PRESSURE / VACUUM
RELIEF VALVE
Model 1200A is designed to protect your tank from
damage created by over-pressure or excessive
vacuum. Costly product evaporation losses due to
normal tank “breathing” are greatly reduced.
Because the Model 1200A retains toxic vapors,
atmospheric contamination is minimized. This MODEL 1200A
helps to provide increased fire protection and safety.
SPECIAL FEATURES
Model 1200A offers Groth’s special “cushioned air”
seating. Superior performing Teflon ® seating
diaphragms are standard to minimize sticking
caused by resinous vapors and atmospheric mois-
ture. The Model 1200A has a self draining housing
body and drip rings to protect seating surfaces from
condensate and freezing. This design also avoids
dangerous pressure or vacuum buildup due to MODEL 1200A
binding or clogging of the valve. Buna-N, Viton®,
and other seating diaphragms can be provided
when required. To insure the proper alignment of
seating surfaces, there is peripheral guiding and a
center stabilizing system.
100
AA
AA
A
A
C
C
CC
CC
AA
BB
BB
SPECIFICATION TABLE • MODEL 1200A‡ Specifications subject to change without notice. Certified dimensions available upon request.
VACUUM
and MAWP
4” 11 oz/in2 19 ” 15. ” 13” 19 ” 27 ” 13” 31
*0.5 oz/in2 WEIGHT 2LOADED
3
} 7
} 1
} 1
}
4 8 2 2
12 PSIG SPRING LOADED
2
16 oz/in2
6” 16 oz/in2 27 ”
3
}
4 22 ”
1
}
4 19” 27 ”
3
}
4 37 ”
3
}
4 19. ” 1
}
2 57
(150 mm) (70.3 gm/cm )
2
(704) (565) (482) (705) (959) (495) (26 kg)
8” 16 oz/in2 33. ”
7
}
8 26. ”
3
}
8 23. ”
5
}
8 33. ”
5
}
8 44 ”
1
}
2 23. ” 1
}
2 75
(200 mm) (70.3 gm/cm2) (860) (669) (600) (854) (1130) (597) (34 kg)
10” 16 oz/in2 40 ”
7
}
8 28. ”
7
}
8 30 ”
3
}
4 38” 53” 25. ” 1
}
2 116
(250 mm) (70.3 gm/cm )
2
(1038) (733) (781) (965) (1346) (648) (53 kg)
†
W.P. = Working Pressure. ‡ On spring loaded valves, change model number. ◊ 150# A.N.S.I. drilling compatibility, F.F. on aluminum and R.F. on carbon steel and stainless steel alloys.
Fiberglass dimensions on request. 16 oz/in2 set with spacer. S.S. set weights-Consult Factory. *Some sizes require non-ferrous components to achieve 0.5 oz./sq.in. setting.
HOW TO ORDER
FOR EASY ORDERING, SELECT PROPER MODEL NUMBER
MODEL # SIZE MATERIAL OPTIONS
O = No Options
Z = Special Options
1200A Weight Loaded Pallet Material O = No Jacket
1201B Pressure Spring 02" Seat Material J = Steam Jacket
1202B Vacuum Spring Thru * Body Material S = Spacer
1203A Pressure & Vacuum Springs 12" H = Steam Jacket and Spacer
1 = Aluminum
3 = Carbon Steel Diaphragm Material (Seat):
5 = B = Buna-N
NOTES
EXAMPLE 1 2 0 0 A 0 2 1 1 5 T 0 0
Indicates a 2" Model 1200A with Aluminum Body and Seat, 316 SS Pallet, Teflon® Seat Diaphragm and no other options.
