100% found this document useful (2 votes)
229 views34 pages

4 EMCPII Demo Monitor y Control

The document discusses switchgear components including an EMCP II electronic control module, generator set control (GSC), and service mode functions. The GSC monitors generator values, engine values, protections, and start/stop control. It can be used to view and clear faults, program configurations, set parameters, and more. The GSC requires proper configuration via option 5 to correctly respond to engine faults from the ECM.

Uploaded by

Marcos Guardia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
229 views34 pages

4 EMCPII Demo Monitor y Control

The document discusses switchgear components including an EMCP II electronic control module, generator set control (GSC), and service mode functions. The GSC monitors generator values, engine values, protections, and start/stop control. It can be used to view and clear faults, program configurations, set parameters, and more. The GSC requires proper configuration via option 5 to correctly respond to engine faults from the ECM.

Uploaded by

Marcos Guardia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

Switchgear

Electronic Module Control Panel


• EMCP II
• Generator Set Control
• GSC
– Mide Valores de Generacion
– Mide Valores del Motor
– Controla la Protecciones del Motor
– Controla el Arranque / Parada
GSC Service mode

OP1
PHASE ENGINE LAMP ALARM SERVICE
EXIT
SELECT METER TEST CODE MODE

SCROLL SCROLL SCROLL SELECT ENTER


RIGHT UP DOWN

VISUALIZACION OP4 Controlar y limpiar las fallas


OP1 DE
FALLA
OP5 Programar las configuraciones
VISUALISACION
OP2 DE
OP6 Configurar las entrada y salidas
CONFIGURACIONES

OP7 Programar la hora


OP3 PASSWORD ENTRY
OP8 Conf. voltimetro / amperimetro

OP9 Verifica la configuracion del Motor

PE: 13231 OP10 Ajusted de Protecciones AC


GSC OP5-0 setpoints
P001 fuel solenoid type 0=ETR, 1=ETS
P002 Units shown 0=Eng, metric
P003 Shutdown override for Engine fault 0=Shutdown, 1=Alarm
P004 Shutdown override for for Sensor fault 0=Alarm, 1=Shutdown
P005 Coolant loss sensor installed 0=w/o sensor, 1=w/sensor
P006 Shutdown override for coolant loss fault 0= shutdown, 1= alarm
P007 System voltage 24 volts or 32 volts
P008 Not used NA
P009 Number of ring gear teeth 95 to 350 teeth
P010 Engine overspeed 500 to 4330 rpm
P011 Crank terminate speed 100 to 1000 rpm
P012 Oil step speed 400 to 1800 rpm
P013 Low oil pressure shutdown at Rated speed 34 to 240 kPa (5 to 61 psi)
P014 Low oil pressure shutdown at Idle speed 20 to 336 kPa (3 to 49 psi)
P015 High water temperature shutdown 85 to 123 C (185o to 253oF)
P016 Low water temperature alarm 0 to 36oC (32 to 97oF)
P017 Total cycle crank time 5 to 360 seconds
P018 Cycle crank time 5 to 300 seconds
P019 Cooldown time 0 to 30 minutes
P020 AC voltage 150V to 30.0 kV
P021 AC current full scale 75A to 4000A
P022 GSC Engine Number 01 to 08
P023 Engine type 0=MUI, 1=Gas, 2=EUI
P024 Crank time delay (only for gas) 0 to 20 seconds
P025 Oil temperature sensor installed 0=w/o sensor, 1=w/sensor
P026 High oil temperature shutdown 85 to 123oC (185 to 253oF)
P027 Shutdown enable for high oil temperature 0=alarm, 1=shutdown
P028 Name plate voltage 100 to 25kV
P029 Name plate Current 0 to 4000A
P030 Name plate power 0 to 10MW
P031 Rated frequency 50, 60 or 400 Hz
P032 Connection configuration of generator 0=wye, 1=delta
P033 Number of generator poles 0 to 254
GSC
Para que responda correctamente el GSC
dependera totalmenta de la configuracion ( OP-5 )

P03 Parada por falla en ECM MOTOR


Este set point en el GSC responder a una falta presión de aceite de motor,
baja temperatura de refrigerante.
No es parte del los codigos de falla del Motor.
El seteo es : 0 – Para Stop
1 – Solo para Alarma

P04 Parada por falla en los SENSORES


El diagnostico de falla pueden ser: Sensor de presion de aceite
Sensor de temperatura
Sensor nivel de refrigerante
Sensado por tension de alimentacion
Son fallas de diagnostico (baterias,sensores y cables…)no son fallas
mecanicas
El Seteo es : 0 – Para Stop
1 – Solo para Alarma
ECS
GSC & ECM

Cat data link

MPU

GSC

ECM
GEN

Speed/timing Sensor

Engine Coolant Engine oil


Temperature Sensor Pressure Sensor
GSC & E C M

Si precenta una "E" el codigo de diagnóstico está


generando en el ECM del Motor, Pase a solucionar la
falla en manual 3500B Procedimieto de reparacion

91 E 8
Codigo generado por el ECM
GSC & E C M

91 E 8 Señal anormal de aceleracion

Este es un defecto común cuando no hay


alimentacion al LSM por lo tanto no existe señal
PWM al ECM)
Truck

PWM
TRIM
POT

Load sharing module


1 2 3
Speed control
Gain Droop
(Converter)
-B S D +B
PWM
TRIM
POT

Load sharing module


1 2 3
Speed control
Gain Droop
(Converter)
-B S D +B
RS 232

DATA LINK
EMCP II Service Manual
Publications

SERVICE MANUALS EMCPII EMCPII+


MUI SENR5809-04 SENR5832-01
PEEC SENR5827-01 RENR1254
EUI SENR5398-02 RENR1200-01
GAS SENR5394 RENR1201

FG Wilson Packages RENR1250 (3306,3406 MUI) RENR1260 (3500 EUI)


RENR1261 (3412,3500 MUI) RENR1249 (3306,3406 MUI)
RENR1259 (3500 EUI) RENR1253 (3412,3500 MUI)
Arquitectura de los Sistemas
De Control
Constan de los siguientes componentes
esenciales:


Hardware.
Propios del ECM. .
 Software.

Sensores.

Externos al ECM. Actuadores


.
 Equipo programador.
Arquitectura
ECM
Señal
de
Control
VARIABLE
CARGA
O
DESCARGA

RESULTADO
CONSTANTE
DEL TRABAJO
Switchgear

• Funcionamieto principal de Switchgear


• Protección
• Monitoreo
• Control
– Automatismo en Paralelo
Cat Switchgear

•Componetes que usa


–Interruptor principal
–Controla el generador
–Mediciones instrumentos
–Protecciones relay
–Componetes que controla carga
Switchgear
• Interruptor Principal
Switchgear

• Mediciones Visibles
– Voltage (GSC)
– Currente (GSC)
– Frequencia (GSC)
– KiloWatt
– VAR
– Factor de Potencia
– Sincronoscopio
Switchgear
• Generador con Carga
• Protective Relays
– 27 Baja Tension
– 32 Potencia Inversa
– 51G Alta Corriente en Neutro
– 81 Alta / Baja Frecuencia
Switchgear
• Control Components
– LSM
– SPM
– Control de voltaje
– PLC
Switchgear
• Tipo de Paralelo
– Manual
– Semi-Automatico
– Automatico

You might also like