DGS-MU-008-R1 Plant Noise Control
DGS-MU-008-R1 Plant Noise Control
DGS-MU-008-R1 Plant Noise Control
DGS-MU-008-Rev-1
Amendment History
1 May 2009 AMD-MU-008-001-BECHTEL Section # 2.0, 7.0, 8.0, 9.1, SMK / QAM / May 2009
10.2, 10.5, 10.7 & 11.0 HD MAY
DGS History
TABLE OF CONTENTS
Engineering & Technical Services Manager, E&PD: Quazi Abdul Matin (QAM)
1.0 GENERAL
1.1 INTRODUCTION
This Specification defines the overall noise control requirements and the procedures
for plant noise control for equipment installed for the Project.
CONTRACTOR shall use the project noise specifications to develop plant and
individual equipment noise limits. These noise limits and the associated equipment
requisitions shall be specified under the guidance of an in-house Noise Control
Engineer/Specialist or an Acoustical Consultant employed by CONTRACTOR.
1.2 PURPOSE
1.3 DEFINITIONS
For the purposes of this specification, the following General Definitions shall apply:
In addition to the above general definitions, the following Technical Definitions shall
apply:
Noise Level may refer to either a sound pressure level (Lp) with reference to 20 µPa,
or a sound power level (Lw) with reference to 1 pW.
Lw = 10 log10(W/W0) W0 = 1 pW
Work Area is any position not less than 1 meter from equipment surfaces accessible
to personnel, or any position where a worker's ear may be exposed to noise in the
normal course of his duty. It includes any platform, walkway, or ladder.
The following codes and standards, to the extent specified herein, form a part of this
specification. When an edition date is not indicated for a code or standard, the latest
edition in force at the time of CONTRACTOR’S/VENDOR’S proposal shall apply.
ISO 15664 Acoustics – Noise Control Design Procedures for Open Plant
The following Project reference documents, to the extent specified herein, form a part
of this specification. When an edition date is not indicated for a document, the latest
edition in force at the time of MANUFACTURER/VENDOR'S proposal submittal shall
apply.
The CONTRACTOR shall notify the COMPANY of any apparent conflict between this
specification, the related data sheets, the Codes and Standards and any other
specifications noted herein. Resolution and/or interpretation precedence shall be
obtained from the COMPANY in writing before proceeding with the
design/manufacture.
In case of conflict, the order of precedence shall be stated in the AGREEMENT or other
PROJECT documents as applicable.
Any technical deviations to this specification and its attachments shall be sought by
the CONTRACTOR only through CONCESSION REQUEST format. CONCESSION
REQUESTS require COMPANY’S review/approval, prior to the proposed technical
changes being implemented. Technical changes implemented prior to COMPANY
approval are subject to rejection.
CONTRACTOR’S proposed quality system shall fully satisfy all the elements of ISO
9001 - 2000 and ISO 9004 - 2000. The quality system shall provide for the planned
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 7 of 32
Abu Dhabi Oil Refining Company
The CONTRACTOR shall assume unit responsibility and overall guarantee for the
noise production for his scope of supply.
EEMUA 140 forms an integral part of this Specification and the EEMUA definitions
have been used throughout. Where conflict arises, the requirements of this
Specification shall take preference.
For acoustical design purposes, all calculations should be performed in the eight
octave bands centered between 63 Hz and 8 kHz (see ISO 266). If the frequency
spectrum of a source is not known, a frequency spectrum can be estimated from
empirical data, published data, measurements of similar equipment, or by using the
noise rating curve numerically 5 dB less than the given dB(A) criterion.. The octave
band values of the appropriate noise rating curves are given in ISO 1996. The
overriding requirement for acoustical design, however, is that the A-weighted Noise
Level shall be met.
Noise limits can be given for each of the above aspects of noise control, relative to
certain areas inside or outside the plant. These noise limits are specified in
Section 9, "General Noise Limits." These general noise limits shall be used by the
CONTRACTOR(S) to derive noise limits for each item of equipment, as applicable,
for its specific position in the plant.
