The prefix "WHD" needs to be deleted from all displayed tags. The font size of tags also needs to be enlarged. Color schemes for valves need to be updated to indicate positions like open, traveling, and closed. Engineering units and choke valve symbols displayed in tags require corrections as well. User-defined alarm configurations should be added to all tags.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
48 views1 page
POGC HMI Format
The prefix "WHD" needs to be deleted from all displayed tags. The font size of tags also needs to be enlarged. Color schemes for valves need to be updated to indicate positions like open, traveling, and closed. Engineering units and choke valve symbols displayed in tags require corrections as well. User-defined alarm configurations should be added to all tags.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
The prefix 201 needs deletion
GENERAL COMMENT:The prefix Description needs to be updated as
WHD needs deletion from all per actual gathering network Manual bypass valve to be displayed tags. Subsequently the scheme incorporated font size of tag needs enlargement
To CI package and WHCP
The color of SSV and SSSV shall be different for Open (Green), Choke valve symbol shown in other Traveling (Flashing Red/Yellow) file need to be used for manual as and Closed positions (Red). well as auto choke. Manual Choke need to be grayed out and auto choke should have colors based on choke feedback as follows; Red if < 2% Yellow if >=2% & < 95% Green if <95% GENERAL COMMENT:All tags shall have the provision of user defined alarm configuration
GENERAL COMMENT:Incorrect Engineering units of the tags needs correction