Electrical System C3.3 Generator Set: Harness and Wire Electrical Schematic Symbols
Electrical System C3.3 Generator Set: Harness and Wire Electrical Schematic Symbols
September 2021
M0132063 VOL 1 of 4
(Dimensions: 56 inches x 35 inches)
C3.3 Generator Set
Electrical System
EC31-UP
EC41-UP
EC51-UP
EC61-UP
RFF1-UP
H371-UP
RFG1-UP
42 Page,
Volume 1 of 4: 6320 Controller
PUBLICATIONS.CAT.COM
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The
circle indicates that the component has screw terminals and a wire can be disconnected from it.
Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.).
No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire. The
grounded wire is fastened to the machine.
Ground (Case): This indicates that the component does not have a wire connected to ground.
It is grounded by being fastened to the machine.
Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the
contacts of a normally open reed switch; it opens the contacts of a normally closed reed switch.
Sender: A component that is used with a temperature or pressure gauge. The sender
measures the temperature or pressure. Its resistance changes to give an indication to
T
the gauge of the temperature or pressure.
© 2021 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L
CONTROL SCHEMATIC 6320 (WITH C1.5 & C2.2 ENGINES) L CONTROL SCHEMATIC 6320 (WITH C1.1 ENGINE)
L L
FUW LC & M14 FRAME ALTS ONLY FUW LC & M14 FRAME ALTS ONLY CONTROL SCHEMATIC 6320 (WITH C3.3 ENGINES)
L L
FUW LC & M17 FRAME ALT'S
5-H5 WH-18 REF [14,F] 53-H19 WH-18 REF [16,I]
FUEL STOP SOLENOID
M0132063 VOL 1 of 4
K K H-C3
DYNO
J J VOLTAGE REGULATOR REF [7,G] 7-A24 WH-18 2 BATTERY POSITIVE
J H-C4
BL H-C5
J
1 BL1-H16 WH-16 1 BL AC IN
5-C16 WH-18 REF [14,F] MCB 2 (6A) FCR A
C-C2
2
FCR
J J
REF [10,G] 1-A26 WH-16 1-A168 WH-16 30 BL BL2-H17 WH-16 3 BL AC IN MCB 2 (6A)
2 C-C4 A-C1 REF [10,G] 1-A26 WH-16 1-A168 WH-16 30
FUEL STOP SOLENOID 10A
1 53-C8 WH-18 3 53-A3 WH-16 87 REF [13,G] 5-H18 WH-16 2 BK BATT - 5-C20 WH-18 REF [14,F] MCB 2 (16A) FCR
10A C-C13
REF [12,B] 5A-A49 WH-18 86 53-A3 WH-16 87
FUEL STOP SOLENOID REF [10,G] 1-A26 WH-16 1-A168 WH-16 30
85 +-H8 RD-8 20A 4 RD BATT + (OUT) REF [12,B] 5A-A49 WH-18 86 2 C-C11 A-C1
MCB 1 (20A) ECR 10A
85 1 53-C22 WH-18 3 53-A3 WH-16 87
I REF [10,F] I 53-H19 WH-18 YL IGN + MCB 1 (20A) ECR
1-A28 WH-16 1-A167 WH-16 30 5
3-A44 WH-18 4 OUTPUT A (POS) I REF [10,F] I REF [12,B] 5A-A49 WH-18 86
H-T3
H 19-A29 WH-18 6 CHARGE ALT O/P H
2 H GLOW PLUGS 19-A29 WH-18 6 CHARGE ALT O/P H CHARGING ALT
4-A45 WH-18 5 OUTPUT B (POS)
(CRANK)
SAR
1
A 3
1
STARTER MOTOR SAR 19
H
58A-C17 WH-12 40A 22 58-A33 WH-12 H
2
C-C1 87
86
10-A30 WH-18 7 OUTPUT C (POS)
58-A33 WH-12
87 2 19-C21 WH-18
NOT REQUIRED 19-A29 WH-18 6 CHARGE ALT O/P
86
GLOW PLUGS 10-A30 WH-18 7 OUTPUT C (POS) SAR
(PREHEAT) 1
A 3
1
PROGRAMMABLE OUTPUTS (PREHEAT) 22 58-A33 WH-12
5-A31 WH-18 PROGRAMMABLE OUTPUTS C-C12 87
86
85 (NOTE A) 5-A31 WH-18 10-A30 WH-18 7 OUTPUT C (POS)
STARTER MOTOR 1-A32 WH-12
30
8 OUTPUT D (POS) 85 (NOTE A)
2
30 (PREHEAT)
+-H13 WH-12 1 1-A32 WH-12 8 OUTPUT D (POS)
7-A161 WH-18 PROGRAMMABLE OUTPUTS
REF [11,B] 5-A31 WH-18
88-A165 WH-18 REF [9,B] 7-A161 WH-18 85 (NOTE A)
1
1 1-A41 WH-12 TERM 9 9 OUTPUT E (POS) STARTER MOTOR 30
1-A41 WH-12 TERM 9 88-A165 WH-18 9 OUTPUT E (POS) 1-A32 WH-12 8 OUTPUT D (POS)
MCB 3 (6A)
G G
+-C50 WH-12 +-C29 WH-12 1-A42 WH-16 7-A27 WH-18 TERM 10 90-A166 WH-18 10 OUTPUT F (POS)
G MCB 3 (6A)
G REF [9,B] 7-A161 WH-18
+ 1-A42 WH-16 7-A27 WH-18
1 1-A41 WH-12 TERM 9 88-A165 WH-18 9 OUTPUT E (POS)
TERM 10 90-A166 WH-18 10 OUTPUT F (POS)
BATT (+)-N1 1 RD-2 G MCB 3 (6A) G
+-C51 RD-8 TERM 12 FT-A152 WH-18 11 OUTPUT G (POS) 5-H18 WH-16 REF [15,I] +-C23 WH-12 +-C29 1 WH-12 1-A42 WH-16 7-A27 WH-18 90-A166 WH-18
TERM 12 FT-A152 WH-18 11 OUTPUT G (POS) TERM 10 10 OUTPUT F (POS)
F 30-P1 BK-2 5-C16 WH-18 REF [15,J] 7-A160 WH-18 F F F 1-A28 WH-16 REF [5,J] 7-A24 WH-18 5-A4 WH-18 REF [12,C]
42 Page,
30 16 ANALOG I/P A (OP) 30 16 ANALOG I/P A (OP) 30-C33 1 WH-18 30-C40 1 WH-18 6 30-A20 WH-18 15 ANALOG SENSOR RETURN
C-C14 C-C14
E GND 2
17 ANALOG I/P B (ET) E E GND 2
17 ANALOG I/P B (ET) E 16 ANALOG I/P A (OP)
SIGNAL 3 OP-C10 WH-18 7 OP-A8 WH-18 SA1-A2 WH-18 18 ANALOG I/P C SIGNAL 3 OP-H2 WH-18 7 OP-A8 WH-18 SA1-A2 WH-18 18 ANALOG I/P C
E 17 ANALOG I/P B (ET)
E
Vs 1 Vs 1
OP SENDER OP OP-C13 WH-18 7 OP-A8 WH-18 SA1-A2 WH-18 18 ANALOG I/P C
19 ANALOG I/P D 19 ANALOG I/P D
1 2
REF [5,D] LFL-A164 WH-18 44 INPUT C
45 INPUT D
EMERGENCY STOP
REF [5,D] LFL-A164 WH-18 44 INPUT C COLOR ABBREVIATIONS
1 2 45 INPUT D
TERM 1 46 INPUT E
1 2 45 INPUT D
ABBREVIATION DESCRIPTION
TERM 1 46 INPUT E
PROGRAMMABLE INPUTS RD
17-A95 WH-18 PROGRAMMABLE INPUTS 17-A95 WH-18
(NOTE A) 47 INPUT F
TERM 1 46 INPUT E RED
(NOTE A) 47 INPUT F 17-A95 WH-18 PROGRAMMABLE INPUTS
TERM 3
