STS - Cathodic Protection
STS - Cathodic Protection
Cathodic Protection
Page 1 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Presentation Topics
Section – 1: Basic Corrosion and Cathodic Protection
1. What is Corrosion?
2. Electrochemical Reaction
3. Corrosion Cell
4. What can Cause Corrosion?
5. Corrosion Type
6. Factor Influencing Corrosion Rate (at Soil)
7. Basic Corrosion Prevention Methods
8. Cathodic Protection
9. Pourbaix Diagram (E – pH)
10. Polarization Curve
11. Cathodic Protection Criteria
12. Type of Cathodic Protection
13. Comparison Sacrificial Anode & Impressed Current System
14. Cathodic Protection Materials
15. Cathodic Protection Application
16. Why should we concern about Corrosion & Cathodic Protection?
Page 2 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 3 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Section – 1
Basic Corrosion and Cathodic Protection
What is Corrosion?
Practical : Tendency of a Metal to Revert to its Native State
Electrochemical Reaction
Oxidation: Fe(s) Fe2+(aq) + 2 e–
Reduction: O2(g) + 4 H+(aq) + 4 e– 2 H2O(l)
–––––––––––––––––––––––––––––––––––––––––––––––––––– +
Overall: 2 Fe(s) + O2(g) + 4 H+(aq) 2 Fe2+(aq) + 2 H2O(l)
Page 5 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 6 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 7 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Stray Current by Electric Train Rail Stray Current by High AC Voltage Line
Page 9 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 10 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Corrosion Type
Uniform Corrosion predictable with corrosion allowance
Localized Corrosion unpredictable
Galvanic Corrosion Stress Corrosion
Pitting Corrosion Intergranular Corrosion
Crevice Corrosion Hydrogen Embrittlement
Corrosion Erosion Microbial Corrosion
Page 11 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 13 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Cathodic Protection
Use of DC current from an external source to oppose the discharge
of corrosion current from anodic areas of the structure.
A technique to control the corrosion of metal surface by making that
surface the cathode of an electrochemical cell – NACE SP0169
A means of rendering the metal immune from corrosion attack by
causing the direct current to flow from its electrolytic environment
into the entire metal surface – BS 7631 – Part 1.
Page 14 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 15 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 16 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Precautions
Use of excessive polarized potential on externally coated pipeline
should be avoided to minimize disbondment of the coating.
Polarized potential that result in excessive generation of hydrogen
should be avoided on all metals.
Page 20 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 22 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Aluminium/Zinc Bracelet Anode Aluminium/Zinc Hull Anode Bare Fe-Si-Cr (HSCI) Anode
Page 23 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Bare String Ti/MMO Anode Canister MMO/Fe-Si-Cr Anode MMO Wire Anode
MMO / Pt-Ti Probe Anode Coke Breeze ICCP Backfill Sacrificial Anode Backfill
Page 24 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Transformer Rectifier Air Cooled Transformer Rectifier Oil Cooled Transformer Rectifier Ex Proof
Isolating Spark Gap Polarization Cell Replacement (PCR) Solid State Decoupler (SSD)
Page 26 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Portable Cu/CuSO4 Ref. Cell Portable Ag/AgCl Ref. Cell Various Reference Electrode
Page 30 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Internal Cooling Water Pipe Internal (Water) Storage Tank / Separator Vessel
Page 33 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 34 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Section – 2
Cathodic Protection in Practice
1. DESIGN STAGE
(1) Design shall be based on real and sufficient data / condition (soil
resistivity, protected structure, coating system, operating temperature,
plant condition / arrangement, etc) need complete data and drawing
(2) Design shall be based on proper References, Standards, and also proven
experiences
(3) Design shall be proper, comprehensive, constructible and also safe for
expected design life time (design parameter, calculation and allowance,
material selection, planned CP installation arrangement and coverage,
etc), but not excessive (for economic and operation reason).
(4) Provision of understandable, informative, and complete/sufficient
documentation (Design Calculation, Drawing, Procedure) for Review and
for Construction.
