5 15kv 27kv VCP W Instruction Booklet Ib131006en
5 15kv 27kv VCP W Instruction Booklet Ib131006en
5 15kv 27kv VCP W Instruction Booklet Ib131006en
WARNING
THE CIRCUIT BREAKER ELEMENTS DESCRIBED IN THIS BOOK ARE
DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE
RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE
EQUIPMENT TO FAIL, RESULTING IN DEATH, SERIOUS PERSONAL INJURY,
AND PROPERTY DAMAGE.
2 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Contents
Description Page
1. Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Preliminary comments and safety pre-cautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Warranty and liability information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Safety precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Type VCP-W vacuum circuit breaker element ratings (Tables 1, 2, 3, 4, 5, and 6). . . . . . . . . . . . . . . . 7
1.4 Outlines and dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2. Safe practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1 Recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3. Receiving, handling, and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Receiving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.4 Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.5 Floor requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.6 Shipping breakers in switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.7 Tools and accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.8 Type VCP-W vacuum circuit breaker element weights (Tables 20, 21, and 22). . . . . . . . . . . . . . . . . 23
4. Initial inspection and installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2 Manual operation check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3 Vacuum interrupter integrity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.4 Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5 Contact erosion and wipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.6 Primary circuit resistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.7 Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.8 Electrical operation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.8.1 Circuit breaker insertion and removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.8.2 Circuit breaker performance check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.9 Circuit breaker/structure interfacing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.9.1 Interface interlocks/interfacing check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5. Description and operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Interrupter assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2.1 Vacuum interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.2 Contact erosion indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.3 Loading spring indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.4 Contact wipe and stroke. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.5 Phase barriers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3 Stored energy mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.3.1 Operation of stored energy mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.3.2 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.3 Closing operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.4 Tripping operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3.5 Trip free operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.4 Control schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.4.1 Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4.2 Secondary disconnects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4.3 Shunt trip device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4.4 Under-voltage trip device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.5 Interlocks and interfacing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.6 Levering mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.7 Operations counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.8 Ground contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.9 MOC and TOC switch operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
EATON www.eaton.com 3
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
6. Inspection, maintenance, and troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.2 Frequency of inspection and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.2.1 Qualified personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.2.2 General torque guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.3 Inspection and maintenance procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.4 Vacuum interrupter integrity test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.5 Contact erosion and wipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.6 Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.7 Insulation integrity check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.8 Primary circuit resistance check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.9 Mechanism check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.9.1 CloSure™ test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.10 Megger and power factor testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.11 Mechanism lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.12 Finger clusters and switchgear stab lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.13 Main contacts to switchgear primary engagement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.14 How to determine the manufacturing date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.15 Troubleshooting chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.16 End of life procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.17 Failure reporting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7. Renewal parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.1.1 Ordering instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8. Optional accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.1 Optional factory installed roll-on-floor wheel kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.2 Optional automatic/manual hybrid secondary for BPI pan assembly . . . . . . . . . . . . . . . . . . . . . . . . 72
8.3 Optional 3,000 A ball screw drive for BPI pan assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
List of figures
Figure Title Page
Figure 1. Type VCP-W (K = 1 & MVA), VCPW-SE, and VCP-WC circuit breaker outlines
and dimensions in inches (mm).. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 2. Type VCPW-ND circuit breaker outlines and dimensions in inches (mm).. . . . . . . . . . . . . . . . . . 12
Figure 3. Typical VCP-W tools and accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 4. Typical front view VCP-W vacuum circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 5. Typical VCP-W vacuum circuit breaker element with front cover removed.. . . . . . . . . . . . . . . . . 27
Figure 6. Typical rear view VCP-W vacuum circuit breaker element.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 7. Typical VCP-W vacuum circuit breaker front cover arrangement.. . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 8. Type VCP-W circuit breaker manual charging handle in use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 9. Insertion of the drawout extension rails.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 10. Lifting and setting the breaker in the housing.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 11. Front panel.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 12. BPI pan assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 13. Non-BPI pan assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 14. Engaging extension rails in a lower circuit breaker compartment. . . . . . . . . . . . . . . . . . . . . . . 36
Figure 15. Typical VCP-W circuit breaker bottom view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 16. Pulling secondary disconnect cage to engage secondaries in TEST position.. . . . . . . . . . . . . . 37
Figure 17. Engaging levering-in crank.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 18. Typical VCP-W rear view showing vacuum interrupters and current carrying system.. . . . . . . . 38
Figure 19. Graphic representation of arc interruption. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 20. Closing cam and trip linkage.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 21. Charging schematic.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 22. Typical VCP-W DC and AC control schemes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 23. 15 kV VCP-WXC 63 kA 1200-3000 A special power plant breakers . . . . . . . . . . . . . . . . . . . . . 45
Figure 23. 5 kV VCP-WXC 63 kA 1200-3000 A special power plant breakers.. . . . . . . . . . . . . . . . . . . . . . 46
Figure 24. 15 kV under-voltage trip device configuration.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 25. Lubrication points.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 26. 50 VCP-W 63 - 63 kA pole unit.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Figure 27. Vacuum interrupter showing contact erosion indicator with breaker open. . . . . . . . . . . . . . . . 54
Figure 28. Vacuum interrupter showing contact erosion indicator with breaker closed. . . . . . . . . . . . . . . 54
Figure 29. Wipe indication procedure.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 30. Starting tape at the bottom of the cam. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 31. Wrapping tape up around the cam. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 32. Attaching tape around to the back of the cam.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 33. Attaching CloSure test tool at hole “A”.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 34. Attaching CloSure test tool at “B”.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 35. Manually charging the closing springs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 36. Manually closing the circuit breaker with the marker in hole “C”.. . . . . . . . . . . . . . . . . . . . . . . 57
Figure 37. Top view of the cam and marker interface.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 38. Move marker 15° to the right.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 39. Move marker 15° to the left. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 40. Remove marked masking tape from the cam.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 41. Place the tape on the right side panel of the breaker.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 42. Illustrative testing tape sample.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 43. Front view of closure tool showing mounting/testing locations (6352C49H01).. . . . . . . . . . . . 58
Figure 44. Typical circuit breaker front view with CloSure tool attached.. . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 45. Roll-on-floor wheel kit (shown installed on a standard 5/15 kV VCP-W breaker). . . . . . . . . . . . 72
Figure 46. Optional automatic/manual secondary for BPI pan assembly.. . . . . . . . . . . . . . . . . . . . . . . . . . 73
List of tables
Table Title Page
Table 1. (ANSI Standardsa) type VCP-W vacuum circuit breaker through 15 kV
rated symmetrical current basis.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 2. (ANSI Standardsa) type VCP-W vacuum circuit breaker 27 kV rated symmetrical current basis..8
Table 3. (ANSI Standards) type VCP-WC extra capability vacuum circuit breaker 5-27 kV
rated symmetrical current basis.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 4. (IEC-56 Standardsa) type VCP-W vacuum circuit breaker through 17.5 kV
rated symmetrical current basis.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 5. (ANSI Standardsa) type VCP-W (K = 1) vacuum circuit breaker through 15 kV
rated symmetrical current basis (standard ratings). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 6. (ANSI Standardsa) type VCP-WXC circuit breaker through 15 kV
rated symmetrical current basis (standard ratings). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 7. Accessories for 36-inch wide breaker compartments for 29-inch frame breaker. . . . . . . . . . . . 16
Table 8. Narrow design accessories for 26-inch-wide breaker compartments. . . . . . . . . . . . . . . . . . . . . 17
Table 9. 27 kV VCP-W accessories.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 10. Simple manual ground and test devices—bus bar type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 11. 15 kV VCP-W simple manual ground and test device—“bail” and “ball” type a .. . . . . . . . . . . 19
Table 12. Complex manual (selectable) ground and test device.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 13. Simple electrically operated ground and test device.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 14. Simple electrically operated ground and test device for VCP-W without key interlocks. . . . . . . 21
Table 15. Simple electrically operated ground and test device for VCP-WXC.. . . . . . . . . . . . . . . . . . . . . . 21
Table 16. VCP-W CEG&TD 1200/2000/3000 A - product code: 6078R.. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 17. VCP-W CEG&TD assessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 18. 27 kV manual ground and test device.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 19. Dummy elementsa. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 20. VCP-W ANSI rated breaker weightsa.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 21. VCP-W IEC rated breaker weightsa.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 22. VCP-W (K = 1) breaker weightsa.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 23. VCP-W & VCP-WC circuit breaker barrier configurations.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 24. Circuit breaker timing.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 25. Torque guidelines.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 26. Test voltage (insulation and vacuum integrity).. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 27. Typical resistance measurements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 28. Closure tool mounting/testing locations by circuit breaker type.. . . . . . . . . . . . . . . . . . . . . . . . 59
Table 29. Recommended renewal parts for ANSI rated breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 30. Recommended renewal parts for IEC rated breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
EATON www.eaton.com 5
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
1. Introduction 1.2 General information
1.1 Preliminary comments and safety pre-cautions The purpose of this book is to provide instructions for unpack-
ing, storage, use, operation, and maintenance of Type VCP-W,
This technical document is intended to cover most aspects associ- VCPW-SE, VCP-WC, and VCPW-ND vacuum circuit breakers. These
ated with the installation, operation, and maintenance of Type circuit breakers are horizontal drawout type removable interrupting
VCP-W, VCPW-SE, VCP-WC,and VCPWND vacuum circuit breakers. elements designed for use in VacClad-W Metal-Clad switchgear
It is provided as a guide for authorized and qualified personnel only. and appropriate VCP-W modules. They provide reliable control and
Please refer to the specific WARNING and CAUTION in Paragraph protection for medium voltage electrical equipment and circuits. All
1.1.2 before proceeding past Section 1. If further information is VCP-W circuit breaker elements are designed to ANSI Standards for
required by the purchaser regarding a particular installation, applica- reliable performance, ease of handling, and simplified maintenance.
tion, or maintenance activity, an Eaton representative should be In addition, some VCP-W circuit breakers have been tested in accor-
contacted. dance with IEC Standards for applications around the world.
1.1.1 Warranty and liability information The VCPW-SE circuit breaker element is a VCP-W circuit breaker
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES designed specifically for special environment applications and operat-
OF FITNESS FOR A PARTICULAR PURPOSE OF MERCHANTABILITY, OR ing conditions through 27 kV. The VCPW-ND circuit breaker element
WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, is a narrow design VCP-W circuit breaker designed specifically for
ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS use in 5 kV applications where floor space requirements would
AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be not allow the industry standard 36 in. (914.4 mm) wide switchgear.
responsible to the purchaser or user in contract, in tort (including From this point on, all circuit breaker elements will be referred to as
negligence), strict liability or otherwise for any special, indirect, inci- Type VCP-W unless the reference is specific to a particular design.
dental, or consequential damage or loss whatsoever, including but The VCP-WC circuit breaker element is a VCP-W circuit breaker
not limited to damage or loss of use of equipment, plant or power designed and tested for extra capabilities beyond one or more of the
system, cost of capital, loss of power, additional expenses in the preferred ratings of the applicable ANSI Standard.
use of existing power facilities, or claims against the purchaser or
user by its customers resulting from the use of the information and WARNING
descriptions contained herein.
SATISFACTORY PERFORMANCE OF THESE BREAKERS IS CONTINGENT
1.1.2 Safety precautions UPON PROPER APPLICATION, CORRECT INSTALLATION, AND ADEQUATE
All safety codes, safety standards, and/or regulations must be MAINTENANCE. THIS INSTRUCTION BOOK MUST BE CAREFULLY READ
strictly observed in the installation, operation, and maintenance of AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR
this device. LONG USEFUL LIFE OF THE CIRCUIT BREAKER ELEMENTS.
WARNING WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE THE CIRCUIT BREAKERS DESCRIBED IN THIS BOOK ARE DESIGNED AND
PROCEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS. OPERATION
AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL,
TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO FAMILIARIZE RESULTING IN DEATH, BODILY INJURY, AND PROPERTY DAMAGE.
PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO
INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY
APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, CAUTIONS ARE
ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW.
CAUTION
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN
THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION,
OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED
PERSONS SHOULD BE PERMITTED TO PERFORM ANY WORK ASSOCIATED
WITH THE EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS
DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO COULD
CAUSE PERMANENT EQUIPMENT DAMAGE.
6 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
1.3 Type VCP-W vacuum circuit breaker element ratings (Tables 1, 2, 3, 4, 5, and 6)
Table 1. (ANSI Standardsa) type VCP-W vacuum circuit breaker through 15 kV rated symmetrical current basis.
Identification Rated values
Circuit Nominal Nominal Voltage Insulation level Current Inter- Permis- Max. Current values
breaker voltage 3-phase rupting sible voltage
type class MVA Max. Voltage Withstand test Continuous Short time d tripping divided Maximum Closing & Closing &
class voltage range voltage current circuit delay by K symmetrical latching latching
factor c at 60 Hz current interrupting capability capability
Power Impulse (at rated capability momentary
frequency max. kV) 2.7 K
(1 min.) times 1.6 K
K times rated times rated
rated short short short
circuit circuit circuit
E K I Y E/K current ce current current
kV MVA kV rms kV rms Amperes kA rms Cycles Seconds kV rms kA rms kA peak kA rms
EATON www.eaton.com 7
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 2. (ANSI Standardsa) type VCP-W vacuum circuit breaker 27 kV rated symmetrical current basis.
Identification Rated values
Circuit Nominal Nominal Voltage Insulation level Current Inter- Permis- Transient Current values
breaker voltage 3-phase rupting sible recovery voltage
type class MVA time d tripping
class Max. Voltage Withstand test Continuous Short delay E2 t2 Closing & Capacitor
voltageb range voltage current circuit rise latching switching
factor c at 60 Hz current time capability & cable
Power Impulse charging
frequency 3 Second 2.7 K
(1 min.) short time times
current rated
carrying short
capability circuit
E K I Y current
kV MVA kV rms kV rms Amperes kA rms Cycles Seconds kV rms kA rms kA peak kA rms
8 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 3. (ANSI Standards) type VCP-WC extra capability vacuum circuit breaker 5-27 kV rated symmetrical current basis.
Identification Rated voltage
Circuit Voltage Insulation level Short circuit current Inter- Max. Transient Capacitor switching ratings Mech-
breaker withstand test rupt- permis recovery anical
type Max. Voltage Sym % DC Asym. Closing Short- ing sible voltage General Definite purpose endur-
voltage range inter- comp- inter- & time time trip- (RRRV) purpose ance
factor rupting onent rupting latching current ping
at V (Idc) (It) capa- for 3 a delay
Power Lighten- Cont- (Isc) bility sec. Isolated Back to back capacitor
freq- ing inuous shunt switching
V K uency impulse current capacitor No-
(1 min.) 1.2x50us at bank Capacitor Inrush Inrush load
60 Hz c current bank current freq- oper-
current uency ations
kA rms kA kA
KV rms kV rms kV peak A rms total % kA rms peak kA rms Cycles Sec. kV / µs A rms A rms peak kHz
Table 4. (IEC-56 Standardsa) type VCP-W vacuum circuit breaker through 17.5 kV rated symmetrical current basis.
Identification Rated values
Circuit Voltage class Insulation level Normal Short circuit 3 second short Short circuit Cable charging
breaker type current breaking current time current making current breaking amps
Power Impulse
frequency withstand
kV rms kV rms kV peak Amperes kA rms kA rms kV peak Amperes
36VCPW-ND25 3.6 10 40 630, 1250 25 25 63 25
36VCPW-ND32 3.6 10 40 630, 1250 31.5 31.5 79 25
72VCPW-ND25 7.2 20 60 630, 1250 25 25 63 25
72VCPW-ND32 7.2 20 60 630, 1250 31.5 31.5 79 25
36VCP-W25 3.6 10 40 630, 1250, 2000 25 25 63 25
36VCP-W32 3.6 10 40 1250, 2000 31.5 31.5 79 25
36VCP-W40 3.6 10 40 1250, 2000 40 40 100 25
72VCP-W25 7.2 20 60 630, 1250, 2000 25 25 63 25
72VCP-W32 7.2 20 60 1250, 2000 31.5 31.5 79 25
72VCP-W40 7.2 20 60 1250, 2000 40 40 100 25
120VCP-W25 12.0 28 75 630, 1250, 2000 25 25 63 25
120VCP-W32 12.0 28 75 1250, 2000 31.5 31.5 79 25
120VCP-W40 12.0 28 75 1250, 2000 40 40 100 25
175VCP-W25 17.5 38 95 1250, 2000 25 25 63 31.5
175VCP-W32 17.5 38 95 1250, 2000 31.5 31.5 79 31.5
175VCP-W40 17.5 38 95 1250, 2000 40 40 100 31.5
a Interrupting time is 3 cycles at 50/60 Hz. Rated operating sequence 0-3 min- CO-3 min-CO.
EATON www.eaton.com 9
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 5. (ANSI Standardsa) type VCP-W (K = 1) vacuum circuit breaker through 15 kV rated symmetrical current basis (standard
ratings).