TERM 3 (NOTE A) 47 INPUT F WH WHITE
REF [11,D] LCL-A150 WH-18 48 INPUT G
LCL-A150 WH-18 48 INPUT G TERM 3
REF [5,I] 5A-A49 WH-18
REF [11,D] REF [5,I] 5A-A49 WH-18
REF [11,D] LCL-A150 WH-18 48 INPUT G OR ORANGE
49 INPUT H REF [5,I] 5A-A49 WH-18
B
49 INPUT H
B
B 5A-A51 WH-18
B B 49 INPUT H B YL YELLOW
REF [8,I] 5A-A51 WH-18 REF [8,I]
TERM 13
TERM 13 REF [8,I] 5A-A51 WH-18 PK PINK
CBL-A4:61-A1 BK-18 CBL-A3:61-A1 BK-18 23 CAN HI TERM 13
CBL-A3:61-A1 BK-18
REF [5,F] 5-A162 WH-18
CBL-A4:61-A1 BK-18 23 CAN HI REF [5,F] 5-A162 WH-18 TERM 14 CBL-A4:61-A1 BK-18 CBL-A3:61-A1 BK-18 23 CAN HI BK BLACK
TERM 14 CBL-A4:62-A2 WH-18 CBL-A3:62-A2 WH-18 24 CAN LO REF [5,F] 5-A162 WH-18 TERM 14
CBL-A4:62-A2 WH-18 CBL-A3:62-A2 WH-18 24 CAN LO
7-A161 WH-18 TERM 15 CBL-A4:62-A2 WH-18 CBL-A3:62-A2 WH-18 24 CAN LO GY GREY
TERM 15 REF [8,G]
7-A161 WH-18 CBL-A4:SCR-A3 CU-20 CBL-A3:SCR-A3 CU-20 25 CAN SCR
REF [8,G] CBL-A4:SCR-A3 CU-20 CBL-A3:SCR-A3 CU-20 25 CAN SCR REF [8,G] 7-A161 WH-18
CBL-A4:SCR-A3 CU-20
TERM 15
CBL-A3:SCR-A3 CU-20 25 CAN SCR
PU PURPLE
265-4123
26 DSE NET B BR BROWN
265-4123
26 DSE NET B
265-4123
A-C3
DSE NET (NOT USED)
(NOTE A)
(NOTE A) 27 DSE NET A DSE NET (NOT USED) GN GREEN
A-C3
27 DSE NET A
A-C3
G
D
C
A
F
J
A A
G
D
H
F
J
G
D
C
A
F
A
J
A 28 DSE NET SCR 28 DSE NET SCR
CU COPPER
SHEET 3 SHEET 4 GN-YL GREEN-YELLOW
SHEET 2
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
ABBREVIATIONS
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ABBREVIATION DESCRIPTION
AVR AUTOMATIC VOLTAGE REGULATOR
AC ALTERNATING CURRENT
POWER SCHEMATIC (3 PHASE) FUW LC FRAME ALT ONLY POWER SCHEMATIC (3 PHASE) FUW M14 & M17 FRAME ALTS ONLY POWER SCHEMATIC (60Hz SINGLE PHASE) FUW C1.1, C2.2 LC & M14 FRAME ALT ONLY AMF AUTOMATC MAINS FAIL
L PARALLEL-STAR (V608) L L L L L
CAR COMMON ALARM RELAY
STAR (6P) (V608) DC DIRECT CURRENT
ECR ENGINE CRANK RELAY
EXCITER
T7 T2
ET ENGINE TEMPERATURE
SERIES DELTA
1 PHASE 3 WIRE
T1 T8
T5
T1 T2
ETH EARTH
T10
T4 T11
EXCITER T12 T1 EXCITER FCR FUEL CONTROL RELAY
K K K K K K GRR GENERATOR RUNNING RELAY
T12 T6
T4
T5
T6
SINGLE PHASE MCB MINIATURE CIRCUIT BREAKER
T9 T4
E T9 T3 T6 T7 OP OIL PRESSURE
T3
STRIPPED 8
TERM TERMINAL
T10 E L1-UA1 BR-8 L4-K2 BK-8
T8 T5 MSR MOTOR SUPPLY RELAY
T11 T2
T3 GBCR GENERATOR BREAKER CLOSE RELAY
E STRIPPED 5 CUSTOMER LOAD
J J J J J N-NA1 BL-8 N2-K1 BK-8
CONNECTION J MBCR MAINS BREAKER CLOSE RELAY
STAR (6S) AC ALTERNATOR
GEN GENERATOR
SERIES STAR STRIPPED 8 5
L3-WA1 BR-8
STRIPPED 6
L6-K4 BK-8 POS POSITION
L1-UA3 BR-8 L5-K12 BK-8
STRIPPED 8
L1-UA1 BR-8 L5-K3 BK-8 EXCITER
STRIPPED 8 6
L2-VA3 BR-8 L6-K10 BK-8
L2-VA1 BR-8
STRIPPED 5
L6-K4 BK-8
CUSTOMER LOAD T1 T2 T3 T4
6 5 4 1 2 3 TERM 11
CUSTOMER LOAD T1
T2 CONNECTION A-C5 (NOTE B)
T1 T5
EXCITER STRIPPED 7
T6
E 102-A9 WH-18 110-A11 WH-18 31 GEN SENSING L3
T4
T8 N-NA1 BL-8 L4-K2 BK-8
6 5 4 1 2 3
TERM 11 MCB 5 (2A)
T7 T11
A-C5 (NOTE B)
6 5 4 1 2 3
TERM 11 101-A48 WH-18 101-A10 WH-18 N/C 103-A47 WH-18 109-A12 WH-18 30 GEN SENSING L2
T10 A-C2 (NOTE B) 6320 CONTROLLER
T12 E
101-A48 WH-18 101-A10 WH-18 MCB 4 (2A)
6320 CONTROLLER T3 MCB 6 (2A) 32 GEN SENSING N
CUSTOMER EARTH ETH-A90 GN-YL-16
H H H 104-A46 WH-18 108-A13 WH-18 29 GEN SENSING L1
H
H T9
T6
MCB 6 (2A) 32 GEN SENSING N H 102-A9 WH-18 110-A11 WH-18 31 GEN SENSING L3
G
R220 AVR
PANEL BODY
G G G G
FUW LC ALTERNATOR (OPTION)
C90-A23 WH-18
C50-A14 WH-18
41 CURRENT SENSING COM
39 CURRENT SENSING L3
G SIGNAL NAMES
C90-A17 WH-18 PANEL DOOR
C30-A15 WH-18 38 CURRENT SENSING L2
CONNECT TO ALTERNATOR T11 RD 0V C90-A17 WH-18 PANEL DOOR C90-A18 WH-18
C10-A16 WH-18 37 CURRENT SENSING L1 CIRCUIT ID COLOR DESCRIPTION
CONNECT TO ALTERNATOR T8 RD 110V C90-A18 WH-18 C90-A19 WH-18 C90-A23 WH-18 41 CURRENT SENSING COM
R120 AVR
RD E+ VOLTS ADJ. POT. C90-A19 WH-18 C90-A23 WH-18 41 CURRENT SENSING COM
1 WH UNFUSED BATTERY POSITIVE SUPPLY
F1 F+-AVR6 WH-18 C50-A14 WH-18 39 CURRENT SENSING L3
BK E- VOLTS ADJ. POT.1
C50-A14 WH-18 39 CURRENT SENSING L3 F2 F--AVR7 WH-18 C30-A15 WH-18 38 CURRENT SENSING L2 10 WH GLOW PLUG RELAY OUTPUT
C30-A15 WH-18 38 CURRENT SENSING L2 N N-AVR8 WH-18 C10-A16 WH-18 37 CURRENT SENSING L1
6320 CONTROLLER 101 WH GEN SENSING NEUTRAL
C10-A16 WH-18 37 CURRENT SENSING L1 U U-AVR9 WH-18
F
R121 AVR
33 MAINS SENSING L1 102 WH GEN SENSING PHASE L3 BEFORE FUSE
F F F N1
F F1 F+-AVR21 WH-16
F
V V-AVR10 WH-18 6320 CONTROLLER
F--AVR22 WH-16
MAINS SENSING 34 MAINS SENSING L2 103 WH GEN SENSING PHASE L2 BEFORE FUSE
F2 (NOT USED) 35 MAINS SENSING L3
6320 CONTROLLER CONNECT TO 'N1' FOR 6P (220/127V , 60Hz) 33 MAINS SENSING L1 N N-AVR23 WH-16 36 MAINS SENSING N
104 WH GEN SENSING PHASE L1 BEFORE FUSE
CONNECT TO 'V' FOR 6S (380/415V , 50Hz) MAINS SENSING
33 MAINS SENSING L1
(NOT USED)
34 MAINS SENSING L2
35 MAINS SENSING L3
U U-AVR24 WH-16 105 WH MOTORISED CHANGEOVER SUPPLY
MAINS SENSING 34 MAINS SENSING L2
