0% found this document useful (0 votes)
145 views4 pages

Numerical Residual Voltage - Neutral Displacement Relay

The document describes a zero sequence voltage/neutral displacement relay that monitors and protects power systems from unbalanced voltages. It continuously monitors line voltages and activates if an abnormal condition persists beyond a set time. It displays line voltages and status on an LCD screen. Key features include accurate residual voltage measurement, configurable settings, fast tripping for phase/neutral interchange, and LED indicators for status. It can be used for voltage unbalance and earth fault protection of equipment.

Uploaded by

Sumit Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
145 views4 pages

Numerical Residual Voltage - Neutral Displacement Relay

The document describes a zero sequence voltage/neutral displacement relay that monitors and protects power systems from unbalanced voltages. It continuously monitors line voltages and activates if an abnormal condition persists beyond a set time. It displays line voltages and status on an LCD screen. Key features include accurate residual voltage measurement, configurable settings, fast tripping for phase/neutral interchange, and LED indicators for status. It can be used for voltage unbalance and earth fault protection of equipment.

Uploaded by

Sumit Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

ZERO SEQUENCE VOLTAGE/NEUTRAL DISPLACEMENT RELAY

Description
Prok Dvs an ISO 9001:2008 Company indigenously develops the power system protection
relays and panel meters for power system. µP based Zero sequence voltage relays are the
state of the art design, to monitor and protect the costly equipments against unbalance
voltages.
The Relay Continuously monitoring all the three phase Line to Line Voltages, if any
abnormal condition persists in the system internal Relay activated with predetermined set
value of definite time.
The Unit Displays Line to Line Voltages on LCD display, Healthy and Fault /Trip status
Information through LED Display.

Features
 Accurate and reliable measurement .of residual voltage.
 Display of voltage magnitudes, using 8 character 2 line LCD
 User friendly Setting Parameters through key pad switch
 Wide range for Selection of residual voltage
 User configurable Definite tripping time (DMT)
 Fast tripping response(<500mS) when Phase and Neutral are Interchanged
 Industrial Rugged design in Din rail mounting as well as Panel Mounting.
 Healthy, Trip Status provided through LED visual indications.
 Auto Reset provided on Healthy voltage resumption
Application
 Voltage Unbalance/Earth fault protection
 Protection of Equipments/Components against Phase and Neutral Interchange
.
Technical Specifications

 Rated System Voltage (Un): 415V AC


 Tripping characteristic: DMT
 Model: DMPND
 Voltage setting range: (1-50) Volts in steps of 1V
 Trip Time setting range: (1-30) Sec In steps of 1Sec
 Trip Time when Ph. & Neutral interchanged: 500mS ( Approx)
 Output Relay: 230VAC 5Amp /24VDC 5Amp
 Auto Reset provided on Healthy voltage resumption
 AUX. Voltage: 85-275V AC/DC Universal input, 50-60Hz
 Display: 8 chars 2 line LCD with backlit
 LED: For Visual indications of healthy & Trip status.
 Mounting: Flush mounting
 Dimensions: FLUSH MOUNTING: 96x96x65 mm (w x h x d) +/- 1mm Tolerance
DIN MOUNTING: 79x93x73 mm (l x h x b) +/- 1mm Tolerance
Setting procedure:

1) Connect aux. supply to the relay ( 50 to 500)V AC/DC

2) Press the key for 3 seconds to make settings to the relay

3) Display Shows

4) Press Key for 3Sec

5) Display changes to

6) Press key

7) Display Changes to

Use / Key to select the value

Save the value by using the Key.

8) Display changes to

Use / Key to set the desired operating time and operate

Set key to save the selected value.


9) Display shows

Press Key to Save the value.

10) Display shows

This completes the setting procedure for the relay.

Press the to reset the relay

The moment 3Ph, line to line voltage is applied to the Relay starts measuring and
Displaying the line voltages of the system.