Identification Rated values a
Circuit Nominal Voltage Insulation level Current Inter- Permis- Max. Current values
breaker voltage rupting sible voltage
type class Max. Voltage Withstand test Continuous Short time tripping divided Closing & Closing &
voltage range voltage current circuit delay by K latching latching
factor b at 60 Hz current capability capability
Power Impulse (at rated momentary
frequency max. kV) 2.6 K
(1 min.) c times 1.6 K
rated times rated
short short
circuit
E K I Y E/K current
Table 6. (ANSI Standardsa) type VCP-WXC circuit breaker through 15 kV rated symmetrical current basis (standard ratings).
See Figure 23 for control schemes and diagram that apply to this breaker. This breaker differs from the standard breaker with the addition of a third motor cut-off switch and
addition of two wires.
Identification Rated voltage
Circuit Voltage Insulation level Short circuit current Inter- Max. Transient Capacitor switching ratings Mech-
breaker withstand test rupting permis recovery anical
type Max. Voltage Sym % DC Asym. Closing Short- time sible voltage General Definite purpose endur-
voltage range inter- comp- inter- & time tripping (RRRV) purpose ance
factor rupting onent rupting latching current b delay
at V (Idc) (It) capa- for 3
Power Lighten- Cont- (Isc) bility sec. Isolated Back to back capacitor
freq- ing inuous shunt switching
V K uency impulse current capaci- No-
(1 min.) 1.2x50us at tor capacitor Inrush Inrush load
60 Hz bank bank current freq- oper-
c current current uency ations
kA rms kA kA
kV rms kV rms kV peak A rms total % kA rms peak kA rms Cycles Sec. kV / µs A rms A rms peak kHz
150 VCP-WXC 17.5 1 42 95 1200 63 61 83 175s 63 5 2 1.07 200,1600(9) 7.7 465 10,000
63 2000 61 83 1.07 200,1600(9) 7.7 465 10,000
3000 61 83 1.07 200,1600(9) 7.7 465 5,000
a All circuit breakers are tested to 60 Hz; however, they can also be applied at 50 Hz with no derating.
b Optional interrupting time of 3 cycles is available.
c For higher RRRV contact Eaton for more information.
10 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
1.4 Outlines and dimensions
29.13
(739.90)
2.25 20.88
(57.15) (530.35)
27.80 24.63
(706.12) (625.60)
29.56
(750.82)
Breaker Identification A B C D E
240 VCP-W, 270 VCP-W & 270 VCP-WC 10 (254.00) 14 (355.60) 16.25 (412.75) 34.80 (883.92) 35.22 (894.59)
50/350, 50/350C, 150/1000, 150/1000C, 150/63, 3000A VCP-W, VCPW-SE,VCP- 10 (254.00) 12 (304.80) 13.63 (346.20) 29.94 (760.48) 31.44 (798.58)
WC & VCP-W K=1>=50 kA
Except those immediately below
All other VCP-W,VCPW-SE & VCP-W K=1<=40 kA 10 (254.00) 12 (304.80) 13.63 (346.20) 29.81 (757.17) 29.44 (747.78)
including 50/25C & 150/25C, 1200 A
Figure 1. Type VCP-W (K = 1 & MVA), VCPW-SE, and VCP-WC circuit breaker outlines and dimensions in inches (mm).
EATON www.eaton.com 11
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
21.38
(543.05)
7.00 7.00
(177.80) (177.80) 3.69
(93.73)
19.44
(493.78)
21.96
(557.78)
30.38
(771.65)
12.00
(304.80)
29.44
(747.78)
13.63
(346.202)
2.25
(57.15) 20.88
(530.35)
24.63
(625.60)
Figure 2. Type VCPW-ND circuit breaker outlines and dimensions in inches (mm).
12 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
2. Safe practices 3. Receiving, handling, and storage
2.1 Recommendations 3.1 General
Type VCP-W vacuum circuit breaker elements are equipped with high Type VCP-W vacuum circuit breaker elements are subjected to
speed, high energy operating mechanisms. They are designed with complete factory production tests and inspection before being
several built-in interlocks and safety features to provide safe and packed. They are shipped in packages designed to provide
proper operating sequences. maximum protection to the equipment during shipment and storage
and at the same time to provide convenient handling. Tools, such as
the maintenance tool, are shipped separately.
WARNING
3.2 Receiving
TO PROTECT THE PERSONNEL ASSOCIATED WITH INSTALLATION,
OPERATION, AND MAINTENANCE OF THESE CIRCUIT BREAKER ELEMENTS, If the circuit breaker element is not to be used immediately but is
THE FOLLOWING PRACTICES MUST BE FOLLOWED. to be placed in storage, maximum protection can be obtained by
keeping it packed as shipped.
• Only qualified persons as defined in section 6.2.1 and with Upon receipt of the equipment, inspect the containers for any signs
respect to the local electric code, who are familiar with the of damage or rough handling. Open the containers carefully to avoid
installation and maintenance of medium voltage circuits and any damage to the contents. Use a nail puller rather than a crow bar
equipment, should be permitted to work on these circuit breaker when required. When opening the containers, be careful to save
elements. any loose items or hardware that may be otherwise discarded with
• Read these instructions carefully before attempting any installa- the packing material. Check the contents of each package against
tion, operation or maintenance of these breakers. the packing list.
• Always remove the breakers from the enclosure before perform- Examine the circuit breaker element for any signs of shipping
ing any maintenance. Failure to do so could result in electrical damage such as broken, missing, or loose hardware, damaged or
shock leading to death, severe personal injury, or property deformed insulation, and other components. File claims immedi-
damage. ately with the carrier if damage or loss is detected and notify the
nearest Eaton office.
• BE EXTREMELY CAREFUL while the circuit breaker is on the
extension rails. Use provided rail clamps to firmly hold the circuit 3.3 Handling
breaker on the extension rails while performing such activities
as charging, closing, and tripping. Carelessness could cause the
circuit breaker to fall from the rails resulting in personal injury to CAUTION
those in the area. DO NOT USE ANY LIFTING DEVICE AS A PLATFORM FOR PERFORMING
MAINTENANCE, REPAIR, OR ADJUSTMENT OF THE BREAKER OR FOR
• Do not work on a closed breaker or a breaker with closing springs
OPENING, CLOSING THE CONTACTS OR CHARGING THE SPRINGS. THE
charged. The closing spring should be discharged and the main
CIRCUIT BREAKER ELEMENT MAY SLIP OR FALL CAUSING SEVERE
contacts open before working on the breaker. Failure to do so
PERSONAL INJURY. ALWAYS PERFORM MAINTENANCE, REPAIR, AND
could result in cutting or crushing injuries.
ADJUSTMENTS ON A SOLID WORK SURFACE CAPABLE OF SUPPORTING
• Do not use a circuit breaker by itself as the sole means of THE BREAKER ELEMENT.
isolating a high voltage circuit. Remove the breaker to the
DISCONNECT position and follow good lockout and tagging rules, When a breaker element is ready for installation, a lifting yoke in
as well as all applicable codes, regulations, and work rules. conjunction with an overhead lifter or portable floor lifter can be used
• Do not leave the breaker in an intermediate position in the cell. to move a breaker element. When a breaker element is to be lifted,
Always have the breaker either in the TEST or CONNECTED position the lifting yoke over the breaker element and insert lifters
position. Failure to do so could result in a flash over and possible into the breaker element side openings with the lifting hole toward
death, personal injury, or property damage. the interrupters. Once the lifting yoke is securely seated in the
holes, the breaker element can be carefully lifted and moved. Also,
• Always remove the maintenance tool from the breaker after charg-
a breaker lift pan in conjunction with the portable floor lifter can be
ing the closing springs.
used to create a breaker lifter. The breaker can be placed or rolled
• Breakers are equipped with safety interlocks. Do not defeat onto the lift pan with the conductors arms pointing away from the
them. This may result in death, bodily injury, or equipment lifter (see IB022015EN for more details).
damage.
3.4 Storage
If the circuit breaker element is to be placed in storage, maximum
protection can be obtained by keeping it packed as shipped. Before
placing it in storage, checks should be made to make sure that the
breaker element is free from shipping damage and is in satisfactory
operating condition.
The circuit breaker element is shipped with its contacts open and
closing springs discharged. The indicators on the front panel should
confirm this. Insert the maintenance tool in the manual charge
socket opening (Figure 5). Charge the closing springs by pumping
the handle up and down approximately 28 to 38 times until a crisp
metallic “click” is heard. This indicates that the closing springs
are charged and is shown by the closing spring “charged” (yellow)
indicator. Remove the maintenance tool. Operate the push-to-close
button. The breaker element will close as shown by the breaker
contacts “closed” (red) indicator. Operate the push-to-open button.
The breaker element will trip as shown by the breaker contacts
“open” (green) indicator. After completing this initial check, leave the
closing springs “discharged” and breaker contacts “open”.
EATON www.eaton.com 13
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Outdoor storage of the breaker element is NOT recommended. 2. Switchgear installed in an outdoor house consisting of a
If unavoidable, the outdoor location must be well drained and a rigid structural base and walls that prevent bowing during
temporary shelter from sun, rain, snow, corrosive fumes, dirt, falling shipping and installation will have less chance of being
objects, and excessive moisture must be provided. Containers damaged. Also, the wall construction should prevent the
should be arranged to permit free circulation of air on all sides switchgear from going out of square during shipping;
and temporary heaters should be used to minimize condensation. 3. The quality of the roads that will be used to ship the outdoor
Moisture can cause rusting of metal parts and deterioration of high house to the site; and
voltage insulation. A heat level of approximately 400 watts for each
100 cubic feet (2.83 cubic meters) of volume is recommended with 4. Will the switchgear require any type of ocean travel?
the heaters distributed uniformly throughout the structure near the Depending on the time of year, ocean travel can be much
floor. more demanding on a structure than road travel.
Indoor storage should be in a building with sufficient heat and air After the determination has been made to ship the breakers in the
circulation to prevent condensation. If the building is not heated, the switchgear cells, then the following criteria should be followed.
same general rule for heat as for outdoor storage should be applied.
• The breaker should be shipped in the “Connected” position with
3.5 Floor requirements the breaker “Open”.
The equipment must be placed on a true and level surface to allow • The accessories like the truck operated cell (TOC) switch and the
for proper functioning of the doors and drawout components. The mechanism operated cell (MOC) switch must have temporary
finished foundation surface is defined as flat and level within 0.06 restrictions (tie downs) designed and installed to prevent interac-
in. (1.6 mm) in 36 in. (914 mm) in any direction, left to right, front to tion with the breaker while being shipped and installed. Only
back, and diagonally. Alternatively, a local flatness “FF” value of 50 after the switchgear has been placed in its permanent location
or higher and an accompanying “FL” value of 37 to 40 as defined in should these tie downs be removed.
industry standard American Society for Testing and Materials (ASTM) Once the switchgear has been installed on the site, it is the respon-
E1155-96 and industry standard American Concrete Institute (ACl) sibility of the OEM or end-use customers to ensure that no damage
117-90 may be used to establish the flatness and levelness of the has occurred to the following items in the breaker switchgear cell
finished foundation. and the breaker:
Design the foundation so it will be strong enough to support the • Ground contacts;
weight of the switchgear without sagging. Be sure to take into • Secondary disconnect;
account the shock or impact weight that occurs when the breaker
trips and when it closes. The impact weight is 1.5 times the weight • Close floor tripper;
of the breaker. • Levering latch;
Careful preparation of the foundation is important for simplicity of • Trip floor tripper;
erection, ease of operation, and good performance. The recom-
mended foundation consists of steel channels embedded in a level • Breaker cell rails;
concrete floor for indoor switchgear. The channels shall be level • Code plates;
within 0.06 in. over 36 in.(0.318 mm in 914.4 mm) left to right, front
to rear, and diagonally, as measured by a laser level. In no case may
• MOC operator; and
the non-supporting areas of the concrete floor be higher than the • TOC operator.
tops of the steel channels. For outdoor switchgear, the same level-
ness and flatness criteria should apply to the supporting foundation Depending on the construction site location, the road conditions may
for the outdoor house. require additional shipping bracing be added to protect the breakers,
even more than normal. It is up to the OEM or end-use customers
The anchor bolts, channels, and other materials are to be furnished
to determine the conditions of the roads that the trucking company
by the purchaser of the switchgear. A 4 in.(106.6 mm) structural
will utilize and if any additional shipping bracing is required.
channel is recommended as the minimum size for the average
indoor switchgear system. If the OEM or end-use customers decides that their structure is rigid
enough to safely support the weight of the breakers during shipping,
3.6 Shipping breakers in switchgear then they need to take pictures of all the cells with the breakers
fully racked in to the “Connect” position and the breaker “Open”.
Eaton has received inquiries from both OEMs and end-use custom-
Also, they need to take pictures of all the shipping bracing that was
ers regarding whether it is acceptable to ship 5 kV to 27 kV breakers
installed per cell prior to shipping and then after the switchgear is
installed in switchgear cells. The answer depends on the construc-
installed prior to removal of the shipping tie downs. If for some
tion of the switchgear and the weight of the breakers being shipped
reason the breakers or the switchgear cell parts are damaged, then
in the switchgear.
Eaton will request to see these pictures first prior to going to the
The OEM and the end-use customer will need to determine if the site to investigate any damage to the breakers, cell components or
structure is rigid enough to handle shipping breakers of varying accessories. All repair cost associated with resolving these issues
weights in their switchgear without causing any permanent damage due to shipping damage will be the responsibility of the OEM or
to the switchgear structure, breaker cell parts, breakers and accesso- end-use customers to collect against their shipper.
ries. This is true for both one high and two high switchgear configu-
rations. Eaton does not recommend shipping stand-alone NEMA 1
switchgear with the breakers installed.
The OEM and the end-use customer should consider the following
when they are making the decision on whether or not to ship the
breakers in the switchgear cells:
14 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
3.7 Tools and accessories Wheel conversion kit (MG & TD only): Due to how the manual
ground and test device is designed this is the best direct roll-in
Tools and accessories, both standard and optional, are available for wheel kit to use.
use with the circuit breaker element (Figure 3). If not specified
accessories can be used for 36 in. wide and 26 in. wide breakers. Wheel conversion kit for direct roll-in: This wheel kit can be used
to convert a standard breaker or electrical ground and test device to
Spin-free levering-in crank: Used to crank breaker between a direct roll-in version.
DISCONNECT, TEST, and CONNECTED positions.
Conversion kit ROF to non-ROF: This kit is used to convert a direct
Extension rails: Permits breaker to be withdrawn from its compart- roll-in cell to a non direct roll-in cell. It provides the teeter totter
ment. feature that prevents removing a breaker from the breaker cell when
Rail clamps: Used to secure breaker to extension rails. the extension rails or MV breaker lift pan are not in place. Also,
Lifting yoke: Used to lift breaker. the short ramp feature in the front of each rail would need to be
removed.
Manual charging handle: Used to charge closing springs manually.
Conversion kit non-ROF to ROF: This kit is used to convert a non-
Portable lifter: Used to lift breaker to or from extended rails. direct roll-in cell to a direct roll-in cell. It provides the ramp feature
Breaker lift pan: This accessory enables the breaker to be lifted that goes on the end of each rail to help guide the steel wheels on
from the ground to any height cell without the extension rails. It the side of the breaker up onto the rail rolling surface. This is only
consists of a portable lifter and a MV breaker lift pan. to be used in the lower switchgear cells that are level with the floor.
The teeter totter feature that keeps the breaker from being rolled out
• Portable lifter; of the cell would need to be removed.
• MV breaker lift pan with short extension rail kit for 36”or 26” wide Secondary conversion kit: This kit converts an automatic secondary
breaker. in a BPI pan assembly to a manual enabled automatic secondary.
Drawout ramp: Used to insert or withdraw breaker from lower When the release lever is raised above the stop feature the second-
compartment without portable lifter. aries will slide forward to automatically connect, see section 8.2 for
more details.
Docking transport dolly: Used to insert or withdraw breaker from
lower compartment without portable lifter or move breaker from one Closed door racking guide: This feature can be added to the front
location to another. of the BPI pan assembly to provide a guide for the manual levering-
in tool when the switchgear door is closed to guide the levering-in
Electrical levering-in device:
crank socket onto the levering-in drive screw nut.
BPI pan assembly:
Integral Motorized Racking (MR2) used to electrically move
breaker between DISCONNECT/TEST, or DISCONNECT, TEST, and
CONNECTED positions is available. Specified by description as
opposed to a style number.
If the external electric levering-in device which mounts to the door or
pan assembly is used, then the breaker can be moved between the
DISCONNECT and CONNECTED positions.
The process of levering the breaker from the DISCONNECT to the
TEST position would need to be performed manually (approximately
6 turns).
Non-BPI pan assembly:
Used to electrically move the breaker between DISCONNECT/TEST
and CONNECTED positions.
Truck operated cell (TOC) switch: Indicates when breaker is in the
CONNECT position. Furnished with standard push on wire termi-
nals. Optional ring tongue terminals are available.