(NOT USED) 35 MAINS SENSING L3 36 MAINS SENSING N
R2
POT
108 WH GEN SENSING L1 PHASE
R1
36 MAINS SENSING N 109 WH GEN SENSING L2 PHASE
FUW M14 ALTERNATOR FRAMES (STANDARD)
110 WH GEN SENSING L3 PHASE
E E E E E E
111 WH MOTORISED CHANGEOVER SUPPLY
115 WH AC CONTROL (-) FROM GEN SENSING
131 WH AUX SUPPLY (-)
132 WH AUX SUPPLY (+)
139 WH BATTERY CHARGER AC SUPPLY
17 WH EMERGENCY STOP
D D D D D D 19 WH CHARGING ALTERNATOR EXCITAION
22 WH GBRRELAY OUTPUT
24 WH REMOTE START
3 WH FUEL CONTROL RELAY OUTPUT
30 WH PANEL ANALOG GROUND
4 WH STARTER MOTOR RELAY OUTPUT SYMBOL LEGEND TABLE
C C C C C C 5 BK BATTERY NEGATIVE
51 WH STARTER MOTOR RELAY CONTROL MINIATURE CIRCUIT BREAKER
C90 WH CT COMMON
ET WH ENGINE TEMPERATURE SENSOR SIGNAL
ETH GN-YL EARTH/GROUND EARTH/GROUND
A A A A A A
OP WH OIL PRESSURE SENSOR SIGNAL
SA1 WH PANEL ANALOGUE INPUT
SHEET 5 SHEET 6 SHEET 7 CURRENT TRANSFORMER
61 BK CAN HI
62 WH CAN LOW
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 PANEL TERMINAL BLOCK
SCR CU CAN SCR
LCL WH LOW COOLANT LEVEL INPUT TERMINAL
LFL WH LOW FUEL LEVEL INPUT
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
CONNECTOR
POWER SCHEMATIC (50Hz SINGLE PHASE) FUW C1.1 , C1-S , C2-2 ADDITIONAL INFORMATION
POWER SCHEMATIC (50Hz SINGLE PHASE) FUW C1.1 , C1.5 , C2.2
HARNESS TABLE
+
L L L L L L BATTERY
M14 FRAME ALT ONLY 1 PHASE 2 WIRE LC FRAME ALT ONLY 1 PHASE 2 WIRE
DIN RAIL 1
WIRE
OP
OP SENSOR (RESISTIVE)
NOTE: ALTERNATOR COMES WITH ALL THE 3 CABLES BUT,
SINGLE PHASE SINGLE PHASE
L2 SHOULD NOT BE USED WITH 1PHASE 2WIRE
K COMPONENT CURRENT RATING DESCRIPTION NOTE K TEMP SENSOR (RESISTIVE)
K SYSTEM FOR CUSTOMER LOAD CONNECTION K K K
MCB 1 MCB 2 MCB 3 MCB 4 MCB 5 MCB 6 MCB 1 20A/25A ECR
MCB 2 6A/16A FCR
IDENT PART NO.
STRIPPED 8
L1-UA1 BR-8 L4-K2 BK-8
DESCRIPTION
STRIPPED 8
L1-UA1 BR-8 L4-K2 BK-8
MCB 3 6A PANEL SUPPLY DC
FUEL SENSOR (RESISTIVE)
MCB 4 2A GEN L1 SENSING
HARNESS AS - -
STRIPPED 7
L2-VA1 BR-8
STRIPPED 7
CUSTOMER LOAD MCB 5 2A GEN L2 SENSING
CUSTOMER LOAD AC ALTERNATOR MCB 6 2A GEN L3 SENSING
AC ALTERNATOR
CONNECTION CONNECTION
FUEL SOLENOID
J
L3-WA1 BR-8 STRIPPED 6
L6-K4 BK-8
J J
L3-WA1 BR-8
STRIPPED 6
L6-K4 BK-8
J J J A 614-4758 CONTROL PANEL
EXCITER
AVR2-T32
EXCITER
E2
T1 T2 T3 T4
6 5 4 1 2 3
C 433-6421 ENGINE (403-15/404-22)
T1 T2 T3 T4
6 5 4 1 2 3 TERM 11 TERM 11
A-C5
AVR2-T31
A-C5
101-A48 WH-18
(NOTE B)
101-A10 WH-18
6320 CONTROLLER E1
101-A48 WH-18
(NOTE B)
101-A10 WH-18
6320 CONTROLLER H 356-4640 ENGINE (403-11)
MCB 6 (2A)
PL -
MCB 6 (2A) 32 GEN SENSING N
I
DIN RAIL 2
I
POWER CABLES
I MCB 5 (2A) I I MCB 5 (2A) I COMPONENT WIRE ID DESCRIPTION
ETH-A90 GN-YL-16
103-A47 WH-18
MCB 4 (2A)
109-A12 WH-18 30 GEN SENSING L2 TERM 1
TERM 2
TERM 3
17
5V
5A
E-STOP N/C
5V SENDER SUPPLY
RELAY COIL COMMON
WIRE/CABLE AS -
CUSTOMER EARTH ETH-A90 GN-YL-16 MCB 4 (2A) CUSTOMER EARTH
104-A46 WH-18 108-A13 WH-18 29 GEN SENSING L1
104-A46 WH-18 108-A13 WH-18 29 GEN SENSING L1 TERM 4
TERM 5
TERM 6
7
7
17A
FUSED PANEL SUPPLY
FUSED PANEL SUPPLY
ESTOP COMMON
GND - EARTH/GROUND
PANEL BODY
PANEL BODY
CONNECT TO ALTERNATOR T1 RD
R220/R221 AVR
0V
TERM 7
TERM 8
TERM 9
5
24
88
BATTERY NEGATIVE
REMOTE START INPUT
COMMON ALARM RELAY (OPTION)
N - BATTERY NEGATIVE
CONNECT TO ALTERNATOR T2 RD 110V H TERM 10 90 GEN RUNNING RELAY (OPTION) H
H C90-A17 WH-18
C90-A18 WH-18
PANEL DOOR H H E+
E-
RD
BK
E+
E-
VOLTS ADJ. POT.
VOLTS ADJ. POT.1
C90-A17 WH-18
C90-A18 WH-18
PANEL DOOR H TERM 11
TERM 12
101
FT
GEN NEUTRAL SENSING
FUEL TRANSFER (OPTION)
P - BATTERY POSITIVE
C90-A19 WH-18 C90-A23 WH-18 41 CURRENT SENSING COM TERM 13 61 CAN HIGH (+)
C90-A19 WH-18 C90-A23 WH-18 41 CURRENT SENSING COM
TERM 14 62 CAN LOW (-)
C50-A14 WH-18 39 CURRENT SENSING L3
C50-A14 WH-18 39 CURRENT SENSING L3 TERM 15 SCR CAN SHIELD (GND)
C30-A15 WH-18 38 CURRENT SENSING L2 PANEL TERMINALS
C30-A15 WH-18 38 CURRENT SENSING L2
C10-A16 WH-18 37 CURRENT SENSING L1
C10-A16 WH-18 37 CURRENT SENSING L1
F1 F+-AVR213 WH-16
R121 AVR
F2 F--AVR214 WH-16
G G G
G N N-AVR215 WH-16 G G
U U-AVR216 WH-16
R2 6320 CONTROLLER
R1
POT 6320 CONTROLLER
33 MAINS SENSING L1
MAINS SENSING 34 MAINS SENSING L2 33 MAINS SENSING L1
(NOT USED) 35 MAINS SENSING L3 MAINS SENSING 34 MAINS SENSING L2
(NOT USED)
36 MAINS SENSING N 35 MAINS SENSING L3
36 MAINS SENSING N
F F
F F
F F WIRE GROUP COLOR DESCRIPTIONS
(+) BATTERY
STARTING CIRCUIT
(-) BATTERY / SENSOR RETURN
SENSOR / ACTUATOR SUPPLY
E E SIGNAL TO ECM
E E E E
J1939 DATA LINK
D D
D D D D
C C
C C C C
B B
B B B B
M0132063 VOL 2 of 4
(Dimensions: 48 inches x 35 inches)
C3.3 Generator Set
Electrical System
EC31-UP
EC41-UP
EC51-UP
EC61-UP
RFF1-UP
H371-UP
RFG1-UP
36 Page,
Volume 2 of 4: Control Panel Options
PUBLICATIONS.CAT.COM
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The
circle indicates that the component has screw terminals and a wire can be disconnected from it.
Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.).
No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire. The
grounded wire is fastened to the machine.
Ground (Case): This indicates that the component does not have a wire connected to ground.
It is grounded by being fastened to the machine.
Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the
contacts of a normally open reed switch; it opens the contacts of a normally closed reed switch.
Sender: A component that is used with a temperature or pressure gauge. The sender
measures the temperature or pressure. Its resistance changes to give an indication to
T
the gauge of the temperature or pressure.
© 2021 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
EARTH LEAKAGE/FAULT
L 1100 SERIES GEN-SETS WITH 6320 CONTROLLER L L L L (PPE1/PPE2) (63-80-100A MCCB) OVERLOAD VIA ALARM SWITCH ON BREAKER (PP01)
L
1100 SERIES GEN-SETS WITH 6320 CONTROLLER (LC FRAME ALT)
CONTROL PANEL OPTIONS
23-ACC2 WH-18
CONTROL PANEL OPTIONS L1 CORE BALANCE CT :95 *
6320 PIN 46
L2 SY
(PAC1) (FLSR)
N NE LINK FOR PPE2 FIT PP01
FL1/FL2 IF REQUIRED * FOR MCBs CONNECT 23 TO :96 SY CONTACT
(Dimensions: 48 inches x 35 inches)
C
EF RELAY
6320 PIN 9 88-CA8 WH-18 A1 A2 SA3-AC2 YL-18 TERM 12 FL-FL111 WH-18 6320 PIN 44 EF1-GF11 WH-18 8 CT
LOW LOW FUEL LEVEL SWITCH TERM 4
11 14 ALTERNATOR HEATER (240 V) EF2-GF12 WH-18 9 CT
12
(SHUTDOWN) REF [13,G] 7-GF20 WH-18
21 24
7-GF13 WH-18 5 +DC (10-60V) QUADRATURE DROOP KIT (AR6)
TERM 21 L
I 22 I I I I TERM 7 5-GF17 WH-18 5-GF14 WH-18
I
7 -DC QUADRATURE DROOP CT
TERM 20 N
VOLTS ADJUST (PSV1)
2
5-GF15 WH-18 13 L1
COMMON ALARM RELAY TERM 22
FOR USE WITH LS ALT
6320 PIN 45 ST-GF18 WH-18 ST-GF16 WH-18 14
AND R450/R250/R220/R221 REGULATOR L2
L3
N
H H
ST-GF19 WH-18
H H FL3 H H
TERM 21 JACKET WATER HEATER (240 V)
REGULATOR MCB7 16A
VOLTS ADJUST POT. * 134-BC9 WH-14 L
TERM 20
N
VT1
E+ VT1 WH-18 REF [12,F] 131-BC28 WH-18 ETH 5-FL212 WH-18 TERM 6 1 2
VOLT FREE CONTACTS E- VT2 TERM 19 CB SHUNT TRIP
VT2 WH-18
(PGR1)
G G G * IF NO CHARGER OPTION SELECTED (HEATER ONLY), WIRE 132 TO BE G G REF [17,I] 7-GF20 WH-18 YO G
REGULATOR
FL-FL213 WH-18 6320 PIN 49
CONNECTED TO MCB7 OTHERWISE CONNECT TO MCB6. (IF BOTH HEATERS
C1 C2
LOW FUEL LEVEL SWITCH
AND CHARGER OPTIONS ARE SELECTED MCB6 & MCB7 WILL BE LINKED)
(ALARM)
TERM 6 5-GR2 WH-18 S1 7 WH-18
VOLTS ADJUST (PSV1) E+
BATTERY CHARGER EARTH LEAKAGE/FAULT S2
FOR USE WITH LS ALT E- 8 WH-18
(PBCBT/PBCB2T) (PPE1/PPE2) (125-250-400-630A MCCB)
AND D350 REGULATOR BC-C1
MCB6 6A (LC FRAME ALT)
F 6320 PIN 10 90-GR1 WH-18 A1 A2
F F TERM 17 132-BC5 WH-14 133-BC21 WH-14 1 C1-1 F F F
12
REF [16,G] 131-BC28 WH-18
3 C1-3
TERM 16 ETH-BC23 GN-YL-16
21 24
REGULATOR L2
22 VOLTS ADJUST POT.
L3
GEN RUN RELAY 0V
E E+ 0V-AT1 WH-18 E E E E N NE LINK FOR PPE2 E
E- AI1 BC-C2
AI1-AT2 WH-18
TERM 4 7-BC24 WH-18 C2-1
1
LOW COOLANT LEVEL
NE LINK FOR PPE1
TERM 6 5-BC25 WH-18 2 C2-2 (WS1)
3 C2-3 1 2
C2-4
4
5
6
C2-5
C2-6 LOW COOLANT LC-C1 7-LC13 WH-18 TERM 4 EF RELAY
7 C2-7 LEVEL SWITCH 155-2267
D D D D D D
1
7
ST1 WH-18 2 6320 PIN 45 ST-GFM28 WH-18 ST-GFM26 WH-18 14
3
7 WH-18 OFF
ST2 3
2
5
ST2 WH-18 (RAISE)
4
ST
B B B B
CB SHUNT TRIP
REF [17,C] 7 YO
A A A A A C1 C2 A
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
TERM 10
TERM N TERM 1 L1 CORE BALANCE CT
TERM 11
TERM 12
L2
TERM 1 TERM 3
TERM 6/9 TERM 3 TERM 3
K K K L3 K
TERM 4 TERM 2
TERM 4
TERM 5/8 TERM 2 TERM 2 N
NEUTRAL/EARTH LINK
NEUTRAL/EARTH LINK NEUTRAL/EARTH LINK 1 2
J J J EF RELAY J
ST-GF19 WH-18
BAR
BAR
H
BAR
H H H
N N
E CB SHUNT TRIP
E
CUSTOMER CONNECTION
CUSTOMER CONNECTION NEUTRAL
G
N
CUSTOMER CONNECTION CUSTOMER CONNECTION
EARTH LINK G G REF [17,I] 7-GF20 WH-18 YO G
NEUTRAL/EARTH LINK
NEUTRAL/EARTH LINK NEUTRAL/EARTH LINK C1 C2
SYMBOL LEGEND TABLE
EARTH LEAKAGE/FAULT
(PPE1/PPE2) (125-250-400-630A MCCB) MINIATURE CIRCUIT BREAKER
F F F (M17/M22 FRAME ALT) F
NEUTRAL/EARTH LINK (M17 & M22 ALTERNATOR FRAME)
EMERGENCY STOP PUSHBUTTON
63A - 100A MCB L1 CORE BALANCE CT
L2
LINK
NE LINK FOR PPE2
LINK RESISTOR
NE LINK FOR PPE1
LINK
LINK LINK
LINK 1 2
LINK EARTH/GROUND
D E E D D EF RELAY D
E E CURRENT TRANSFORMER
EF1-GFM21 WH-18 8 CT
CUSTOMER CONNECTION TERM 4
EF2-GFM22 WH-18 9 CT PANEL TERMINAL
CUSTOMER CONNECTION CUSTOMER CONNECTION CUSTOMER CONNECTION
REF [13,A] 7
NEUTRAL/EARTH LINK 7-GFM23 WH-18 5 +DC (10-60V) TERMINAL
NEUTRAL/EARTH LINK NEUTRAL/EARTH LINK
NEUTRAL/EARTH LINK TERM 7 5-GFM27 WH-18 5-GFM24 WH-18 7 -DC
C C C 5-GFM25 WH-18 13 C CONNECTOR
TERM 22
6320 PIN 45 ST-GFM28 WH-18 ST-GFM26 WH-18 14
BATTERY
SPLICE
B B B
ST
B WIRE
M0132063 VOL 3 of 4
(Dimensions: 56 inches x 35 inches)
C3.3 Generator Set
Electrical System
EC31-UP
EC41-UP
EC51-UP
EC61-UP
RFF1-UP
H371-UP
RFG1-UP
42 Page,
Volume 3 of 4: 1103/1104 GE5 ENGINE
PUBLICATIONS.CAT.COM
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The
circle indicates that the component has screw terminals and a wire can be disconnected from it.
Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.).
No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire. The
grounded wire is fastened to the machine.