MODEL 1200A
Set Pressure Air Flow Capacity at 100% Over-pressure (Double Set Pressure)
(Ps) 1000 Standard Cubic Feet per Hour at 60° F
In WC Oz/Sq In 2” 3” 4” 6” 8” 10” 12”
0.87 0.50 7.65 16.2 28.9 61.9 108 174 217
1.00 0.58 8.22 17.4 31.1 66.5 116 187 233
1.73 1.00 10.8 22.8 40.8 87.2 152 246 305
2.00 1.16 11.6 24.5 43.8 93.7 164 264 328
2.60 1.50 13.2 27.8 49.8 106 186 300 373
3.00 1.73 14.1 29.9 53.4 114 200 322 400
3.46 2.00 15.2 32.0 57.3 123 214 345 429
4.00 2.31 16.3 34.4 61.5 131 230 371 460
6.00 3.47 19.8 41.8 74.7 160 279 450 560
8.00 4.62 22.7 47.9 85.7 183 320 516 641
10.0 5.78 25.1 53.1 95.1 203 355 573 712
12.0 6.93 27.3 57.8 103 221 386 623 774
15.0 8.66 30.2 63.9 114 244 427 689 856
20.0 11.6 34.3 72.5 130 277 485 781 971
25.0 14.4 37.7 79.6 142 305 532 859 1067
30.0 17.3 40.6 85.7 153 328 573 925 1149
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-pressure. Example—To find “C” factor from table:
Read “C” factor for 75% Over-pressure at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OP 5 0.87
Read the flow capacity at 100% over-pressure directly from the table above. Use linear “C” Factor Table
interpolation if the set pressure is not listed. (Ref: Page TPD1) %OP 0 1 2 3 4 5 6 7 8 9
If the allowable over-pressure is less than 100%, modify the flow capacity using the 10 0.42 0.43 0.44 0.45 0.46 0.46 0.47 0.48 0.49 0.50
appropriate “C” factor from the table. If allowable over-pressure is more than 100%, 20 0.51 0.52 0.52 0.53 0.54 0.55 0.56 0.56 0.57 0.58
consult page TPD1 or your Groth Representative.
30 0.59 0.59 0.60 0.61 0.61 0.62 0.63 0.64 0.64 0.65
Calculate the percentage over-pressure by the following formula. Note that all 40 0.66 0.66 0.67 0.68 0.68 0.69 0.70 0.70 0.71 0.72
pressures are gage pressure expressed in the same units of measure.
50 0.72 0.73 0.73 0.74 0.75 0.75 0.76 0.77 0.77 0.78
Pf 5 Flowing pressure 60 0.78 0.79 0.80 0.80 0.81 0.81 0.82 0.82 0.83 0.84
Ps 5 Set pressure
% OP 5 [(Pf 2 Ps)/Ps] 3 100 70 0.84 0.85 0.85 0.86 0.86 0.87 0.88 0.88 0.89 0.89
80 0.90 0.90 0.91 0.91 0.92 0.92 0.93 0.93 0.94 0.94
Calculate flow capacity at less than 100% over-pressure according to the following
example. 90 0.95 0.95 0.96 0.96 0.97 0.97 0.98 0.99 0.99 1.00
102
®
MODEL 1200A
Set Pressure Air Flow Capacity at 100% Over-pressure (Double Set Pressure)
(Ps) 1000 Normal Cubic Meters per Hour at 0° C
mm WC mb 2” 3” 4” 6” 8” 10” 12”
22 2.16 0.22 0.46 0.82 1.74 3.05 4.91 6.11
50 4.90 0.32 0.68 1.22 2.62 4.58 7.38 9.17
75 7.35 0.40 0.83 1.49 3.19 5.58 9.00 11.2
100 9.80 0.45 0.96 1.72 3.67 6.42 10.4 12.9
125 12.3 0.51 1.07 1.91 4.09 7.15 11.5 14.3
150 14.7 0.55 1.17 2.09 4.47 7.81 12.6 15.6
175 17.2 0.59 1.26 2.25 4.81 8.40 13.5 16.8
200 19.6 0.63 1.34 2.39 5.12 8.95 14.4 17.9
225 22.1 0.67 1.41 2.53 5.41 9.46 15.3 18.9
250 24.5 0.70 1.49 2.66 5.68 9.93 16.0 19.9
275 27.0 0.73 1.55 2.78 5.94 10.4 16.7 20.8
300 29.4 0.76 1.62 2.89 6.18 10.8 17.4 21.6
375 36.8 0.85 1.79 3.20 6.84 12.0 19.3 23.9
500 49.0 0.96 2.03 3.63 7.76 13.6 21.9 27.2
625 61.3 1.05 2.23 3.99 8.52 14.9 24.0 29.9
750 73.5 1.14 2.40 4.29 9.18 16.1 25.9 32.2
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-pressure. Example—To find “C” factor from table:
Read “C” factor for 75% Over-pressure at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OP 5 0.87
Read the flow capacity at 100% over-pressure directly from the table above. Use linear “C” Factor Table
interpolation if the set pressure is not listed. (Ref: Page TPD1) %OP 0 1 2 3 4 5 6 7 8 9
If the allowable over-pressure is less than 100%, modify the flow capacity using the 10 0.42 0.43 0.44 0.45 0.46 0.46 0.47 0.48 0.49 0.50
appropriate “C” factor from the table. If allowable over-pressure is more than 100%, 20 0.51 0.52 0.52 0.53 0.54 0.55 0.56 0.56 0.57 0.58
consult page TPD1 or your Groth Representative.