Mechanism operated cell (MOC) switch: Provides additional
normally open and closed contacts for when control and protection
scheme exceeds the available auxiliary contacts in the breaker.
Furnished with standard push on wire terminals. Optional ring
tongue terminals are available.
This feature is available in two different configurations:
1.) Functions in both the TEST and CONNECT positions, or
2.) Functions only in the CONNECT position.
Eaton strongly recommends use of the TEST and CONNECT position
configuration.
Test jumper: Used to operate breaker electrically while breaker is on
extension rails or transport dolly.
Test cabinet: Used to provide power to operate breaker outside its
compartment for the purpose of testing functionality.
Key provisions with positional interlock: This enables locking of
the levering-in cage when the breaker is in the TEST position with a
padlock or keyed cylinder lock.
EATON www.eaton.com 15
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 7. Accessories for 36-inch wide breaker compartments for 29-inch frame breaker.
Description Style number
TOC (truck-operated cell) switch 1C20006G12
4A/5B contacts
TOC (truck-operated cell) switch 1C20006G15
4A/5B contacts ring-tongue terminals
MOC (mechanism-operated cell) switch
5A/5B TOC switch 5A/5B MOC switch
5A/4B contacts (test and connect) 1C20007G12
5A/4B contacts (connect only) 1C20007G13
10A/8B contacts (test and connect) 1C20007G14
10A/8B contacts (connect only) 1C20007G15
15A/12B contacts (test and connect) 1C20007G16
15A/12B contacts (connect only) 1C20007G17
5A/4B contacts (test and connect) ring-tongue terminals 1C20007G28
5A/4B contacts (connect only) ring-tongue terminals 1C20007G29
Standard set of accessories
10A/8B contacts (test and connect) ring-tongue terminals 1C20007G30
10A/8B contacts (connect only) ring-tongue terminals 1C20007G31
15A/12B contacts (test and connect) ring-tongue terminals 1C20007G32
15A/12B contacts (connect only) ring-tongue terminals 1C20007G33
Spin-free levering-in crank with clutch 701B601G11
Extension rails (right and left, one set) 7813C41G03
Set of rail clamps 6511C83G11
Lifting yoke 691C607G11
Portable lifter Manual charging handle 8064A02G11
Standard set of accessories 1A30136G02
Spin-free levering-in crank with clutch
Extension rails (right and left, one set)
Manual charging handle
Set of rail clamps
Portable lifter (26-/36-inch convertible) 1C19086H01
MV breaker lift pan 1C20220G01
Drawout ramp 1C14163G08
Docking transport dolly 6510C71G21
Portable lifter and lift pan Electrical levering-in device 1A30257G01
Test jumper 6526C23G11
Test cabinet
Any DC close and any trip 8346A28G21
AC or DC close and DC trip 8346A28G22
120 Vac close and capacitor trip 8346A28G23
240 Vac close and capacitor trip 8346A28G60
AC or DC charge, DC close and trip 8346A28G24
Key provisions with positional Interlock 6510C48G22
This allows for key locking the levering-in cage
Optional accessories include (clockwise): when the breaker is in the TEST position.
lifting yoke, test cabinet, spin-free levering
crank, and test jumper Wheel conversion kit (MG & TD only) 68C5010G41
Wheel conversion kit for direct roll-in 68C5010G42
Conversion kit ROF to NON-ROF 1C19779G101
Conversion kit NON- ROF to ROF 1C19779G102
Secondary conversion kit: to convert automatic 1C20335G01
secondary to manual operation
Closed door racking guide 1C20339G02
16 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 8. Narrow design accessories for 26-inch-wide breaker compartments.
Description Style number
TOC (truck-operated cell) switch 4A/3B contacts 7797C20G01
MOC (mechanism-operated cell) switch
4A/3B contacts (test and connect) 7797C24G02
4A/3B contacts (connect only) 7797C24G03
8A/6B contacts (test and connect) 7797C24G04
8A/6B contacts (connect only) 7797C24G05
12A/9B contacts (test and connect) 7797C24G06
Set of ND accessories Spin-free levering-in crank with clutch 701B601G11
Primary contact spanner wrench 502A850G01
Extension rails (right and left, one set) 7813C41G03
Set of rail clamps 6511C83G12
Lifting yoke 691C607G02
Manual charging handle 8064A02G11
Set of ND accessories 1A30136G04
Spin-free levering-in crank with clutch
Primary contact spanner wrench
Extension rails (right and left, one set)
Manual charging handle
ND 4A/3B ND 4A/3B Set of rail clamps
TOC switch MOC switch
Portable lifter (26-/36-inch convertible) 1C19086H01
MV breaker lift pan and short extension rail kit 1C19086G01
Drawout ramp 1C14163G01
Docking transport dolly 6510C71G02
Electrical levering-in device 1A30257G01
Test jumper 1C15331G01
Test cabinets
Any DC close and any trip 8346A28G41
AC or DC close and DC trip 8346A28G42
Electric levering-in Padlock/key 120 Vac close and capacitor trip 8346A28G43
device interlock
240 Vac close and capacitor trip 8346A28G60
Padlock/key provisions with positional interlock 6510C48G01
Includes the padlock assembly plus a
positional interlock. This allows for key
locking the levering-in cage when the
breaker is locked in the DISCONNECT position
EATON www.eaton.com 17
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 9. 27 kV VCP-W accessories.
Description Style number
TOC (truck operated cell) switch 5A/5B contacts 6510C49G12
TOC (direct roll-in) 691C568G06
MOC (mechanism operated cell) switch 5A/4B contacts (test and connect) 6529C58G02
5A/4B contacts (connect only) 6529C58G03
10A/8B contacts (test and connect) 6529C58G04
10A/8B contacts (connect only) 6529C58G05
15A/12B contacts (test and connect) 6529C58G06
15A/12B contacts (connect only) 6529C58G07
Spin-free levering-in crank 701B601G11
Standard levering-in crank 701B601G12
Epoxy stand-off insulator Extension rails (right and left—one set) 7813C41G03
Set of rail clamps 6511C83G11
Lifting yoke 691C607G11
Manual charging handle 8064A02G11
Standard set of 27 kV accessories Levering-in crank with clutch manual 1A30136G02
charging handle
Wheel kit (for direct roll-in) 68C5010G42
Portable lifter 1C19086H01
MV breaker lift pan 1C20220G01
Drawout ramp 1C14163G02
Docking transport dolly 6510C71G11
Electrical levering-in device (120 Vac) 1A30257G01
Epoxy cable support Test cabinet Any DC close and any trip 8346A28G21
AC or DC close and DC trip 8346A28G22
120 Vac close and capacitor trip 8346A28G23
240 Vac close and capacitor trip 8346A28G60
Test jumper 6526C23G11
120 Vac capacitor trip device 3A39175G01
240 Vac capacitor trip device 3A39175G02
27 kV epoxy cable support 7799C52H01
8.25 inch epoxy stand-off insulator 1A34286H01
18 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Ground and test device (G&TD) accessories: Eaton offers a broad spectrum of manual and electrical G&TDs. All of the manual G&TDs
provide access to all the line and load terminals to enable phase checking. Also, they provide the ability to verify operation of the voltage
sensing equipment against a live source while verifying that the other connection does not have any voltage present prior to applying the
grounds. The simple electrical G&TDs only provide access to line or load terminals. One of the designs provides the ability to perform cable
testing as well as grounding the desired circuit.
Table 10. Simple manual ground and test devices—bus bar type.
25 and 40 kA 50 kA 63 kA
Description Style number Style number Style number
Upper and lower terminals 1200 A (26” narrow design) 4A35130G01 — —
Upper and lower terminals 1200/2000 A 66A5092G42 66A5092G02 66A5092G12
Upper and lower terminals 3000 A 66A5092G43 66A5092G03 66A5092G13
Upper terminals only 1200/2000 A 66A5092G44 66A5092G04 66A5092G14
Lower terminals only 1200/2000 A 66A5092G45 66A5092G05 66A5092G15
Upper terminals only 3000 A 66A5092G46 66A5092G06 66A5092G16
Lower terminals only 3000 A 66A5092G47 66A5092G07 66A5092G17
Upper and lower terminals 66A5092G82 66A5092G62 66A5092G72
1200/2000 A with ROF wheels installed
Upper and lower terminals 66A5092G83 66A5092G63 66A5092G73
3000 A with ROF wheels installed
Simple manual ground
and test device Upper terminals only 66A5092G84 66A5092G64 66A5092G74
1200/2000 A with ROF wheels installed
Lower terminals only 66A5092G85 66A5092G65 66A5092G75
1200/2000 A with ROF wheels installed
Upper terminals only 66A5092G86 66A5092G66 66A5092G76
3000 A with ROF wheels installed
Lower terminals only 66A5092G87 66A5092G67 66A5092G77
3000 A with ROF wheels installed
Table 11. 15 kV VCP-W simple manual ground and test device—“bail” and “ball” type a .
Description Style number
Bail 1200/2000 A upper/lower 66A5201G01
Bail 3000 A upper/lower 66A5201G02
Ball 1200/2000 A upper/lower 66A5291G01
Ball 3000 A upper/lower 66A5291G02
Bail type manual ground
and test device Bail 1200/2000 A upper/lower with ROF wheels installed 66A5201G11
Bail 3000 A upper/lower with ROF wheels installed 66A5201G12
Ball 1200/2000 A upper/lower with ROF wheels installed 66A5291G11
Ball 3000 A upper/lower with ROF wheels installed 66A5291G12
Bail connector Ball connector a Cables are not provided
EATON www.eaton.com 19
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 13. Simple electrically operated ground and test device.
25 and 40 kA 50 kA 63 kA
Description Style number Style number Style number
Without roll-on-floor wheels (ROF) factory installed
Upper terminal
1200/2000 A, 48 Vdc 66A5302G75 — —
1200/2000 A, 125 Vdc or 120 Vac 66A5302G76 — —
1200/2000 A, 250 Vdc or 240 Vac 66A5302G77 — —
1200/2000 A, 48 Vdc — 66A5302G02 —
1200/2000 A, 125 Vdc or 120 Vac — 66A5302G03 —
Simple electrically operated ground 1200/2000 A, 250 Vdc or 240 Vac — 66A5302G04 —
and test device 3000 A, 48 Vdc — 66A5302G05 —
3000 A, 125 Vdc or 120 Vac — 66A5302G06 —
3000 A, 250 Vdc or 240 Vac — 66A5302G07 —
1200/2000/3000 A, 48 Vdc — — 66A5302G12
1200/2000/3000 A, 125 Vdc or 120 Vac — — 66A5302G13
1200/2000/3000 A, 250 Vdc or 240 Vac — — 66A5302G14
Lower terminal
1200/2000 A, 48 Vdc 66A5302G85 — —
1200/2000 A, 125 Vdc or 120 Vac 66A5302G86 — —
1200/2000 A, 250 Vdc or 240 Vac 66A5302G87 — —
1200/2000 A, 48 Vdc — 66A5302G22 —
1200/2000 A, 125 Vdc or 120 Vac — 66A5302G23 —
1200/2000 A, 250 Vdc or 240 Vac — 66A5302G24 —
3000 A, 48 Vdc — 66A5302G25 —
3000 A, 125 Vdc or 120 Vac — 66A5302G26 —
3000 A, 250 Vdc or 240 Vac — 66A5302G27 —
1200/2000/3000 A, 48 Vdc — — 66A5302G32
1200/2000/3000 A, 125 Vdc or 120 Vac — — 66A5302G33
1200/2000/3000 A, 250 Vdc or 240 Vac — — 66A5302G34
With roll-on-floor wheels (ROF) factory installed
Upper terminal
1200/2000 A, 48 Vdc with ROF 66A5302G53 — —
1200/2000 A, 125 Vdc or 120 Vac with ROF 66A5302G54 — —
1200/2000 A, 250 Vdc or 240 Vac with ROF 66A5302G55 — —
1200/2000 A, 48 Vdc with ROF — 66A5302G35 —
1200/2000 A, 125 Vdc or 120 Vac with ROF — 66A5302G36 —
1200/2000 A, 250 Vdc or 240 Vac with ROF — 66A5302G37 —
3000 A, 48 Vdc with ROF — 66A5302G38 —
3000 A, 125 Vdc or 120 Vac with ROF — 66A5302G39 —
3000 A, 250 Vdc or 240 Vac with ROF — 66A5302G40 —
1200/2000/3000 A, 48 Vdc with ROF — — 66A5302G41
1200/2000/3000 A, 125 Vdc or 120 Vac with ROF — — 66A5302G42
1200/2000/3000 A, 250 Vdc or 240 Vac with ROF — — 66A5302G43
Lower terminal
1200/2000 A, 48 Vdc with ROF 66A5302G57 — —
1200/2000 A, 125 Vdc or 120 Vac with ROF 66A5302G58 — —
1200/2000 A, 250 Vdc or 240 Vac with ROF 66A5302G59 — —
1200/2000 A, 48 Vdc with ROF — 66A5302G44 —
1200/2000 A, 125 Vdc or 120 Vac with ROF — 66A5302G45 —
1200/2000 A, 250 Vdc or 240 Vac with ROF — 66A5302G46 —
3000 A, 48 Vdc with ROF — 66A5302G47 —
3000 A, 125 Vdc or 120 Vac with ROF — 66A5302G48 —
3000 A, 250 Vdc or 240 Vac with ROF — 66A5302G49 —
1200/2000/3000 A, 48 Vdc with ROF — — 66A5302G50
1200/2000/3000 A, 125 Vdc or 120 Vac with ROF — — 66A5302G51
1200/2000/3000 A, 250 Vdc or 240 Vac with ROF — — 66A5302G52
20 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 14. Simple electrically operated ground and test device for VCP-W without key interlocks.
Description Style number
Lower terminal
1200/2000 A, 125 Vdc or 120 Vac, 40 kA with ROF 66A5312G45
Note: These units are also available as direct-roll-on-the-floor products via a separately purchased wheel kit.
Table 15. Simple electrically operated ground and test device for VCP-WXC.
Description Style number
Upper terminal
1200/2000/3000 A, 125 Vdc or 120 Vac, 63 kA 66A5302G83
Lower terminal
1200/2000/3000 A, 125 Vdc or 120 Vac, 63 kA 66A5302G93
Note: These units are also available as direct-roll-on-the-floor products via a separately purchased wheel kit.
EATON www.eaton.com 21
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 17. VCP-W CEG&TD assessories.
Description Style number
Replacement voltage probe – 1 probe (692C899H01) 81A4936G01
Replacement voltage probe – 3 probes (692C899H01) 81A4936G02
Replacement 38kV HD probe - 1 probe (692C899H02) 81A4936G03
692C899H02 Replacement 38kV HD probe - 3 probes (692C899H02) 81A4936G04
Replacement CEGTD SP probe - 1 probe (692C899H03) 81A4936G05
Replacement CEGTD SP probe - 3 probes (692C899H03) 81A4936G06
SP. No insert probe - 1 probe (692C899H11) 81A4936G11
SP. No insert probe - 3 probes (692C899H11) 81A4936G12
692C899H03 15kV, 50kA 1200/2000A finger cluster conversion kit 83C4864G03
15kV, 25/40kA 1200/2000A finger cluster conversion kit 83C4864G04
BPI cell position indication label for CEG&TD a 1C19649H13
692C899H01 692C899H11
a One of these is required for every switchgear cell that will accommodate a CEG&TD.
22 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 19. Dummy elementsab. 3.8 Type VCP-W vacuum circuit breaker element weights
Style (Tables 20, 21, and 22).
Description number
5 kV, 1200 A (up to 50 kA) 691C605G03 Table 20. VCP-W ANSI rated breaker weightsa.
5 kV, 2000 A (up to 50 kA) 691C605G04 Rating Amperes Lbs. (kg)
5 kV, 3000 A (up to 63 kA) 691C605G05 50VCPW-ND250 1200 345 (157)
15 kV, 1200 A (up to 50 kA) 691C605G06 50VCP-W250 1200 350 (159)
15 kV, 2000 A (up to 50 kA) 691C605G07 50VCPW-SE250 2000 410 (186)
15 kV, 3000 A (up to 63 kA) b 691C605G08 3000 525 (238)
a Dummy elements applicable for breakers rated VCP-W MVA, VCP-W K = 1, and VCP-WSE. 50VCP-W350 1200 460 (209)
50VCPW-SE350 2000 490 (222)
b Dummy element also applicable for VCP-WXC breaker.