Ground (Case): This indicates that the component does not have a wire connected to ground.
It is grounded by being fastened to the machine.
Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the
contacts of a normally open reed switch; it opens the contacts of a normally closed reed switch.
Sender: A component that is used with a temperature or pressure gauge. The sender
measures the temperature or pressure. Its resistance changes to give an indication to
T
the gauge of the temperature or pressure.
© 2021 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1103/1104 GE5 ENGINE WIRING POWER SCHEMATIC FUW LC FRAME ALT ONLY POWER SCHEMATIC FUW M17 & M22 FRAMES ALT ONLY
L L L L L L
SERIES DELTA 400A BREAKER 125A & 160A BREAKER 400A BREAKER
125A & 160A BREAKER
K K K K K K
(Dimensions: 56 inches x 35 inches)
EXCITER T12 T1
T1 L1-UE1 T1 L1-UC1
T1 L1-UK1 T1 L1-UL1
N N-NE1 N N-NC1
4 CAN - E
N N-NK1 N N-NL1
5 CAN +
C-C5
OP SENDER 230-4013
6 CAN SHD
3P BREAKER 3P BREAKER 3P BREAKER 3P BREAKER
SIGNAL 3 SA1-C1 WH-18 SA1-C1 WH-18 9 OIL PRESS-SA1
TERM 9
VS 1 5V-C29 WH-18 5V-C29 WH-18 5V-C2 WH-18 7 5V OP SUPPLY
TERM 8
I GND 2 30-C31 WH-18 30-C30 WH-18 30-C3 WH-18 8 ANAL SENSOR GND I I I I I
200A BREAKER 250A BREAKER PARALLEL STAR 200A BREAKER 250A BREAKER
PARALLEL STAR
30-C32 WH-18
H C-C8 TERM 12
13
H H T3 T3
H H T12 T6 T3 L3-WG1 T3 L3-WF1 H
ELECTRONIC GOVERNOR T12 T6 L3-WH1 L3-WJ1
155-2252 C-C7 MAGNETIC PICKUP 2 SA3-C8 WH-18 11 SPARE ANAL I/P
155-2269 FCS
POWER INPUT + 1 53A-C41 WH-18 REF[11,D]
E T9 T3
53A-C34 WH-18 REF[11,D] E T9 T3
MPU GND 3 56-C42 WH-18 1 N N-NG1 N N-NF1
TERM 7 N N-NH1 N N-NJ1
5-C35 WH-18 5-C28 WH-18 5-C9 WH-18 15 BATT NEGATIVE
MPU + 11 57-C46 WH-18 2
REF[11,C] 5-C36 BK-8 CONNECT TO START (AUTO) 24-C10 WH-18 16 REMOTE START
THROTTLE POSITION OUTPUT 2
TERM 6 TERM 5
REF[10,F] 5-C37 WH-18
G
POWER INPUT GND
AUX INPUT 4
5
6
5-C89 WH-18 G G 3 PHASE 4 WIRE 3P BREAKER 4P BREAKER G G 3 PHASE 4 WIRE 3P BREAKER 4P BREAKER
G
63A, 80A & 100A BREAKER 63A, 80A & 100A BREAKER
5V OUTPUT 7
42 Page,
6
2
4
1
3
5
C10-C59 WH-16 6 (CURRENT SENSING L1) F1-RD
LR-C1 MCB 1 (2A)
R220/R250 REGULATOR MCB 1 (2A)
L1 4 L1 104-FL2 WH-16 4 104-C80 WH-18 108-C60 WH-18 8 (VA GEN IN)
ECR U-FB1 WH-18 4 104-C80 WH-18 108-C60 WH-18 8 (VA GEN IN)
F2-BK MCB 2 (2A)
G S
REF[9,B] 1-C25 WH-16 30 REFER TO DOOR SCHEMATIC 2-LR4 WH-16
3-LR3 WH-16
0V
110V 3 103-C81 WH-18
MCB 2 (2A)
109-C52 WH-18 9 (VB GEN IN)
L2 3 L2 103-FL1 WH-16 3 103-C81 WH-18 109-C52 WH-18 9 (VB GEN IN)
STARTER MOTOR V-FB2 WH-18 MCB 3 (2A)
5+-LR2 WH-16 E+ V ADJ POT
87A
25A FOR MATING CONNECTOR 6--LR1 WH-16 E- V ADJ POT
2 102-C82 WH-18
MCB 3 (2A)
110-C53 WH-18 10 (VC GEN IN)
L3 2 102-FL3 WH-16 2 102-C82 WH-18 110-C53 WH-18 10 (VC GEN IN)
30 REF[9,D] 87 W-FB3 WH-18 NEUTRAL TERM
C MOT BTRY 51A-C26 WH-16
86
C C NEUTRAL TERM C C N 1 N 101-FL4 WH-16 1 101-C83 WH-18 101-C51 WH-18 7 (AC NEUTRAL)
C
507-C27 WH-18 N-FB4 WH-18 1 101-C83 WH-18 101-C51 WH-18 7 (AC NEUTRAL)
FL-C1 C-C12 EARTH TERM
REF[2,G] 85 EARTH TERM FL-C3 FL-C2
4A-C231 WH-18 FB-C1 C-C12 ETH-C65 GN-YL-16 11 (EARTH TERM)
M 394-7590 ETH-C65 GN-YL-16 11 (EARTH TERM)
1-C40 RD-8
12
31 12
D350 AVR D350 AVR &
& PMG OPTION SHUNT OPTION
REF[10,G] 5-C36 BK-8 (3PHASE SENSING)
FUW LL1500 & LL3100
FUW LL1500 & LL3100
REFER TO DOOR SCHEMATIC R120 AVR REFER TO DOOR SCHEMATIC
1-C21 WH-16 REF[5,D]
FOR MATING CONNECTOR
F1
FOR MATING CONNECTOR
BATT(-)-N1 BK-2
PMG
BATT(+)-P1 RD-2
DROP CT S2
DROP CT S1
DROP CT S2
DROP CT S1
1 3
VOLTS ADJ
VOLTS ADJ
VOLTS ADJ
VOLTS ADJ
W 1 102-A3 1 WH-16 CONNECT TO MCB 3 5 5 W 1 102-A3 WH-16 CONNECT TO MCB 3 L1
1-C23 RD-8 Vout (5v) BR TERM 9 V 2 103-A2 1 WH-16 CONNECT TO MCB 2 V 2 103-A2 WH-16 CONNECT TO MCB 2 L2
U 3 104-A1 1 WH-16 CONNECT TO MCB 1 ADP-C2 ADP-C1 U 3 104-A1 WH-16 CONNECT TO MCB 1 W W
Q2 Q1 VOLTAGE SENSING V
A REF[4,H]
GND BK TERM 6 A A A A A
+ ALT 19-C5 WH-18 CONNECT V&W FOR 380-480V (3PH,6S)
GND CONNECT L1&L2 FOR 190-240V (3PH,6P) & (1PH,M)
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L
POWER SCHEMATIC FUW LC FRAME ALT ONLY L L
POWER SCHEMATIC FUW M17 & M22 FRAME ALT ONLY L
3
4
SP-C1
SP-C1
EARTH/GROUND
I I I C90-C56 WH-18 I
C91-C55 WH-18
C92-C54 WH-18
C50-C57 WH-18 TO CONTROLLER CURRENT TRANSFORMER
RAIL CURRENT RATING WIRE ID DESCRIPTION
1 C30-C58 WH-18
101-C60 WH-18 MCB 1 2A 104, 108 L1 SENSING (AC)
C10-C59 WH-18 MCB 2 2A 103, 109 L2 SENSING (AC) PANEL TERMINAL
2 102-C52 WH-18 MCB 3 2A 102, 110 L3 SENSING (AC)
TERM 101 NEUTRAL TERMINAL
3 103-C53 WH-18
TO MCBS MCB 4 10A +, 7 PANEL SUPPLY
TERMINAL
T4 L3 1 L3 101-FH1 WH-16 1 101-C60 WH-18