The specified limits shall be met for the design operating conditions of the plant and
for other operating conditions which occur occasionally, such as startup, shutdown,
regeneration and maintenance. The only requirement for emergency situations, i.e.
any conditions other than just described, which can be foreseen or predicted (e.g.
relief) is that the absolute limit of subsection 9.2.3 shall not be exceeded.
During construction, noise levels shall not exceed the limits applicable for operation
of the completed plant. During precommissioning, noise levels shall not exceed the
absolute limits applicable for operation of the completed plant.
For some equipment, calculations or measurements may indicate that the noise
limits will be exceeded, but with a margin of uncertainty extending down to levels
below the limit (i.e. there is a possibility that the limits may be met). For such
equipment the application of noise control measures shall not be postponed until
actual noise levels have been obtained after startup, unless installation of
prospective retrofit noise controls, which may be needed, is feasible. Feasible
includes ability to provide adequate noise reduction and space has been allocated. If
there is doubt about the feasibility of prospective retrofit noise controls, the
COMPANY’S advice shall be sought.
The Phase 1 HSEIA Report will provide details on existing background noise levels.
For design purposes, this sound pressure limit shall be converted into a maximum
allowable sound power level for the plant or composing parts of the plant under
consideration. The resultant limit(s) shall be included in the project specifications by
the CONTRACTOR. Conversion of environmental sound pressure levels into plant
sound power levels and vice versa shall be carried out in accordance with EEMUA
140 (using the calculation curves for either minimal or significant screening effects)
or in accordance with a national standard agreed by the COMPANY.
Sound Pressure Level, superimposed on the existing background noise level, in the
work area within the new facilities shall not exceed 85 dB(A) at any point 1 meter
away from any equipment surface. Where it is not practical to achieve 85 dB(A) at
any point 1 meter away from equipment surface, Section 9.2.2 shall apply
Restricted areas are those work areas in the plant where it is not reasonably
practicable to reduce the noise level below the work area limit. Such a restricted
area limit may be between 85 and 115 dB(A). However, attempts shall be made to
reduce the level below 90 dB(A). In all cases, the absolute limit of 115 dB(A)
remains valid in such areas.
If it is unavoidable that the work area limit will be exceeded around particular
equipment, action shall be taken to reduce the area involved as much as feasible;
this may include the installation of an acoustical enclosure. It is accepted that areas
inside acoustical enclosures around such equipment are restricted areas.
Permanent warning signs to indicate the mandatory use of ear protectors shall be
erected at the boundaries of restricted areas. The signs should be of the type given
in ISO 3864.
The sound pressure level for broadband noise shall not exceed 115 dB(A), measured
with an instrument set to slow response, at any time and at any place which is
accessible to personnel in any situation, including emergencies such as the blowing
of safety relief valves. The absolute limit does not apply inside of any vendor
supplied enclosure.
The following noise level limits shall apply in order to reduce speech and work
interference from equipment to acceptable proportions:
NOTE: The maximum allowable sound pressure level mentioned here above refer
to the background noise existing inside the concerned area (room) when unoccupied,
and includes ventilation and contribution of all external noise sources, Noise that is
not related to equipment, but is produced by users of the various areas need not be
considered.
9.3.3 Accommodation
The sound pressure level shall not exceed 40 dB(A) inside personnel
accommodation such as bedrooms, private cabins, etc.. This requirement is
applicable even for the on-site accommodation provided during construction period
either for COMPANY’S or CONTRACTOR’S personnel.
Noise levels inside buildings or shelters shall be calculated, taking into account both
the noise from equipment in the building and the noise from outside. Calculation of
the attenuation of noise from outside to within a building, and vice versa, shall be
based on standard acoustical principles.
Screening effects of large buildings and tanks shall be taken into account where
relevant.
All sirens, audio alarms, sentinel valves, etc. shall be effective under all operating
conditions. If public address systems are used, they shall be designed and installed
to provide effective speech intelligibility in all areas designated for speech
communications. In any area expected to exceed 90 dBA, visible strobe warnings
shall be used in addition.
