Adjustment during
Commissioning (APN-084)
www.siemens.com/siprotec
SIPROTEC 5 Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
SIPROTEC Application
SIPROTEC 5 – Point on Wave: Adjustment
during Commissioning
APN-084, Edition 1
Content
APN-084 2 Edition 1
SIPROTEC 5Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
The first two poles (CA) close when the VCA voltage is zero (30° of reference voltage, ph A). The last pole, B,
closes at 120° which is the zero crossing of the VB voltage. The diagram below shows the voltage on the
capacitor with near perfect closing. The transient has only a small magnitude.
Edition 1 3 APN-084
SIPROTEC Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
The closing and pre-arcing times have been set using the data provided for the circuit breaker as shown
above.
As there are no compensating factors via transducers in this application (e.g. closing voltage magnitude,
temperature etc.) the calculated closing time equals the set closing time (e.g. 62.4 ms for phase A). The
measured values (e.g. 63.364 ms for phase A) may not deviate severely so that the closing time (0.963 ms
for phase A) remains small (not more than approx. 3 ms, for larger values check the CB data and settings).
APN-084 4 Edition 1
SIPROTEC 5Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
The measured closing time is derived from the reference contact or if this is not available from the auxiliary
contact. In this example there is no reference contact, so that the following binary signals are responsible for
the measured closing time:
The diagram below from the manual shows the closing time: start, stop and adjustment. For the adjustment
of the closing time the following parameters are used:
The “ closing time” measured will be subtracted from the set “Time delay ref.contact”. This is the reason why
settings may be negative when the “ closing time” was positive. See example calculation under heading
“Adapting the Reference contact delay”.
Edition 1 5 APN-084
SIPROTEC Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
The calculated make time is the set closing time minus the pre-arc time. The pre-arc time depends on the
voltage across the CB contacts as the breaker is closing. As the PoW always closes at the same point on wave
this is approximately the same every time. The pre-arc time is therefore not used to compensate the
measured make time. The parameters used to adjust the make time are the following:
The “CB correction time” is used to adapt the PoW response (make time). The applied correction time is added
to the closing time. A positive setting will therefore result in an earlier close command (longer closing time).
The positive make time in the fault log above indicates that the measured make time was longer than
expected. The values from the fault log (green box) are therefore added to the old setting (in this case the old
settings are zero, so the make time can be set directly as follows (only 2 decimal places):
The next closing operation will include these settings in the calculated close time (longer) and the make time
should now have a very small delta (exactly zero is generally not possible).
APN-084 6 Edition 1
SIPROTEC 5Application
SIPROTEC 5 – Point on Wave: Adjustment during Commissioning
By subtracting the delta closing in the fault log from the “old setting” of “Time delay ref. cont.” in each phase
the make time is adjusted. The next close should show significantly smaller closing time values:
In this test case the modified settings produce a perfect result with 0 ms deviation in all phases.
1.4 Conclusion
The PoW function can be adapted with the relevant settings using the information recorded in the fault log.
After adjustment the correct response can be checked with a new closure of the plant. In the above example
a shunt capacitor with ungrounded neutral was used, but the basic principles of the adjustment apply to all
types of plant.