PCS 915SC
PCS 915SC
PCS-915SC Centralized Busbar Relay • Voltage blocking is an option for the current differential
protection and breaker failure protection, which will improve
the reliability of current differential protection and breaker
failure protection.
PCS-915SC centralized busbar relay integrates busbar differential • Selectable IEC, ANSI inverse-time characteristic curves, also
protection, bus coupler/section protection (includes overcurrent the curve can be defined by users and the inverse-time dropoff
protection, switch-onto-fault protection, dead zone fault protection curve selection is supported.
and breaker failure protection) and feeder protection (includes
With the disconnector position status monitor and memory
overcurrent protection, dead zone fault protection and breaker
function, the device can check the rationality of the memorized
failure protection). With its flexibility and the powerful PCS-Studio
disconnector position status and automatically correct the
configuration tool, PCS-915SC offers future-oriented busbar
error.
solutions with high investment security and low operating costs.
• Users can disable the discrimination zone differential element
by the external binary input during the busbar maintenance.
Also the bay can be disabled by the external binary input when
it is in maintenance.
Functions
Protection and Control
• Busbar current differential protection (87B)
Features It consists of phase current differential protection and DPFC
differential protection. Voltage control element and CT
• Applicable for single busbar, single bus with bus section,
saturation blocking element are available to supervise the
double busbar, double busbar with bus section, etc. busbar
current differential protection.
arrangement, and the busbar differential protection can
connect up to 4 busbars and 32 bays.
° DPFC differential protection
• Comprehensive functionality including phase segregated DPFC differential protection is sensitive to high resistance
current differential protection, breaker failure protection, fault and is immune to load fluctuations.
overcurrent protection and dead zone protection, etc.
° Voltage control element
• The phase segregated differential protection adopts both of
The used voltage can be phase voltage, zero sequence
deviation of power frequency component (DPFC) and
voltage or negative sequence voltage.
steady-state component, that can guarantees fast and reliable
performance during CT saturation. It can ensure no
° Detection of CT saturation
mal-operation of external fault and fast operation of internal
Two principles for CT saturation detection are provided:
fault in the case of the correct transfer time of CT is no less
patented adaptive weighted anti-saturation algorithm and
than 3ms.
harmonic algorithm. It keeps the current differential
• With patented adaptive-weight anti-saturation algorithm and protection stable to external faults and quickly clears internal
harmonic restrain algorithm, the DPFC differential protection faults and external-to-internal evolving faults during CT
operates fast and not affected by load current, the typical saturation.
operation time is within 15ms.
79
www.nrec.com/en
Specifications
Electrical Specifications
AC Current Input
Linear to 0.1A~200A
Thermal withstand
-continuously 20A
-for 10s 150A
-for 1s 500A
-for half a cycle 1250A
AC Voltage Input
Linear to 1V~300V
Power Supply
Burden
Quiescent condition <20W
Operating condition <40W
DC Analog Input
86
PCS S Series
0.5A@48Vdc L/R=40ms
0.35A@110Vdc L/R=40ms
Breaking capacity
0.30A@125Vdc L/R=40ms
(10000 operations)
0.20A@220Vdc L/R=40ms
0.15A@250Vdc L/R=40ms
0.5A@48Vdc L/R=40ms
0.35A@110Vdc L/R=40ms
Cyclic capacity
0.30A@125Vdc L/R=40ms
(2.5 cycle/second)
0.20A@220Vdc L/R=40ms
0.15A@250Vdc L/R=40ms
30A@3s
Short duration current
50A@1s
10A@48V L/R=40ms
Breaking capacity 10A@110V L/R=40ms
(10000 operations) 10A@125V L/R=40ms
10A@250V L/R=20ms
Cyclic capacity (4cycles in 10A@48V L/R=40ms
1 second, 10A@110V L/R=40ms
followed by 2 minutes idle 10A@125V L/R=40ms
for thermal dissipation) 10A@250V L/R=20ms
30A@3s
Short duration current
50A@1s
87
www.nrec.com/en
Mechanical Specifications
Protection Class
Standard IEC 60529-2013
Operating temperature -40°C to +80°C (Readability of display may be impaired below -20°C or above 70°C)
Pollution degree II
Altitude <3000m
Communication Port
EIA-485 Port
Max. capacity 32
88
PCS S Series
Connector type LC
Connector type LC
Connector type ST
Print Port
Type RS-232
89
www.nrec.com/en
Type Tests
Environmental Tests
Mechanical Tests
Electrical Tests
Electromagnetic Compatibility
IEC 60255-26:2013
IEC 61000-4-2-2008
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
IEC 60255-26:2013
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 5kHz, 5/50ns
IEC 60255-26:2013
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
IEC 60255-26:2013
Conducted RF electromagnetic disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Spot frequency
10V/m (rms), f=27MHz/68MHz
IEC 61000-4-8:2009
Power frequency magnetic field immunity
Class V, 100A/m for 1min, 1000A/m for 3s
90
PCS S Series
IEC 61000-4-9:2016
Pulse magnetic field immunity
Class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2016
Damped oscillatory magnetic field immunity
Class V, 100kHz & 1MHz–100A/m
IEC 60255-26:2013
Conducted emission 0.15MHz ~ 0.50MHz: 79dB(μV) quasi peak, 66dB(μV) average
0.50MHz ~ 30MHz: 73dB(μV) quasi peak, 60dB(μV) average
IEC 60255-26:2013
Below 30MHz ~ 230MHz: 40dB(μV/m) quasi peak @10m, 50dB(μV/m) quasi peak @3m
Radiated emission 1GHz 230MHz ~ 1000MHz: 47dB(μV/m) quasi peak @10m, 57dB(μV/m) quasi peak @3m
Voltage dips Up to 200ms for dips to 40% of rated voltage without reset
Auxiliary power supply performance 50ms for interruption without rebooting without energy
storage board (Typical application)
Voltage short interruptions
500ms for interruption without rebooting with energy
storage board (Typical application)
Terminals
Management Function
Clock Performance
91
www.nrec.com/en
Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded duration
92