10.1 GENERAL
For equipment where no other limit than the work area limit is applicable, the
equipment sound pressure limits as given in the following shall apply:
Where more or less stringent area noise limits apply, the equipment noise limits
given below shall be adapted accordingly.
The equipment noise limits shall be given in an overall dB(A) value or, where
considered more appropriate, the corresponding octave band spectrum may be
specified instead.
In all cases, the appropriate equipment noise limit(s) shall be established by the
CONTRACTOR and shall be based on his acoustical calculations, performed per
EEMUA 140. These limits shall be given to the VENDOR on the project Equipment
Noise Data Sheet (attached to DGS-MU-009).
Unless other limits are established via this specification, the equipment noise limit
shall be a sound pressure level of 85 dB(A) +0. The specified noise limit shall be
guaranteed by the VENDOR and met at any measuring location not less than 1
meter from the equipment surface.
If equipment consists of components, e.g. a driver and a driven part, the above limits
applied to each component separately will not ensure that the assembled equipment
meets the work area limit. For such equipment, more stringent limits shall be
specified by CONTRACTOR on the data/requisition sheets for the separate
components. The permissible noise limit, per component, shall be based on
acoustical calculations. As a guideline, the CONTRACTOR should use the following
rules:
A further reduction of the equipment noise limit shall be made when several
equipment items or trains are to be mounted close together, i.e. when the distance
between equipment surfaces is less than the largest equipment dimension or when
equipment is located in a reverberant area. The appropriate equipment noise limit
shall be based on acoustical calculations by the CONTRACTOR.
emitting continuous noise, given above. The maximum level shall not be more than
10 dB(A) higher than the limit for continuous noise.
8 hours 85
4 hours 88
2 hours 91
1 hour 94
provided that no significant noise (i.e. above 70 dB(A)) is emitted for the remaining
time in the 8-hour period.
Where the equipment emits noise fluctuating in a more complicated manner, the
equivalent continuous sound level shall be calculated according to the method given
in EEMUA 140, paragraph 3.1.6.
The maximum allowable sound pressure level at 1 meter from the equipment for
equipment located outside the work area may be higher than the limits given in
subsections 10.2 and 10.3. At positions which are inaccessible for personnel, such
as may be the case for vent stacks and certain control valves, the allowable increase
shall be:
Where x is the shortest distance from the equipment under consideration to the
nearest work area, expressed in meters. For valves, the distance should be taken
from directly-connected piping to the nearest work area.
Further noise level restrictions shall apply when the noise of an equipment item
contains narrow-band and/or impulsive components, as defined in EEMUA 140. Any
narrow-band or impulsive components shall be reduced sufficiently below the
broadband noise from the equipment so that it is no longer audible (see Appendix E
of EEMUA 140). If this is not feasible, the equipment noise limit shall be reduced by 5
dB(A) for such equipment and the COMPANY’S advice shall be obtained.
For each control valve and its associated pipe work, the requirements of sections
10.2 through 10.5 apply. This also holds for low-rate depressuring valves.
Control valve noise shall be determined for three operating conditions: minimum,
normal, and maximum throughput. Noise limits shall not be exceeded for any of
these three conditions.
Unless otherwise specified, control valve noise evaluation shall follow the prediction
method given by the following IEC publications:
The noise from safety/relief valves and hi-rate depressuring valves (and their piping)
which blow under emergency conditions only, shall not exceed the absolute limit of
115 dB(A) in any work area.
The party which sizes safety/relief and emergency depressurizing valves shall also
be responsible for the calculation of their noise levels, according to a method to be
approved by the COMPANY. If these calculations are performed by the
CONTRACTOR, they shall be confirmed by the VENDOR, and vice versa.
