damage.
108 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
DC generatrix check
1) Check the voltage of DC generatrix, the normal value should be 510 to 580V. If the value is less than
510V, go to next step.
2) Check the wiring connection of rectifier circuit, find out any loose in the circuit, and check the filter board,
single-phase rectifier stack, and three-phase rectifier stack. Note DC and AC switch in the
measurement.
3) If none of the above works, replace the PCB.
Module check
Compressor
which is took
apart from
malfunction
system.
Fig. A
Fig. B
Fig. C Fig. D
110 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
5.14.2 L1/L4 troubleshooting
Step 1: Check the DC voltage between P and N terminal, the normal value should be 510V~580V, if the
voltage is lower than 510V, go to step 2.
Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If
wires are OK, replace the PCB.
5.14.3 L2 troubleshooting
Step 1: Check the DC voltage between P and N terminal, the normal value should be 510V~580V, if the
voltage is higher than 580V, go to step 2.
Step 2: Check the voltage between two electrolytic capacitors, the normal value should be 510V±30V or
310V±30V, if not in the range then the Main board has malfunction, it needs to be replaced.
Troubleshooting 111
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
Attached table 1:
Resistance value of ambient temperature and pipe temperature sensor
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(℃) value (kΩ) (℃) value (kΩ) (℃) value (kΩ) (℃) value (kΩ)
-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5
P
62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.219 25 10 65 1.96532 105 0.54448
-14 79.311 26 9.55074 66 1.89627 106 0.52912
-13 74.536 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.486
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44 36 6.13059 76 1.34105 116 0.4006
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.2133 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.5705 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.3239
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.8795 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.2777
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.918 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231
112 Troubleshooting
MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
Attached table 2:
Resistance value of compressor discharge temperature sensor
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
(℃) value (kΩ) (℃) value (kΩ) (℃) value (kΩ) (℃) value (kΩ)
-20 542.7 20 68.66 60 13.59 100 3.702
-19 511.9 21 65.62 61 13.11 101 3.595
-18 483 22 62.73 62 12.65 102 3.492
-17 455.9 23 59.98 63 12.21 103 3.392
-16 430.5 24 57.37 64 11.79 104 3.296
-15 406.7 25 54.89 65 11.38 105 3.203
-14 384.3 26 52.53 66 10.99 106 3.113
-13 363.3 27 50.28 67 10.61 107 3.025
-12 343.6 28 48.14 68 10.25 108 2.941
-11 325.1 29 46.11 69 9.902 109 2.86
-10 307.7 30 44.17 70 9.569 110 2.781
-9 291.3 31 42.33 71 9.248 111 2.704
-8 275.9 32 40.57 72 8.94 112 2.63
-7 261.4 33 38.89 73 8.643 113 2.559
-6 247.8 34 37.3 74 8.358 114 2.489
-5 234.9 35 35.78 75 8.084 115 2.422
-4 222.8 36 34.32 76 7.82 116 2.357
-3 211.4 37 32.94 77 7.566 117 2.294
-2 200.7 38 31.62 78 7.321 118 2.233
-1 190.5 39 30.36 79 7.086 119 2.174
0 180.9 40 29.15 80 6.859 120 2.117
1 171.9 41 28 81 6.641 121 2.061
2 163.3 42 26.9 82 6.43 122 2.007
3 155.2 43 25.86 83 6.228 123 1.955
4 147.6 44 24.85 84 6.033 124 1.905
5 140.4 45 23.89 85 5.844 125 1.856
6 133.5 46 22.89 86 5.663 126 1.808
7 127.1 47 22.1 87 5.488 127 1.762
8 121 48 21.26 88 5.32 128 1.717
9 115.2 49 20.46 89 5.157 129 1.674
10 109.8 50 19.69 90 5 130 1.632
11 104.6 51 18.96 91 4.849
12 99.69 52 18.26 92 4.703
13 95.05 53 17.58 93 4.562
14 90.66 54 16.94 94 4.426
15 86.49 55 16.32 95 4.294 B(25/50)=3950K
16 82.54 56 15.73 96 4.167
17 78.79 57 15.16 97 4.045 R(90℃)=5KΩ±3%
18 75.24 58 14.62 98 3.927
19 71.86 59 14.09 99 3.812
Troubleshooting 113
R410A DC Inverter V4 Plus 50Hz MCAC-VTSM-2014-04
Attached table 3: Commissioning and operating parameters of refrigerant system
Conditions 1: Make sure outdoor unit can detect all the indoor units, the quantity of indoor units display steadily and be equal
to actual quantity of installed indoor units.
Conditions 2: Make sure all the valves in outdoor unit are open, indoor units EXV have connected to indoor PCB.
Conditions 3: The ratio of connectable indoor units is 100%. When ambient temperature is high, operate the system in
cooling mode and set the temperature 17℃. When ambient temperature is low, operate the system in heating mode and set
the temperature 30℃. Then get the parameters after system running normally more than 30 minutes.
Outdoor unit cooling parameters table
Ambient temperature (T4) ℃ 20-27 27-33 33-38 38-45
Discharge pressure (spot check) MPa 2.1-2.3 2.8-3.1 3.3-3.5 3.7-3.9
Pressure of high pressure valve MPa 1.8-2.0 2.4-2.7 2.8-3.0 3.2-3.5
Pressure of low pressure valve MPa 0.7-0.9 0.8-1.0 1.0-1.2 1.2-1.4
Discharge temperature (spot check) ℃ 50-65 70-85 70-90 80-90
DC Inverter compressor current (spot check) A 4-5 6-7 7-8 9-11
Fixed compressor current (spot check) A 6-7 8-9 9-11 11-12
Average temperature of evaporator outlet T2B ℃ 8-9 12-15 16-17 20
Outdoor unit heating parameters table
Ambient temperature (T4) ℃ -15--5 -5-5 5-12 12-18
Discharge pressure (spot check) MPa 2.0-2.2 2.2-2.7 3.0-3.1 2.6-2.7
Pressure of high pressure valve MPa 1.7-1.8 1.8-2.4 2.6-2.8 2.1-2.4
Pressure of low pressure valve MPa 2.0-2.2 2.2-2.6 3.0-3.1 2.5-2.7
Discharge temperature (spot check) ℃ 50-70 60-70 60-85 60-70
DC Inverter compressor current (spot check) A 5 5-6 6-8 5-6
Fixed compressor current (spot check) A 6 6-7 9-10 8-9
Average temperature of condenser outlet T2 ℃ 33 33-40 46-50 39-41
114 Troubleshooting