3000 525 (238)
75VCP-W500 1200 375 (170)
75VCPW-SE500 2000 410 (186)
3000 525 (238)
150VCP-W500 1200 350 (159)
150VCPW-SE500 2000 410 (186)
3000 525 (238)
150VCP-W750 1200 350 (159)
150VCPW-SE750 2000 410 (186)
3000 525 (238)
150VCP-W1000 1200 460 (209)
150VCPW-SE1000 2000 490 (222)
3000 525 (238)
150VCP-W1500(63) 1200 525 (238)
150VCPW-SE1500(63) 2000 530 (241)
3000 550 (250)
270VCP-W750(16) 600 460 (209)
1200 480 (218)
2000 500 (227)
270 VCP-W1000(22) 600 460 (209)
1200 480 (218)
2000 500 (227)
270 VCP-W1250(25) 600 460 (209)
1200 480 (218)
2000 500 (227)
270 VCP-W1600(32) 1200 545 (245)
2000 560 (252)
270VCP-W2000(40) 1200 545 (245)
2000 560 (252)
a Does not include shipping carton.
EATON www.eaton.com 23
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 21. VCP-W IEC rated breaker weightsa. Table 22. VCP-W (K = 1) breaker weightsa.
Normal Rating Amperes Lbs. (kg)
current
Rating amperes Lbs. (kg) 150 VCP-W 25 1200 350 (159)
2000 375 (170)
36VCPW-ND25 630 350 (159) 3000 500 (227))
1250 350 (159)
150 VCP-W 40 1200 375 (170)
36VCPW-ND32 630 350 (159) 2000 375 (170)
1250 350 (159) 3000 500 (227)
72VCPW-ND25 630 350 (159) 150 VCP-W 50 1200 480 (218)
1250 350 (159) 2000 490 (222)
72VCPW-ND32 630 350 (159) 3000 500 (227)
1250 350 (159) 150 VCP-W 63 1200 460 (209)
36VCP-W25 630 350 (159) 2000 490 (222)
1250 350 (159) 3000 525 (238)
2000 410 (186) 75 VCP-W 40 1200 375 (170)
36VCP-W32 1250 350 (159) 2000 375 (170)
2000 410 (186) 3000 500 (227)
36VCP-W40 1250 375 (170) 75 VCP-W 50 1200 480 (218)
2000 410 (186) 2000 490 (222)
72VCP-W25 630 350 (159) 3000 525 (227)
1250 350 (159) 50 VCP-W 25 1200 350 (159)
2000 410 (186) 2000 375 (170)
72VCP-W32 1250 350 (159) 3000 500 (227)
2000 410 (186) 50 VCP-W 40 1200 375 (170)
72VCP-W40 1250 375 (170) 2000 375 (170)
2000 410 (186) 3000 500 (227)
120VCP-W25 630 350 (159) 50 VCP-W 50 1200 480 (218)
1250 350 (159) 2000 490 (222)
2000 410 (186) 3000 500 (227)
120VCP-W32 1250 350 (159) 50 VCP-W 63 1200 460 (209)
2000 410 (186) 2000 490 (222)
3000 525 (238)
120VCP-W40 1250 375 (170) a Does not include shipping carton.
2000 410 (186)
175VCP-W25 630 350 (159)
1250 350 (159)
2000 410 (186)
175VCP-W32 1250 375 (170)
2000 410 (186)
175VCP-W40 1250 375 (170)
2000 410 (186)
240 VCP-W1 6 630 462 (210)
1250 484 (220)
2000 506 (230)
240 VCP-W20 630 462 (210)
1250 484 (220)
2000 506 (230)
40 VCP-W25 630 462 (210)
1250 484 (220)
2000 506 (230)
a Does not include shipping carton.
24 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Figure 3. Typical VCP-W tools and accessories. (Note: products shown for representation only. New products may include design
improvements and alternate nameplate configurations.)
EATON www.eaton.com 25
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
b
d
c h
Figure 4. Typical front view VCP-W vacuum circuit breaker. (See Figure 45 for an example of a roll on the floor wheel kit.)
26 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
a b d
m
c
n
e j
f g o q
1. L.H. closing spring 7. Shunt trip assembly 13. Manual charge socket
2. Anti-pump relay 8. Charging motor 14. Operation counter
3. Auxiliary switch 9. Charging pawl 15. Optional second shunt trip
4. Motor cutoff switch 10. Ratchet wheel 16. Optional roll on floor wheels
5. Closing cam 11. R. H. closing spring 17. Position switches
6. Spring release (close coil) assembly 12. Opening spring
Figure 5. Typical VCP-W vacuum circuit breaker element with front cover removed.
EATON www.eaton.com 27
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
1. Vacuum interrupter
2. Phase barrier
3. V-flex current transfer system
4. Direct reading contact erosion indicator
5. Contact loading spring (wipe spring)
6. TOC operator (BPI pan assembly)
28 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
c
e
d f
h g
EATON www.eaton.com 29
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
4. Initial inspection and installation
4.1 Introduction
WARNING
BEFORE PLACING THE CIRCUIT BREAKER IN SERVICE, CAREFULLY FOLLOW
THE INSTALLATION PROCEDURE GIVEN BELOW. NOT FOLLOWING THE
PROCEDURE CAN FAIL TO UNCOVER SHIPPING DAMAGE THAT MAY
RESULT IN INCORRECT CIRCUIT BREAKER OPERATION LEADING TO DEATH,
BODILY INJURY, AND EQUIPMENT DAMAGE.
NOTICE
IF THE SPRINGS ARE TO BE CHARGED ON A CLOSED CIRCUIT BREAK- Figure 8. Type VCP-W circuit breaker manual charging handle in
ER, NO CLICK IS HEARD AT THE END OF CHARGING OPERATION. use.
DISCONTINUE CHARGING AND REMOVE THE MAINTENANCE TOOL AS
SOON AS “CHARGED” FLAG IS FULLY VISIBLE. CONTINUED ATTEMPTS TO 4.8 Electrical operation check
CHARGE FURTHER MAY RESULT IN DAMAGE TO THE MECHANISM.
After having completed all previous checks and tests, the circuit
breaker is ready to be operated electrically. It is preferred that this
Remove the maintenance tool. Close and trip the circuit breaker.
check be made with the circuit breaker in a TEST position or by using
Repeat several times.
a test cable, if the circuit breaker is outside the cell structure.
4.3 Vacuum interrupter integrity
Using a dry, lint free cloth or paper towel, clean all the accessible CAUTION
insulating surfaces of the pole units. Conduct a vacuum interrupter
BEFORE INSERTING THE CIRCUIT BREAKER, EXAMINE THE INSIDE OF
integrity check as described in Section 6.
THE CELL STRUCTURE FOR EXCESSIVE DIRT OR ANYTHING THAT MIGHT
4.4 Insulation INTERFERE WITH THE CIRCUIT BREAKER MOVEMENT.
Check the circuit breaker’s primary and secondary insulation as
described in Section 6.
4.5 Contact erosion and wipe WARNING
EXTREME CAUTION MUST BE EXERCISED TO INSURE THAT PRIMARY
Manually charge the closing springs and close the circuit breaker. CIRCUITS ARE NOT ENERGIZED WHILE CHECKS ARE PERFORMED IN THE
Check contact erosion and wipe as described in Section 6. CIRCUIT BREAKER COMPARTMENT. FAILURE TO DO SO MAY RESULT IN
4.6 Primary circuit resistance PERSONAL INJURY OR DEATH.
Check the primary circuit resistance as described in Section 6. The
resistance should not exceed the values specified. Record the values The circuit breaker is normally tested electrically in its cell structure
obtained for future reference. in the TEST position. To achieve the TEST position, first determine
if the breaker cell has a BPI Pan Assembly, Figure 12 or a non-BPI
4.7 Nameplate Pan Assembly, Figure 13. Then follow the appropriate instructions in
Compare the circuit breaker nameplate information with switchgear section 4.8.1 to move/lever the circuit breaker into the TEST position.
drawings for compatibility.
4.8.1 Circuit breaker insertion and removal
CAUTION
DO NOT USE ANY TOOL OTHER THAN THE LEVERING-IN CRANK PROVIDED
TO LEVER THE CIRCUIT BREAKER FROM TEST OR CONNECTED POSITIONS.
CORRECT OPERATION OF SOME OF THE INTERLOCKS IS DEPENDENT ON
USE OF THE PROVIDED LEVERING-IN CRANK. PERSONAL INJURY OR
EQUIPMENT DAMAGE COULD RESULT FROM THE USE OF A TOOL OTHER
THAN THE PROPER LEVERING-IN CRANK.
30 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
NOTICE
THE CIRCUIT BREAKER AND INTEGRAL LEVERING MECHANISM INCLUDES
ALL NECESSARY INTERLOCKS THAT, WHEN INTERFACED WITH A COM-
PATIBLE STRUCTURE, WILL RENDER THE CIRCUIT BREAKER MECHANISM
MECHANICALLY AND ELECTRICALLY TRIP-FREE DURING THE LEVERING
PROCESS. FOR INFORMATION PERTAINING TO INDIVIDUAL INTERLOCKS,
REFER TO PARAGRAPH 4.9 IN THIS SECTION.
Inserting breaker:
EATON www.eaton.com 31
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
C. Racking the breaker from CONNECTED position to TEST or 2. Insert the levering-in crank onto the hex drive nut on the
DISCONNECT/TEST position levering system. In order to engage the hex drive nut, you
must push in the levering system slider.
BPI pan assembly:
3. Rotate the levering-in crank in a counterclockwise direction
1. Insert the levering-in crank onto the hex drive nut on the until the breaker is in the DISCONNECT/ TEST position.
levering system. In order to engage the hex drive nut, you
Note: The breaker secondary control receptacle on the compartment levering
must push in the levering system slider.
system is automatically disengaged from the breaker secondary plug when
Note: If the breaker is closed, it will trip as the levering-in crank is moved to the DISCONNECT/TEST position.
pushed in to gain access to the hex drive nut in the levering system.
Automatic/manual hybrid BPI pan assembly:
2. Rotate the levering-in crank in a counterclockwise direction
1. If the breaker is closed in the CONNECTED position, then
until the breaker is in the TEST or the DISCONNECT position.
access to the hex drive nut on the levering system will be
Note: The breaker secondary control receptacle on the compartment denied. The breaker must be opened prior to levering opera-
levering system is automatically disengaged from the breaker secondary tion being performed.
plug when moved to the DISCONNECT position.
2. Insert the levering-in crank onto the hex drive nut on the
Non-BPI pan assembly: levering system. In order to engage the hex drive nut, you
must push in the levering system slider.
1. If the breaker is closed in the CONNECTED position, then 3. Rotate the levering-in crank in a counterclockwise direction
access to the hex drive nut on the levering system will be until the breaker is in the DISCONNECT/TEST position.
denied. The breaker must be opened prior to levering opera-
tion being performed. Note: The breaker secondary control receptacle on the compartment levering
system is automatically disengaged from the breaker secondary plug when
moved to the DISCONNECT/ TEST position.
c
e
d f
h g
32 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Note: The legend for Figures 12 and 13 follow Figure 13.
EATON www.eaton.com 33
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
2
1 8
9
3 4 5 7 6
34 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Breaker pan assembly:
Call out descriptions for Figure 12 and 13. 9. The breaker mechanism-operated cell (MOC) switch is an
1. Grounding contact grounds the breaker in the DISCONNECT, assembly of switches that is operated by a lever on the breaker
TEST, and CONNECTED positions. mechanism. It can contain as many as 15 normally closed and
15 normally open contacts (beneath the cover) in the standard
2. The levering system prevents removal of the breaker in any design.
position other than the DISCONNECT position (BPI pan) or
DISCONNECT/TEST position (non-BPI pan). The MOC switch is activated by the breaker closing. It extends
a plunger out the bottom of the mechanism and pushes down on
3. The control wiring is arranged for pullout disconnecting by means the MOC switch operating mechanism. This, in turn, transmits
of a 25-point female receptacle arranged to connect to a male the motion to operate the switch.
plug on the breaker. The secondary disconnect is the connection
for the control leads between the removable breaker and the 10. The truck operated cell (TOC) switch has nine poles - four
stationary housing. normally open and five normally closed contacts that change
state as the breaker is levered to the connected position. As the
Automatic secondary: Figure 12 represents an automatically breaker is being levered into the connected position, a bracket
engaged secondary, as offered on the BPI pan assembly, on the breaker pushes the TOC switch lever during the last inch
requires no manual input from the customer to engage the of travel. As a result, the TOC switch can be used to electrically
secondary harness. The secondary harness will engage auto- indicate whether or not the breaker is in the connected position
matically when the breaker is levered-in to the discrete TEST (beneath cover).
position.
11. Code plates: (see Interface interlocks/interfacing check, Section
The secondary harness will then disengage automatically when 4.9.1).
the breaker returns to the DISCONNECT position.
12. Provision for padlocking a breaker in any position. Also a location
Manual secondary: Figure 13 represents a manually engaged for a key interlock.
secondary assembly which requires the customer to engage
the secondary harness manually when the breaker is in the 13. Picture frame provides a closed barrier to the primary compart-
DISCONNECT position. When engaged, the breaker will now be ment when the breaker is connected.
in the TEST position. 14. Rail on which the breaker rolls.
Automatic/manual hybrid secondary (optional): Figure 46 15. Optional MR2 integral racking provisions for inclusion during
represents an automatic engaging secondary with a manual manufacturing or aftermarket.
release feature incorporated into the BPI pan assembly. It
requires the customer to manually lift up the secondary release For additional information on the levering mechanism, refer to para-
lever to allow the secondary harness to engage the breaker in graph 5.6 in this manual.
the DISCONNECT/TEST position.
4.8.2 Circuit breaker performance check
The secondary harness will then disengage automatically when
the breaker returns to the DISCONNECT/TEST position.
1. Study and understand the electrical drawings furnished with
4. Racking screw performs breaker insertion and withdrawal. each switchgear system.
5. Moving block couples to breaker for insertion and withdrawal. 2. Install the circuit breaker in the DISCONNECT position.
6. Slider is used with #8 to prevent levering a closed breaker. May 3. Engage secondaries or lever breaker to TEST position to auto-
also be used in conjunction with #12 to padlock a breaker in matically engage secondaries:
either position. Automatic secondary: To engage secondary harness, lever the
7. Indicates when the breaker is in the fully connected position. breaker to the TEST position to engage the control circuit.
Manual secondary: To engage secondary harness, lift and pull
Breaker position indication (BPI) label: Figure 12 represents the secondary disconnect forward to engage the control circuit.
positive indication of breaker location at any position through use
of a colored label mounted on the top flange of the right hand rail Note: It is recommended that the power to the secondary connector
assembly. Green indicates the DISCONNECT position, yellow be de-energized prior to manually engaging the secondaries to prevent
indicates the TEST position, and red indicates the CONNECT damage to the secondary pins associated with the spring charging motor
position. Upon arriving at any of the three discrete positions; circuit.
DISCONNECT, TEST, and CONNECT, there is a black mark that Automatic/manual hybrid secondary (optional): To engage
aligns with the breaker cover to indicate exact location. secondary harness, lift and release the secondary disconnect so
Standard indication: Figure 13 represents positive indication that it automatically slides forward to engage the control circuit.
of the breaker in the CONNECT position by use of a red flag
4. Verify breaker operation; once the secondaries are engaged the
that rotates into viewing position when the breaker is fully
closing springs will automatically charge unless inhibited by the
connected.
switchgear control circuit, the condition will be indicated by a
8. Slider interlocks: Spring Charged/Discharged indicator on the front of the circuit
BPI pan assembly: Figure 12 displays the “L” shaped slider breaker (Figure 7). In addition, the status of the main contacts,
interlock that enables tripping of a closed breaker by pushing in open or closed, is indicated on the front of the circuit breaker.
on the slider (item 6) that prevents access to the racking screw. Close and trip the circuit breaker several times to verify closing
Non-BPI pan assembly: Figure 13 displays the “Z” shaped and tripping operations. Conclude by closing the circuit breaker.
slider interlock that prevents a closed breaker from being levered The circuit breaker is now closed in the TEST position with
out of the cell. springs charged.
EATON www.eaton.com 35
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
4.9 Circuit breaker/structure interfacing
WARNING
NEVER DISABLE OR DEFEAT ANY INTERLOCKS. THEY ARE INTENDED FOR
PROPER AND SAFE OPERATION. FAILURE TO COMPLY COULD RESULT IN
DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY DAMAGE DUE TO
THE HAZARDOUS VOLTAGE PRESENT.
NOTICE
EVEN WITH THE CODING PLATES, IT IS POSSIBLE TO PUT A BREAKER INTO
THE COMPARTMENT THAT’S CONTROL WIRING IS NOT COORDINATED
WITH THAT OF THE COMPARTMENT. ALWAYS CHECK THE SHOP ORDER
DRAWING TO MAKE SURE THE CONTROL WIRING OF THE BREAKER AND
THE COMPARTMENT ARE THE SAME.
Maintenance interlock
This interlock trips, closes, and trips the circuit breaker if it is
closed and charged as the circuit breaker is withdrawn from the
DISCONNECT (BPI pan assembly) or DISCONNECT/TEST posi-
tion on to the extension rails or rolled out of the cell for the direct
roll-in-breaker. The circuit breaker open and closing springs are,
therefore, discharged. A closed breaker cannot be moved into the
DISCONNECT (BPI pan assembly) or DISCONNECT/TEST position
from the extension rails, or from the floor as a roll-on-floor breaker.