If it is not feasible to remain within the absolute limit for safety/relief or emergency
de-pressuring valves, they should either be:
• Positioned well away from the work area, so that personnel shall not have
access to their immediate vicinity. [In this case the maximum allowable sound
pressure level, Lp, 1 meter away from the valve and/or piping shall be
calculated using the following equations:
Lp = 115 + 20 log10 (x) dB(A) for point sources (e.g. relief valves) and
Lp = 115 + 10 log10 (x) dB(A) for line sources (e.g. pipe line)
where:
x is the shortest distance in meters between the source and the nearest work area;
and/or
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 15 of 32
Abu Dhabi Oil Refining Company
• Provided with a screen that shall deflect noise away from the nearest work
area.
NOTES:
a. The above procedures will allow safety/relief valves and their piping to emit
noise above the limits of 115 dB(A) at 1 meter distance. The corresponding
high levels of vibrational energy in the piping, which could cause acoustic
fatigue, shall be taken into account in the design of the piping system.
b. Deleted
c. Connected pipe work can also radiate excessive noise. Care shall be taken
that these noise sources are taken into account and/or fitted with silencers or
acoustical insulation. Suggestions and/or proposals for pipe noise mitigation
should be submitted by the VENDOR to the CONTRACTOR and the
COMPANY for approval.
d. CONTRACTOR shall assess all such high noise valves (and all other high
differential pressure devices) in accordance with CONCAWE Report No. 85/52
and Marine Technology Directorate Publication No. 99/100. CONTRACTOR
shall prepare a report recording this assessment and identifying any proposal
modifications to piping design to mitigate the risk of acoustic failure. These
mitigating measures shall be subject to approval by COMPANY.
10.6.3 Piping
Noise emitting from piping is of major importance in plant noise control and shall be
subject to the same restrictions as General Equipment. Such noise usually has its
origin in equipment such as a valve or compressor. The CONTRACTOR shall
control piping noise by selecting low-noise equipment (by design) or, when this is not
reasonably practicable, by incorporating in-line silencers or acoustical insulation.
Guidance into the assessment and reduction of noise emitting from piping by the use
of acoustical insulation is given in DGS-MU-010. The use of in-line silencers in the
suction line of compressors requires approval from the COMPANY.
10.6.4 Vents
All vents incorporated in the design to meet operational requirements shall be subject
to the same restrictions as General Equipment. Vents intended for emergency use
only shall be subject to the same requirements as safety/relief valves per subsection
10.6.2. Where necessary, 'vent' or 'blow-down' silencers shall be incorporated in the
design.
NOTES:
10.6.5 Flares
Since there are environmental noise requirements for this project, low-noise flares
are required, even if the flare is to be used for emergency conditions only.
Elevated flares shall not exceed 85 dB(A) — i.e. the work area limit — at the
perimeter of the sterile area (which should be at least 60 meters from the flare base)
when operating at flow rates up to 15% of maximum flaring capacity.
Sound Pressure level shall not exceed 115 dB(A) at the perimeter of the sterile area
when flow rates exceed 15 % of maximum flaring capacity.
Ground flares shall not exceed 85 dB(A) outside the windscreen or louver wall.
For each mechanical and / or rotating equipment such as air conditioner, fan, pump,
etc including their drivers, Vendors shall note that emitted noise shall be subject to
the same restrictions as general equipment, see section # 12.2 of Specification DGS-
MU-009.
For the air distribution devices used for heating and / or ventilating, the indoor
acoustical objective shall be as defined in the indoor design conditions mentioned in
Specification DGS-AU-063.
When an environmental noise limit is specified in terms of sound power level, the
sound power limit for individual equipment shall be determined such that the sum of
the levels of all equipment does not exceed the total limit.
The allocation to individual equipment items in an early stage of a project can best be
performed using VENDOR data, data bases, and experience taking into account
type, size, and speed of equipment.
The equipment noise limits of sections 10.2 through 10.6 are sufficient only to ensure
that the work area limit will not be exceeded in the completed plant. Since other
noise limits also apply, it shall be investigated by the CONTRACTOR as to whether
they will be met by using the standard individual equipment noise level limits.