30 0.59 0.59 0.60 0.61 0.61 0.62 0.63 0.64 0.64 0.65
Calculate the percentage over-pressure by the following formula. Note that all 40 0.66 0.66 0.67 0.68 0.68 0.69 0.70 0.70 0.71 0.72
pressures are gage pressure expressed in the same units of measure.
50 0.72 0.73 0.73 0.74 0.75 0.75 0.76 0.77 0.77 0.78
Pf 5 Flowing pressure 60 0.78 0.79 0.80 0.80 0.81 0.81 0.82 0.82 0.83 0.84
Ps 5 Set pressure
% OP 5 [(Pf 2 Ps)/Ps] 3 100 70 0.84 0.85 0.85 0.86 0.86 0.87 0.88 0.88 0.89 0.89
80 0.90 0.90 0.91 0.91 0.92 0.92 0.93 0.93 0.94 0.94
Calculate flow capacity at less than 100% over-pressure according to the following
example. 90 0.95 0.95 0.96 0.96 0.97 0.97 0.98 0.99 0.99 1.00
MODEL 1200A
Set Vacuum Air Flow Capacity at 100% Over-vacuum (Double Set Vacuum)
(Ps) 1000 Standard Cubic Feet per Hour at 60° F
In WC Oz/Sq In 2” 3” 4” 6” 8” 10” 12”
0.87 0.50 4.70 10.3 16.0 34.7 60.5 91.1 129
1.00 0.58 5.05 11.0 17.2 37.3 65.0 97.9 138
1.73 1.00 6.63 14.5 22.6 49.0 85.3 129 182
2.00 1.16 7.12 15.6 24.2 52.6 91.6 138 195
2.60 1.50 8.10 17.7 27.6 59.8 104 157 222
3.00 1.73 8.70 19.0 29.6 64.2 112 169 238
3.46 2.00 9.33 20.4 31.8 68.9 120 181 256
4.00 2.31 10.0 21.9 34.1 74.0 129 194 274
6.00 3.47 12.2 26.7 41.5 90.1 157 237 334
8.00 4.62 14.0 30.6 47.7 103 180 272 384
10.0 5.78 15.6 34.0 53.0 115 200 302 427
12.0 6.93 17.0 37.1 57.8 125 218 329 465
15.0 8.66 18.8 41.1 64.0 139 242 365 516
20.0 11.6 21.4 46.8 72.9 158 276 415 587
25.0 14.4 23.6 51.5 80.3 174 304 457 646
30.0 17.3 25.4 55.6 86.6 188 327 493 697
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-vacuum. Example—To find “C” factor from table:
Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OV 5 0.87
Read the flow capacity at 100% over-vacuum directly from the table above. Use linear “C” Factor Table
interpolation if the set vacuum is not listed. (Ref: Page TPD1) %OV 0 1 2 3 4 5 6 7 8 9
If the allowable over-vacuum is less than 100%, modify the flow capacity using the 10 0.42 0.43 0.44 0.45 0.46 0.46 0.47 0.48 0.49 0.50
appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, 20 0.51 0.52 0.52 0.53 0.54 0.55 0.56 0.56 0.57 0.58
consult page TPD1 or your Groth Representative.