This interlock consists of the interaction between the switchgear cell
1. Ground contact features and the close floor tripper and the trip floor tripper found
2. Secondary disconnect under the breaker per Figure 15.
3. Close floor tripper
4. Levering latch
5. Trip floor tripper
6. Code plates
7. MOC operator
8. TOC operator (Non-BPI pan assembly
36 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
1. BPI pan assembly (Figure 12): If the breaker is closed in the
CONNECTED position, then as levering-in crank is pushed in
to gain access to the hex drive nut on the levering system the
breaker will trip Open automatically.
Negative interlock
Figure 16. Pulling secondary disconnect cage to engage second-
aries in TEST position (old version shown). New version will The negative interlock prevents the circuit breaker from closing
have BPI pan with automatic secondaries. between the CONNECTED and TEST positions.
EATON www.eaton.com 37
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
TOC switches will also operate once the CONNECTED position is 5. Description and operation
reached, if TOC switches are provided in the structure. Remove the
levering-in crank at this point. 5.1 Introduction
Type VCP-W, VCPW-SE, VCP-WC, and VCPW-ND vacuum circuit
Close the circuit breaker. Any provided MOC switches will operate breakers are horizontal drawout designs for use in metal-clad switch-
and the motor closing springs will charge if control power is avail- gear compartments. Most ratings can be stacked two high in a
able. vertical section resulting in a considerable savings of floor space.
Engage the levering-in crank. The slider can be pushed in to engage Vacuum interrupters are used with all circuit breakers to close and
the levering-in crank and the circuit breaker will automatically trip. open the primary circuit. All VCP-W circuit breakers are operated by
Lever the circuit breaker out approximately halfway towards the a front mounted spring type stored energy mechanism
TEST position. (Figure 5). The stored energy mechanism is normally charged by an
Attempt to lift the circuit breaker lift/pull handle to pull the circuit electric motor, but can be charged manually with the manual main-
breaker out. The position withdrawal interlock will prevent lifting the tenance tool. Since the same basic, front accessible mechanism is
handle high enough to disengage the levering latch from the nut. used for all VCP-W circuit breakers, a minimum investment in spare
This prevents the circuit breaker from being pulled out. parts is required.
The primary insulation used with Type VCP-W circuit breakers is
Non-BPI pan assembly:
flame retardant and track resistant glass polyester except for the
Engage the levering-in crank and the circuit breaker will automatically Type VCPW-SE circuit breaker. The VCPW-SE special environment
trip and the MOC switches will operate if the circuit breaker cell is circuit breaker design utilizes cycloaliphatic epoxy for its primary
equipped with MOC switches designed to operate in the TEST posi- insulation. “Fast On” type secondary control terminations are used
tion. on Types VCP-W, VCP-WC, and VCPW-ND circuit breakers, while the
Lever the circuit breaker towards the CONNECTED position. As Type VCPW-SE circuit breaker utilizes ring type secondary control
the circuit breaker moves, protective compartment shutters will terminations.
automatically begin to open uncovering fixed primary contacts. The rest of this section describes the overall operation of the VCP-W
TOC switches will also operate once the CONNECTED position is circuit breaker as well as the function and operation of all major
reached. TOC switches are provided in the structure. Remove the sub-assemblies and/or parts. Keep in mind that VCP-W will be used
levering-in crank at this point, if equipped with this option. throughout the text when referring to any one of the three types
Close the circuit breaker. Any provided MOC switches will operate of circuit breakers, unless there is a specific difference between
and the motor closing springs will charge if control power is avail- VCP-W, VCPW-SE, VCP-WC, and VCPW-ND.
able. 5.2 Interrupter assembly
Attempt to engage the levering crank. The slider cannot be pushed Vacuum interrupters are mounted vertically and supported from the
far enough to engage the levering-in crank. Trip the circuit breaker, fixed stem which is clamped to the top conductor. The exclusive
engage the levering-in crank, and lever the circuit breaker out current transfer system consists of a series of plated, high-
approximately halfway towards the DISCONNECT/TEST position. conductivity copper leaf conductors that are pressed on the movable
Attempt to lift the circuit breaker lift/pull handle to pull the circuit interrupter stem. This design provides a multipoint contact resulting
breaker out. The position withdrawal interlock will prevent lifting the in low electrical and thermal resistance. Utilizing this non-sliding
handle high enough to disengage the levering latch from the nut. current transfer system between the movable stem and the breaker
This prevents the circuit breaker from being pulled out. main conductor eliminates the need for maintenance (Figure 18).
Multiple finger, floating type primary disconnecting contacts at the
Attempt to close the circuit breaker by pushing the manual close ends of the top and bottom conductors provide a means for
button. The circuit breaker will go trip free (springs discharge but interfacing with the primary conductors mounted in the switchgear
circuit breaker will not close). Lever the circuit breaker to the (Figure 18).
DISCONNECT/TEST position. The secondary contacts will disengage
automatically.
NOTICE
THE INTERFACE CHECKS OUTLINED IN THIS MANUAL AND THE MANUAL
PROVIDED WITH THE ASSEMBLY STRUCTURE ARE INTENDED TO VERIFY
SAFE AND PROPER OPERATION. IF OBSERVED CONDITIONS ARE NOT AS
DESCRIBED, CONTACT EATON FOR ASSISTANCE.
38 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Direct acting insulated operating rods in conjunction with the circuit In order to determine if the contacts have eroded to the extent that
breaker’s mechanism provide a fixed amount of interrupter movable the interrupter must be replaced, observe the erosion mark placed
stem motion. This motion is directly related to the interrupter’s on each moving stem from the rear of the breaker with the breaker
“wipe” and “stroke,” each of which is discussed in detail later in this closed. The interrupter is satisfactory if the mark on the stem is
section. visible with the breaker closed. The entire interrupter assembly
must be replaced if the mark is no longer visible.
5.2.1 Vacuum interrupter
Type VCP-W vacuum circuit breakers utilize vacuum interrupters for 5.2.3 Loading spring indicator
interruption and switching functions. The vacuum interrupters use The loading spring indicator is an additional method provided to
petal type copper chrome contacts for superior dielectric strength, indicate conditions within the interrupter. The indicator is used to
better performance characteristics, and lower chop current. Vacuum indicate whether the contact springs are maintaining the adequate
interruption provides the advantages of enclosed interrupters, contact pressure to keep the contacts closed. Severe contact
reduced size and weight, short interrupting time, long life, reduced erosion would result in an unacceptable indication from the indicator
maintenance, and environmental compatibility. (Figure 29). Depending upon the structural design, a small mirror
Arc interruption is simple and fast (Figure 19). In the closed posi- may be required to inspect all three poles.
tion, current flows through the interrupter. When the contacts Note that the actual configuration and/or appearance of the indica-
are opened, the arc is drawn between the contact surfaces. It is tor can vary from one circuit breaker rating to another. The actual
moved rapidly around the slotted contact surfaces by a self-induced appearance of the indicator depends upon the color of the contact
magnetic force, which prevents gross contact erosion as well as springs in a specific circuit breaker. When making this inspection,
the formation of hot spots on contact surfaces. The arc burns in an first observe the color of the contact springs to determine how the
ionized metal vapor which continually leaves the contact area and indicator will appear. Figure 29 illustrates what the actual indicator
condenses on the surrounding metal shield. appearance will be, depending upon the color of the springs.
CAUTION
THERE IS NO PROVISION FOR IN-SERVICE ADJUSTMENTS OF CONTACT
Figure 19. Graphic representation of arc interruption. WIPE AND STROKE. ALL SUCH ADJUSTMENTS ARE FACTORY SET AND
SHOULD NOT BE ATTEMPTED IN THE FIELD.
At current zero, the arc is extinguished and vapor production ceases.
Very rapid dispersion, cooling, recombination, and deionization of the 5.2.5 Phase barriers
metal vapor plasma, together with the fast condensation of metal Phase barriers on all VCP-W circuit breakers are made of glass poly-
vapor products, cause the vacuum to be quickly restored. Hence, the ester. Table 23 gives the number and configuration of the barriers
opened contacts withstand the transient recovery voltage. required for each circuit breaker rating.
5.2.2 Contact erosion indication
The purpose of a contact erosion indicator is to monitor the erosion
of the vacuum interrupter contacts, which is very minimal over time
with vacuum interrupters utilizing copper-chrome contact material. If
contact erosion reaches 1/8 in. (3.18 mm), the interrupter must be
replaced. A horizontal colored or machined contact erosion indicator
mark is located on the moving stem of the interrupter (Figures 27
and 28).
EATON www.eaton.com 39
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 23. VCP-W & VCP-WC circuit breaker barrier VCP-W (K = 1) circuit breaker barrier configurations.(cont).
configurations. Reference
Reference ANSI vacuum
ANSI vacuum breaker interrupter Number
breaker interrupter Number identification Amps diameter inches of barriers
identification Amps diameter inches of barriers
150 VCP-W40 1200 2000 3000 5 4
50VCPW-ND250 1200 4 0 5 4
50VCP-W250 1200 4 2 (OUTER) 7 2 (INNER)
2000 5 4 150 VCP-W50 1200 2000 3000 5 2 (INNER), 2 in cell
3000 7 2 (INNER) 2 in cell 5 2 (INNER), 2 in cell
50VCP-W350 1200 7 or 5 2 (INNER) 2 in cell 7 2 (INNER), 2 in cell
2000 7 or 5 2 (INNER) 2 in cell 150 VCP-W63 1200 2000 3000 7 2 (INNER), 2 in cell
3000 7 2 (INNER) 2 in cell 7 2 (INNER), 2 in cell
75VCP-W500 1200 5 or 4 2 (OUTER) 7 2 (INNER), 2 in cell
2000 5 4
3000 7 2 (INNER) 2 in cell
150VCP-W500 1200 4 or 3 2 (OUTER)
2000 5 4 m WARNING
3000 7 2 (INNER) 2 in cell
DO NOT PLACE THE CIRCUIT BREAKER IN ITS COMPARTMENT WITHOUT
150VCP-W750 1200 4 2 (OUTER)
2000 5 4 THE PHASE BARRIERS IN PLACE. THE ABSENCE OF THE BARRIERS COULD
3000 7 2 (INNER)2 in cell CAUSE A CATASTROPHIC FAILURE DURING INTERRUPTION OR OPERATION
RESULTING IN DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY
150VCP-W1000 1200 7 or 5 2 (INNER) 2 in cell
2000 7 or 5 2 (INNER) 2 in cell DAMAGE.
3000 7 2 (INNER) 2 in cell
150VCP-W63 1200 7 2 (INNER) 2 in cell The multiple finger primary disconnect contacts are silver plated and
2000 7 2 (INNER) 2 in cell waxed. In order to provide visual indication of the presence of wax,
3000 7 2 (INNER) 2 in cell a blue dye is added during the waxing process to give a bluish color
270VCP-W 630 4 2 (INNER) 2 in cell to the disconnect contacts. The wax acts as a conductive lubricant
1200 4 or 5 2 (INNER) 2 in cell without attracting dirt. For this reason the contacts do not require
2000 5 2 (INNER) 2 in cell any additional lubricant.
50VCP-W25C 1200 4 2 (INNER) 2 in cell
2000 5 2 (INNER) 2 in cell 5.3 Stored energy mechanism
3000 7 2 (INNER) 2 in cell
150VCP-W25C 1200 4 2 (INNER) 2 in cell
2000 5 4 WARNING
3000 7 2 (INNER) 2 in cell KEEP HANDS AND FINGERS AWAY FROM THE CIRCUIT BREAKER’S
50VCP-W40C 1200 5 2 (INNER) 2 in cell INTERNAL PARTS WHILE THE CIRCUIT BREAKER CONTACTS ARE CLOSED
150VCP-W40C 2000 5 2 (INNER) 2 in cell OR THE CLOSING SPRINGS ARE CHARGED. THE CIRCUIT BREAKER
50VCP-W50C 3000 7 2 (INNER) 2 in cell
150VCP-W50C CONTACTS MAY OPEN OR THE CLOSING SPRINGS DISCHARGE CAUSING
A CRUSHING INJURY. DISCHARGE THE SPRINGS AND OPEN THE CIRCUIT
50VCP-W63C 1200 7 2 (INNER) 2 in cell BREAKERS BEFORE PERFORMING ANY CIRCUIT BREAKER MAINTENANCE,
150VCP-W63C 2000 7 2 (INNER) 2 in cell
3000 7 2 (INNER) 2 in cell INSPECTION, OR REPAIR.
Note: Although only standard ANSI rated VCP-W breakers are
given in these configurations, all VCPW-SE and IEC rated The spring stored energy operating mechanism is arranged vertically
breakers follow the same barrier configurations based on in front of all VCP-W circuit breakers (Figure 5). It includes all the
the diameter of the vacuum interrupter. elements for storing the energy, closing and tripping of the circuit
breaker, as well as manual and electrical controls. The manual
VCP-W (K = 1) circuit breaker barrier configurations.
controls are all front accessible. Motion to close and open the
Reference
ANSI vacuum interrupter contacts is provided through operating rods connect-
breaker interrupter Number ing the mechanism pole shaft to the bell cranks of the interrupter
identification Amps diameter inches of barriers
assemblies.
50VCP-W25 1200 3 2 (INNER)
2000 4 4 5.3.1 Operation of stored energy mechanism
3000 5 2 (INNER)
50VCP-W40 1200 4 4 The mechanism stores the closing energy by charging the closing
2000 4 4 springs. The mechanism may rest in any one of the four positions
3000 5 2 (INNER) shown in Figure 20 and as follows:
50 VCP-W50 1200 5 2 (INNER), 2 in cell
2000 5 2 (INNER), 2 in cell a. Breaker element open, closing springs discharged;
3000 5 2 (INNER), 2 in cell b. Breaker element open, closing springs charged;
50 VCP-W63 1200 7 2 (INNER), 2 in cell
2000 7 2 (INNER), 2 in cell c. Breaker element closed, closing springs discharged; and
3000 7 2 (INNER), 2 in cell d. Breaker element closed, closing springs charged.
75 VCP-W40 1200 4 4
2000 4 4
3000 7 2 (INNER)
75 VCP-W50 1200 5 2 (INNER), 2 in cell
2000 5 2 (INNER), 2 in cell
3000 7 2 (INNER), 2 in cell
150 VCP-W25 1200 3 2 (INNER)
2000 4 4
3000 7 2 (INNER)
40 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
EATON www.eaton.com 41
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
42 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
5.3.2 Charging 5.4 Control schemes
Figure 21 is a schematic view of the spring charging parts of the There are two basic control schemes for VCP-W circuit breakers: one
stored energy mechanism. for DC control and one for AC control voltages (Figure 22), however,
The major component of the mechanism is a cam shaft assembly there are many other more advanced control schemes that can
which consists of a drive shaft to which are attached two closing be configured by the switchgear provider. There may be different
spring cranks (one on each end), the closing cam, drive plates, and control voltages or more than one tripping element, but the principal
a free-wheeling ratchet wheel. The ratchet wheel is actuated by an mode of operation is as follows.
oscillating mechanism driven by the motor eccentric. As the ratchet As soon as the control voltage is applied, the spring charging motor
wheel rotates, it pushes the drive plates which in turn rotate the automatically starts charging the closing springs. When the springs
closing spring cranks and the closing cam with it. are charged, the motor cut off LS1/bb switch turns the motor off.
The closing spring cranks have spring ends connected to them, The circuit breaker may be closed by making the control switch close
which are in turn coupled to the closing springs. As the cranks (CS/C) contact. Automatically upon closing of the circuit breaker, the
rotate, the closing springs are charged. When the closing springs motor starts charging the closing springs. The circuit breaker may be
are completely charged, the spring cranks go over dead center, and tripped at any time by making the control switch trip (CS/T) contact.
the closing stop roller comes against the spring release latch. The Note the position switch (PS1) contact in the spring release circuit
closing springs are now held in the fully charged position. in the scheme. The contact remains made while the circuit breaker
Closing springs may also be charged manually. Insert the mainte- is being levered between the TEST and CONNECTED positions.
nance tool in the manual charging socket. Move it up and down Consequently, it prevents the circuit breaker from closing automati-
approximately 28 to 38 times until a clicking sound is heard, and the cally, even though the control close contact (CS/C) may have.
closing springs charging indicator indicates “Charged.” Any further
motion of the maintenance tool will result in free wheeling of the
ratchet wheel.
EATON www.eaton.com 43
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Figure 22. Typical VCP-W DC and AC control schemes. (Dashed lines represent customer wiring and components. This is just one of
the many wiring methods that can be used to control the breaker.)
44 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Figure 23. 15 kV VCP-WXC 63 kA 1200-3000 A special power plant breakers, styles: 4A35390G10, 4A35391G10,
4A35392G10 - DC control scheme and diagram. (Dashed lines represent customer wiring and components.)
Note: This differs from the standard VCP-W breaker with the addition of a third motor-cut-off switch and other wiring changes.