For the purpose of this investigation, the sound power levels of individual equipment
should be estimated. Sound power levels are either derived according to section
10.7 or are calculated from equipment sound pressure levels, assuming that the
requirements of sections 10.2 through 10.6 will just be met. Where actual sound
power levels or sound pressure levels are known, they should be used instead.
The sound power levels of individual equipment and their location thus form the basis
of a calculation of noise levels in the plant. Calculations shall be carried out in
accordance with EEMUA 140 or in accordance with an industry standard agreed to
by the COMPANY.
The CONTRACTOR shall consider the extent of noise control measures to be taken
versus the severity of the requirements and consult with the COMPANY, as needed.
Prior approval of the COMPANY is required for any of the above noise control
measures, except when acoustical insulation Class A, B or C is used on pipelines.
Further guidelines, details, and requirements for corrective measures and silencing
equipment are contained in section 13.2 of DGS-MU-009.
The CONTRACTOR shall prepare equipment noise limit data sheets for all relevant
items of equipment or of an equipment train, specifying the limits as given in
sections 10.2 through 10.8, and include the same in the inquiry/order. The project
Equipment Noise Data Sheet shall be used (see Attachment 1 of DGS-MU-009).
The equipment noise limit data sheet shall specify either a maximum sound pressure
level at any location 1 meter from the equipment surface or a maximum sound power
level, or both.
NOTE: The maximum for sound pressure level and sound power level need not be
related or equivalent since they may originate from different general limits,
i.e. the sound pressure limit may originate from the work area noise limit
and the sound power limit from the environmental limit.
Also, where a technical choice is available between equipment of low noise emission
by design and equipment with 'path-treatment', the former is preferred. However, the
estimated cost in operation and maintenance that may result from path treatment
should be capitalized and taken into account in the ultimate selection. In decisions
involving trade-offs between noise control performance and additional
expenditure(s), the COMPANY shall be consulted and shall have the final decision.
The CONTRACTOR shall ensure that all VENDORS have provided in their
tenders all the information required in accordance with the project noise
specifications. Further, the CONTRACTOR shall ensure that the VENDOR is
made aware of the obligation to state noise guarantees for the equipment to be
provided, for any of the conditions of operation for which the equipment may
be expected to be used.
The CONTRACTOR shall decide which equipment shall have a noise test run at the
VENDOR'S works and shall inform the COMPANY and the VENDOR accordingly.
The purpose of the shop acceptance test is to identify and rectify major problems, if
any, to assure that the equipment, when finally tested at site, will meet the overall
noise level criteria. All shop test runs shall reflect the in-situ arrangement and a
suitable test procedure shall be agreed upon by the CONTRACTOR and the
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 19 of 32
Abu Dhabi Oil Refining Company
VENDOR. The COMPANY reserves the right to review and comment on any shop
noise test procedure.
During the shop noise test, noise control treatments (such as job silencers and/or
acoustical enclosures) may be used, provided they are included in the equipment
tender.
If the equipment exceeds the guaranteed noise limits during an on-site field test,
remedial action shall still be required to be performed by the CONTRACTOR.
The CONTRACTOR shall ensure that all noise acceptance tests are conducted by
the VENDOR(S) in accordance with the provisions and requirements of subsections
15.3.2 through 15.3.4 of DGS-MU-009.
Since more than one CONTRACTOR may be involved with the Project, each
CONTRACTOR shall submit a separate bid package, for the Ambient Noise Survey.
This package shall include evidence of similar previous efforts, proposed personnel
(with experience summaries), and proposed survey procedures and instrumentation.
At the discretion of the COMPANY, a single CONTRACTOR or a collaboration of
several CONTRACTORS may be selected to perform the Ambient Noise Survey for
this project.
In particular, the report shall identify the requirement for noise control measures such
as acoustic insulation, silencers and enclosures, and shall be sufficiently early in the
engineering phase that allowance for these measures can be incorporated in plant
layout.
