1.3 REFERENCES
A. ANSI/NFPA 70 - National Electrical Code.
B. ARI 640 - Commercial and Industrial Humidifiers.
C. UL 900 - Test Performance of Air Filter Units.
D. EN 13501-1 - Fire classification of construction products and building elements.
1.4 SUBMITTALS
A. Submit under provisions of Section 01300.
B. Product Data: Including but not limited to product descriptions, models, dimensions,
component sizes, rough-in requirements, service sizes, and finishes. Include rated
capacities, operating weights, furnished specialties, and accessories.
1. Manufacturer's installation instructions.
2. Operation and maintenance data.
3. Minimum water quality requirements and water pressure requirements.
D. Test Results.
A. Manufacturer:
1. Products manufactured in an ISO 9001 certified facility.
2. For each product specified, provide components by single manufacturer
throughout.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in
NFPA 70, Article 100, by a testing agency acceptable to authority having jurisdiction,
and marked for intended use.
C. Humidifiers: In compliance with ARI 640 - Standard for Commercial and Industrial
Humidifiers and applicable “New Approach” CE Directives.
1.6 COMMISSIONING
B. Documentation and testing of these systems, as well as training of the Owner’s operation
and maintenance personnel, is required in cooperation with the Commissioning
Authority.
A. Deliver all materials in their original sealed containers bearing manufacturer's name and
identification of product.
B. Do not store products in location with conditions outside manufacturer's absolute limits.
C. Materials delivered to the site shall be examined for concealed damage or defects in
shipping. Defects shall be noted and reported to the Owner’s Representative in writing.
A. Coordinate location and installation of humidifiers in ducts and air-handling units in the
space it serves with the electrical, mechanical, and plumbing contractors. Revise
locations and elevations to suit field conditions and to ensure proper humidifier
operation.
1.9 WARRANTY
A. Manufacturer’s Standard Warranty: Two year warranty covers defects in materials and
workmanship, commences on date of shipment.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Acceptable Manufacturer: NORTEC; 826 Proctor Ave. P. O. Box 698; Ogdensburg, NY
13669. Toll Free: 866-NORTEC-1. Email: [email protected]. Web:
www.humidity.com.
B. Acceptable Manufacturer: Condair plc; Artex Avenue, Rustington, LITTLEHAMPTON
West Sussex. BN16 3LN. UK Tel. 01903850200 Email: [email protected] Web:
www.condair.co.uk
C. Substitutions: Not permitted.
B. General:
1. Packaged evaporative media humidifier providing humidification and air-cooling using
the principle of surface evaporation over a wetted media. Designed for installation in air-
handling systems or ductwork. Air downstream of humidifier is free of aerosols, cooler,
and more humid.
2. Humidifier accepts potable, softened, reverse osmosis and de-ionized water ( >5μS).
3. Humidifier designed around glass fiber media as humidifying medium. Fire protection
shall be in accordance with UL 900 / EN 13501-1.
4. Electronic controller, which monitors the operation of the system, controls output levels
and initiates self-cleaning flushing cycles to ensure hygiene and prolong media life span.
5. Humidifier powered by 120 volts single phase power supply with power consumption up
to 0.278kW.
6. Recirculation system to capture and reuse excess water. Improved water conservation
through either performing drains based on operating time and water added or optionally
by monitoring conductivity to maintain a programmable maximum mineral
concentration.
7. Duct shall contain metalwork and media boxes. Pumps, valves, controls, and other
mechanical components shall be provided in a separate module for installation internal or
external to duct.
8. Control panel includes Modbus interface for integration into building automation system.
BACnet, LonWorks, available as options.
C. Evaporative Media:
1. Media: Made of glass fiber, packaged in stainless steel casing.
2. Compliance: The material shall have a flame retardant coating and fire protection in
compliance with UL 900 / EN 13501-1.
3. Replacement: Lift out stainless steel media casings are hooked into the humidifier frame.
No tools required for media removal.
4. Rate of Evaporation: Dependent on the air volume, air temperature, cross sectional area
of the humidifier and the media depth.
5. Depth: Dictates the maximum efficiency of up to 75 percent (4 inch, 102 mm media), 85
percent (6 inch, 152 mm media), or 95% (8 inch, 203mm).
