Smoke Control System Design
Smoke Control System Design
Smoke control systems keep building occupants safe from smoke generated
during unwanted fires. Requirements for smoke control systems are given in
Section 909 of the 2007 and 2010 International Building Code (IBC), the
primary model building code used in the United States. For atrium smoke
control, IBC 909 refers to NFPA 92B, “Standard for Smoke Management
Systems in Malls, Atria, and Large Spaces” for the design of smoke control
systems.
Smoke control system design in high-rise buildings is accomplished using the
pressurization method (IBC 909.6). Mechanical ventilation systems are used
to create small pressure differences (minimum of 0.05 inches of water
column) across smoke barriers, a special type of fire-resistant construction
defined in IBC 709 and IBC 909.5. Maximum pressure differences are limited
by door opening forces, which must remain less than 30 lb. During a fire,
small pressure differences created by smoke control systems keep smoke
confined to one smoke control zone. Smoke control systems based on the
pressurization method are designed to prevent smoke from spreading to
adjacent smoke control zones, but they are not intended to maintain a tenable
environment in the smoke control zone where the fire originates. Instead, that
is the purpose of smoke control systems based on the exhaust method —
widely used for atrium smoke control.
1. Tall spaces (> 5 stories). The algebraic equations in NFPA 92B assume
that all air entrained into a fire plume instantly becomes smoke, and the
total amount of smoke produced increases super-linearly with height
above the fire. Application of NFPA 92B’s algebraic equations to
determine exhaust rates in tall atria will lead to unnecessarily large
exhaust requirements. This will result in an over-designed atrium smoke
control system, which adds significant construction costs but does not
improve occupant safety over an appropriately-sized system.
For cases where the NFPA 92B algebraic equations for smoke exhaust rate
do not apply, or would lead to unnecessarily large exhaust rates, computer fire
modeling is usually applied to determine the required exhaust rate. This is
accomplished by performance-based design, or an ASET/REST analysis
(Available Safe Egress Time vs. Required Safe Egress Time) which is usually
addressed through IBC 104.11 “Alternative materials, design and methods of
construction and equipment” or California Building Code Section 108.7
“Alternate materials, designs, tests and methods of construction”.
Applying techniques such as computer fire modeling, ASET/RSET analyses,
and performance-based design to atrium smoke control systems can often
lead to significant construction cost savings and make innovative designs
possible. Since makeup air (or supply air) is usually provided at 85% to 95%
of the exhaust rate, reduction of the exhaust rate can lead to major reductions
in makeup air requirements. From an aesthetic and cost standpoint, this is
often more significant than reducing the exhaust rate because exhaust fans
and inlets can usually be incorporated in the ceiling construction, but low-level
makeup air inlets are often problematic in atria.
Reax Engineering, Inc. has considerable expertise in sizing and design of
smoke control systems, including application of NFPA 92B’s algebraic
equations, computer fire modeling, ASET/RSET analyses, and performance-
based design. For inquiries related to smoke control system design or atrium
smoke control, please contact David Rich.