4 104-C51 WH-18
FROM
H H H 2 2 102-C52 WH-18 H CONNECTOR
F-C1 C-C12 ALTERNATOR TO MCBS
3 3 103-C53 WH-18
TERMINALS
T1 L1 4 L1 104-FH2 WH-16 4 104-C51 WH-18 +
BATTERY
C92-C56 WH-18 FH-C3 FH-C2 FH-C1 C-C12
C91-C55 WH-18
SPLICE
C90-C54 WH-18 TERM NO. WIRE ID DESCRIPTION
C50-C57 WH-18 TO CONTROLLER R121 AVR ETH EARTH WIRE
1 6 ECM POWER
F1 F1-RD TO EXCITER E1
C30-C58 WH-18 2 7 BATTERY POSITIVE
G G G F2 F2-BK TO EXCITER E2 G 3 7 BATTERY POSITIVE SCREEN CABLE
C10-C59 WH-18 N N 4 7A BATTERY POSITIVE (AMMETER)
U U 5 24 REMOTE START
POT R2
R1 6 5 BATTERY NEGATIVE
50
7 5 BATTERY NEGATIVE
8 30 SENSOR RETURN
9 5V 5V SENSOR SUPPLY G S
1 PHASE 3 WIRE
0V 31
Z1 Z1-TAL1 WH-18 4
X2 X2-TAL2 WH-18 1 14
X1
Z2
X1-TAL3 WH-18
Z2-TAL4 WH-18
2
3
15
16
PMG
2 1
RELAY
F1 (+) F1 TO EXCITER E1 4 3
F2 (-) F2 TO EXCITER E2
L1 L4 V
L1 L1 V VOLTAGE SENSING L1 L1 L4
L1 L1 TERMINAL/CONNECTION POINT
L2 W VOLTAGE SENSING L3 L1
E U
E E Q2 Q1 W
E
L2 L5
L2 L5
TO ALTERNATOR L2 L2 220V
TO ALTERNATOR L2 L2 220V
N
TERMINAL BOX L3 TERMINAL BOX 3 POLE BREAKER
L6 L3
L3 L3 L6
L3 L3
V
4
3
SP-C1 SP-C1
D D D D
C92-C56 WH-18
C91-C55 WH-18
C90-C54 WH-18 4 POLE BREAKER
C50-C57 WH-18 TO CONTROLLER
1 101-C60 WH-18 C30-C58 WH-18
2 C10-C59 WH-18
102-C52 WH-18
3 103-C53 WH-18
TO MCBS
C C C T4 L3 1 L3 1 101-C60 WH-18 C
4 104-C51 WH-18 FROM
2 102-FJ1 WH-16 2 102-C52 WH-18
F-C3 C-C12
ALTERNATOR TO MCBS
T2 L2 3 101-FJ3 WH-16 3 103-C53 WH-18
TERMINALS
T1 L1 4 L1 104-FJ5 WH-16 4 104-C51 WH-18
C92-C56 WH-18
C91-C55 WH-18 FJ-C3 FJ-C2 FJ-C1 C-C12
C90-C54 WH-18
A A A A
SIGNAL NAMES
CIRCUIT ID COLOR DESCRIPTION
1 WH BATTERY POSITIVE
W
V WH
WH
R120 / R121 / R180 / VOLTAGE SENSING
R180 / VOLTAGE SENSING VOLUME 3 of 4: 1103/1104 GE5 ENGINE
N WH NEUTRAL SENSING Do not operate or work on this product unless you have
X1
X2
WH
WH
SHUNT EXCITATION
SHUNT EXCITATION read and understood the instruction and warnings in the MEDIA NUMBER: M0132063
Z1 WH AREP EXCITATION relevant Operation and Maintenance Manuals and
Z2
F1
WH
RD
AREP EXCITATION
FGL ALT EXCITATION POSITIVE relevant service literature. Failure to follow the instruc- SCHEMATIC PART NUMBER: 616-0679, CHANGE: 00, VERSION: DK
F2 BK FGL ALT EXCITATION NEGATIVE tions or heed the warnings could result in injury or Components are shown installed on a fully operable generator set in a non powered state.
death. Proper care is your responsibility. Refer to the appropriate Service Manual for Troubleshooting, Specifications and Systems Operations.
Refer to the Parts Manual using a specific serial number prefix in SIS before ordering parts from this schematic.
M0132063
September 2021
M0132063 VOL 4 of 4
(Dimensions: 56 inches x 35 inches)
C3.3 Generator Set
Electrical System
EC31-UP
EC41-UP
EC51-UP
EC61-UP
RFF1-UP
H371-UP
RFG1-UP
42 Page,
Volume 4 of 4: 1103/1104 GE0 ENGINE
PUBLICATIONS.CAT.COM
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The
circle indicates that the component has screw terminals and a wire can be disconnected from it.
Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.).
No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire. The
grounded wire is fastened to the machine.
Ground (Case): This indicates that the component does not have a wire connected to ground.
It is grounded by being fastened to the machine.
Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the
contacts of a normally open reed switch; it opens the contacts of a normally closed reed switch.
Sender: A component that is used with a temperature or pressure gauge. The sender
measures the temperature or pressure. Its resistance changes to give an indication to
T
the gauge of the temperature or pressure.
© 2021 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not
be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1103 & 1104 GE0 ENGINE WIRING POWER SCHEMATIC FUW LC FRAME ALT ONLY POWER SCHEMATIC FUW M17 & M22 FRAMES ALT ONLY
L L L L L L
K K K K K K
T1 L1-UL1 T1 L1-UE1 T1 L1-UC1
T12 T1
EXCITER
T1 L1-UK1
5
C-C5 CAN +
OP SENDER 230-4013
6
CAN SHD 3P BREAKER 3P BREAKER
SIGNAL 3 SA1-C1 WH-18 SA1-C1 WH-18 9
3P BREAKER 3P BREAKER
OIL PRESS-SA1
TERM 9
VS 1 5V-C29 WH-18 5V-C29 WH-18 5V-C2 WH-18 7
5V OP SUPPLY
TERM 8
I GND 2 30-C31 WH-18 30-C30 WH-18 30-C3 WH-18 8
ANAL SENSOR GND I I I I 200A BREAKER 250A BREAKER I
PARALLEL STAR 200A BREAKER 250A BREAKER
30-C32 WH-18
PARALLEL STAR T1 L1-UG1 T1 L1-UF1
1 30-C33 WH-18
T1 L1-UH1 T1 L1-UJ1
2 SA2-C4 WH-18 SA2-C4 WH-18 10
COOL TEMP-SA2 T7 T2
155-2269 EXCITER
ET SENDER C-C6 REF[11,A] 19-C5 WH-18 14 T1 T8 T2 L2-VG1 T2 L2-VF1
CHARGE ALT T7 T2
T5 T2 L2-VH1 T2 L2-VJ1