EATON www.eaton.com 45
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
WARNING
15 KV VCP-WXC 63 KA 1200-3000 A SPECIAL POWER PLANT BREAKERS
STYLES: 4A35390G10, 4A35391G10, 4A35392G10 CIRCUIT BREAKERS
ARE CONFIGURED FOR POWER PLANT SPECIFIC APPLICATIONS ONLY.
POTENTIALLY SEVERE UNINTENDED CONSEQUENCES COULD RESULT IF
THESE DEVICES ARE MISAPPLIED. PLEASE CONSULT AN EATON APPLICA-
TION ENGINEER FOR ANY QUESTIONS BEFORE USE OF THESE PRODUCTS.
46 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
When the CS/C contact is made, the SR closes the circuit breaker. 5.4.4 Under-voltage trip device
If the CS/C contact is maintained after the circuit breaker closes, the
Y relay is picked up. The Y/a contact seals in Y until CS/C is opened. The under-voltage trip device for VCP-W circuit breakers is an electro-
The Y/b contact opens the SR circuit, so that even though the circuit mechanical device that operates to open the circuit breaker at 30%
breaker would subsequently open, it could not be reclosed before or less of the voltage rating of the trip coil. The device does not
CS/C was released and remade. This is the anti-pump function. open the circuit breaker at values above 60% of the voltage rating
of its trip coil. It may operate, however, to open the circuit breaker
5.4.1 Timing when the voltage across the trip coil is greater than 30%, but less
than 60% of the voltage rating of its trip coil. The circuit breaker can
The opening and closing times for the circuit breakers vary depend- be closed as long as the voltage to the trip coil is maintained at 85%
ing upon the control voltage and the power rating. Typical values for or above the rated level. The under-voltage trip device is available
VCP-W breaker elements are shown in Table 24. only as an instantaneous type with rated voltages of
48 Vdc, 125 Vdc, 250 Vdc, 120 Vac, and 240 Vac.
Table 24. Circuit breaker timing (made while the circuit breaker For a basic understanding of the operation of the under-voltage trip
is levered to the CONNECTED position). device refer to the specific items identified in Figure 24 and the
Event Milliseconds (maximum) following operation description.
Closing time 45-60
(From Initiation of close signal to contact make) 1. With the circuit breaker closed and sufficient voltage on the
Opening time 30-45 under-voltage trip device coil, the moving clapper (1) is held
(Initiation of trip signal to contact break) to the stationary yoke (2) by the magnetic force produced by
the coil (3) against the extension springs (4) pulling the moving
Reclosing time 140-165
(Initiation of trip signal to contact make) clapper apart from the yoke.
2. The moving clapper is connected to the mechanism trip “D”
shaft lever (5) by a slotted link (6).
5.4.2 Secondary disconnects
3. When the voltage to the under-voltage trip coil goes down as
The circuit breaker control wiring is arranged to connect a standard described earlier, the extension springs force overcomes the
25 point male plug with a corresponding switchgear compartment reduced magnetic force and pulls the moving clapper up. The
mounted female plug. The circuit breaker plug is fixed mounted slotted link in turn upsets the trip “D” shaft and the circuit
on the left side under the bottom pan of the mechanism (Figure breaker trips open.
15). The female plug is mounted in the compartment on a movable
carriage (Figure 12 and 13). 4. As the circuit breaker opens, the reset lever (8) connected to the
pole shaft lever (7) operates to reset the moving clapper. As long
To engage secondary contacts: as the circuit breaker remains open, the reset lever holds down
• For BPI: secondary contacts engage automatically in TEST the moving clapper to the yoke.
position 5. When the circuit breaker closes, the reset lever moves away
• For non-BPI: raise the handle and pull the carriage all the way from the moving clapper. If the under-voltage trip device coil has
towards the front (Figure 16). at least 85% of the rated voltage applied, the moving clapper is
held to the yoke by the magnetic force, even though the reset
• For automatic/manual hybrid: raise the handle, spring pres-
lever has moved up.
sure will force the carriage all the way towards the front. Check
contacts fully engaged.
To disengage secondary contacts:
• For BPI: rack the breaker to the DISCONNECT position.
• For non-BPI: push the carriage to the rear, contacts will
disengage.
• For automatic/manual hybrid: push the carriage to the rear
against spring pressure, contacts will disengage. Allow carriage
handle to catch in latch cutout of mechanism.
EATON www.eaton.com 47
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
48 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
5.5 Interlocks and interfacing Although the device is mounted in the switchgear compartment, a
brief description here will help understand the operation (Figures 13
Refer to Paragraph 4.9 of this manual for detailed information and 15). For additional information on the insertion and removal of a
concerning circuit breaker interlocks and their interfacing with a circuit breaker from its compartment, refer to paragraph 4.8.1 in this
switchgear structure compartment. In addition, refer to the instruc- manual.
tion manual supplied with the switchgear assembly.
The levering device consists of a racking screw, a racking nut,
5.6 Levering mechanism moving block, two side rails, and a slider. In the TEST position, the
moving block is all the way to the front of the racking screw. As
BPI pan assembly: (Figure 12) the circuit breaker is pushed into the breaker cell, the levering latch
The purpose of the levering device is to move the circuit breaker snaps on the moving block. In order to turn the racking nut, push
between the DISCONNECT, TEST, and CONNECTED positions. For on the slider with the levering-in crank until fully engaged. Turning
Type VCP-W circuit breakers, the device is a racking screw, racking the levering-in crank clockwise while still pushing forward on the
nut, and moving block. slider advances the circuit breaker toward the CONNECTED position.
Although the device is mounted in the switchgear compartment, a During this travel, the Trip Floor Tripper is lifted up holding the circuit
brief description here will help understand the operation (Figures 12 breaker trip free. When the circuit breaker reaches the CONNECTED
and 15). For additional information on the insertion and removal of a position, the levering-in crank will “spin-free” and cannot advance
circuit breaker from its compartment, refer to paragraph 4.8.1 in this the breaker any further. A red flag indicates that the circuit breaker
manual. is fully engaged.
The levering device consists of a racking screw, a racking nut, If the circuit breaker is closed in the CONNECTED position, the
moving block, two side rails, and a slider. In the DISCONNECT slider cannot be pushed forward to permit engagement of the
position, the moving block is all the way to the front of the racking levering-in crank due to the “Z” shaped slider interlock.
screw. As the circuit breaker is pushed into the breaker cell, the After tripping the circuit breaker, push on the slider with the levering-
levering latch snaps on the moving block. In this position the front in crank until fully engaged. Turning the levering-in crank clockwise
cover of the breaker will be aligned with the black line associated while still pushing forward on the slider advances the circuit breaker
with the green area of the label. In order to turn the racking nut, toward the DISCONNECT position. This position is indicated by no
push on the slider with the levering-in crank until fully engaged. further motion of the crank and by the green flag indicating that the
Turning the levering-in crank clockwise while still pushing forward circuit breaker has reached the TEST position
on the slider advances the circuit breaker toward the TEST (approxi-
mately six full turns) position. In this position, the front cover of the Automatic/manual hybrid secondary (optional - Figure 46): It will
breaker will be aligned with the black line associated with the yellow function the same as the Non-BPI pan assembly above due to the
area of the label. During this travel, the trip floor tripper is lifted replacement of the “L” bracket with the “Z” bracket.
up holding the circuit breaker trip free. When the circuit breaker
reaches the TEST position, the breaker can be closed. Turning the 5.7 Operations counter
levering-in crank clockwise while pushing forward advances the All circuit breakers are equipped with a mechanical operations
circuit breaker toward the CONNECT position. counter. As the circuit breaker opens, the linkage connected to the
Rotate the levering-in crank in a clockwise direction until the torque pole shaft lever advances the counter reading by one (Figure 5).
limiter on the levering-in crank “breaks free.” As a position verifica-
tion: 5.8 Ground contact
The ground contact is an assembly of spring loaded fingers providing
• BPI pan assembly: the breaker cover plate MUST align with the a disconnectable means for grounding the circuit breaker chassis,
black line associated with the CONNECTED position, location after it has been inserted into a switchgear structure. The ground
shown on the BPI label (Figure 12, item 7). contact is located on the left side of the circuit breaker under the
If the circuit breaker is closed in the CONNECTED position, the mechanism bottom pan. An extension of the switchgear ground bus
slider can be pushed forward to permit engagement of the levering- is secured to the cell floor in such a position to engage the ground
in crank which will trip the breaker by pushing up on the trip floor contact automatically, when the circuit breaker is moved into the
tripper. This functionality is enabled by the “L” shaped slider inter- DISCONNECT or DISCONNECT / TEST position. It remains engaged
lock. in all other circuit breaker positions within the cell (Figures 12, 13,
The breaker can be moved to the TEST position by pushing forward and 15).
on the levering-in crank and turning the racking screw counterclock-
5.9 MOC and TOC switch operations
wise until the breaker reaches the TEST position.
The breaker can be moved to the DISCONNECT position by pushing The mechanism operated cell (MOC) switch operator is coupled to
forward on the levering-in crank and turning the racking screw coun- the pole shaft (Figure 15). In the TEST and CONNECTED positions
terclockwise until the breaker reaches the DISCONNECT position of the circuit breaker, the operator aligns directly above the MOC
(approximately six full turns). switch bell crank levers in the cell. As the circuit breaker closes,
the operator moves down and pushes the bell crank lever to change
The circuit breaker levering latch can be disengaged only when the the MOC switch contact position. Thus, the MOC switch contacts
circuit breaker is in the DISCONNECT position by lifting the lift/pull operate in the same manner as the auxiliary switch contacts in the
handle. As the circuit breaker is withdrawn, it comes out with the circuit breaker. Although the MOC switch operator is provided on all
contacts open and the springs discharged because of the close floor circuit breakers, the cell mounted MOC switches are only provided
tripper and trip floor tripper interlocks. when specified with the switchgear order. The standard electri-
cal connector for the control wires is a plug on style connector.
Non-BPI pan assembly: (Figure 13) Optional ring tongue lug connectors can be provided.
The purpose of the levering device is to move the circuit breaker The truck operated cell (TOC) switch operator is mounted inside the
between the TEST and CONNECTED positions. For Type VCP-W right corner of the circuit breaker cell (Figure 15). It operates the
circuit breakers, the device is a racking screw, racking nut, and TOC switch as the circuit breaker moves to the CONNECTED posi-
moving block. tion in the switchgear cell.
EATON www.eaton.com 49
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
6. Inspection, maintenance, and trouble- 3. Fault interruptions have the greatest impact on contact erosion
inside of the vacuum interrupters. Circuit breakers that have
shooting been subjected to 15 full rated fault interruptions should be
6.1 Introduction immediately inspected and the schedule for inspection and
maintenance should be re-evaluated based upon the inspec-
tion results. Additionally, because of the variability of system
WARNING fault characteristics, if there are any customer uncertainties in
· DO NOT WORK ON A BREAKER ELEMENT WITH PRIMARY POWER the records of the magnitude, duration, or other fault details,
increased inspection frequency should be considered.
APPLIED.
4. Follow the steps presented in paragraph 6.3 entitled “Inspection
· DO NOT WORK ON A BREAKER ELEMENT WITH SECONDARY CONTACTS and Maintenance Procedures” for scheduled programs.
CONNECTED. 5. Create and maintain a dated permanent record of all inspections,
maintenance performed, actions taken, observations made,
· DO NOT WORK ON A BREAKER ELEMENT WITH SPRINGS CHARGED OR and measurements taken. Not only will this provide valuable
CONTACTS CLOSED. historical information, it can help to establish whether or not the
present schedule needs to be adjusted.
· DO NOT DEFEAT ANY SAFETY INTERLOCKS. 6. Perform ongoing visual inspections, when possible, of all equip-
ment on a regular basis. Be alert for an accumulation of dirt
· DO NOT LEAVE MAINTENANCE TOOL IN THE SOCKET AFTER CHARGING in and around the circuit breaker elements, loose hardware or
discolored insulation.
THE CLOSING SPRINGS.
· DO NOT STAND LESS THAN ONE METER AWAY FROM THE BREAKER For assistance in establishing or updating a detailed inspection and
maintenance schedule for a specific application, please contact your
ELEMENT WHEN TESTING FOR VACUUM INTEGRITY.
local Eaton representative.
FAILURE TO FOLLOW ANY OF THESE INSTRUCTIONS MAY CAUSE DEATH, Eaton’s vacuum interrupters are tested to exceed the minimum fault
SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. SEE SECTION 2 - SAFE interruptions as required by IEEE/ANSI and IEC Standards without
PRACTICES - FOR MORE INFORMATION. inspection. Please contact your local Eaton representative if you
would like a copy of the life curve of the vacuum interrupters in your
specific circuit breakers.
6.2 Frequency of inspection and maintenance
In addition to the instructions in this instruction book, Eaton has
Periodic inspections and associated maintenance are essential to created a visual tool to assist maintenance personnel. Contact
the safe and reliable operation of VCP-W vacuum circuit breaker Eaton for the Visual Instruction Booklet Essentials (VIBE) which is
elements. The inspection frequency and associated maintenance an interactive PDF with embedded videos to show how to perform
recommended are intended to insure the best possible ongoing many common types of field testing and part replacements.
service. It is imperative that an established schedule be followed.
To establish an exact schedule for a specific installation, use the
following guidelines.
6.2.1 Qualified personnel
1. Customers such as utilities having extensive experience with For the purpose of operating this type of equipment, only individuals
power distribution components should schedule their inspection thoroughly trained in the operation of power circuit breakers and
and maintenance intervals using well established best practices associated equipment, and having knowledge of connected loads
in their industry. may be considered to be qualified.
2. All other customers should use the following guidelines as good Refer to further definitions in the National Electrical Safety Code.
conservative practice:
For the purpose of inspecting and maintaining such equipment,
a. For installations defined as normal service conditions per a qualified person must also be trained in regard to the hazards
IEEE C37.20.2 and considered clean, non-corrosive environ- inherent to working with electricity and the proper way to perform
ments, inspect, and maintain each circuit breaker every 500 such work. Such an individual should be able to de-energize, clear,
operations or 10 years, whichever comes first. If it is deter- and tag circuits in accordance with established safety practices. In
mined after completing the “Inspection and maintenance addition, these individuals should have access to and be trained in
procedures” in section 6.3 of this manual that the breaker the use of protective equipment, such as rubber gloves and flash
is still like new based on visual inspection and performance, clothes.
then the next maintenance interval shouldn’t exceed 500
operations or 10 years from the date of the inspection. All personnel should be familiar with and understand the material
presented in this instruction manual and other related manuals.
b. For special conditions such as frequent circuit breaker
element operation, contaminated environments, and high
temperature/humidity conditions, the inspection frequency
should be a minimum of twice per year.
50 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
6.2.2 General torque guidelines Table 25. Torque guidelines.
Bolts and screws must be properly torqued. This is especially Bolt size Torque lb-in (lb-ft)
true if part(s) and/or accessory(ies) are added or replaced. Table 8 - 32 24
25 provides guidelines on torque levels. The table is intended as 10 - 32 36
a general guideline and should be applied in conjunction with the 1/4 - 20 72 (6 lb-ft)
experience and good judgment of the individual performing the
work. 5/16 - 18 144 (12 lb-ft)
3/8 - 16 300 (25 lb-ft)
1/2 - 13 540 (45 lb-ft)
CAUTION
OVER TORQUING CAN CAUSE PERMANENT DAMAGE WHILE UNDER
TORQUING WILL NOT PROVIDE THE PROPER CLAMPING FORCE AND MAY
EVENTUALLY WORK LOOSE.
X-washer
EATON www.eaton.com 51
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
6.3 Inspection and maintenance procedures
No./section Inspection item Criteria Inspection method Corrective action
1.Insulation Drive insulator, barriers, No dirt Visual check Clean with lint-free cloth
and and or
stand-off insulators No cracking Visual check replace cracked piece.
Insulation integrity Main circuit to ground Withstand Hipot tester Clean and retest or replace .
Between main circuit terminals Withstand Hipot tester Clean and retest or replace.
Control circuit to ground Withstand Hipot tester Clean and retest or replace.
2. Power elements Vacuum interrupters Visibility of contact Visual - Close the circuit breaker If a mark is not visible, then check if the
erosion marks and observe if all black, blue pole unit plastic bushing is intact on
or machined groove marks on the moving stem of the VI just below
moving stems are visible the cup plate. If the bushing is intact,
then replace the interrupter assembly
and perform contact wipe check. If the
bushing is NOT intact, then glue back the
bushing to the cup plate and observe the
mark again.
Contact wipe indicator visible Refer to paragraph 6.5 Replace interrupter assembly.
Adequate vacuum Proceed with integrity check as If integrity check is not satisfactory,
described in Paragraph 6.4 replace interrupter assembly.
Primary disconnects Dirt on ceramic body Visual check Clean with lint-free cloth.
Pole unit X-washers Every 1000 operations Operation counter Replace all X-washers per Figure 26.
for 150 VCP-W 63
3. Control circuit parts Closing and tripping device Smooth and correct operation Test closing and tripping of the Replace any defective device. Identify
including disconnects by control power circuit breaker twice per trouble-shooting chart .