30 0.59 0.59 0.60 0.61 0.61 0.62 0.63 0.64 0.64 0.65
Calculate the percentage over-vacuum by the following formula. Note that all 40 0.66 0.66 0.67 0.68 0.68 0.69 0.70 0.70 0.71 0.72
pressures are gage pressure expressed in the same units of measure.
50 0.72 0.73 0.73 0.74 0.75 0.75 0.76 0.77 0.77 0.78
Pf 5 Flowing pressure 60 0.78 0.79 0.80 0.80 0.81 0.81 0.82 0.82 0.83 0.84
Ps 5 Set pressure
% OV 5 [(Pf 2 Ps)/Ps] 3 100 70 0.84 0.85 0.85 0.86 0.86 0.87 0.88 0.88 0.89 0.89
80 0.90 0.90 0.91 0.91 0.92 0.92 0.93 0.93 0.94 0.94
Calculate flow capacity at less than 100% over-vacuum according to the following
example. 90 0.95 0.95 0.96 0.96 0.97 0.97 0.98 0.99 0.99 1.00
104
®
MODEL 1200A
Set Vacuum Air Flow Capacity at 100% Over-vacuum (Double Set Vacuum)
(Ps) 1000 Normal Cubic Meters per Hour at 0° C
mm WC mb 2” 3” 4” 6” 8” 10” 12”
22 2.16 0.13 0.29 0.45 0.98 1.71 2.58 3.65
50 4.90 0.20 0.44 0.68 1.48 2.58 3.88 5.48
75 7.35 0.24 0.53 0.83 1.81 3.15 4.74 6.70
100 9.80 0.28 0.62 0.96 2.08 3.62 5.46 7.72
125 12.3 0.31 0.69 1.07 2.32 4.04 6.09 8.60
150 14.7 0.34 0.75 1.17 2.53 4.41 6.65 9.40
175 17.2 0.37 0.81 1.26 2.73 4.75 7.16 10.1
200 19.6 0.39 0.86 1.34 2.91 5.07 7.64 10.8
225 22.1 0.42 0.91 1.42 3.08 5.36 8.08 11.4
250 24.5 0.44 0.96 1.49 3.23 5.64 8.49 12.0
275 27.0 0.46 1.00 1.56 3.38 5.90 8.88 12.6
300 29.4 0.48 1.04 1.62 3.52 6.14 9.25 13.1
375 36.8 0.53 1.16 1.80 3.91 6.81 10.3 14.5
500 49.0 0.60 1.32 2.05 4.45 7.75 11.7 16.5
625 61.3 0.66 1.45 2.26 4.90 8.54 12.9 18.2
750 73.5 0.72 1.57 2.44 5.29 9.22 13.9 19.6
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-vacuum. Example—To find “C” factor from table:
Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OV 5 0.87
Read the flow capacity at 100% over-vacuum directly from the table above. Use linear “C” Factor Table
interpolation if the set vacuum is not listed. (Ref: Page TPD1) %OV 0 1 2 3 4 5 6 7 8 9
If the allowable over-vacuum is less than 100%, modify the flow capacity using the 10 0.42 0.43 0.44 0.45 0.46 0.46 0.47 0.48 0.49 0.50
appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, 20 0.51 0.52 0.52 0.53 0.54 0.55 0.56 0.56 0.57 0.58
consult page TPD1 or your Groth Representative.
30 0.59 0.59 0.60 0.61 0.61 0.62 0.63 0.64 0.64 0.65
Calculate the percentage over-vacuum by the following formula. Note that all 40 0.66 0.66 0.67 0.68 0.68 0.69 0.70 0.70 0.71 0.72
pressures are gage pressure expressed in the same units of measure.