12 T10 EXCITER T1 T8
T4 T11
T5
T3 L3-WG1 T3 L3-WF1
H TERM 12
13
H H T3 T3
H H T4
T10
T11
H
T12 T6 L3-WH1 L3-WJ1
SA3-C8 WH-18 11
SPARE ANAL I/P
FCS
T12 T6
G 1 2
G G 3 PHASE 4 WIRE 3P BREAKER 4P BREAKER G G 3 PHASE 4 WIRE 3P BREAKER 4P BREAKER G
53A-C45 WH-18 REF[11,D]
D-C2
FLPS
1
63A, 80A & 100A BREAKER 63A, 80A & 100A BREAKER
42 Page,
1 2
17D-G7 WH-18 1 2 5-C39 WH-18
REF[5,C]
17E-G8 WH-18 2 155-2269
C-C8
4A-C11 WH-18 19
CRANK
63A, 80A & 100A BREAKER 63A, 80A & 100A BREAKER
AL-T1 1
CSA T2 AL-T2 1
T1 T5
T1 T5
EXCITER N-NA1
EXCITER N-ND1 E2 E2
3
4
2
TERM 4 T8
T4 344-0415
4
5
6
1
2
3
T8
T4
22
PRE-HEAT E2 C-C7
C-C7 T7 T11
TERM 3 T7 T11
344-0415
T10 T10
53A-C201 WH-18
E TERM 2 E E T12
E E T12
E
REF[9,B] 1-C19 WH-16 7-C18 WH-16 7-C17 WH-18 23
BATT POSITIVE E1 E1
MCB 4 (10A) E1 T9
T9
T6
T6
E 234-1858
E
C-C3 C-C3
234-1858 T3
FCR T3
C92-C56 WH-16 1 (CURRENT SENSING EARTH L1)
C92-C54 WH-16 C92-C54 WH-16 1 (CURRENT SENSING EARTH L1)
AL-T3 1
REF[10,B] 1-C21 WH-16 30
BASEFRAME C91-C55 WH-16 2 (CURRENT SENSING EARTH L2)
REF[10,G] 53A-C45 WH-18 87A BASEFRAME CUSTOMER C91-C55 WH-16 C91-C55 WH-16 2 (CURRENT SENSING EARTH L2) CUSTOMER
15A GND GND
REF[10,H] 53A-C34 WH-18 53A-C22 WH-16 53A-C22 WH-16 87 GND GND C90-C56 WH-16 C90-C56 WH-16 3 (CURRENT SENSING EARTH L3)
C90-C54 WH-16 3 (CURRENT SENSING EARTH L3)
D 507-C38 WH-18 86 D D CONNECT TO T7 D D D
CONNECT TO T10 C50-C57 WH-16 4 (CURRENT SENSING L3)
85 C50-C57 WH-16 C50-C57 WH-16 4 (CURRENT SENSING L3)
51A-C26 WH-16 REF[4,C] REF[2,F] 3A-C13 WH-18
50
LSA-C1 C30-C58 WH-16 5 (CURRENT SENSING L2)
C30-C58 WH-16 C30-C58 WH-16 5 (CURRENT SENSING L2)
STD (LSA)
507-C24 WH-18 24
6
2
4
1
3
5
RELAY COIL SUPPLY C10-C59 WH-16 6 (CURRENT SENSING L1)
C10-C59 WH-16 C10-C59 WH-16 6 (CURRENT SENSING L1)
LR-C1 F1-RD MCB 1 (2A) 1
R220/R250 REGULATOR MCB 1 (2A)
L1 4 L1 104-FL2 WH-16 4 104-C80 WH-18 108-C60 WH-18 8 (VA GEN IN)
ECR U-FB1 WH-18 4 104-C80 WH-18 108-C60 WH-18 8 (VA GEN IN)
F2-BK MCB 2 (2A) 1
G S
REF[9,B] 30
REFER TO DOOR SCHEMATIC 2-LR4 WH-16 0V MCB 2 (2A)
L2 3 L2 103-FL1 WH-16 3 103-C81 WH-18 109-C52 WH-18 9 (VB GEN IN)
1-C25 WH-16 3-LR3 WH-16 110V V-FB2 WH-18 3 103-C81 WH-18 109-C52 WH-18 9 (VB GEN IN)
STARTER MOTOR 5+-LR2 WH-16 E+ V ADJ POT MCB 3 (2A) 1
87A
25A FOR MATING CONNECTOR 6--LR1 WH-16 E- V ADJ POT
2 102-C82 WH-18
MCB 3 (2A)
110-C53 WH-18 10 (VC GEN IN)
L3 2 102-FL3 WH-16 2 102-C82 WH-18 110-C53 WH-18 10 (VC GEN IN)
30 REF[9,D] 87 W-FB3 WH-18
NEUTRAL TERM
C MOT BTRY 51A-C26 WH-16
86
C C NEUTRAL TERM C C N 1 N 101-FL4 WH-16 1 101-C83 WH-18 101-C51 WH-18 7 (AC NEUTRAL)
C
507-C27 WH-18 N-FB4 WH-18 1 101-C83 WH-18 101-C51 WH-18 7 (AC NEUTRAL)
EARTH TERM
REF[2,G] 4A-C11 WH-18 85 EARTH TERM FL-C3 FL-C2 FL-C1 C-C9
FB-C1 C-C9 ETH-C65 GN-YL-16 11 (EARTH TERM)
M 394-7590 ETH-C65 GN-YL-16 11 (EARTH TERM)
1-C40 RD-8
12
31 12
D350 AVR &
D350 AVR SHUNT OPTION
REF[10,G] 5-C36 BK-8 & PMG OPTION (3PHASE SENSING)
FUW LL1500 & LL3100 FUW LL1500 & LL3100
REFER TO DOOR SCHEMATIC R120 AVR REFER TO DOOR SCHEMATIC
REF[5,D]
1-C21 WH-16
FOR MATING CONNECTOR
F1
FOR MATING CONNECTOR
BATT(-)-N1 BK-2
PMG
BATT(+)-P1 RD-2
B 1-C19 WH-16 REF[5,E] B B 362-0122 B B N N-BL R180 AVR & PMG OPTION B
H-C3 J-C1 ADP-C2 ADP-C1
REQUIRED FOR MECH ENGINES ONLY - 5V SUPPLY FOR OIL PRESSURE SENSOR U U-YL
J-C1
USED FOR CONTROL PANEL WITHOUT 5V OUTPUT D350 Z1 1 4 D350 Z1 1 5 N1 R180 AVR 351-6707
X2 2 14-H2 WH-18 1 14 X2 2 2-ADP 1
X1 3 15-H3 WH-18 2 15 X1 4 3-ADP 4 Z1 Z1-TAL1 WH-18 4
DC VOLTAGE REGULATOR FREQ ADJ Z2 4 16-H4 WH-18 3 16 FREQ ADJ Z2 5 3 CONNECT TO LSA-C1 V V-GR X2-TAL2 WH-18 1 14
+
FREQ ADJ F-
F+
5
6
H-C1 FREQ ADJ F-
F+
3
6
(6-)-ADP
(5+)-ADP
6
2
REF D18
X2
X1
Z2
X1-TAL3 WH-18
Z2-TAL4 WH-18
2
3
15
16
PMG
Vin (6.5v - 30v) RD TERM 4 3 (6-)-ADP 6
6--H5 WH-18
5+-H6 WH-18 6 (5+)-ADP 2 CONNECT TO LSA-C1 CONNECT TO 'N1' FOR 6P (220/127V, 60Hz)
F1 (+) F1 TO EXCITER E1
Vout (5v) 1 2-ADP 1 CONNECT TO 'V' FOR 6S (380/415V, 60Hz) TO EXCITER E2
BATTERY BR TERM 9 LS-C1 4 3-ADP 4
F2 (-) F2
REF D18 LS-C1 V VOLTAGE SENSING U
V
DROP CT S2
DROP CT S1
DROP CT S2
DROP CT S1
2 3
VOLTS ADJ
VOLTS ADJ
VOLTS ADJ
VOLTS ADJ
GND W 1 102-A6 WH-16 CONNECT TO MCB 3 5 5 W 1 102-A3 WH-16 CONNECT TO MCB 3 L1
+-C23 RD-8 BK TERM 6 V 2 103-A5 WH-16 CONNECT TO MCB 2 V 2 103-A2 WH-16 CONNECT TO MCB 2 L2
U 3 104-A4 WH-16 CONNECT TO MCB 1 ADP-C2 ADP-C1 U 3 104-A1 WH-16 CONNECT TO MCB 1 W W
Q2 Q1 VOLTAGE SENSING V
A REF[4,H]
A A FOR 1PHASE VOLTAGE SENSING, WITH PMG OPTION CONNECT WIRE 104 TO MCB 1, A A A
+ ALT 19-C5 WH-18 CONNECT V&W FOR 380-480V (3PH,6S)
WIRE 102 TO MCB 2 AND WIRE 103 TO BE TIED BACK.