Wiring Securely tied in proper place Visual check Repair or tie as necessary.
Dust or foreign matter No dust or foreign matter Visual check Clean as necessary.
Lubrication Smooth operation and no Sight, feel and per maintenance Refer to Figure 25 and paragraph 6.10
excessive wear schedule and lubricate very sparingly with mineral
oil.
Deformation or excessive wear No excessive deformation or Visual and operational Remove cause and replace parts.
wear
Manual ooperation Smooth operation Manual charging, closing and Correct per troubleshooting chart if
tripping necessary.
CloSure test 0.6 inch over-travel CloSure Test (6.9.1) If < 0.6, contact your local Eaton Sales
and Service Center.
52 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
6.4 Vacuum interrupter integrity test CAUTION
Vacuum interrupters used in Type VCP-W vacuum circuit breaker SOME DC HIGH POTENTIAL UNITS, OPERATING AS UNFILTERED HALF-
elements are highly reliable interrupting elements. Satisfactory WAVE RECTIFIERS, ARE NOT SUITABLE FOR USE TO TEST VACUUM
performance of these devices is dependent upon the integrity of the INTERRUPTERS BECAUSE THE PEAK VOLTAGE APPEARING ACROSS THE
vacuum in the interrupter and the internal dielectric strength. Both INTERRUPTERS CAN BE SUBSTANTIALLY GREATER THAN THE VALUE READ
of these parameters can be readily checked by a one minute AC high ON THE METER.
potential test. Refer to Table 26 for the appropriate test voltage.
During this test, the following warning must be observed. 6.5 Contact erosion and wipe
Since the contacts are contained inside the interrupter, they remain
WARNING clean and require no maintenance. However, during high current
APPLYING ABNORMALLY HIGH VOLTAGE ACROSS A PAIR OF CONTACTS interruptions there may be a minimum amount of erosion from the
IN VACUUM MAY PRODUCE X-RADIATION. THE RADIATION MAY contact surfaces. Maximum permitted erosion is about 1/8 in.
INCREASE WITH THE INCREASE IN VOLTAGE AND/OR DECREASE IN (3.18 mm). To determine contact erosion, close the breaker and
CONTACT SPACING. X-RADIATION PRODUCED DURING THIS TEST observe the vacuum interrupter moving stem from the rear of the
WITH RECOMMENDED VOLTAGE AND NORMAL CONTACT SPACING breaker. If the mark on each stem is visible, erosion has not reached
IS EXTREMELY LOW AND WELL BELOW MAXIMUM PERMITTED BY maximum value thus indicating satisfactory contact surface of the
STANDARDS. HOWEVER, AS A PRECAUTIONARY MEASURE AGAINST interrupter. If the mark is not visible, the pole unit assembly must be
POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE replaced (Figures 27 and 28).
AND/OR BELOW NORMAL CONTACT SPACING, IT IS RECOMMENDED THAT The adequacy of contact wipe can be determined by observing the
ALL OPERATING PERSONNEL STAND AT LEAST 13 FEET (4 METERS) AWAY vacuum interrupter side of the operating rod assembly on a closed
IN FRONT OF THE BREAKER ELEMENT. circuit breaker. Figure 29 shows the procedure for determining the
contact wipe. If the wipe is not adequate, the vacuum interrupter
With the breaker element open, connect all top primary studs (bars) assembly (pole unit) must be replaced. A field adjustment is not
together and to the high potential machine lead. Connect all bottom possible. Refer to IL131030EN for the pole unit replacement
studs together and ground them along with the breaker frame. Start procedure..
the machine at zero potential, increase to appropriate test voltage
and maintain for one minute.
WARNING
A successful withstand indicates that all interrupters have a satisfac-
tory vacuum level. If there is a break-down, the defective interrupter FAILURE TO REPLACE A POLE UNIT ASSEMBLY, WHEN CONTACT EROSION
or interrupters should be identified by an individual test and replaced MARK IS NOT VISIBLE OR WIPE IS UNSATISFACTORY, WILL CAUSE THE
before placing the breaker in service. BREAKER TO FAIL TO INTERRUPT AND THEREBY CAUSE PROPERTY
DAMAGE OR PERSONAL INJURY.
WARNING
AFTER THE HIGH POTENTIAL IS REMOVED, AN ELECTRICAL CHARGE
MAY BE RETAINED BY THE VACUUM INTERRUPTERS. FAILURE TO
DISCHARGE THIS RESIDUAL ELECTROSTATIC CHARGE COULD RESULT IN
AN ELECTRICAL SHOCK. ALL SIX PRIMARY TERMINALS AND THE CENTER
RING OF EACH VACUUM INTERRUPTER OF THE CIRCUIT BREAKER SHOULD
BE GROUNDED TO REDUCE THIS ELECTRICAL CHARGE BEFORE COMING IN
CONTACT WITH THE PRIMARY CIRCUIT.
EATON www.eaton.com 53
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Cup
plate
Figure 27. Vacuum interrupter showing contact erosion indicator Figure 28. Vacuum interrupter showing contact erosion indica-
with breaker open (shown here for clarity purposes only). tor with breaker closed (indicators are checked only when the
breaker is closed).
Any part of red or gray indicator visible Any part of “T” shape indicator visible Any part of indicator visible
– “Wipe” satisfactory. – “Wipe” satisfactory. – “Wipe” satisfactory.
Red or gray indicator not visible “T” shape indicator not visible Indicator not visible
– “Wipe” unsatisfactory. – “Wipe” unsatisfactory. – “Wipe” unsatisfactory.
Figure 29. Wipe indication procedure (performed only with the breaker closed).
54 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
6.6 Insulation 6.9 Mechanism check
Type VCP-W circuit breaker insulation maintenance primarily consists Make a careful visual inspection of the mechanism for any loose
of keeping all insulating surfaces clean. This can be done by wiping parts such as bolts, nuts, pins, and rings. Check for excessive wear
off all insulating surfaces with a dry lint free cloth or dry paper towel. or damage to the circuit breaker components. Operate the circuit
In case there is any tightly adhering dirt that will not come off by breaker several times manually and electrically. Check the closing
wiping, it can be removed with mild solvent or distilled water. Be and opening times to verify that they are in accordance with the
sure that the surfaces are dry before placing the circuit breaker in limits in Table 24.
service. If a solvent is required to cut dirt, use Stoddard’s Solvent
Eaton 55812CA or commercial equivalent. Secondary control wiring 6.9.1 CloSure™ test
also requires inspection for insulation damage. Introduction
6.7 Insulation integrity check The CloSure test is a simple yet extremely effective means to deter-
mine and monitor the ability of the mechanism to close the breaker
Primary circuit: contacts fully. It provides a quantitative measure of the extra
The integrity of primary insulation may be checked by the 60 Hz AC energy available in terms of over travel in inches to close the breaker
high potential test. The test voltage depends upon the maximum contacts to their full extent. It maybe used periodically to monitor
rated voltage of the breaker. For the breaker elements rated 4.76 kV, the health of the mechanism.
8.25 kV, 15 kV, and 27 kV, the test voltages are 15 kV, 27 kV, 27 kV, At times, circuit breakers are called upon to operate mechanism
and 45 kV RMS respectively. Conduct the test as follows. operated cell (MOC) switches that place extra load upon the closing
Close the breaker. Connect the high potential lead of the test mechanism of the circuit breaker. If this load is excessive, it can
machine to one of the poles of the breaker. Connect the remaining prevent the circuit breaker from closing fully. In such a case, it is
poles and breaker frame to ground. Start the machine with output important to determine that the circuit breaker will close fully. The
potential at zero and increase to the test voltage. Maintain the test CloSure test provides this assurance.
volt-age for one minute. Repeat for the remaining poles. Successful
withstand indicates satisfactory insulation strength of the primary General information
circuit. The CloSure test can be per-formed on the VCP-W, VCP-WR, VCPW-
If a DC high potential machine is used, make certain that the peak ND, DHP-VR, W-VACR, and W-VAC lines of vacuum circuit breakers.
voltage does not exceed the peak of the corresponding AC RMS test Refer to Table 28 a for list of circuit breakers. If the CloSure travel
voltage. obtained is as specified, the mechanism performance is satisfactory.
If the CloSure travel does not conform as shown in Figure 36, con-
Secondary circuit: tact Eaton for further information (see Step 13).
Isolate the motor by pulling apart the two insulated quick discon-
necting terminals in the two motor leads provided for this purpose, WARNING
or remove the two motor wires from the ring tongue terminals
(Figure 5). Connect all points of the secondary disconnect pins with DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE OR TESTS ON
shooting wire. Connect this wire to the high potential lead of the THE EQUIPMENT WHILE IT IS ENERGIZED. NEVER PUT YOUR HANDS NEAR
test machine. Ground the circuit breaker frame. Starting with zero, THE MECHANISM WHEN THE CIRCUIT BREAKER IS IN THE CHARGED OR
increase the voltage to 1125 Vac RMS, 60 Hz. Maintain the voltage CLOSED POSITION. DEATH OR SEVERE PERSONAL INJURY CAN RESULT
for one minute. Successful withstand indicates satisfactory insula- FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO
tion strength of the secondary control circuit. Remove the shooting VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS
wire and reconnect motor leads. FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES.
6.8 Primary circuit resistance check 6.10 Megger and power factor testing
Since the main contacts are inside the vacuum chamber, they Both the megger and power factor type testing of high voltage
remain clean and require no maintenance at any time. Unlike many insulation are not recognized by IEEE as a design, production, or
typical circuit breaker designs, VCP-W breakers do not have sliding conformance test for determining product acceptance during initial
contacts at the moving stem either. Instead they use a highly reli- commissioning. If an end user wishes to use these tests for trend-
able and unique flexible clamp design that eliminates the need for ing purposes, then they should record the initial readings during
lubrication and inspection for wear. commissioning along with temperature and humidity during the
If desired, the DC resistance of the primary circuit may be measured testing. The trend of the test results should be tracked over the life
as follows: of the product and any abnormalities should be investigated.
• Close the circuit breaker, pass at least 100 amps DC current Safety precautions
through the circuit breaker. With a low resistance instrument, Read and understand these instructions before attempting any main-
measure resistance across the studs on the circuit breaker side of tenance, repair, or testing on the breaker. The user is cautioned to
the disconnects for each pole. observe all recommendations, warnings, and cautions relating to the
The resistance should not exceed the values shown in Table 27. safety of personnel and equipment.
The recommendations and information contained herein are based
Table 27. Typical resistance measurements. on Eaton experience and judgment, but should not be considered to
Rated continuous current Resistance be all-inclusive or covering every application or circumstance which
(amperes) (microohms) may arise. If further information is required, you should consult
1200 60 Eaton.
2000 40
3000 20
EATON www.eaton.com 55
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Testing procedures
Assuming that the breaker is safely pulled out to the Test/Disconnect
position in the enclosure or placed on the workbench, follow this
procedure to perform the CloSure test. For further instructions on
disconnecting the circuit breaker consult Section 4 of this manual. If
the enclosure is equipped with the MOC operating in the test posi-
tion also, make certain that the MOC is connected to operate.
1. On the front cover identify the status indicators. Make sure the
closing spring status indicates “Discharged” and the main
contact indicator shows “Open” (Figure 7).
2. Remove the circuit breaker front cover. Be sure to save the
original fasteners for reassembly.
3. Cut a piece of one-inch (25.4 mm) wide drafting/masking tape
approximately 8 to 10 in. (203 to 254 mm) long.
4. Place the tape around the cam starting from the bottom up.
Make certain that the tape adheres well to the cam surface (see Figure 34. Attaching CloSure test tool at “B”.
Figures 30, 31, and 32).
5. Mount the transparent CloSure test tool with two bolts and
washers. Refer to Figures 43, 44, and Table 28 for appropriate
mounting holes. Hand tighten the bolts (Figures 33, 34, 43,
and 44).
56 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
6. A Sanford® Sharpie® black fine point permanent marker, item no.
30001, is recommended for this next step. Place the marker tip
in the proper hole (“C”). Refer to Figure 43 and make a heavy
mark on the tape as shown in Figure 34.
Figure 36. Manually closing the circuit breaker with the marker
in hole “C”.
EATON www.eaton.com 57
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
10. Remove the marker from hole “C”.
11. Push the “push to open” clapper to open the circuit breaker.
5.19 in.
5.19 in.
58 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
13. Evaluate the CloSure performance by comparing the test tape For breakers built after 1/1/2018
with the illustrations in Figure 41. If the marking is similar to All parts that require lubrication have been lubricated during the
42, detail A, measure the over travel “x”. If “x” is greater than assembly with Eaton’s new synthetic grease. Over a period of time,
or equal to 0.6 in. (15.2 mm), the circuit breaker performance this lubricant may be pushed out of the way or degrade. Proper
is satisfactory. If “x” is less than 0.6 in. (15.2 mm) or if the lubrication at regular intervals is essential for maintaining the reliable
marking is similar to 42, detail B or 42, detail C, immediately performance of the mechanism. Every 500 operations or 10 years
contact the Product Integrity Center for Technical Support at whichever comes first, the circuit breaker should be lubricated.
(412) 787-6518.
Roller bearings are used on the pole shaft, the cam shaft, the main
14. Remove the CloSure tool. Reassemble the front cover onto the link, and the motor eccentric. These bearings are packed at the
circuit breaker. Return the circuit breaker to its original configura- factory with a top grade synthetic grease which will be effective for
tion and setup. 10 years. They should not be disturbed.
6.11 Mechanism lubrication If it becomes necessary to disassemble the mechanism, the bear-
ings and related parts should be thoroughly cleaned. Remove old
For breakers built prior to 01/01/18 grease in a good grease solvent. Do not use carbon tetrachloride.
All parts that require lubrication have been lubricated during the They should then be washed in light machine oil until the cleaner is
assembly with molybdenum disulfide grease (Eaton Material No. removed. After the oil has been drawn off, the bearings should be
53701 QB) which is no longer available. Over a period of time, packed with Eaton’s synthetic grease.
this lubricant may be pushed out of the way or degrade. Proper
lubrication at regular intervals is essential for maintaining the reliable 6.12 Finger clusters and switchgear stab lubrication
performance of the mechanism. Once a year or every 500 opera- The breaker finger clusters are shipped with a lubricating blue wax
tions whichever comes first, the circuit breaker should be lubricated, applied from the factory and the switchgear stabs are shipped with a
as shown in Figure 24, with a drop of mineral oil. lubricating blue wax applied from the factory. The blue wax is used
The mineral oil shall be “3-In-One” Multi-Purpose Oil. Fluorosilicone instead of grease lubrication purposes for the following reasons:
oil is not compatible with Eaton’s grease and shall not be used in
the lubrication of Eaton breakers. 1. The blue wax has a higher melting point and a lower viscosity
point then grease. So the blue wax will stay on warm contact
Table 28. Closure tool mounting/testing locations by circuit surfaces instead of dripping off like some greases.
breaker type. 2. Dust particles are less likely to stick to blue wax as opposed to
Approximate grease. Dirty grease can be a poor conductor.
mechanism Upper Lower Marker
cabinet mounting mounting placement
Breaker line width (inch) hole hole hole 3. The blue additive is added by Eaton to provide the ability to
perform visual checks of the breaker finger cluster engagement
DHP-VR 20 A1 B2 C2 on the switchgear stabs.
29 A1 B1 C5
VCPW-ND 20/21 A1 B2 C2 The breaker should never be levered into the cell when the blue wax
VCP-W, 29 A1 B2 C5 has been removed from the breaker finger clusters or the switchgear
33 A2 B2 C6 stabs.
VCP-WR 18 A1 B2 C1 When routine maintenance is performed on the breaker or switch-
20 A1 B2 C2 gear, the blue wax can be reapplied under de-energized conditions.
29 A1 B2 C5 The blue wax can be purchased from Eaton by ordering material
W-VAC, 18 A1 B2 C1 code number 83342CE.
W-VACR 25 A1 B1 C4
6.13 Main contacts to switchgear primary engagement
33 A2 B2 C6
When the circuit breaker is in the complete and fully connected
After lubrication, operate the circuit breaker several times manually position, the circuit breaker main contacts should be engaged on the
and electrically. flat portion of the stationary primary contacts and not on the leading
Roller bearings are used on the pole shaft, the cam shaft, the radius.
main link, and the motor eccentric. These bearings are packed at
6.14 How to determine the manufacturing date
the factory with a top grade grease, as specified by code, which
normally should be effective for many years. They should not be The date code is located in the serial number - see the example:
disturbed unless there is definite evidence of sluggishness, dirt, or
parts are dismantled for some reason.
Serial no. X X X X X X X XX
If it becomes necessary to disassemble the mechanism, the bear-
ings and related parts should be thoroughly cleaned. Remove old
grease in a good grease solvent. Do not use carbon tetrachloride. The first four characters provide the date information. The first two
They should then be washed in light machine oil until the cleaner is characters are the year and the next two characters are the month.
removed. After the oil has been drawn off, the bearings should be The last five characters are the production unit identifier.
packed with Eaton’s synthetic grease.