50 0.72 0.73 0.73 0.74 0.75 0.75 0.76 0.77 0.77 0.78
Pf 5 Flowing pressure 60 0.78 0.79 0.80 0.80 0.81 0.81 0.82 0.82 0.83 0.84
Ps 5 Set pressure
% OV 5 [(Pf 2 Ps)/Ps] 3 100 70 0.84 0.85 0.85 0.86 0.86 0.87 0.88 0.88 0.89 0.89
80 0.90 0.90 0.91 0.91 0.92 0.92 0.93 0.93 0.94 0.94
Calculate flow capacity at less than 100% over-vacuum according to the following
example. 90 0.95 0.95 0.96 0.96 0.97 0.97 0.98 0.99 0.99 1.00
MODEL 1201B
Set Pressure Air Flow Capacity at 100% Over-pressure (Double Set Pressure)
(Ps) 1000 Standard Cubic Feet per Hour at 60° F
PSIG 2” 3” 4” 6” 8” 10” 12”
1.00 28.0 53.4 92.5 210 345 529 739
2.00 40.3 77.4 134 304 500 767 1070
3.00 50.2 96.9 168 381 625 960 1340
4.00 58.8 114 198 448 736 1130 1577
5.00 66.5 130 225 510 838 1286 1794
6.00 73.7 144 250 568 932 1431 1997
7.00 80.4 158 274 622 1022 1568 2188
8.00 86.7 171 297 674 1107 1699 2371
9.00 92.8 184 319 724 1189 1825 2546
10.0 98.6 196 340 772 1267 1945 2714
11.0 104 208 360 818 1343 2062 2877
12.0 110 219 380 863 1417 2176 3036
13.0 115 231 400 907 1489 2286 3189
14.0 120 241 418 949 1559 2393 3339
15.0 125 252 437 991 1627 2498 3486
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-pressure. Example—To find “C” factor from table:
Read “C” factor for 75% Over-pressure at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OP 5 0.83
Read the flow capacity at 100% over-pressure directly from the table above. Use linear “C” Factor Table
interpolation if the set pressure is not listed. (Ref: Page TPD1) %OP 0 1 2 3 4 5 6 7 8 9
If the allowable over-pressure is less than 100%, modify the flow capacity using the 10 •••Consult Factory•••
appropriate “C” factor from the table. If allowable over-pressure is more than 100%, 20 0.27 0.29 0.30 0.32 0.33 0.35 0.36 0.38 0.39 0.40
consult page TPD1 or your Groth Representative.
30 0.42 0.43 0.44 0.45 0.47 0.48 0.49 0.50 0.51 0.52
Calculate the percentage over-pressure by the following formula. Note that all 40 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62
pressures are gage pressure expressed in the same units of measure.
50 0.63 0.64 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.71
Pf 5 Flowing pressure 60 0.72 0.72 0.73 0.74 0.75 0.76 0.76 0.77 0.78 0.79
Ps 5 Set pressure
% OP 5 [(Pf 2 Ps)/Ps] 3 100 70 0.80 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.85 0.86
80 0.87 0.87 0.88 0.89 0.90 0.90 0.91 0.92 0.92 0.93
Calculate flow capacity at less than 100% over-pressure according to the following
example. 90 0.94 0.94 0.95 0.96 0.96 0.97 0.97 0.98 0.99 1.00
106
®
MODEL 1201B
Set Pressure Air Flow Capacity at 100% Over-pressure (Double Set Pressure)
(Ps) 1000 Normal Cubic Meters per Hour at 0° C
BarG 2” 3” 4” 6” 8” 10” 12”
0.07 0.82 1.57 2.72 6.16 10.1 15.5 21.7
0.10 0.99 1.89 3.28 7.45 12.2 18.8 26.2
0.15 1.23 2.36 4.09 9.28 15.2 23.4 32.6
0.20 1.43 2.76 4.80 10.9 17.9 27.4 38.3
0.25 1.62 3.14 5.44 12.3 20.3 31.1 43.4
0.30 1.79 3.48 6.04 13.7 22.5 34.5 48.2
0.35 1.95 3.81 6.61 15.0 24.6 37.8 52.7
0.40 2.10 4.12 7.14 16.2 26.6 40.9 57.0
0.45 2.25 4.41 7.66 17.4 28.5 43.8 61.1
0.50 2.39 4.70 8.16 18.5 30.4 46.6 65.1
0.55 2.52 4.98 8.64 19.6 32.2 49.4 68.9
0.60 2.65 5.25 9.10 20.6 33.9 52.1 72.6
0.70 2.89 5.76 10.0 22.7 37.2 57.2 79.7
0.80 3.13 6.25 10.8 24.6 40.4 62.1 86.5
0.90 3.35 6.72 11.7 26.5 43.5 66.7 93.1
1.00 3.56 7.18 12.5 28.3 46.4 71.2 99.4
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-pressure. Example—To find “C” factor from table:
Read “C” factor for 75% Over-pressure at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OP 5 0.83
Read the flow capacity at 100% over-pressure directly from the table above. Use linear “C” Factor Table
interpolation if the set pressure is not listed. (Ref: Page TPD1) %OP 0 1 2 3 4 5 6 7 8 9
If the allowable over-pressure is less than 100%, modify the flow capacity using the 10 •••Consult Factory•••
appropriate “C” factor from the table. If allowable over-pressure is more than 100%, 20 0.27 0.29 0.30 0.32 0.33 0.35 0.36 0.38 0.39 0.40
consult page TPD1 or your Groth Representative.
