387351P-EN R04 SIGA-MCT2 Dual Input Module Installation Sheet PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Notes

• The SIGA-MCT2 is shipped from the factory as an assembled unit;


it contains no user-serviceable parts and should not be
disassembled.
• This module will not operate without electrical power. As fires
SIGA-MCT2 Dual Input Module frequently cause power interruption, we suggest that you discuss
further safeguards with your local fire protection specialist.

Installation Sheet • The SIGA-MCT2 does not support conventional smoke detectors.
To install the module:
1. Plug the module into any available position on the motherboard.
See Figure 1.
2. Secure the module to the motherboard with the two captive
screws.
3. Write the address assigned to the module on the label provided,
and then apply the label to the module. Remove the serial number
label from the detector, and then attach it to the project
documentation.
4. Wire in accordance with “Wiring” below.

Figure 1: Mounting on a UIO2R motherboard

Description
The SIGA-MCT2 Dual Input Module is an addressable device that
provides one or two Class B, normally-open, dry contact initiating
device circuits (IDCs) on a Signature signaling line circuit (SLC).
The module requires two addresses on the SLC. Addresses are
assigned electronically. There are no address switches.
Diagnostic LEDs provide a visible indication of the module state.
• Normal: green LED flashes
• Alarm/active: red LED flashes
The SIGA-MCT2 plugs into a SIGA-UIO2R, SIGA-UIO6, or
SIGA-UIO6R motherboard. Field wiring connections are made using
terminals on the motherboard.

Personality codes
A personality code downloaded from the Signature controller
determines how the module operates. Table 1 shows the personality
codes available for the SIGA-MCT2.

Table 1: Personality codes Wiring


Code Description Strip 1/4 in. (about 6 mm) from the ends of all wires that connect to the
terminal block.
1 Alarm - NO latching (Class B) [1]
2 Alarm - NO delayed latching (Class B) Notes

3 Active - NO nonlatching (Class B) • When stripping wire ends, exposing more wire may cause a
ground fault or circuit malfunction on unsupervised wiring;
4 Active - NO latching (Class B)
exposing less wire may result in a faulty connection.
[1] Factory default setting • Refer to the Signature loop controller installation sheet for SLC
wiring specifications.

Installation • Each terminal on the motherboard is limited to a single conductor.

Install and wire this device in accordance with applicable national and To wire the module:
local codes, ordinances, and regulations. 1. Verify that all field wiring is free of opens, shorts, and ground faults.

WARNING: Electrocution hazard. To avoid personal injury or death 2. Make all wiring connections as shown in Figure 2.
from electrocution, remove all sources of power and allow stored
energy to discharge before installing or removing equipment.

© 2017 United Technologies Corporation 1/2 P/N 387351P-EN • REV 04 • ISS 15MAR17
Figure 2: Wiring the module

(4) (1) Class B initiating device circuit


(2) Power-limited and supervised
(1)(2)(3) (3) 50 Ω max. per channel (25 Ω per wire). With
UIO2R / EOLR in place, normal terminal voltage is
UIO6R UIO6 10 VDC nominal.
(4) 47 kΩ EOLR (P/N EOL-47)
(5) Power-limited and supervised.
(6) Signaling line circuit from previous device
(8) (7) Signaling line circuit to next device
(8) No connection for the SIGA-MCT2
(5)

(6) +
-
(7) +
-

(8) (8)

(8)

Specifications Regulatory information

Voltage 15.20 to 19.95 VDC North American CAN/ULC-S527, UL 864


standards
Current
Standby 450 µA FCC compliance This device complies with part 15 of the FCC
Activated 700 µA Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
Ground fault 10 kΩ
interference, and (2) this device must accept any
impedance
interference received, including interference that
Initiating device circuit may cause undesired operation.
EOLR 47 kΩ, UL Listed
Circuit resistance 50 Ω (25 Ω per wire) max.
Circuit capacitance 0.1 µF max. Contact information
Signaling line circuit Class A (Style 6) or Class B (Style 4) For contact information, see www.edwardsfiresafety.com.
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
Mounting UIO2R, UIO6, UIO6R
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
Storage temperature −4 to 140°F (−20 to 60°C)

2/2 P/N 387351P-EN • REV 04 • ISS 15MAR17