SIPROTEC 7SJ85

Feeder and overcurrent protection

www.siemens.com/siprotec

Description
The SIPROTEC 7SJ85 overcurrent protection has been de-
signed specifically for the protection of feeders and lines.
With its modular structure, flexibility, and the high-perfor-
mance DIGSI 5 engineering tool, the SIPROTEC 7SJ85 de-
vice offers futureoriented solutions for protection, control,
automation, monitoring, and Power Quality – Basic..
Main function Feeder and overcurrent protection for all
voltage levels
Feeder and overcurrent protection SIPROTEC 7SJ85
Inputs and out- 5 predefined standard variants with 4 (housing width 1/3 x 19’’ to 2/1 x 19’’)
puts current transformers, 4 voltage trans-
formers, 11 to 59 binary inputs, 9 to 33 • Detection and recording of power-quality data in the
binary outputs
mediumvoltage and subordinate low-voltage power
Hardware flexibi- Flexibly adjustable and expandable I/O system
lity quantity structure within the scope of
Functions
the modular SIPROTEC 5 system; 1/6 ex-
pansion modules can be added, available DIGSI 5 permits all functions to be configured and com-
with large or small display, or without bined as required.
display
• Directional and non-directional overcurrent protection
Housing width 1/3 × 19 inch to 2/1 × 19inch with additional functions
Applications • Protection of up to 9 feeders with up to 40 analog in-
puts
• Detection and selective 3-pole tripping of short cir-
cuits in electrical equipment of star networks, lines • Optimized tripping times due to directional compari-
with infeed at 1 or 2 ends, parallel lines, and open-cir- son and protection data communication
cuited or closed ring systems of all voltage levels up to
• Detection of ground faults of any type in compen-
AC 400 V
sated or isolated electrical power systems using the
• Backup protection for differential protection devices following functions: 3I0>, V0>, transient ground-fault
of all kind for lines, transformers, generators, motors, function, cos φ, sin φ, dir. detection of intermittent
and busbars ground faults, harmonic detection, and admittance
measurement
• Protection and monitoring of capacitor banks
• Arc protection
• Phasor Measurement Unit (PMU)
• Ground fault detection using the pulse detection me-
• Reverse-power protection
thod
• Load shedding applications
• Detection of intermittent ground faults with auto-
• Automatic switchover matic blocking of statically measuring functions to
avoid message and fault-record flooding
• Regulation or control of power transformers (two-
winding transformers, three-winding transformers, • Arc protection
grid coupling transformers)
Efficient and modular

• Fault locator plus for accurate fault location with in- IEC 61850-9-2 Client, IEC 60870-5-103, IEC 60870-5-
homogenous line sections and targeted automatic 104, Modbus TCP, DNP3 serial and TCP, PROFINET IO,
overhead-line section reclosing (AREC) PROFINET IO S2 redundancy)
• Overvoltage and undervoltage protection • Virtual network partitioning (IEEE 802.1Q - VLAN)
• Power protection, configurable as active or reactive- • Serial protection communication via optical fibers,
power protection two-wire connections, and communication networks
(IEEE C37.94 and others), including automatic switch-
• Frequency protection and frequency-change protec-
over between ring and chain topology
tion for load-shedding applications
• Reliable data transmission via PRP and HSR redun-
• Automatic frequency relief for underfrequency load
dancy protocols
shedding, taking changed infeed conditions due to
decentralized power generation into consideration • Extensive cybersecurity functionality, such as role-
based access control (RBAC), logging of security-re-
• Protection functions for capacitor banks, such as over-
lated events, signed firmware, or authenticated IEEE
current, overload, current-unbalance, peak overvolt-
802.1X network access.
age, or differential protection
• Simple, fast, and secure access to the device via a
• Directional reactive-power undervoltage protection
standard Web browser to display all information and
(QU protection)
diagnostic data, vector diagrams, single-line and de-
• Detection of current and voltage signals up to the vice display pages
50th harmonic with high accuracy for selected protec-
• Phasor measurement unit (PMU) for synchrophasor
tion functions (such as peak overvoltage protection
measured values and IEEE C37.118 protocol
for capacitors) and operational measured values
• PQ – Basic: Voltage unbalance; voltage changes: over- • Time synchronization using IEEE 1588
voltage, dip, interruption; TDD, THD, and harmonics • Control of power transformers
• Point-on-wave switching • High-performance fault recording (buffer for a max.
record time of 80 s at 8 kHz or 320 s at 2 kHz)
• Control, synchrocheck, and switchgear interlocking
protection • Auxiliary functions for simple tests and commission-
ing
• Circuit-breaker failure protection
Benefits
• Circuit-breaker reignition monitoring
• Safety due to powerful protection functions
• Graphical logic editor to create high-performance au-
tomation functions in the device • Cybersecurity in accordance with NERC CIP and BDEW
Whitepaper requirements
• Single-line representation in the small or large display
• Highest availability even under extreme environmen-
• Fixed integrated electrical Ethernet RJ45 interface for
tal conditions by standard coating of the modules
DIGSI 5 and IEC 61850 (reporting and GOOSE)
• Full compatibility between IEC 61850 Editions 1, 2.0,
• 2 slots for optional communication modules, usable
and 2.1
for different and redundant protocols (IEC 61850-8-1,

For all products using


security features of
Siemens 2020 For the U.S. published by OpenSSL, the
Siemens Industry Inc. following shall apply:
Smart Infrastructure
Digital Grid 100 Technology Drive This product includes
software developed
Humboldtstrasse 59 Alpharetta, GA 30005
by the OpenSSL Pro-
90459 Nuremberg, United States ject for use in the
Germany OpenSSL Toolkit
(www.openssl.org),
Customer Support: http://www.siemens.com/csc cryptographic soft-
ware written by Eric
Young
© Siemens 2020. Subject to changes and errors. ([email protected])