After the major part of the equipment selection has taken place, an interim Noise
Control Design Report shall be prepared for approval by the COMPANY. The report
shall give sufficient data and calculations to demonstrate to the satisfaction of the
COMPANY that the acoustical design of the plant will meet the requirements. If there
is a significant change in the overall noise control features of the plant design after all
the equipment has been selected/tested, an updated Noise Control Design Report
shall be prepared for approval by the COMPANY.
After the plant has been operating at normal condition for at least 14 days, the
CONTRACTOR’S engineer or the Consultant shall make a survey of the plant noise
and issue interim noise results for all of the plant and the surrounding neighborhood.
This information may be used by Contractor to identify areas of concern requiring
further noise control measures, as well as providing information to update the data
base and the acoustical model of the plant. At this stage, CONTRACTOR shall
satisfactorily resolve all the areas of concern with the COMPANY.
Once the plant is in normal operation, a noise level acceptance survey of the plant
and surroundings shall be made by CONTRACTOR’S noise control engineer or the
Acoustical Consultant. The results of this acceptance test shall be reported in a
Noise Verification Survey Report which shall include measured noise level contour
maps of the work areas showing contours of 75 dB(A) and higher, with incremental
steps of 5 dB(A). The report shall also present the survey data regarding
environmental noise issues. The COMPANY’S approval is required for the timing of
this survey. The environmental survey and the work area noise contours shall
conclusively establish that all contractual obligations have been met by the
CONTRACTOR. Responsibility of the CONTRACTOR for meeting the specified
noise limits will not end until the noise level survey has shown that limits are not
exceeded. Corrective action shall be taken if actual sound levels or levels calculated
from measurements made in the acceptance test exceed the specified limits. The
corrective measures shall have the COMPANY’S approval.
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 21 of 32
Abu Dhabi Oil Refining Company
When all corrective measures have been implemented and when all project noise
limits have been met, the CONTRACTOR shall issue the Final Noise Control Report.
This final report shall contain all the updated acoustical data, final noise control
treatments, and measured results of the Noise Verification Survey.
14.2.1 Instrumentation
Sound pressure levels shall be measured using a precision, Type 1 sound level
meter, SLM (or equivalent) that is fitted with A- and C-weighting filter networks in
accordance with IEC 61672 or BS EN 61672. If frequency-level measurements are
made for design purposes, the frequency-band filter set should comply with the
requirements of IEC 61260 or BS EN 61260. The center frequencies of these bands
should correspond to those given in ISO 266.
All sound level measurement equipment used for any noise test procedure, whether
by a CONTRACTOR or a VENDOR, shall have had its calibration certified by an
authorized service center or calibration laboratory (per the MANUFACTURER’S
specifications/instructions) within one year of the actual measurement sessions(s).
14.2.2 Procedures
All A-weighted sound pressure levels and any findings shall be recorded, along with
the following information.
• Local weather conditions during the measurement (wind speed and direction,
rain, humidity level, atmospheric pressure, temperature, fog, smog, etc.)
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 22 of 32
Abu Dhabi Oil Refining Company
• Description of the source of noise and its position in the area where
measurements are carried out. Include Plant Unit/Tag Number of the
equipment/Line number, as applicable.
• In the case of closed spaces, room dimensions, location of openings, and the
position of windows and doors (indicate whether open or closed) shall be
recorded.
14.2.3 Calculations
All noise level calculations, including general acoustical calculations, methods for
calculating sound power levels, and the conversion of sound pressure levels to
sound power levels shall be performed per EEMUA 140.
The CONTRACTOR shall be responsible for the generation of the following reports.
In all design reports, due attention shall be given to the prediction and control of
piping noise.
14.3.1 The Ambient Noise Survey Report shall include the following:
1. Measurement data
1. Specified limits
• Assumptions used
• Tables of octave band sound power, sound pressure, and overall levels of
all equipment per plant unit.
14.3.3 The (interim and updated) Noise Control Design Reports shall include the
following:
• The guaranteed noise level data has been obtained from VENDORS.