D. Mist Eliminator:
1. Patented integral mist eliminator prevents water droplets in cases where the face velocity
across the media exceeds 688 ft/s (3.5 m/s).
2. Allows face velocities operation up to 886 fpm (4.5 m/s).
3. Material Compliance: Meets UL 900 / EN 13501-1.
E. Management System:
1. Unit includes electronic control cabinet with NRTL-c approval to include electrical fuses,
main switch.
2. Microprocessor control using a proportional-integral method for interpreting analog
signals from a humidistat and or building control systems.
3. The controller determines which stages should be activated to meet humidification loads.
4. The controller activates self-maintenance cycles. This includes controlled flushing of the
water tank in conjunction with filling cycles, and scheduled drain cycles to maintain
cleanliness of the water tank.
5. The controller will manage programmable self-wash cycles. This cycle reduces scaling
on the media and ensures clean hygienic operation. In addition, the controller flushes
water lines after a period of inactivity.
6. Control panel complete with on/off switch, auto drain switch, and LED’s for fault,
maintenance, and operational indication.
F. Control panel with backlit Touch Screen Display to have the following functionality:
1. Service indicator and LED power on.
2. Intuitive touch screen back-lit graphic display.
3. Display of relative humidity and set point.
4. Display of operating hours.
5. Capacity output.
6. Real-time date and time.
7. Error history indication.
8. Clean mode and media drying.
9. Limited capacity adjustment.
10. Inlet flush, drain time and drying cycles.
11. Adjustable maintenance intervals.
12. Remote relay testing.
13. Modbus standard host protocol.
14. Terminal block installed for easy field connection of low voltage 24VAC control cable
from prewired hydraulic unit with 16.4 feet (5 m) of cabling included.
J. Optional Features/Accessories:
1. Conductivity Monitoring Sensor: Maintains water quality at programmed level which
maximizes life of evaporative media.
2. Submerged UV assembly.
3. In-Line UV assembly.
4. In-Line Water filter with 5 micron filter.
5. PureFlo Ag+ In-Line Silver Filter.
6. On/Off digital duct high limit humidistat.
7. Air proving switch.
8. Remote fault indication board.
9. Frost protection stat.
10. Leak detection sensor.
11. 10V Digital Duct Humidistat package.
12. 0 - 10V Digital Wall Humidistat.
13. 2-10V Dig Wall Humidity Sensor.
14. 2-10V Duct Humidity Sensor.
15. System: BACnet or LonWorks connection as manufactured by NORTEC.
a. Description: Remote building management system capability using BACnet /IP, or
LonWorks, networks for monitoring and controlling.
b. Variable definitions, addresses, and values.
c. External Interface File (XIF) for LonWorks integration.
d. Protocol Implementation Conformance Statement (PICS) for BACnet integration.
e. BACnet Interoperability Building Blocks (BIBBS) for BACnet Services.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine ducts, air-handling units, and conditions for compliance with requirements for
installation tolerances and other conditions affecting performance.
B. Examine roughing-in for piping systems to verify actual locations of piping connections
before humidifier installation
C. If preparation is the responsibility of another installer, notify Architect of deviations from
manufacturer’s recommended installation tolerances and conditions.
D. Do not proceed with installation until substrates have been properly prepared and
deviations are corrected.
E. Commencement of installation constitutes acceptance of conditions.
3.2 INSTALLATION
A. Install components plumb and level, in accordance with approved shop drawings, product
installation details and manufacturer’s recommendations.
1. Install humidifiers and steam dispersion panels per manufacturers' instructions.
2. Seal humidifier dispersion-tube duct penetrations with flange.
3. Install with required clearance for service and maintenance.
3.4 TRAINING
A. Engage a factory-authorized service representative to train Owner's maintenance
personnel to adjust, operate, and maintain humidifiers.
1. Train Owner's maintenance personnel on procedures and schedules for starting
and stopping, troubleshooting, servicing, and maintaining equipment and
schedules.
2. Review data in maintenance manuals.
3. Schedule training with Owner, through Architect, with at least seven days
advance notice.
END OF SECTION