30 0.42 0.43 0.44 0.45 0.47 0.48 0.49 0.50 0.51 0.52
Calculate the percentage over-pressure by the following formula. Note that all 40 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62
pressures are gage pressure expressed in the same units of measure.
50 0.63 0.64 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.71
Pf 5 Flowing pressure 60 0.72 0.72 0.73 0.74 0.75 0.76 0.76 0.77 0.78 0.79
Ps 5 Set pressure
% OP 5 [(Pf 2 Ps)/Ps] 3 100 70 0.80 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.85 0.86
80 0.87 0.87 0.88 0.89 0.90 0.90 0.91 0.92 0.92 0.93
Calculate flow capacity at less than 100% over-pressure according to the following
example. 90 0.94 0.94 0.95 0.96 0.96 0.97 0.97 0.98 0.99 1.00
MODEL 1202B
Set Vacuum Air Flow Capacity at 100% Over-vacuum (Double Set Vacuum)
(Ps) 1000 Standard Cubic Feet per Hour at 60° F
PSIG 2” 3” 4” 6” 8” 10” 12”
1.00 13.8 30.5 52.9 120 197 302 422
1.10 14.5 31.9 55.4 126 206 316 442
1.20 15.1 33.2 57.7 131 215 330 460
1.30 15.7 34.5 59.9 136 223 342 478
1.40 16.2 35.7 62.0 141 231 355 495
1.50 16.8 36.9 64.0 145 239 366 511
1.75 18.0 39.6 68.7 156 256 393 548
2.00 19.1 42.0 73.0 166 272 417 582
2.25 20.1 44.3 76.9 174 286 439 613
2.50 21.0 46.3 80.4 183 300 460 641
2.75 21.9 48.2 83.7 190 312 478 667
3.00 22.7 49.9 86.6 197 323 495 691
3.25 23.4 51.4 89.3 203 333 511 713
3.50 24.0 52.8 91.8 208 342 525 732
>3.50 CONSULT FACTORY FOR VACUUM SETTINGS GREATER THAN 3.5 PSI
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-vacuum. Example—To find “C” factor from table:
Read “C” factor for 75% Over-vacuum at intersection of row 70 and column 5
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 75% OV 5 0.83
Read the flow capacity at 100% over-vacuum directly from the table above. Use linear “C” Factor Table
interpolation if the set vacuum is not listed. (Ref: Page TPD1) %OV 0 1 2 3 4 5 6 7 8 9
If the allowable over-vacuum is less than 100%, modify the flow capacity using the 10 •••Consult Factory•••
appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, 20 0.27 0.29 0.30 0.32 0.33 0.35 0.36 0.38 0.39 0.40
consult page TPD1 or your Groth Representative.
30 0.42 0.43 0.44 0.45 0.47 0.48 0.49 0.50 0.51 0.52
Calculate the percentage over-vacuum by the following formula. Note that all 40 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62
pressures are gage pressure expressed in the same units of measure.