2. Specified limits
• Tables of octave band sound power, sound pressure, and overall levels of
all equipment per plant unit. The origin of the data shall be indicated
(estimate from VENDOR, guarantee from VENDOR, estimate from
CONTRACTOR, test data from CONTRACTOR, etc.).
• A list of control valves with a noise level above 80 dB(A) with an indication
where low-noise control valves will be applied.
5. Calculations
• In-plant work area noise contour maps showing projected contour levels
of 75 dB(A) and higher, with incremental steps of 5 dB.
• Evaluation of the expected sound power level of the plant even in the
case that no plant sound power limit is required.
14.3.4 The Noise Verification Survey Report shall include the following:
1. Measurement data
• Evaluation of the aggregate sound power level, Lw, of the entire plant
(even in the case that no plant sound power limit is required).
• Absolute limit
• Others, as appropriate
14.3.5 The Final Noise Control Report shall include the following:
1. A summary discussing:
• The final acoustical design of the plant (including plant piping noise and
its control).
• Tables of octave band sound power, sound pressure, and overall levels of
all installed equipment per plant unit. The origin of the final data shall be
indicated (estimate from VENDOR, guarantee form VENDOR, estimate
from CONTRACTOR, test data from CONTRACTOR, etc.) The tables
should clearly indicate all updates and/or deviations from the last Noise
Control Design Report.
• A list of control valves with a noise level above 80 dB(A) with an indication
where low-noise control valves were applied.
• Final in-plant work area noise contour maps showing measured contour
levels of 75 dB(A) and higher, with incremental steps of 5 dB. These final
contour maps should include all noise mitigation treatments used to
achieve compliance.
1. Extent of Investigation
2. Study Methodology
Takreer DGS-MU-008-Rev-1 May-2009 Printed 30-Jun-09 09:02:49 Initials Page 26 of 32
Abu Dhabi Oil Refining Company
3. Results of Assessments
1. Extent of Investigation
2. Study Methodology
3. Results of Assessments
ADDENDUM SHEET
All revisions to this DGS subsequent to the issue of Rev Zero shall be recorded in this addendum
sheet and shall be incorporated into the DGS in the next revision.
British Standards
In Section # 7.0:
In Section # 8.0:
In Section # 9.1:
In Clause # 9.2.1:
In Clause # 9.2.3:
Add at the end “The absolute limit does not apply inside of any
vendor supplied enclosure”
In Clause # 9.3.2:
In Clause # 9.3.5:
Add at the end “In any area expected to exceed 90 dBA, visible
strobe warnings shall be used in addition”
In Section # 10.2:
In Clause # 10.6.1:
In Clause # 10.6.2:
Delete Note b
“CONTRACTOR shall assess all such high noise valves (and all
other high differential pressure devices) in accordance with
CONCAWE Report No. 85/52 and Marine Technology Directorate
Publication No. 99/100. CONTRACTOR shall prepare a report
recording this assessment and identifying any proposal
modifications to piping design to mitigate the risk of acoustic
failure. These mitigating measures shall be subject to approval by
COMPANY.”
In Clause # 10.6.5:
Add “Sound Pressure level shall not exceed 115 dB(A) at the
perimeter of the sterile area when flow rates exceed 15 % of
maximum flaring capacity”
In Section # 10.7:
Replace in the last paragraph “at any time” with “during design
operating conditions”
In Section # 11.0:
In Clause # 14.1.2:
Add “In particular, the report shall identify the requirement for
noise control measures such as acoustic insulation, silencers and
enclosures, and shall be sufficiently early in the engineering
phase that allowance for these measures can be incorporated in
plant layout.”
In Clause # 14.1.4:
In Clause # 14.2.1:
In Clause # 14.2.2:
In Clause # 14.3.2:
* Assumptions used
1. Extent of Investigation
2. Study Methodology
3. Results of Assessments
1. Extent of Investigation
2. Study Methodology
3. Results of Assessments