GND CONNECT L1&L2 FOR 190-240V (3PH,6P) & (1PH,M)
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
POWER SCHEMATIC FUW LC FRAME ALT ONLY POWER SCHEMATIC FUW M17 & M22 FRAME ALT ONLY
L L
L L
K 1 PHASE 2 WIRE K
K
1 PHASE 2 WIRE K
125A, 200A, 250A, 400A & 630A BREAKER 125A, 200A, 250A, 400A & 630A BREAKER
ADDITIONAL INFORMATION
L1 L4
L1 L1
U
L1
L1 L4 CUSTOMER DIN RAIL INFORMATION
L1
J TO ALTERNATOR
L5
220V J NOTE: ALTERNATOR COMES WITH ALL THE 3 CABLES BUT,
J J
L2 SHOULD NOT BE USED WITH 1PHASE 2WIRE
TERMINAL BOX V
TO ALTERNATOR L2 220V
SYSTEM FOR CUSTOMER LOAD CONNECTION
L3 L6
L3 L3
N
TERMINAL BOX L3 L6
L3 L3
4
SP-C1
3
SP-C1
I I
I I
C90-C56 WH-18
C91-C55 WH-18
C92-C54 WH-18
101-C60 WH-18
1 C50-C57 WH-18 TO CONTROLLER
2 102-C52 WH-18 C30-C58 WH-18
TO MCBS C10-C59 WH-18
3 103-C53 WH-18 RAIL CURRENT RATING WIRE ID DESCRIPTION
MCB 1 2A 104, 108 L1 SENSING (AC)
4 104-C51 WH-18 MCB 2 2A 103, 109 L2 SENSING (AC)
1 1
H H T4 L3 L3 101-FH1 WH-16 101-C60 WH-18 MCB 3 2A 102, 110 L3 SENSING (AC)
F-C2 C-C9
H FROM H TERM 101 NEUTRAL TERMINAL
2 2 102-C52 WH-18 MCB 4 10A +, 7 PANEL SUPPLY
ALTERNATOR TO MCBS
3 3 103-C53 WH-18
C92-C56 WH-18
TERMINALS
T1 L1 4 L1 104-FH2 WH-16 4 104-C51 WH-18
C91-C55 WH-18
F 1 PHASE 3 WIRE F
F F
10
11
12
SA1
SA2
SA3
SPARE ANALOG INPUT 1
SPARE ANALOG INPUT 2
SPARE ANALOG INPUT 3
125A, 160A, 200A, 250A & 630A BREAKER R180 AVR & PMG OPTION
J-C2
1 PHASE 3 WIRE
R180 AVR 351-6707 125A, 160A, 200A, 250A & 630A BREAKER
Z1 Z1-TAL1 WH-18 4
X2-TAL2 WH-18 1 14
X2
X1
Z2
X1-TAL3 WH-18
Z2-TAL4 WH-18
2
3
15
16
PMG
L1 L4 F1 (+) F1 TO EXCITER E1
L1 F2 (-) F2 TO EXCITER E2
L1 V
V VOLTAGE SENSING L1 L1 L4
E U E L1
L1 L1
L2
E Q2 Q1
L2
W
W VOLTAGE SENSING L3 E
TO ALTERNATOR L2 L2 220V
N L2 L5
TERMINAL BOX TO ALTERNATOR L2 L2 220V
L3 L6
L3 L3 TERMINAL BOX L3
V L6
L3 L3 SYMBOL LEGEND TABLE
4
3
D SP-C1 D
EMERGENCY STOP PUSHBUTTON
C90-C56 WH-18
C91-C55 WH-18
C92-C54 WH-18
1 FUSED AUTOMOTIVE RELAY
101-C60 WH-18 C50-C57 WH-18 TO CONTROLLER
2 102-C52 WH-18 C30-C58 WH-18
3
TO MCBS C10-C59 WH-18
103-C53 WH-18
C C RESISTOR
4 104-C51 WH-18 C 1 1
C
T4 L3 L3 101-C60 WH-18
F-C4 C-C9 FROM
2 102-FJ1 WH-16 2 102-C52 WH-18
EARTH/GROUND
ALTERNATOR TO MCBS
T2 L2 3 101-FJ3 WH-16 3 103-C53 WH-18
C92-C56 WH-18 TERMINALS
T1 L1 4 L1 104-FJ5 WH-16 4 104-C51 WH-18
C91-C55 WH-18
FJ-C3 FJ-C2 C-C9
SIGNAL NAMES CURRENT TRANSFORMER
FJ-C1
C90-C54 WH-18 CIRCUIT ID COLOR DESCRIPTION
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 3A WH FUEL/RUN/STOP
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 3D WH FUEL/RUN/STOP
4 WH CRANK NEGATIVE (ECM)
G S
4A WH CRANK POSITIVE (ECM)
STARTER MOTOR
5 WH PANEL DC NEGATIVE
30
5+ WH ALT EXCITATION POSITIVE MOT BTRY
5V WH 5V SENSOR SUPPLY
6- WH ALT EXCITATION NEGATIVE
61 WH CAN1 (+)
62 WH CAN1 (+) + ALT COLOUR ABBREVIATIONS
6A WH ECM POWER GND CHARGING ALTERNATOR
ABBREVIATION DESCRIPTION
6C
7
WH
WH
ECM POWER
FUSED PANEL POSITIVE
BK
CU
BLACK
COPPER
HARNESS TABLE
BATT (+) RD BATTERY POSITIVE GN-YL GREEN-YELLOW IDENT PART NO. CGH DESCRIPTION
BATT(-) BK BATTERY NEGATIVE 2 1 RD RED
RELAY HARNESS AS - - -
C10 WH CT PHASE L1 WH WHITE
4 3 ADP 482-1687 - D340/R450 ADAPTOR
C30 WH CT PHASE L2 BR BROWN C 557-9649 - ENGINE
C50 WH CT PHASE L3 GR GREEN D 345-1116 - LINK E-STOP
C90 WH CT COMMON L1
TERMINAL/CONNECTION POINT BL BLUE FB NA - VOLTAGE SENSING (LEORY SOMER)
C91 WH CT COMMON L2 YL YELLOW A 480-1626 - VOLTAGE SENSING ( LL PMG D350/R450)
C92 WH CT COMMON L3
G 345-1117 - CANOPY E-STOP
ETH GN-YL EARTH/GROUND
H 362-0449 - AVR (D350/R450 PMG)
ET WH ENGINE TEMPERATURE
LR NA - AVR (R250)
F+ WH EXCITER FIELD NEGATIVE
LSA NA - AVR CONNECTOR (SUPPLIED)
F- WH EXCITER FIELD POSITIVE
3 POLE BREAKER N AS SUPPLIED BATTERY -
GND WH EARTH/GROUND
P AS SUPPLIED BATTERY +
L1 BK PHASE L1
TAL 591-1583 R180 TO PMG HARNESS
L2 BK PHASE L2
L3 BK PHASE L3 ABBREVIATIONS FL
FH
600-9118
600-9123
HARNESS ASM FOR 3PH - 4W FGL ALTERNATOR
HARNESS ASM FOR 1PH - 2W FGL ALTERNATOR
N BK NEUTRAL POWER CABLE
ABBREVIATION DESCRIPTION FJ 600-9126 HARNESS ASM FOR 1PH - 3W FGL ALTERNATOR
OP WH OIL PRESSURE
SA1 WH SPARE ANALOGUE INPUT 1 AC ALTERNATING CURRENT
SA2 WH SPARE ANALOGUE INPUT 2 AVR AUTOMATIC VOLTAGE REGULATOR
SA3 WH SPARE ANALOGUE INPUT 3 CHARGE ALT CHARGING ALTERNATOR
SCR CU CAN1 (SHIELD) CSA COLD START ADVANCE
ST1 WH RAISE SPEED DC DIRECT CURRENT
ST2 WH LOWER SPEED DIN EMCP DIGITAL INPUT
U WH R120 / R121 / VOLTAGE SENSING E-STOP EMERGENCY STOP PUSHBUTTON
V WH R120 / R121 / R180 / VOLTAGE SENSING ECR ENGINE CRANK RELAY
W WH R180 / VOLTAGE SENSING
4 POLE BREAKER ETH EARTH
N WH NEUTRAL SENSING FCS FUEL CONTROL SOLENOID
X1 WH SHUNT EXCITATION FLPS FUEL LIFT PUMP
X2 WH SHUNT EXCITATION MCB MINIATURE CIRCUIT BREAKER
Z1 WH AREP EXCITATION MPU MAGNETIC PICKUP
Z2 WH AREP EXCITATION OP OIL PRESSURE SENDER
F1 RD FGL ALT EXCITATION POSITIVE PMG PERMANENT MAGNET GENERATOR
F2 BK FGL ALT EXCITATION NEGATIVE TERM PANEL TERMINAL
WIRE GROUP COLOR DESCRIPTIONS THIS SCHEMATIC IS FOR THE C3.3 GENERATOR SET ELECTRICAL SYSTEM
(+) BATTERY Do not operate or work on this product unless you have VOLUME 4 of 4: 1103/1104 GE0 ENGINE
STARTING CIRCUIT read and understood the instruction and warnings in the
(-) BATTERY / SENSOR RETURN relevant Operation and Maintenance Manuals and MEDIA NUMBER: M0132063
SENSOR / ACTUATOR SUPPLY relevant service literature. Failure to follow the instruc-
SIGNAL TO ECM tions or heed the warnings could result in injury or SCHEMATIC PART NUMBER: 616-0680, CHANGE: 00, VERSION: DK
death. Proper care is your responsibility. Components are shown installed on a fully operable generator set in a non powered state.
Refer to the appropriate Service Manual for Troubleshooting, Specifications and Systems Operations.
Refer to the Parts Manual using a specific serial number prefix in SIS before ordering parts from this schematic.