50 0.63 0.64 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.71
Pf 5 Flowing pressure 60 0.72 0.72 0.73 0.74 0.75 0.76 0.76 0.77 0.78 0.79
Ps 5 Set pressure
% OV 5 [(Pf 2 Ps)/Ps] 3 100 70 0.80 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.85 0.86
80 0.87 0.87 0.88 0.89 0.90 0.90 0.91 0.92 0.92 0.93
Calculate flow capacity at less than 100% over-vacuum according to the following
example. 90 0.94 0.94 0.95 0.96 0.96 0.97 0.97 0.98 0.99 1.00
108
®
MODEL 1202B
Set Vacuum Air Flow Capacity at 100% Over-vacuum (Double Set Vacuum)
(Ps) 1000 Normal Cubic Meters per Hour at 0° C
BarG 2” 3” 4” 6” 8” 10” 12”
0.07 0.41 0.90 1.55 3.52 5.77 8.87 12.4
0.10 0.48 1.06 1.83 4.16 6.83 10.5 14.6
0.11 0.51 1.11 1.92 4.35 7.14 11.0 15.3
0.12 0.53 1.15 1.99 4.53 7.43 11.4 15.9
0.13 0.55 1.20 2.07 4.69 7.70 11.8 16.5
0.14 0.56 1.24 2.14 4.85 7.96 12.2 17.1
0.15 0.58 1.27 2.20 5.00 8.21 12.6 17.6
0.16 0.60 1.31 2.27 5.14 8.44 13.0 18.1
0.17 0.61 1.35 2.33 5.28 8.66 13.3 18.6
0.18 0.63 1.38 2.38 5.41 8.88 13.6 19.0
0.19 0.64 1.41 2.44 5.53 9.08 13.9 19.4
0.20 0.66 1.44 2.49 5.65 9.27 14.2 19.8
0.22 0.68 1.49 2.58 5.86 9.62 14.8 20.6
0.24 0.70 1.54 2.67 6.05 9.93 15.2 21.3
>0.24 CONSULT FACTORY FOR VACUUM SETTINGS GREATER THAN 0.24 BARG
Flow capacity is certified by Groth Corporation, based on actual tests conducted in compliance with API Std. 2000.
Flow measurement accuracy has been verified by an independent testing laboratory.
Flow capacity values listed above are based on full open valves at 100% over-vacuum. Example—To find “C” factor from table:
Read “C” factor for 42% Over-vacuum at intersection of row 40 and column 2
For an equivalent size fiberglass valve, reduce tabulated capacities by 32%. “C” factor at 42% OV 5 0.55
Read the flow capacity at 100% over-vacuum directly from the table above. Use linear “C” Factor Table
interpolation if the set vacuum is not listed. (Ref: Page TPD1) %OV 0 1 2 3 4 5 6 7 8 9
If the allowable over-vacuum is less than 100%, modify the flow capacity using the 10 •••Consult Factory•••
appropriate “C” factor from the table. If allowable over-vacuum is more than 100%, 20 0.27 0.29 0.30 0.32 0.33 0.35 0.36 0.38 0.39 0.40
consult page TPD1 or your Groth Representative.
30 0.42 0.43 0.44 0.45 0.47 0.48 0.49 0.50 0.51 0.52
Calculate the percentage over-vacuum by the following formula. Note that all 40 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62
pressures are gage pressure expressed in the same units of measure.
50 0.63 0.64 0.65 0.66 0.67 0.67 0.68 0.69 0.70 0.71
Pf 5 Flowing pressure 60 0.72 0.72 0.73 0.74 0.75 0.76 0.76 0.77 0.78 0.79
Ps 5 Set pressure
% OV 5 [(Pf 2 Ps)/Ps] 3 100 70 0.80 0.80 0.81 0.82 0.82 0.83 0.84 0.85 0.85 0.86
80 0.87 0.87 0.88 0.89 0.90 0.90 0.91 0.92 0.92 0.93
Calculate flow capacity at less than 100% over-vacuum according to the following
example. 90 0.94 0.94 0.95 0.96 0.96 0.97 0.97 0.98 0.99 1.00