Eaton’s synthetic grease can be mixed with the molybdenum disul-
fide grease with no side effects.
EATON www.eaton.com 59
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
6.15 Troubleshooting chart
Symptom Inspection Probable defects
Fails to close
• Closing springs not charged • Control circuit • Control power (fuse blown or switch off)
• Secondary disconnects
• Motor cut-off switch (poor or burned contacts, lever not operational)
• Terminals and connectors (poor or burned contacts)
• Motor (brushes worn or commutator segment open)
• Mechanism • Pawls (slipping or broken)
• Ratchet wheel (teeth worn or broken)
• Cam shaft assembly (sluggish or jammed)
• Oscillator (reset spring off or broken)
• Closing spring charged but breaker does • No closing sound • Control power (fuse blown or switch off)
not close (close coil does not pick up) • Secondary disconnects
• Anti-pump relay Y relay N. C. (contact open or burned or relay picks up)
• Close coil (open or burned)
• Latch check switch (contact open-bad switch or trip bar not reset)
• Auxiliary switch (B contact open or burned)
• Motor cut-off (contacts open or burned)
• Trip coil assembly (clapper fails to reset)
• Closing sound but no close • Pole shaft (not open fully)
• Trip latch reset spring (damaged or missing)
• Trip bar-d shaft (fails to remain reset)
• Trip latch-hatchet (fails to remain reset)
• Trip floor tripper (fails to remain reset)
• Close latch (binding)
• Close latch roller (binding)
• Trip circuit energized
Undesirably closes
• Control circuit • Close circuit (CS/C getting shorted)
• Mechanism • Close release latch (fails to reset)
• Close floor tripper (fails to reset)
Fails to trip
• No trip sound • Control circuit • Control power (fuse blown or switch off)
• Secondary disconnect
• Auxiliary switch (A contact not making, poor or burned)
• Trip coil (burned or open)
• Terminals and connections (poor or burned or open)
• Trip mechanism • Trip clapper (jammed)
• Trip sound but no trip • Trip mechanism • Trip bar, trip latch (jammed)
• Pole shaft (jammed)
• Operating rod assembly (broken or pins out)
• Vacuum interrupter
(one or more welded)
Undesirably trips
• Control circuit • Control Power (CS/T Switch, remains made)
• Mechanism • Trip coil clapper (not resetting)
• Trip bar or trip latch (poor engagement of mating or worn surfaces)
• Trip bar reset spring (loss of torque)
60 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
7. Renewal parts 7.1.1 Ordering instructions
7.1 General 1. Always specify the breaker rating information and shop order
In order to minimize production downtime, it is recommended number.
that an adequate quantity of spare parts be carried in stock. The 2. Describe the item, give the style number, and specify the quan-
quantity will vary from customer to customer, depending upon the tity required.
service severity and continuity requirements. Each customer should 3. Provide the style number from the interrupter assembly.
develop their own stock level based on operating experience. Refer
to Tables 29 and 30 for guidance. 4. Specify the voltage for electrical components.
5. Specify the method of shipping desired.
6. Send all orders or correspondence to the nearest Eaton sales
office.
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
Interrupter Assembly
1 50/250, 1200 A-58 kA 8297A02H01 8297A02H02 8297A02H03 3
2 50/250, 1200 A-58 kA (4” SC) 8297A02H21 8297A02H22 3
3 50/250H, 1200 A-78 kA 8297A05H01 8297A05H02 3
4 50/250, 2000 A-58 kA 8297A03H01 8297A03H02 3
5 50/250, 2000 A-58 kA (5” SC) 8297A03H21 8297A03H22 3
6 50/250H, 2000 A-78 kA 8297A06H01 8297A06H02 3
Interrupter Assembly
7 50/250, 3000 A-58 kA 8297A04H01 8297A04H02 3
8 50/250H, 3000 A-78 kA 8297A07H01 8297A07H02 3
Interrupter Assembly
9 50/350, 1200 A-78 kA 8297A08H01 8297A08H02 3
10 50/350, 1200 A-78 kA (5” SC) 8297A08H21 8297A08H22 3
11 50/350C, 1200 A-78 kA 8297A08H23 8297A08H24 3
12 50/350, 2000 A-78 kA 8297A09H01 8297A09H02 3
13 50/350, 2000 A-78 kA (5” SC) 8297A09H21 8297A09H22 3
14 50/350C, 2000 A-78 kA 8297A09H23 8297A09H24 3
Interrupter Assembly
15 50/350, 3000 A-78 kA 8297A10H01 8297A10H02 3
16 50/63, 1200 A 8297A29H05 3
17 50/63, 2000 A 8297A30H05 3
18 50/63, 3000 A 8297A31H03 3
19 50VCP-W40C, 3000 A 8297A10H23 3
20 50VCP-W50C, 3000 A 8297A10H23 3
Interrupter Assembly
21 75/500, 1200 A-66 kA (5”) 8297A11H01 8297A11H02 3
22 75/500, 1200 A-66 kA (4”) 8297A11H03 8297A11H04 3
23 75/500, 2000 A-66 kA 8297A12H01 8297A12H02 3
24 50VCP-WC, 1200 A 8297A11H23 3
25 50VCP-WC, 2000 A 8297A12H23 3
Interrupter Assembly
26 75/500, 3000 A-66 kA 8297A13H01 8297A13H02 3
27 75VCP-W50C, 3000 A 8297A13H23 3
Interrupter Assembly
28 150/500, 1200 A-37 kA (4”) 8297A17H01 8297A17H02 3
29 150/500, 1200 A-37 kA (3” SC) 8297A17H21 8297A17H22 3
30 150/500H, 1200 A-58kA 8297A20H01 8297A20H02 3
31 150/500, 2000 A-37 kA 8297A18H01 8297A18H02 3
32 150/500H, 2000 A-58 kA 8297A21H01 8297A21H02 3
33 150VCP-W25C, 1200 A 8297A20H23 3
EATON www.eaton.com 61
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
Interrupter Assembly
34 150/500, 3000 A-37 kA 8297A19H01 8297A19H02 3
35 150/500, 3000 A-58 kA 8297A22H01 8297A22H02 3
Interrupter Assembly
36 150/750, 1200 A-58 kA 8297A23H01 8297A23H02 3
37 150/750H, 1200 A-77 kA 8297A26H01 8297A26H02 3
38 150/750, 2000 A-58 kA 8297A24H01 8297A24H02 3
39 150/750H, 2000 A-77 kA 8297A27H01 8297A27H02 3
Interrupter Assembly
40 150/750, 3000 A-58 kA 8297A25H01 8297A25H02 3
41 150/750H, 3000 A-77 kA 8297A28H01 8297A28H02 3
Interrupter Assembly
42 150/1 000, 1200 A-77 kA (7”) 8297A29H01 8297A29H02 3
43 150/1 000, 1200 A-77 kA (5”) 8297A29H03 8297A29H04 3
44 150/1 000, 1200 A-77 kA (5”)LT 8297A29H21 8297A29H22 3
45 150/1000C, 1200 A-77 kA (5”)LT 8297A29H23 8297A29H24 3
46 150/1 000, 2000 A-77 kA (7”) 8297A30H01 8297A30H02 3
47 150/1 000, 2000 A-77 kA (5”) 8297A30H03 8297A30H04 3
48 150/1 000, 2000 A-77 kA (5”)LT 8297A30H21 8297A30H22 3
49 150/1000C, 2000 A-77 kA (5”)LT 8297A30H23 8297A30H24 3
50 150VCP-W40C, 1200 A 8297A29H36 3
51 1 50VCP-W40C, 2000 A 8297A30H36 3
52 150VCP-W50C, 1200 A 8297A29H37 3
53 150VCP-W50C, 2000 A 8297A30H37 3
Interrupter Assembly
54 150/1000, 3000 A-77 kA 8297A31H01 8297A31H02 3
55 150/63, 1200 A 8297A29H31 3
56 150/63, 2000 A 8297A30H31 3
57 150/63, 3000 A 8297A31H31 3
Interrupter Assembly
58 270/16/22/25-630 A-37 kA 8299A04H01 3
59 270/16/22/25-1200 A-37 kA 8299A05H01 3
60 270/16/22/25-2000 A-37 kA 8299A02H01 3
61 270/32, 1200 A-50 kA 8299A05H21 3
62 270/32 2000 A-50 kA 8299A02H21 3
63 270/40, 1200 A-64 kA 8299A05H31 3
64 270/40, 2000 A-64 kA 8299A02H31 3
Primary disconnects
65 Up to 15 kV, 1200 A 508B022G01 508B022G01 (SE only) 502A851G02 6
Primary disconnects
66 Up to 15 kV, 2000 A 508B012G01 508B012G01 (SE only) 6
62 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
Primary disconnects
67 Up to 15 kV, 3000 A 692C037G01 692C037G01 (SE only) 6
68 All 63 kA 692C037G01 692C037G01 6
69 27 kV, 630 A 699B352G01 6
70 27 kV, 1200 A 699B352G01 6
71 27 kV, 2000 A 502A852G02 6
75 All 63 kA 691C648G02 1
Charging motor
87 48 Vdc 699B196G03 699B196G06 699B196G03 1
88 125 Vdc/120 Vac 699B196G01 699B196G04 699B196G01 1
89 250 Vdc/240 Vac 699B196G02 699B196G05 699B196G02 1
EATON www.eaton.com 63
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
94 Rectifier (120/240 Vac) 3759A79G01 3759A79G02 3759A79G01 1
UV trip coils
104 48 Vdc 8064A19G01 8064A19G01 8064A19G01 1
105 125 Vdc 8064A19G02 8064A19G02 8064A19G02 1
106 250 Vdc 8064A19G03 8064A19G03 8064A19G03 1
107 120 AC 8064A19G09 8064A19G09 8064A19G09 1
108 240 AC 8064A19G10 8064A19G10 8064A19G10 1
64 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
114 Trip D-shaft 694C638G02 694C638G02 694C638G02 1
EATON www.eaton.com 65
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 29. Recommended renewal parts for ANSI rated breakers (continued next page).
Style number
Qty. per
Line no. Description VCP-W VCPW-SE & 27 kV VCPW-ND breaker
121 Fasteners kit 8061A01G01 8061A01G01 8061A01G01 1
Fasteners in kit Qty.
X-washer - 0.188” 32
X-washer - 0.250” 14
X-washer - 0.312” 18
X-washer - 0.375” 40
X-washer - 0.500” 18
E-ring - 0.250” 11
E-ring - 0.500” 6
C-ring - 0.125” 6
C-ring - 0.375” 6
Envelope AR
Bag 1
Tag, style number 1
Ret. ring - 0.250” 5
Ret. ring - 0.375” 5
X-washer - 0.625” 5
Sppring clip III 6
Ret. ring - 0.188” 6
Gripping - Ret. ring HD 6
Ret. grip ring - 0.375” 6
Fiber washer 10
X-washer 0.500” stainless 18
66 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
EATON www.eaton.com 67
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers (continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
Interrupter assembly
1 36/25- 630 A 8299A01H01 3
2 36/25- 1250 A 8299A01H02 3
3 36/25- 2000 A 8299A01H03 3
Interrupter assembly
4 36/32-1250 A 8299A01H04 3
5 36/32- 2000 A 8299A01H05 3
Interrupter assembly
6 36/40-1250 A 8299A01H06 3
7 36/40-2000 A 8299A01H07 3
Interrupter assembly
8 72/25- 630 A 8299A01H08 3
9 72/25- 1250 A 8299A01H09 3
10 72/25- 2000 A 8299A01H10 3
Interrupter assembly
11 72/32-1250 A 8299A01H11 3
12 72/32- 2000 A 8299A01H12 3
Interrupter assembly
13 72/40- 1250 A 8299A01H13 3
14 72/40- 2000 A 8299A01H14 3
Interrupter assembly
15 120/25-630 A 8299A01H15 3
16 120/25-1250 A 8299A01H16 3
17 120/25-2000 A 8299A01H17 3
Interrupter assembly
18 120/32-1250 A 8299A01H18 3
19 120/32-2000 A 8299A01H19 3
Interrupter assembly
20 120/40-1250 A 8299A01H20 3
21 120/40-2000 A 8299A01H21 3
Interrupter assembly
22 175/25-1250 A 8299A01H22 3
23 175/25-2000 A 8299A01H23 3
Interrupter assembly
24 175/32-1250 A 8299A01H24 3
25 175/32-2000 A 8299A01H25 3
68 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers (continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
Interrupter assembly
26 175/40-1250 A 8299A01H26 3
27 175/40-1250 A 8299A01H27 3
Interrupter assembly
28 240/25-650 A 8299A01H28 3
29 240/25-1250 A 8299A01H29 3
30 240/25-2000 A 8299A01H30 3
Primary disconnects
31 Up to 175/40-630 A 699B104G01 6
32 Up to 175/40-1250 A 699B104G01 6
Primary disconnects
33 Up to 175/40-2000 A 508B012G01 6
Primary disconnects
34 240/25-630 A 699B352G01 6
Primary disconnects
35 240/25-1250 A 699B352G01 6
36 240/25-2000 A 699B352G02 6
Phase barriers
37 Up to 175/40 691C176H04 2
38 240/25 691C218H01 2
EATON www.eaton.com 69
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers (continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
Push rod assemblies
39 Up to 175/40-white springs 691C650G01 3
40 Up to 175/40-blue springs 691C651G01 3
41 240/25 691C241G01 3
Tie bars
42 Up to 175/40 3619A09H01 6
43 240/25 691C223H01 6
Charging motor
44 48 Vdc 699B196G03 699B196G06 1
45 125 Vdc/120 Vac 699B196G01 699B196G04 1
46 250 Vdc/240 Vac 699B196G02 699B196G05 1
70 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers (continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
UV trip coils
61 48 Vdc 8064A19G01 8064A19G01 1
62 125 Vdc 8064A19G02 8064A19G02 1
63 250 Vdc 8064A19G03 8064A19G03 1
64 120 AC 8064A19G09 8064A19G07 1
65 240 AC 8064A19G08 8064A19G08 1
EATON www.eaton.com 71
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers (continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
Front panel W/O escutch
74 240/25 691C214H01 1
75 All others 691C192H03 1
72 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Table 30. Recommended renewal parts for IEC rated breakers .(continued next page).
Style number
Qty. per
Line no. Description Up to 17.5 kV 24 kV breaker Typical view
80 Wiring harness repair kit (repairs/ 691C28G01 691C281G01 1
replaces the secondary disconnect
only)
UV trip kit 1
81 48 Vdc 691C274G01 691C274G01
125 Vdc 691C274G02 691C274G02
250 Vdc 691C274G03 691C274G03
120 Vac 691C274G04 691C274G04
240 Vac 691C274G05 691C274G05
82 CloSure test 6352C58G01 6352C58G01 1
EATON www.eaton.com 73
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
8. Optional accessories
8.1 Optional factory installed roll-on-floor wheel kit
Eaton (29” wide frame) breakers:
• Rated at 5, 15, or 27 kV - can be ordered with the “optional”
factory installed, roll-on-floor wheel kit, as configured through
Bidmanager.
Note: This roll-on-floor wheel kit can also be ordered as an aftermarket item
and installed in the field as required.
74 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Legend
1. Ground contacts 8. Slider interlocks
2 Levering system. 9. MOC switch
3. Automatic/manual secondary 10. TOC switch location (see Figure 12 for actual TOC)
4. Racking screw 11. Coding plates
5. Moving block 12. Provision for padlocking
6. Slider 13. Picture frame
7. Breaker position indication 14. Breaker rail
EATON www.eaton.com 75
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
8.3 Optional 3,000 A ball screw drive for BPI pan assembly
A ball screw kit has been developed for the BPI pan assembly to
reduce the required force to manually rack in a 63 kA or 3,000 A
breaker. If the customer is using a MR2 system to lever in the
breakers, then this system is not required.
This optional accessory is style number 1C20376G01.
76 EATON www.eaton.com
Instructions for installation, Instruction Booklet IB131006EN
operation, and maintenance of type Effective July 2021
VCP-W vacuum circuit breakers
Notes:
EATON www.eaton.com 77
Instruction Booklet IB131006EN Instructions for installation,
Effective July 2021 operation, and maintenance of type
VCP-W vacuum circuit breakers
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety nota-
tions in this document are based on Eaton Corporation’s (“Eaton”)
experience and judgment and may not cover all contingencies.
If further information is required, an Eaton sales office should be
consulted. Sale of the product shown in this literature is subject
to the terms and conditions outlined in appropriate Eaton selling
policies or other contractual agreement between Eaton and the
purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY,
OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT
STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF
THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY
ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in
contract, in tort (including negligence), strict liability or other-wise
for any special, indirect, incidental or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims
against the purchaser or user by its customers resulting from the
use of the information, recommendations and descriptions contained
herein. The information contained in this manual is subject to change
without notice.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2021 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. IB131006EN / TBG001412 All other trademarks are property
July 2021 of their respective owners.