Page 35 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
3. CONSTRUCTION STAGE
(1) CP construction sequence shall be following / accordance to Plant
construction schedule/progress.
Page 36 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 37 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Buried Open Drain Pipe contact with A/G Protected U/G pipe contact through other
piping pipe (Useless Insulation Flange)
CP Loss Current through Instrument Tubing Protected U/G Pipeline contact with metallic
and Earthing Wire fence
Page 38 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Protected U/G Pipeline contact with metallic Protected U/G pipe and A/G pipe is bonding
support (Useless Insulation Flange)
Protected U/G Pipe is contact with concrete Incomplete installed Insulation Flange
steel rebar at concrete manhole / pit / floor
Page 39 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Short Insulating Joint through heat insulation CP Loss Current through Instrument Tubing
aluminium jacket and its screws
Protected U/G Pipe is contact with concrete Use Isolating Spark Gap to avoid CP Current
steel rebar at concrete pit / manhole / floor drained by Plant Earthing system
Page 40 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Protected U/G Pipe is purposely welded to Any risk of CP Current loss if using Armoured
steel rebar at concrete manhole Cable for Connection to U/G Pipe
Page 41 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 43 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 44 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 45 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Terminal, make sure the reading as per indicated by Meter. Make sure the
all measurement result is as per indicated by Panel Meter. If there is any
large different, it could be any problem on the Panel meter. Replace
module/parts.
Page 46 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 47 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 48 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 49 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 50 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 51 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Possible Problems
(1) Depleted or faulty Sacrificial Anode
(2) Broken Cable / Cable to Pipe Connection
(3) Damage Test Station Box
(4) Electrically Short at Insulating Flange, Casing, support or others
4.2.4. Schedule
(1) Checking of SACP System for U/G Piping/Pipeline is recommended to be
performed each three month (maximum each six month).
(2) Trouble shooting checking should be done immediately after finding of
abnormal reading.
Page 53 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
increase and anode current output can be resulted become smaller. It will
cause the resulted pipe protection level also gradually decrease.
So, if any section which the pipes are considered have not sufficiently
protected and also indicated by low anode natural potential, indicate of
depleted / consumed anode material. In such case, new magnesium anode
shall be installed. Excavation shall be done (preferred at existing anode
position or Test Station Box), therefore no new cable to pipe connection is
required. Anode cable can be connected to existing anode cable or
terminated at Test Station Box.
Quantity of new installed anode shall be calculated based on historical anode
current output record. If actual current requirement is quite high (indication of
highly corrosive soil condition and worst pipe coating condition), higher
anode quantity shall be installed.
Page 54 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 55 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 56 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Potential Measurement
Potential measurement only can be done if any pre-installed Permanent
Reference Electrode inside the protected Tank/Vessel.
Oherwise, potential measurement only can be done when the Tank/Vessel is
containing “only” water, no pressure and no flowing condition, and any access
Page 57 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 58 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 59 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
By checking the anode dimension, it can be estimated how much the anode
have been consumed, and then whether it have been depleted and need to be
replaced with new anode, or it still can be used until next overhauled schedule.
Comparison with previous Check Record also can be used for prediction, how
fast the anode actually will be consumed.
Checking of anode visually also needed to make sure the anode surface are
kept active and therefore sacrificial anode are working/functioning. Usually it is
indicated by any soft “chalk” layers at anode surface (Aluminium Oxide and
Aluminium Hydroxide), and when this anode corrosion product is removed, the
anode surface will be seen as consumed uniformly. Another case, it also
possible that anode cannot function due to its surface is covered by oil or any
paint pigment. These anode surface will need to be cleaned or grinded to
reveal the aluminium metal surface.
It is possible that consumption level of each anodes in one Tank/Vessel are not
same. Therefore, complete check is needed, either for anodes at Tank Bottom
level and anodes at Tank Wall.
Anode – Tank continuity check also need to be done, at least by sampling. If
any anode’s bolt is loose, re-tighten it, and perform “spot welding” if
allowed/possible.
Page 60 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 61 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 62 of 63
PT SOUTHERN TRISTAR CATHODIC PROTECTION
Page 63 of 63